General Recommendations for a Federal Data Center Energy Management Dashboard Display
|
|
|
- Claud Jefferson
- 10 years ago
- Views:
Transcription
1 General Recommendations for a Federal Data Center Energy Management Dashboard Display Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National Laboratory Rod Mahdavi, PE, LEED AP July 2014
2 Contacts Rod Mahdavi, P.E., LEED AP Lawrence Berkeley National Laboratory 1 Cyclotron Road Berkeley, CA (510) [email protected] For more information on the Federal Energy Management Program, please contact: Will Lintner, P.E., CEM Federal Energy Management Program U.S. Department of Energy 1000 Independence Ave SW Washington, DC (202) [email protected] i
3 Acknowledgements The Department of Energy funded the research and study required to prepare this whitepaper. ii
4 Abbreviations and Acronyms AHU ASHRAE Btu CRAC EIS EPA EPT FEMP IP IT kw kwh LBNL MWh PDU PUE SAT UPS V W Air Handler Unit American Society of Heating, Refrigerating and Air-Conditioning Engineers British Thermal unit Computer Room Air Conditioner Energy Information System Environmental Protection Agency Energy Performance Tracking Federal Energy Management Program Internet Protocol Information Technology Kilowatt (1,000 Watts) Kilowatt-hour Lawrence Berkeley National Lab Megawatt-hour (1,000,000 Watt-hours) Power Distribution Units Power Usage Effectiveness Supply Air Temperature Uninterruptible Power Supply Volt Watt iii
5 Contents Executive Summary... vi Introduction... 7 Key Characteristics of a Dashboard... 8 Objectives and Stakeholders... 8 Stakeholders List of Preferred Dashboard Displays... 9 Monitoring Points and Dashboards Recommended Information for Dashboard Displays Examples of Commercially Available Energy Management Dashboards References iv
6 List of Figures Figure 1. Energy Use by Data Centers in the United States (Modified from the EPA Report to Congress 2007)... 7 Table 1. Primary Monitoring Points and Metrics... 9 Table 2. Comparison of Three Measurement Levels Figure 2. Monitoring-Level Sliding Scale Figure 3. ASHRAE Sample Dashboard (Courtesy of ASHRAE) Figure 4. Suggested Dashboard for All Users Using Level 3 Tools Figure 5. IT Manager s Specific Dashboard Using Level 3 Tools Figure 6. Facility Manager s Specific Dashboard Using Level 3 Tools Figure 7. Dashboard for Capacity Management, PUE, and Energy Use by End Use (Courtesy of Schneider Electric) Figure 8. Dashboard for PUE, and Energy Use over Time and by End Use (Courtesy of Modius).. 16 Figure 9. Dashboard for PUE, and Energy Use over Time and by End Use (Courtesy of Synapsense) List of Tables Table 1. Primary Monitoring Points and Metrics... 9 Table 2. Comparison of Three Measurement Levels v
7 Executive Summary Within the past decade, the focus has increased on improving data center energy efficiency. Today, the cost of the electricity needed to run the IT equipment and its supporting infrastructure is surpassing the capital cost of the IT equipment itself over its lifetime. Data center operators are interested in reducing energy use while maintaining or increasing computational workloads. To achieve this, first, energy use needs to be measured and benchmarked. Next, energy data needs to be collected and transformed into actionable information. Throughout this process, energy use data can be presented to facilitate analysis through visual displays. Dashboards help to track energy use, inform decisions for taking corrective action and can be used to track the performance of energy-efficiency improvements once they have been implemented. This guide discusses some typical dashboard content that is useful for energy management. vi
8 Introduction Historically, energy use by data centers has doubled every 5 to 7 years. As Figure 1 illustrates, the estimated energy use by data centers was between 65 to 85 billion (10 9 ) kilowatt-hours (BkWh) in From , computing performance increased approximately twenty-five times, but energy efficiency increased only eight times (EPA Report to Congress 2007). The average amount of power consumed per server increased by approximately four times. The 2010 estimated energy use is reported by Koomey (2011) and is not part of EPA 2007 report. Note that no actual data is available for those years beyond 2006 so numbers are just stimates Estimated Energy Use Figure 1. Energy Use by Data Centers in the United States (Modified from the EPA Report to Congress 2007) The objective of this guide is to provide general recommendations to help select or tailor the energy elements or parameters of a data center infrastructure dashboard. Data center operators are constantly looking for strategies to reduce the power needs of their data centers, but they can t manage what they don t measure. Hence, monitoring and continuous fine-tuning of energyintensive systems is a necessity, and a dashboard energy information system (EIS) can play a key role in helping operators manage (e.g., reduce, optimize) data center energy use. Based on dashboard readings or trends, an operator can investigate further for more detailed data and then initiate energy-efficiency actions. Most data centers are just starting to install and use dashboards for energy management. Energy use of various physical data center components can be measured in, or near, real time, and these data can be trended and then visualized in a dashboard. A dashboard is defined as a visual display of the most important information needed to achieve one or more objectives, consolidated and arranged on a screen so that the information can be monitored at a glance. It 7
9 can display monitored, measured, and calculated parameters. The fundamental philosophy behind a dashboard information system is that it provides quick access to actionable visual data. Key Characteristics of a Dashboard Some of the key characteristics of a dashboard are that it: Displays the most important performance indicators and performance measures being monitored; these are usually user-defined, user-friendly, and easy to understand. Displays content in various charts or graphs; measured or calculated numbers are presented graphically. Displays information for various stakeholders (workforce, middle management, and executives). Displays data on a computer screen. Different screens can display different energy parameters. Automatically updates displays of data without any assistance from the user. Supports interactivity filtering, drilling down, or customizing screens to meet various stakeholder needs. Has the ability to store and generate reports on various aspects of energy, as needed or defined by the stakeholders. Objectives and Stakeholders The objectives of these activities are to: Identify and prioritize a set of data center energy parameters to be monitored/measured using a system that displays them in a dashboard format. Identify potential stakeholder(s) for each energy parameter. The stakeholders will be interested in tracking both the real-time and trend values of the different energy parameters, with the goal of reducing energy usage and costs. Document recommendations to help the data center community choose which parameters they want to monitor and manage. The following individuals were identified as a typical set of key stakeholders interested in various energy dashboard displays and reports: 1. Director: Responsible for the overall center s activity 2. Facility Manager: Primarily responsible for the data center s physical infrastructure 3. Information Technology (IT) Manager: Primarily responsible for the information technologies (both hardware and software) in the data center Each target stakeholder has different information display needs. Additional stakeholders could have been identified, but these stakeholders were chosen to illustrate several major user groups interested in the actionable display of energy information. 8
10 Stakeholders List of Preferred Dashboard Displays For an actual survey effort, a set of energy parameters for data centers was developed for each target stakeholder. The stakeholders were given the list of dashboard display elements and instructed to assign each an interest level (or priority) as it applied to them. The choices were: 1 for high priority, 2 for medium priority, 3 for low priority, and N to represent no interest. Of course, not all items are applicable to every site (for example, Reuse energy factor (REF) would only apply to a site with the proper energy recovery system). Although this list offers initial candidates for dashboard displays, stakeholders should revise it to meet their specific needs. Table 1 shows the level of interest of different stakeholders to energy parameters. # Primary Information Director IT Manager Facility Manager 1 Power Usage Effectiveness Total power Power cost Carbon emission IT power Average IT utilization 2 1 N 7 IT efficiency Power factor N N 2 9 UPS output power N UPS input power N PDU input power N PDU output power N N 2 13 Electrical chain efficiency IT fan power N Data center temperature (map) N Subfloor, duct pressure map N N 2 17 Outdoor dry-bulb and wet-bulb temperatures N N 2 18 Total CRAC power, except fan N N 2 19 Chilled water plant load N N 2 20 Chilled water plant power N N 2 21 District cooling power use N N 2 22 Cooling efficiency N Standby generator, block heater power /energy N N 3 24 Standby generator, fuel equivalent N N 3 25 Green energy consumed (GEC) 3 N 2 26 Reuse energy factor (REF) 3 N 2 Table 1. Primary Monitoring Points and Metrics 9
11 Monitoring Points and Dashboards Users can select from three levels of energy performance tracking (EPT) approaches. Each level of metering hardware, software, and data acquisition should be prioritized according to business drivers, and will be influenced by the available budget. These three levels correspond to the ASHRAE guidelines (ASHRAE 2010) three defined measurement levels: minimum practical (Level 1), best practical (Level 2), and state-of-the art (Level 3). Measurement Level Level 1 Level 2 Level 3 Human Activity Periodic manual measurement and recording Some manual recording and some automated Automated recording Measurement Equipment Manual Hybrid Automated Measurement Frequency Once a month, a week, a day Some manual frequency, some continuous Continuous PUE Estimate Accuracy Reliance on Manufacturer Data +30% +15% Less than +5% High Less None Infrastructure Upgrade Very low Limited, less expensive upgrades High Reports Manual, no trending, no training Limited trending, no vendor assistance All types of reports, vendor-assisted implementation Dashboards None Limited Highly beneficial Table 2. Comparison of Three Measurement Levels 10
12 The ideal option is Level 3, but the available budget plays a key role in which level is selected. Figure 2 below shows the benefits and costs of the three measurement levels, using a sliding scale. The author recommends that a Level 3 measurement package is best to enable a datadriven approach to data center energy management. The figure suggests that going from Level 1 to Level 3 will: Increase both cost and accuracy. Facilitate decision making based on better data. Increase automatic data collection. Provide continuous communication. Figure 2. Monitoring-Level Sliding Scale 11
13 Recommended Information for Dashboard Displays Standardization of dashboards and reports is important to make them more useful. Development of the energy dashboard is a team effort. Figure 3 shows a sample dashboard from ASHRAE s guide, Real-Time Energy Consumption Measurements in Data Centers (ASHRAE 2010). This level of displayed data can be only possible if an extensive (and expensive) measurement system is installed. Figure 3. ASHRAE Sample Dashboard (Courtesy of ASHRAE) Figure 4 illustrates a dashboard that is built around the key metrics and can be used by different levels of stakeholders, including senior management. The dashboard is arranged in three columns. The first column illustrates the real-time figures for energy cost, power usage by function (kwh/hour) and power usage effectiveness (PUE). The second column illustrates average figures during the last 7 days, last 30 days, and last 12 months for the same performance metrics. The third column illustrates the trending capabilities of the dashboard for the same metrics. The examples shown are for trends from the beginning of the year. By moving the cursor on the graph, a user can define trending by any start/finish (date/hour) with whatever granularity he or she desires. 12
14 Last 7 days $ 50k $ Hourly Energy Cost $500 Last 30 days $ 150k Last 12 months $ 800k JAN FEB MAR ENERGY COST Fans 8% Others 7% kwh Fans Others 8% 7% kwh Cooling 25% IT 50% Cooling 23% IT 55% EE Loss 10% AVG Power Last 7 days Fans 6% EE Loss 7% AVG Power Last 30 days Others 7% kwh kwh TOTAL IT Percent POWER USE Real Time Cooling 20% IT 60% COOLING FANS EE Loss 7% AVG Power Last 12 months Last 7 days ENERGY USE trend EE LOSS Last 30 days 2 1 PUE 3 Last 12 months Avg PUE 1 JAN FEB MAR PUE trend Figure 4. Suggested Dashboard for All Users Using Level 3 Tools Figure 5 illustrates a dashboard that can best serve the IT manager, in addition to the dashboard in figure 4. The IT manager will see the same dashboard as the director but also see a second window that shows IT utilization. The first column illustrates real-time IT utilization. The second column illustrates IT utilization averages during the last 7 days, last 30 days, and last 12 months, and the third column graph is used for trending. By moving the cursor on the graph, a user can define trending by any start/finish (date/hour) with whatever granularity he or she desires. All other stakeholders can observe this dashboard if they like. 13
15 . 50 Last 7days 35 % 100 Last 30days 35 % Last 12months 35 % 0 JAN FEB MAR IT UTILIZATION AVG IT UTILIZATION IT utilization trend Figure 5. IT Manager s Specific Dashboard Using Level 3 Tools Figure 6 illustrates a dashboard that can best serve a facility manager, in addition to the previous dashboards. The facility manager will see the same dashboard as the director but also see a second window will allow observation of the electrical distribution efficiency, the cooling efficiency, and a thermal map of the data center. Representative examples are shown for trending from the beginning of the year. In the actual case, by moving the cursor on the graph, a user can define trending based on any start/finish (date/hour) and with any granularity he or she desires (a few hours, few days, weeks, or more). A thermal map also can be defined for any time/date. In addition, a movie can be set up by defining the start and end point, so that changes can be observed over any period of time in the past. All other stakeholders can observe this dashboard if they like. 50 WEEK TO DATE MONTH TO DATE % % ELEC DIST EFFICIENCY YEAR TO DATE 90 AVG ELEC DIST EFFICIENCY % 0 JANFEB MAR ELEC DIST EFFICIENCY 1 WEEK TO DATE MONTH TO DATE.8.8 kw/ton kw/ton COOLING EFFICIENCY YEAR TO DATE.8 AVG COOLING EFFICIENCY kw/ton 0 JANFEB MAR COOLING EFFICIENCY Thermal Map Figure 6. Facility Manager s Specific Dashboard Using Level 3 Tools 14
16 Examples of Commercial Energy Management Dashboards Dashboard technology exists to provide customized visualization of various energy metrics. This section shows sample dashboards that illustrate how different vendors visualize different metrics. Different types and different levels of dashboards have been developed, from homemade versions, to packaged systems that cannot be customized, to packaged systems that are customized to meet specific user needs. Some vendors claim their dashboard can be customized according to customer needs. Figures 7, 8, and 9 illustrate commercially available dashboard displays that show capacity management, PUE, and energy use by function. Figure 7. Dashboard for Capacity Management, PUE, and Energy Use by End Use (Courtesy of Schneider Electric) 15
17 Figure 8. Dashboard for PUE, and Energy Use over Time and by End Use (Courtesy of Modius) Figure 9. Dashboard for PUE, and Energy Use over Time and by End Use (Courtesy of Synapsense) 16
18 References ASHRAE Real-Time Energy Consumption Measurements in Data Centers. CA Technologies. CA DCIM. Accessed August 30, CA Technologies. CA Technologies Expands DCIM and IT Energy Management Capabilities With Enhanced CA ecosoftware Solution. Accessed August 30, Energy-Management-Capabilities.aspx. Chiang, Alexander. What is a Dashboard? Defining dashboards, visual analysis tools and other data presentation media. Few, S Information Dashboard Design: The effective visual communication of data. O Reilly Media, Inc. IBM. Active Energy Manager (AEM). Accessed August 30, ibm.com/systems/software/director/aem/. JouleX. JouleX Energy Management (JEM). Accessed August 30, SynapSense. SynapSense Active Control. Accessed August 30, Report to Congress on Server and Data Center Energy Efficiency, Public Law (8/2/2007): 17
19 DOE/EE-1107 July 2014
Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers
Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
Guideline for Water and Energy Considerations During Federal Data Center Consolidations
Guideline for Water and Energy Considerations During Federal Data Center Consolidations Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
Guidelines for Datacenter Energy Information System
Guidelines for Datacenter Energy Information System Reshma Singh, Rod Mahdavi, Paul A. Mathew, Jessica Granderson, Lawrence Berkeley National Laboratory; Yash Shukla, CEPT University December 2013 Environmental
Data Center Metering and Resource Guide. Version 1.1. July 30th, 2015. Rod Mahdavi and Steve Greenberg. Lawrence Berkeley National Laboratory
Data Center Metering and Resource Guide Version 1.1 July 30th, 2015 Rod Mahdavi and Steve Greenberg Lawrence Berkeley National Laboratory Note to users: Please submit comments and suggestions to Steve
DC Pro Assessment Tools. November 14, 2010
DC Pro Assessment Tools November 14, 2010 William Tschudi, PE Lawrence Berkeley National Laboratory [email protected] 510-495-2417 1 Slide 1 Assessment tools LBNL is developing tools to assist in performing
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment
Managing Power Usage with Energy Efficiency Metrics: The Available Me...
1 of 5 9/1/2011 1:19 PM AUG 2011 Managing Power Usage with Energy Efficiency Metrics: The Available Metrics and How to Use Them Rate this item (1 Vote) font size Data centers consume an enormous amount
Reducing Data Center Energy Consumption
Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate
Recommendations for Measuring and Reporting Overall Data Center Efficiency
Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 1 Measuring PUE at Dedicated Data Centers 15 July 2010 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations
Data Center Leadership In the DOE Better Buildings Challenge
Symposium Southern California February 18th, 2015 Data Center Leadership In the DOE Better Buildings Challenge Applying Best Practices to meet the Challenge Dale Sartor, PE Lawrence Berkeley National Laboratory
Data Center Energy Use, Metrics and Rating Systems
Data Center Energy Use, Metrics and Rating Systems Steve Greenberg Energy Management Engineer Environmental Energy Technologies Division Lawrence Berkeley National Laboratory October 31, 2007 Today s s
Self-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10. Sponsored by:
Self-benchmarking Guide for Data Center Infrastructure: Metrics, Benchmarks, Actions 6-28-10 Sponsored by: Disclaimer This document was prepared as an account of work sponsored by the United States Government.
Smarter Data Centers. Integrated Data Center Service Management
Smarter Data Centers Integrated Data Center Service Management Approx. 3.500 ton CO² is generated by: Diesel Car-6l /100 km 20.000 km Airplane 5 * Brussels-Barcelona Server, 1.5 A, 24*7*365*3.000 Kwhr
Harmonizing Global Metrics for Data Center Energy Efficiency
Harmonizing Global Metrics for Data Center Energy Efficiency Dan Azevedo, Symantec Chairman - Metrics & Measurements Work Group Industry Trends Energy Efficient IT The Climate Group: Smarter technology
Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics
On January 13, 2010, 7x24 Exchange Chairman Robert Cassiliano and Vice President David Schirmacher met in Washington, DC with representatives from the EPA, the DOE and 7 leading industry organizations
How green is your data center?
Siemens Answers: Sustainable Future How green is your data center? Istanbul June 01, 2010 Agenda 1 Solution 2 Siemens Data Center Approach 2 Designing with multiple power density zones can reduce energy
Cisco EnergyWise and CA ecosoftware: Deliver Energy Optimization for the Data Center
Cisco EnergyWise and CA ecosoftware: Deliver Energy Optimization for the Data Center Executive Summary Managing energy consumption and power loads in the data center, as part of Data Center Infrastructure
Variable-Speed Fan Retrofits for Computer-Room Air Conditioners
Variable-Speed Fan Retrofits for Computer-Room Air Conditioners Prepared for the U.S. Department of Energy Federal Energy Management Program Technology Case Study Bulletin By Lawrence Berkeley National
Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres
What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy
Recommendations for Measuring and Reporting Overall Data Center Efficiency
Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 2 Measuring PUE for Data Centers 17 May 2011 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations for Measuring
Increasing Energ y Efficiency In Data Centers
The following article was published in ASHRAE Journal, December 2007. Copyright 2007 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes
Top-Level Energy and Environmental Dashboard for Data Center Monitoring
2010. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). For personal use only. Additional reproduction, distribution, or transmission in either print or
Recommendation For Incorporating Data Center Specific Sustainability Best Practices into EO13514 Implementation
Recommendation For Incorporating Data Center Specific Sustainability Best Practices into EO13514 Implementation Version 1.0 - November, 2011 Incorporating Data Center-Specific Sustainability Measures into
Energy Efficient High-tech Buildings
Energy Efficient High-tech Buildings Can anything be done to improve Data Center and Cleanroom energy efficiency? Bill Tschudi Lawrence Berkeley National Laboratory [email protected] Acknowledgements California
Re Engineering to a "Green" Data Center, with Measurable ROI
Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices
Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie
Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie Mukesh Khattar, Energy Director, Oracle National Energy Efficiency Technology Summit, Sep. 26, 2012, Portland, OR Agenda
Guide to Minimizing Compressor-based Cooling in Data Centers
Guide to Minimizing Compressor-based Cooling in Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By: Lawrence Berkeley National Laboratory Author: William Tschudi
Dallas/Fort Worth International Airport District Energy Plant Upgrades Project Making More with Less Sustainable Communities Conference Dallas, TX
Dallas/Fort Worth International Airport District Energy Plant Upgrades Project Making More with Less Sustainable Communities Conference Dallas, TX March 10, 2009 Agenda DFW Capital Development Program
CIBSE ASHRAE Group. Data Centre Energy Efficiency: Who, What, Why, When, Where & How
CIBSE ASHRAE Group Data Centre Energy Efficiency: Who, What, Why, When, Where & How Presenters Don Beaty PE, FASHRAE Founder, President & Managing Director DLB Associates Consulting Engineers Paul Finch
Data center lifecycle and energy efficiency
Data center lifecycle and energy efficiency White Paper Lifecycle management, thermal management, and simulation solutions enable data center energy modernization Introduction Data centers are coming under
Server Technology, Inc.
Server Technology, Inc. Cabinet Power Monitoring, Management & Control Within the Data Center White Paper STI-100-011 2010-Sept-27 by Calvin Nicholson, Senior Director Software and Strategic Alliances,
Understanding Power Usage Effectiveness (PUE) & Data Center Infrastructure Management (DCIM)
Understanding Power Usage Effectiveness (PUE) & Data Center Infrastructure Management (DCIM) Salim Janbeh Physical Infrastructure Consultant [email protected] PANDUIT You Can t Manage What You Don t Measure:
How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems
How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems Paul Mathew, Ph.D., Staff Scientist Steve Greenberg, P.E., Energy Management Engineer
Improving Data Center Efficiency with Rack or Row Cooling Devices:
Improving Data Center Efficiency with Rack or Row Cooling Devices: Results of Chill-Off 2 Comparative Testing Introduction In new data center designs, capacity provisioning for ever-higher power densities
Managing Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
Data Center Infrastructure Management (DCIM) Utility Energy Efficiency Opportunities Discussion & Demos July 2, 2013
Data Center Infrastructure Management (DCIM) Utility Energy Efficiency Opportunities Discussion & Demos July 2, 2013 Ted Brown Sr. Energy Management Analyst Data Center / IT Energy Efficiency [email protected]
ERE: A METRIC FOR MEASURING THE BENEFIT OF REUSE ENERGY FROM A DATA CENTER
WHITE PAPER #29 ERE: A METRIC FOR MEASURING THE BENEFIT OF REUSE ENERGY FROM A DATA CENTER EDITOR: MIKE PATTERSON, INTEL CONTRIBUTORS: BILL TSCHUDI, LAWRENCE BERKELEY NATIONAL LABORATORY OTTO VANGEET,
Benchmarking results from Indian data centers
Benchmarking results from Indian data centers Data Center Energy Efficiency 24 February, ACREX 2011, New Delhi Madhav Kamath. A Energy Efficiency Finance Lead USAID ECO-III Project Data Center Benchmarking
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
How High Temperature Data Centers and Intel Technologies Decrease Operating Costs
Intel Intelligent Management How High Temperature Data Centers and Intel Technologies Decrease Operating Costs and cooling savings through the use of Intel s Platforms and Intelligent Management features
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.
Data Center RD&D at EPRI
Data Center RD&D at EPRI Mukesh Khattar Technical Executive Critical facilities Round Table Meeting Palo Alto, CA 16 October 2015 EPRI Focus for Data Centers RD&D Address problems facing the member electric
IT Cost Savings Audit. Information Technology Report. Prepared for XYZ Inc. November 2009
IT Cost Savings Audit Information Technology Report Prepared for XYZ Inc. November 2009 Executive Summary This information technology report presents the technology audit resulting from the activities
Infrastructure & Cities Sector
Technical Article Infrastructure & Cities Sector Building Technologies Division Zug (Switzerland), October 18, 2011 Saving Energy in a Data Center A Leap of Faith? New guidelines from ASHRAE (American
Data Center Lifecycle and Energy Efficiency
Data Center Lifecycle and Energy Efficiency Lifecycle infrastructure management, power management, thermal management, and simulation solutions enable data center modernization. White Paper October 2014
Case study: End-to-end data centre infrastructure management
Case study: End-to-end data centre infrastructure management Situation: A leading public sector organisation suspected that their air conditioning units were not cooling the data centre efficiently. Consequently,
Overview of Green Energy Strategies and Techniques for Modern Data Centers
Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.
Data Center Energy Efficient Cooling Control Demonstration PIR 10 052. (formerly Federspiel Controls)
Data Center Energy Efficient Cooling Control Demonstration PIR 10 052 (formerly Federspiel Controls) Background 2009 PIER sponsored project resulted in the installation of intelligent supervisory control
Data Center Energy Efficiency. SC07 Birds of a Feather November, 2007 Bill Tschudi [email protected]
Data Center Energy Efficiency SC07 Birds of a Feather November, 2007 Bill Tschudi [email protected] Benchmark results helped to find best practices The ratio of IT equipment power to the total (or its
Guidance for Calculation of Efficiency (PUE) in Data Centers
Guidance for Calculation of Efficiency (PUE) in Data Centers White Paper 158 Revision 3 by Victor Avelar Executive summary Before data center infrastructure efficiency can be benchmarked using PUE or other
San Francisco Chapter. Deborah Grove, Principal Grove-Associates
Deborah Grove, Principal Grove-Associates Why Green IT is Important 1. The energy consumed by servers in the US (and associated air -conditioning) is equivalent to the annual output of about 20 new coal-fired
AIA Provider: Colorado Green Building Guild Provider Number: 50111120. Speaker: Geoff Overland
AIA Provider: Colorado Green Building Guild Provider Number: 50111120 Office Efficiency: Get Plugged In AIA Course Number: EW10.15.14 Speaker: Geoff Overland Credit(s) earned on completion of this course
How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel
Foreseer Services. Product application guide. Table of contents
Product application guide Foreseer Services Table of contents 1.0 General.......................................... 2 1.1 What are Foreseer Software and Engineering Services.... 3 1.1.1 Foreseer Service
Guidance for Calculation of Efficiency (PUE) in Data Centers
Guidance for Calculation of Efficiency (PUE) in Data Centers White Paper 158 Revision 1 by Victor Avelar > Executive summary Before data center infrastructure efficiency can be benchmarked using PUE or
Green Data Centers. Energy Efficiency Data Centers. André ROUYER Director of Standardization & Environment. The importance of standardization
Green Data Centers GOING FORWARD ENERGY EFFICIENCY TRENDS André ROUYER Director of Standardization & Environment All content in this presentation is protected 2008 American Power Conversion Corporation
Data Centers: Definitions, Concepts and Concerns
Data Centers: Definitions, Concepts and Concerns Arash Mousavi DCC September 2013 Agenda 1. Introduction 2. Issues in Modern Data Centers: Siemens Integrated Data Center Solutions 3. Issues in Modern Data
DOE Data Center Air-Management (AM) Tool: Data Collection Guide. Version 1.18 (November 24, 2014)
DOE Data Center Air-Management (AM) Tool: Data Collection Guide Version 1.18 (November 24, 2014) The Data Collection Guide and the Air Management Tool were developed jointly by Lawrence Berkeley National
Energy Efficiency. Energy Efficient Water Heating: Purchasing a new electric water heater. Hot water use has a significant impact on your bill.
Energy Efficiency Energy Efficient Water Heating: Purchasing a new electric water heater. Water heating accounts for about 18 percent of your home energy bill. Only space heating and cooling account for
How to Maximize Data Center Efficiencies with Rack Level Power Distribution and Monitoring
How to Maximize Data Center Efficiencies with Rack Level Power Distribution and Monitoring Brian Rehnke e-pdu Business Development Manager November, 2011 The Problems Energy Usage in most data centers
Report to Congress on Server and Data Center Energy Efficiency Public Law 109-431. U.S. Environmental Protection Agency ENERGY STAR Program
Report to Congress on Server and Data Center Energy Efficiency Public Law 109-431 U.S. Environmental Protection Agency ENERGY STAR Program August 2, 2007 Table of Contents Table of Contents... i Executive
Green Data Centre Design
Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS
BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0
BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 To achieve GREEN MARK Award Pre-requisite Requirement All relevant pre-requisite requirements for the specific Green Mark Rating are to be complied
Energy Efficiency: Integrated Design and HVAC Systems HEALTHCARE - TOP 5 GREEN BUILDING STRATEGIES
EPA Publication 909-F-07-001 What? Energy use in healthcare facilities is higher than nearly all other building types. With rising energy costs and climate change concerns energy efficiency is financially
How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent
Wireless Sensors Improve Data Center Energy Efficiency
Wireless Sensors Improve Data Center Energy Efficiency Technology Case Study Bulletin: September 2010 As data center energy densities, measured in power per square foot, increase, energy savings for cooling
SynJet: Low-Power Green Cooling
TECHNOLOGY SynJet: Low-Power Green Cooling Nuventix, Inc. 4301 Westbank Dr. Building A150 Phone: 512-382-8100 Fax: 512-382-8101 Email: [email protected] Introduction The realities of finite petroleum resources
CRITICAL COOLING FOR DATA CENTERS
IDEA 100 th Annual Conference & Trade Show CRITICAL COOLING FOR DATA CENTERS Presented by Ron Johanning, PE, LEED AP Mission Critical Market Leader Agenda EPA Report Data Center Energy Trends IT Best Practice
DOE Data Center Energy Efficiency Program
DOE Data Center Energy Efficiency Program Paul Scheihing U.S. Department of Energy Energy Efficiency and Renewable Energy April 2009 1 DOE Industrial Technologies Program Worki king to improve th e energy
Legacy Data Centres Upgrading the cooling capabilities What are the options?
Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems
Reducing Data Center Loads for a Large-Scale, Net Zero Office Building
rsed Energy Efficiency & Renewable Energy FEDERAL ENERGY MANAGEMENT PROGRAM Reducing Data Center Loads for a Large-Scale, Net Zero Office Building Energy Efficiency & Renewable Energy Executive summary
Metrics for Data Centre Efficiency
Technology Paper 004 Metrics for Data Centre Efficiency Workspace Technology Limited Technology House, PO BOX 11578, Sutton Coldfield West Midlands B72 1ZB Telephone: 0121 354 4894 Facsimile: 0121 354
Data Center Infrastructure Management: How to Optimize Data Center Operations
Data Center Infrastructure Management: How to Optimize Data Center Operations Khaled Nassoura, PE [email protected] General Manager Raritan, Inc. Question of the Day Question: Would any CFO run
I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015
I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 8, Loughborough University, 29 th June 2015 Topics to be considered 1. Progress on project tasks 2. Development of data centre test facility
Data Center Energy Efficiency Looking Beyond PUE
Data Center Energy Efficiency Looking Beyond PUE No Limits Software White Paper #4 By David Cole 2011 No Limits Software. All rights reserved. No part of this publication may be used, reproduced, photocopied,
Green Data Centre: Is There Such A Thing? Dr. T. C. Tan Distinguished Member, CommScope Labs
Green Data Centre: Is There Such A Thing? Dr. T. C. Tan Distinguished Member, CommScope Labs Topics The Why? The How? Conclusion The Why? Drivers for Green IT According to Forrester Research, IT accounts
Data Center Infrastructure Management: ERP for the Data Center Manager
Data Center Infrastructure Management: ERP for the Data Center Manager 1 2 Topics What s DCIM & the ERP Analogy Why DCIM How DCIM Works How DCIM Helps 3 DCIM by Definition DCIM is a system that collects
How to Measure Energy Consumption in Your Data Center
How to Measure Energy Consumption in Your Data Center Gartner RAS Core Research Note G00205428, Rakesh Kumar, 8 September 2010, R3506 02112011 This research outlines a pragmatic approach that should be
Optimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
Green IT Solutions From Desktop to Datacenter. Dave Spear Sr. Engagement Manager & Sustainability Advocate dave.spear@microsoft.
Green IT Solutions From Desktop to Datacenter Dave Spear Sr. Engagement Manager & Sustainability Advocate [email protected] Agenda Our Commitment Today s Environment PC, Server, Storage Computerworld