Identifying Energy Saving Opportunities in the Data Center
|
|
|
- Jeffry Nelson
- 10 years ago
- Views:
Transcription
1 Identifying Energy Saving Opportunities in the Data Center Andrew Fanara US EPA ENERGY STAR Product Development (206) (Seattle, WA) 1
2 Data Centers are INFORMATION FACTORIES Data centers are energy intensive facilities Server racks now designed to carry 25 kw load Surging demand for data storage Typical facility ~ 1MW, can be > 20 MW Nationally 1.5% of US Electricity consumption in 2006 Could double in next 5 years New research by The Uptime Institute shows data center energy consumption in the top quartile of sites researched grew percent annually in 2006 and This far exceeds the EPA's prediction of 9 percent growth from 2006 to
3 Simplified Data Center Layout Source: Emerson Network Power, DCUG 2007
4 Where Data Center Power Goes Air Movement 12% Electricity Transformer/ UPS 10% Cooling 25% Lighting, etc. 3% IT Equipment 50% Source: EYP Mission Critical Facilities Inc., New York Source: Jack Pouchet, Emerson Electric Co, Digital Power Forum
5 IT Equipment Power Distribution Other 44% HDD 6% Processor 30% Memory 11% Processor Memory PCI Planar HDD Standby Other Standby 2% Planar 4% PCI 3% Source: IBM, US EPA CSC Data Center Seminar, December
6 The Rising Cost of Ownership From , computing performance increased 25x but energy efficiency only 8x Amount of power consumed per $1,000 of servers purchased has increased 4x Cost of electricity and supporting infrastructure now surpasses capital cost of IT equipment Perverse incentives -- IT and facilities costs separate Source: Ken Brill, The Uptime Institute,
7 Market Challenges Current Status No existing, widely accepted metrics for equipment or data centers re: energy performance Lack of consistent information available to the end user Challenges IT technologies/applications rapidly changing Fears of unreliability with increased efficiencies Lack of communication between IT and facilities management 7
8 Industry Efforts Green market emerging aimed at reducing energy consumption in the data center Several industry led initiatives working to provide metrics, tools, and incentives to measure and/or reduce energy use: Climate Savers Computing Initiative The Green Grid The Uptime Institute Other industry groups getting involved: Silicon Valley Leadership Group, Critical Facilities Roundtable, ASHRAE, AFCOM, others 8
9 What s the Government s Role? Federal agencies (EPA & DOE) can be catalyst Stimulate competition on energy efficiency Foster discussions between key stakeholders Provide key recommendations (EPA Report to Congress) Developing standardized test procedures and metrics to measure energy consumption (e.g., ENERGY STAR) Take the lead on best practices and metering federal datacenters Promote initiatives regionally (e.g., utilities) and globally (e.g., EU, China, Japan, Australia) 9
10 Government Leadership EPA National Computing Center RTP, NC 95,322 gross square feet, 46 Billion Btu/year LEED silver certification in 2005 Solar roof system and street lighting Energy efficient lighting in facility Building automation system, outside air economizers, variable speed HVAC systems Energy audit conducted in February For more information: 10
11 EPA/DOE Collaboration Section 453 of the Energy Independence and Security Act Requires DOE and EPA to initiate a voluntary national data center energy efficiency information program Incorporate activities from the DOE Industrial Technologies Program (i.e., Save Energy Now), DOE FEMP program, and EPA ENERGY STAR program Close coordination with numerous industry stakeholders who are developing a variety of tools and informational resources to assist data center operators in their efforts to reduce energy use More information: 11
12 DOE Data Center Initiative Save Energy Now Program Elements Develop DC Pro Software tool suite Create consensus metrics Develop and publicize case studies through pilot energy assessments Create best practices information and training curriculum Develop qualified specialists program for data centers Create guidelines for Best-In-Class data center 12
13 Key DOE Milestones May 2008: DC Pro tool beta release May - September: Training curriculum piloted September 2008: DC Pro tool version 1.0 release December 2008: Qualified Specialist training More information: www1.eere.energy.gov/industry/saveenergynow/par tnering_data_centers.html Paul Scheihing, DOE: [email protected] Bill Tschudi, LBNL: [email protected] 13
14 ENERGY STAR Rating for Data Center Infrastructure Unit of Analysis: IT Energy/Total Energy What: measure of infrastructure efficiency Captures impact of cooling and support systems Does not capture IT efficiency Why: Best available whole building measure Important to start tracking, measuring, improving Industry still developing ways to understand and measure IT output and efficiency How: Express ratio (IT/Total) as an ENERGY STAR 1-to-100 rating Percentile of performance Ratio value adjusted for: climate, tier level, other key factors 14
15 Key EPA Milestones February: Industry stakeholder meetings to discuss data collection needs March: Initiate data collection with data center operators May 2009: Conclude data collection Summer/Fall 2009: Review and analyze data and develop energy performance rating system Fall 2009: Share analytical results with industry January 2010: Launch data center infrastructure energy performance rating in Portfolio Manager; ENERGY STAR label available for stand-alone data centers 15
16 ENERGY STAR for Servers Key Elements of Draft 1 specification Initial focus on volume servers, including blades if possible Power supply efficiency/power factor Standard reporting requirements Power and temperature reporting requirements Tier 2: Energy and computing performance metric TBD Other potential requirements Idle power Power management, virtualization 16
17 Key EPA Milestones February 14: Draft 1 specification released Comments deadline March 14 April 2: On-line stakeholder meeting Mid/Late May: Draft 2 specification released Mid June: In-person stakeholder meeting June November: Additional drafts as needed December: Final specification published/effective More Information (click on New Specs in Development) 17
18 Shaping the Opportunity Data centers a key economic and CO2 reduction opportunity Few technology barriers to increased efficiency Technologies available now to reduce consumption Few options to go off the grid or diversify supply Data center operators looking for room to grow Good candidates for efficiency investments by utilities to reduce peak loads 18
DOE Data Center Energy Efficiency Program
DOE Data Center Energy Efficiency Program Paul Scheihing U.S. Department of Energy Energy Efficiency and Renewable Energy April 2009 1 DOE Industrial Technologies Program Worki king to improve th e energy
Smarter Data Centers. Integrated Data Center Service Management
Smarter Data Centers Integrated Data Center Service Management Approx. 3.500 ton CO² is generated by: Diesel Car-6l /100 km 20.000 km Airplane 5 * Brussels-Barcelona Server, 1.5 A, 24*7*365*3.000 Kwhr
Green Data Centers. Energy Efficiency Data Centers. André ROUYER Director of Standardization & Environment. The importance of standardization
Green Data Centers GOING FORWARD ENERGY EFFICIENCY TRENDS André ROUYER Director of Standardization & Environment All content in this presentation is protected 2008 American Power Conversion Corporation
Code of Conduct on Data Centre Energy Efficiency. Endorser Guidelines and Registration Form. Version 3.0.0
1 EUROPEAN COMMISSION DIRECTORATE-GENERAL JRC JOINT RESEARCH CENTRE Institute for Energy Renewable Energies Unit Ispra, 1 st January 2015 Code of Conduct on Data Centre Energy Efficiency Endorser Guidelines
Data Center Energy Use, Metrics and Rating Systems
Data Center Energy Use, Metrics and Rating Systems Steve Greenberg Energy Management Engineer Environmental Energy Technologies Division Lawrence Berkeley National Laboratory October 31, 2007 Today s s
EU Code of Conduct for Data Centre Efficiency
EU Code of Conduct for Data Centre Efficiency A Green Practice Accredited by British Computer Society (BCS) EU Code of Conduct for Data Centre Efficiency Local Organizer Practices in Data Centre Industry
Harmonizing Global Metrics for Data Center Energy Efficiency
Harmonizing Global Metrics for Data Center Energy Efficiency Dan Azevedo, Symantec Chairman - Metrics & Measurements Work Group Industry Trends Energy Efficient IT The Climate Group: Smarter technology
Reducing Data Center Energy Consumption
Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate
Energy Efficient High-tech Buildings
Energy Efficient High-tech Buildings Can anything be done to improve Data Center and Cleanroom energy efficiency? Bill Tschudi Lawrence Berkeley National Laboratory [email protected] Acknowledgements California
ENERGY STAR Data Center Infrastructure Rating Development Update. Web Conference November 12, 2009
ENERGY STAR Data Center Infrastructure Rating Development Update Web Conference November 12, 2009 Web Conference Tips Background Noise Please mute your phone until you are ready to speak. Hold & Music
FEAR Model - Review Cell Module Block
F.E.A.R. Returns: 5 Steps Toward Data Center Efficiency Today Objectives Benefits for ITS professionals Brief review of the FEAR data center Define data center efficiency Link efficiency to the FEAR data
Guideline for Water and Energy Considerations During Federal Data Center Consolidations
Guideline for Water and Energy Considerations During Federal Data Center Consolidations Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
Idle Data Analysis & Charts for the Draft 3 ENERGY STAR Computer Server Specification 10/31//08
Idle Data Analysis & Charts for the Draft 3 ENERGY STAR Computer Server Specification 10/31//08 A. Idle Power Base Levels Table 1 and Chart 1, below, show the proposed Idle categories, unit counts from
Recommendations for Measuring and Reporting Overall Data Center Efficiency
Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 1 Measuring PUE at Dedicated Data Centers 15 July 2010 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment
How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems
How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems Paul Mathew, Ph.D., Staff Scientist Steve Greenberg, P.E., Energy Management Engineer
Auditing a data centre but to what standard?
Auditing a data centre but to what standard? Matt Flowerday RCDD Capitoline LLP [email protected] www.capitoline.me Data centre auditing Capitoline has audited over 30 data centres in the UK,
DATA CENTERS: AN ACCOUNT OF FEDERAL INITIATIVES AND DATA CENTER ASSESSMENTS FOR FACILITY MANAGERS. David Cosaboon, LEED AP O+M
P a g e 1 DATA CENTERS: AN ACCOUNT OF FEDERAL INITIATIVES AND DATA CENTER ASSESSMENTS FOR FACILITY MANAGERS David Cosaboon, LEED AP O+M Facility Engineering Associates, P.C. 12701 Fair Lakes Circle, Suite
Managing Power Usage with Energy Efficiency Metrics: The Available Me...
1 of 5 9/1/2011 1:19 PM AUG 2011 Managing Power Usage with Energy Efficiency Metrics: The Available Metrics and How to Use Them Rate this item (1 Vote) font size Data centers consume an enormous amount
Greener Pastures for Your Data Center
W H I T E P A P E R Greener Pastures for Your Data Center 2 Executive Summary Following a green path, once a concept relegated to a small group of environmentalists and the U.S. Environmental Protection
DC Pro Assessment Tools. November 14, 2010
DC Pro Assessment Tools November 14, 2010 William Tschudi, PE Lawrence Berkeley National Laboratory [email protected] 510-495-2417 1 Slide 1 Assessment tools LBNL is developing tools to assist in performing
The EU Code of Conduct on Data Centres
The EU Code of Conduct on Data Centres Liam Newcombe BCS Data Centre Specialist Group Secretary EU CoC Data Centres Chair, Best Practice Working Group Development Becoming a Signatory Best Practices Use
Green Data Centre Design
Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS
Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics
On January 13, 2010, 7x24 Exchange Chairman Robert Cassiliano and Vice President David Schirmacher met in Washington, DC with representatives from the EPA, the DOE and 7 leading industry organizations
Recommendations for Measuring and Reporting Overall Data Center Efficiency
Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 2 Measuring PUE for Data Centers 17 May 2011 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations for Measuring
Enabling an agile Data Centre in a (Fr)agile market
Enabling an agile Data Centre in a (Fr)agile market Phil Dodsworth Director, Data Centre Solutions 2008 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without
Data Center Energy Efficiency. SC07 Birds of a Feather November, 2007 Bill Tschudi [email protected]
Data Center Energy Efficiency SC07 Birds of a Feather November, 2007 Bill Tschudi [email protected] Benchmark results helped to find best practices The ratio of IT equipment power to the total (or its
Protecting Our Information, Protecting Our Resources
Solutions For Business-Critical Continuity Protecting Our Information, Protecting Our Resources Energy Efficient Power And Cooling For IT And Telecommunications Network Infrastructures The Challenge You
Data Centers: How Does It Affect My Building s Energy Use and What Can I Do?
Data Centers: How Does It Affect My Building s Energy Use and What Can I Do? 1 Thank you for attending today s session! Please let us know your name and/or location when you sign in We ask everyone to
Data Center RD&D at EPRI
Data Center RD&D at EPRI Mukesh Khattar Technical Executive Critical facilities Round Table Meeting Palo Alto, CA 16 October 2015 EPRI Focus for Data Centers RD&D Address problems facing the member electric
The Mission Critical Data Center Understand Complexity Improve Performance
The Mission Critical Data Center Understand Complexity Improve Performance Communications Technology Forum Fall 2013 Department / Presenter / Date 1 Rittal IT Solutions The State of the Data Center Market
General Recommendations for a Federal Data Center Energy Management Dashboard Display
General Recommendations for a Federal Data Center Energy Management Dashboard Display Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National
Green Evaluation Metrics and Software Tool for Data Center
Green Evaluation Metrics and Software Tool for Data Center Wong Hui Shin Faculty of Computing and Informatics, Multimedia University, Cyberjaya, Selangor, Malaysia. [email protected] Saravanan Muthaiyah
ENERGY STAR for Data Centers
ENERGY STAR for Data Centers Alexandra Sullivan US EPA, ENERGY STAR February 4, 2010 Agenda ENERGY STAR Buildings Overview Energy Performance Ratings Portfolio Manager Data Center Initiative Objective
How green is your data center?
Siemens Answers: Sustainable Future How green is your data center? Istanbul June 01, 2010 Agenda 1 Solution 2 Siemens Data Center Approach 2 Designing with multiple power density zones can reduce energy
Auditing a Data Centre But to What Standard?
Auditing a Data Centre But to What Standard? Barry Elliott, RCDD Capitoline LLP [email protected] www.capitoline.eu Data Centre Auditing Capitoline has audited over 30 data centres in the UK, Ireland,
Green IT Solutions From Desktop to Datacenter. Dave Spear Sr. Engagement Manager & Sustainability Advocate dave.spear@microsoft.
Green IT Solutions From Desktop to Datacenter Dave Spear Sr. Engagement Manager & Sustainability Advocate [email protected] Agenda Our Commitment Today s Environment PC, Server, Storage Computerworld
FIRST ANNOUNCEMENT AND CALL FOR ABSTRACTS. 7th International Conference on Energy Efficiency in Domestic Appliances and Lighting (EEDAL 13)
FIRST ANNOUNCEMENT AND CALL FOR ABSTRACTS 7th International Conference on Energy Efficiency in Domestic Appliances and Lighting (EEDAL 13) 11-13 September 2013 Coimbra, Portugal Introduction Citizens and
ENERGY STAR Data Center Storage Version 1.0 Certification Body (CB) Training. RJ Meyers John Clinger
ENERGY STAR Data Center Storage Version 1.0 Certification Body (CB) Training RJ Meyers John Clinger 1 Agenda 1 ENERGY STAR Overview 2 Version 1.0 Storage Specification Overview 3 Overview of CB Details
Green HPC - Dynamic Power Management in HPC
Gr eenhpc Dynami cpower Management i nhpc AT ECHNOL OGYWHI T EP APER Green HPC Dynamic Power Management in HPC 2 Green HPC - Dynamic Power Management in HPC Introduction... 3 Green Strategies... 4 Implementation...
San Francisco Chapter. Deborah Grove, Principal Grove-Associates
Deborah Grove, Principal Grove-Associates Why Green IT is Important 1. The energy consumed by servers in the US (and associated air -conditioning) is equivalent to the annual output of about 20 new coal-fired
The Green Data Center
The Green Data Center Energy Efficient Computing In The 21st Century The Green Data Center: Energy Efficient Computing In The 21 st Century Matt Stansberry Site Editor TechTarget [email protected]
The Key to Energy Efficiency in Buildings
The Key to Energy Efficiency in Buildings ASHRAE s Response to the McKinsey Report Unlocking Energy Efficiency in the U.S. Economy Energy Efficiency offers a vast, low-cost energy resource for the U.S.
Energy Savings in the Data Center Starts with Power Monitoring
Energy Savings in the Data Center Starts with Power Monitoring As global competition intensifies, companies are increasingly turning to technology to help turn mountains of data into a competitive edge.
ECO-FRIENDLY COMPUTING: GREEN COMPUTING
ECO-FRIENDLY COMPUTING: GREEN COMPUTING Er. Navdeep Kochhar 1, Er. Arun Garg 2 1-2 Baba Farid College, Bathinda, Punjab ABSTRACT Cloud Computing provides the provision of computational resources on demand
Project context and scope
Project context and scope Cat McAlister Intertek PLC Ecodesign Technical Assistance Study on Standards for Enterprise Servers and Data Storage (Lot 9) 1 Final Stakeholder Meeting Monday, 25th April 2016
Specialty Environment Design Mission Critical Facilities
Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,
Electrical Systems. <Presenter>
Review Root Causes of Energy Inefficiency Roadmap to Maximize Energy Efficiency Best Practices Alternative Energy Sources Controls Take Aways Seek Professional Help. ENERGY INEFFICIENCY OF
SoSe 2014 Dozenten: Prof. Dr. Thomas Ludwig, Dr. Manuel Dolz Vorgetragen von Hakob Aridzanjan 03.06.2014
Total Cost of Ownership in High Performance Computing HPC datacenter energy efficient techniques: job scheduling, best programming practices, energy-saving hardware/software mechanisms SoSe 2014 Dozenten:
Datacenter Power Delivery Architectures : Efficiency and Annual Operating Costs
Datacenter Power Delivery Architectures : Efficiency and Annual Operating Costs Paul Yeaman, V I Chip Inc. Presented at the Darnell Digital Power Forum September 2007 Abstract An increasing focus on datacenter
Power Distribution Considerations for Data Center Racks
Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Table of Contents 3 Overview 4 At what voltage do you run all the IT equipment? 4 What electrical
Data Centers: Definitions, Concepts and Concerns
Data Centers: Definitions, Concepts and Concerns Arash Mousavi DCC September 2013 Agenda 1. Introduction 2. Issues in Modern Data Centers: Siemens Integrated Data Center Solutions 3. Issues in Modern Data
Increasing Energ y Efficiency In Data Centers
The following article was published in ASHRAE Journal, December 2007. Copyright 2007 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes
Greening Data Centers
Greening Data Centers Dallas Thornton SDSC Division Director, Cyberinfrastructure Services March 2, 2011 Data Centers Are Enormous Users of Power US Data Centers (TeraWatt Hours per Year) 125 US Televisions
THE GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCiE
THE GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCiE 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any
AbSTRACT INTRODUCTION background
february 20, 2007 GREEN GRID METRICS: Describing Datacenter Power Efficiency Technical Committee White Paper white paper 1 Abstract The Green Grid is an association of IT professionals seeking to dramatically
Data Center Combined Heat and Power Benefits and Implementation. Justin Grau, Google Inc. Sam Brewer, GEM Energy
Data Center Combined Heat and Power Benefits and Implementation Justin Grau, Google Inc. Sam Brewer, GEM Energy Data Center Challenges Electric Load Densification Thermal Dissipation Requires constant
A Market Transformation Programme for Improving Energy Efficiency in Data Centres
A Market Transformation Programme for Improving Energy Efficiency in Data Centres Paolo Bertoldi, European Commission Joint Research Centre ABSTRACT The European Code of Conduct for Data Centres is a voluntary
Insourcing vs. Outsourcing. Bart Leung Senior Associate, Ehvert Mission Critical
Insourcing vs. Outsourcing Bart Leung Senior Associate, Ehvert Mission Critical 1 Agenda Ehvert Mission Critical Data Centres Then and Now Power & Cooling Considerations Costs Making the Choice 2 History
Introduction to Hitachi Group Environment- conscious Data Center Programme for inspiring change
Introduction to Hitachi Group Environment- conscious Data Center Programme for inspiring change DATA CENTRE LOCATIONS Forum Kouvola, Finland Hitachi in Europe September 2011 By Ian Blond Head of Data Centre
Selecting an Industry-Standard Metric for Data Center Efficiency
Selecting an Industry-Standard Metric for Data Center Efficiency By Neil Rasmussen White Paper #157 Executive Summary The development of standards for the measurement and specification of data center efficiency
Greening The Data Center
Greening The Data Center A Five Step Method for CIO s and Data Center Managers Professionals who manage Data Centers know what is expected from them for performance and uptime. What many are only just
DATA CENTERS BEST IN CLASS
Data Energy Audit Chameleon Data Center DATA CENTERS BEST IN CLASS... By Wouter Kok, MSc, Strategic Advisor Global Data Center Practice Deerns leads the way in making data centers greener, by reducing
Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie
Energy Efficiency in New and Existing Data Centers-Where the Opportunities May Lie Mukesh Khattar, Energy Director, Oracle National Energy Efficiency Technology Summit, Sep. 26, 2012, Portland, OR Agenda
Applying Data Center Infrastructure Management in Collocation Data Centers
Applying Data Center Infrastructure Management in Collocation Data Centers Infrastructure Management & Monitoring for Business-Critical Continuity TM Applying Data Center Infrastructure Management (DCIM)
Green Data Centre: Is There Such A Thing? Dr. T. C. Tan Distinguished Member, CommScope Labs
Green Data Centre: Is There Such A Thing? Dr. T. C. Tan Distinguished Member, CommScope Labs Topics The Why? The How? Conclusion The Why? Drivers for Green IT According to Forrester Research, IT accounts
The Evolution of Qualcomm s Data Center Strategy. Norm Fjeldheim SVP & CIO
The Evolution of Qualcomm s Data Center Strategy Norm Fjeldheim SVP & CIO Qualcomm Overview Enabling the Wireless Industry: Developed Code Division Multiple Access (CDMA) technology Continually advancing
How to build your Data Center Digitice roadshow Vaasa 3.12.2015
How to build your Data Center Digitice roadshow Vaasa 3.12.2015 Mikko Aho Sales Director 044 593 4698 1 A Strong Family The Friedhelm Loh Group a successful business 11.500 employees worldwide 78 int.
Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
AIA Provider: Colorado Green Building Guild Provider Number: 50111120. Speaker: Geoff Overland
AIA Provider: Colorado Green Building Guild Provider Number: 50111120 Office Efficiency: Get Plugged In AIA Course Number: EW10.15.14 Speaker: Geoff Overland Credit(s) earned on completion of this course
Measuring Energy Efficiency in a Data Center
The goals of the greening of the Data Center are to minimize energy consumption and reduce the emission of green house gases (carbon footprint) while maximizing IT performance. Energy efficiency metrics
THE ROOFPOINT ENERGY AND CARBON CALCULATOR A NEW MODELING TOOL FOR ROOFING PROFESSIONALS
THE ROOFPOINT ENERGY AND CARBON CALCULATOR A NEW MODELING TOOL FOR ROOFING PROFESSIONALS James L. Hoff, VP of Research Center for Environmental Innovation in Roofing Tools and Models Tools require models
Richard Sweetser, Principal Investigator, EXERGY Partners Corp. Email: [email protected], Phone: 703.707.0293
Richard Sweetser, Principal Investigator, EXERGY Partners Corp. Email: [email protected], Phone: 703.707.0293 U.S. DOE Industrial Distributed Energy Portfolio Review Meeting Washington, D.C.