Pt 100 Temperature-Relay TR 122 D(A)

Similar documents
Safety technique. Emergency stop module BO 5988 safemaster

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start * see variants. Applications.

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX M1 02 E MES FLOW CALCULATOR /1

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

13 SERIES. Electronic step relays A

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

ADM1TE 5/30A DIN rail single phase two wire energy meter

Shutter Actuator Standard, 4-fold, 230 VAC, MDRC RA/S , GH Q R0111. ABB i-bus EIB

Electronic Pressure Switch EDS 300

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

mecotron Safety relay ESTOP-2 For emergency stop monitoring

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

HERZ-Thermal Actuators

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q R0001

RM35UA13MW. range V. Main. Product or component type. Relay monitored parameters

Temperature Controller CD401/CD901/CD701/CD501/CD100/CD101 Instruction Manual

TEMON 8-C. Doc. N MO-0370-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 8-C OPERATION MANUAL. Microener - Copyright 2010 FW 2.2 Date Rev.

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

Fixed - Over/Under voltage limits, ( ) U N respectivity Link selectable - 5 min or 10 min delay. Fixed limits

E-STOP relays, safety gate monitors

PNOZsigma - Base units

R4D0-FB-IA* FieldBarrier. Features. Assembly. Function. Connection IN + - S OUT Spur 2. Spur 1. Zone 1. Zone 0

GREISINGER electronic GmbH

Quick Connect. quick - simple - efficient.

RM4TG20 three-phase network control relay RM4-T - range V

Telefon (+45) Telefax (+45) Installation and operating manual

MONITORING RELAYS. w VOLTAGE MONITORING RELAY UR5U1011. w SCHRACK-INFO. w TECHNICAL DATA

PROCESS AUTOMATION MANUAL OVERSPEED/UNDERSPEED MONITOR KF**-DWB-(EX)1.D ISO9001

Safety Relays ESM/ESM-F

Electronic Pressure Switch EDS 3000

SKR - industry relay

E-STOP relays, safety gate monitors

Contents. Document information

TLK 48 MICROPROCESSOR-BASED DIGITAL ELECTRONIC REGULATOR

TMS TANK MANAGEMENT SYSTEM

Circuit Breakers. NRC Series. NRC Series

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Thyristor-controlled power supplies and battery chargers

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

Safety automation solutions

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

DALI RC BASIC SO. Control unit Operating instructions

Product and functional description

Drayton Digistat +2RF/+3RF

H/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current.

ABB i-bus EIB / KNX Analogue Input AE/S 4.2

E-STOP relays, safety gate monitors

Control Devices Catalogue. Control Devices. Preferred and Standard Products

ABB i-bus EIB Shutter Actuators JA/S , JA/S , JA/S , JA/S M, JA/S M, JA/S

DLP-PU/E Instruction Manual

VEO. V4PF480Y/277VSYTK02 Art.Nr.: V4PF480Y/277VSYTK02P Art.Nr.: TECHNICAL DATA

Power Supplies 3. SDN-P DIN Rail Series

Short information Parameters are programmed via front-side membrane keypad

Thermistor motor protection

PHOENIX CONTACT Features

Power Supply and Indicator Unit Type Fig. 1 Type Mounting and Operating Instructions EB 9539 EN

Panel Meters and Controllers Modular Panel Meter Type EDM 35

Switch Actuator, 8-fold, 10 A, MDRC AT/S , GH Q R0111

GAE953 Electrical Alarm Unit 19" with Indicator

instabus KNX / EIB System System E F G H

Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in

Installation manual. Generator Paralleling Controller GPC multi-line C

C13 User Manual Document ID: 2CMC486004M0201 Revision: A

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

TCR easy Plus Alarm. Operating Instructions

Preset Counter signo 721

Pluggable interface relays CR-P Pcb relays

E-STOP relays, safety gate monitors

ISOMETER IRDH275. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Vorläufiges Datenblatt

*.ppt 11/2/ :48 PM 1

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)

RRV934. Multi-controller. Synco living

Technical data. General specifications. Signal voltage V DC Signal duration. 1 s Input 2. Signal voltage. 1 s Analog output.

TIG INVERTER INSTRUCTION MANUAL

DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS. Construction Automotive Industry

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

Programmable Room Thermostat 7 Day (5-2 Day) Models: / Power Supply: Battery / Mains

AZ420 MINIATURE GENERAL PURPOSE RELAY

650W Single Output Power Supply 15V 24V. 27V 48V Rated Current. 0 ~ 100A 0 ~ 50A 0 ~ 40A 0 ~ 27A 0 ~ 24A 0 ~ 13.6A Rated Power

Photoelectric switches WLL 170(T), fibre-optic cables LL 3: flexible solutions with fibre-optic cable systems

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Heating Controller. Building Technologies HVAC Products

Contact expansion modules

Reference V, 50 Hz A V,60 Hz V, 50/60 Hz A V, 50/60 Hz V, 50 Hz A V, 60 Hz

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

1000W Single Output Power Supply 15V 24V. Protection type: Total Power limit, Latch-style (Recovery after reset AC power ON or inhibit)

is then retained absolutely without interruption.

RVL470. Heating Controller. Building Technologies HVAC Products. Series B

Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases

CONFIGURABLE SAFETY RELAYS

FIREDEX Conventional Fire Panels

Operating Manual for the Electronic Built-in Interval Timer. Micro II (Countdown Timer)

Technical Manual. FAN COIL CONTROLLER COOLING or HEATING ANALOG or PWM Art A

Contactless Encoder RI360P0-QR24M0-INCRX2-H1181

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

E-STOP relays, safety gate monitors

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit

Transcription:

MINIPAN digital panel meters, temperature- and mains controlling, special purpose instruments for customer requirements www.ziehl.com Operating Manual Pt 100 Temperature-Relay TR 122 D(A) Page 1 von 14

Index Page Application and short description... 3 Overview of the functions... 3 Connection plan... 3 Programs... 4 Important informations... 4 Installation... 5 Starting... 5 Display mode... 5 Menu mode... 6 Parameter setting mode... 6 Indication of the digital display... 8 Operation Program 1 1 temperature sensor / 2 limit values... 9 Operation Program 2 1 resistance / 2 limit values... 10 Function diagram... 11 Factory setting... 11 Error search and measures... 12 Technical data... 12 Housing... 14 Page 2 von 14

Application and Short Description Switching-Relays Typs TR 122 D(A) monitor the input-signal for 2 limits. The TR 122 DA transduces the measured temperature/resistance to a proportional DC-current. Applications of the TR 122 D(A) are: Monitoring of temperatures with pre-alarm and alarm in machines and plants Controlling of temperatures e.g. for heated sample gas lines or refrigerating plants Transducer for Pt 100 (RTD) and resistance (TR 122 DA only) Overview of Functions 1 input sensor, Pt 100 (RTD) or resistance Measuring ranges -199 C / 0 Ω Resolution 0,1 C / Ω within the ranges -19,9...99,9 C / 0-99,9 Ω 2 relay outputs (each 1 change-over contact) 1 analog output 0/4-20 ma scaleable (TR 122 DA only, not potentially separated from the inputs) Universal power supply AC/DC 24-240 V Storage and display of the measured MIN- and MAX-values Connection Plans TR 122 DA K1 K2 1 2 3 4 5 6 7 8 9 10 11 12 3-wire temperature sensor Pt 100 / resistor 2-wire ~ Us Netz + ~ - + A TR 122 D K1 K2 1 2 3 4 5 6 7 8 9 10 11 12 3-wire temperature sensor Pt 100 / resistor 2-wire ~ Us Netz + ~ Page 3 von 14

Programs 2 programs (Pr) can be selected for measuring of temperatures with Pt 100 (RTD) and for measuring resistances. Due to these programs, the device can be adapted very easily to the application. Choose the program, which fits to your application and after that change the parameters! In case of changing the program, each parameter is being resetted to "factory setting". (see chart "factory setting"). Choosing the programs: When applying the power supply hold the pushbutton Set for 10 s. Then the program (Pr1 or Pr2) can be selected with the pushbuttons up/down and confirmed with Set. Pr Input Measuring Range 1* 1 temperature-sensor Pt100-200 +850 C (RTD) 2 1 resistance 0 850 Ω * factory setting Important Information ATTENTION Dangerous electrical voltage! May lead to electrical shock and burn. Before beginning of work switch unit and equipment free of voltage. To use the equipment flawless and safe, transport and store properly, install and start professionally and operate as directed. Only let persons work with the equipment who are familiar with installation, start and use and who have appropriate qualification corresponding to their function. They must observe the contents of the instructions manual, the information which are written on the equipment and the relevant security instructions for the setting up and the use of electrical units. The equipments are built according to DIN / EN and checked and leave the plant according to security in perfect condition. If, in any case the information in the instructions manual is not sufficient, please contact our company or the responsible representative. Instead of the industrial norms and regulations written in this instructions manual valid for Europe, you must observe out of their geographical scope the valid and relevant regulations of the corresponding country. Page 4 von 14

Observe the maximum temperature permissible when installing in switchgear cabinet. Make sure sufficient space to other equipment or heat sources. If the cooling becomes more difficult e.g. through close proximity of apparatus with elevated surface temperature or hindrance of the cooling air, the tolerable environmental temperature is diminishing. Attention! Universal power supply The unit is equipped with an universal power supply, that is suitable for DC- and ACvoltages. Before connecting the unit to the current, make sure that the allowed scope of voltage of the control voltage Us, written on the lateral type plate, corresponds to the supply voltage of the unit!! Attention! When all relays are programmed in operating-current mode (= pick up at alarm), a loss of supply-voltage or an instrument failure can remain unidentified. When the relay is applied as a monitoring instrument the operator must ensure, that this is recognized by regular examinations. We recommend to program and accordingly evaluate at least one relay in the closed-circuit current mode (released = alarm). Installation The unit can be installed as follows: Installation in switchgear cabinet on 35 mm mounting rail according to EN 60715 With screws M4 for installation on walls or panel. Connection according to connection plan or type plate. Putting into operation Decimal point behind the last digit: Off = display mode On = menu mode, select the menu items blinking = parameter setting mode Display Mode Indication of the current measured value. The temperature is shown in degrees centigrade and the resistance in Ω. Function of buttons UP/DOWN Push short Push for > 2 s change into menu mode Display of the stored MIN- or MAX-values Function of button SET/RESET Push short Display sensor / alarm limit 1 / alarm limit 2 Push for 2 s Reset restart interlock Push for 4 s Display of chosen program Push for 10 s Display of software version Page 5 von 14

Menu mode (Decimal point behind the last digit ON) Selection of the menu items for changing the parameters Function button UP/DOWN Push short Selection of menu item; change into display mode Function button SET/RESET Push short Change into parameter setting mode Parameter setting mode (Decimal point behind the last digit FLASHES) Function button UP/DOWN Press short/long Adjustment of parameter value (slow/fast) Function button SET/RESET Press short Storage of setting and choice of next parameter. Change into menu mode after the last parameter Parameterizing the sensor: Choose menue item with up/down until in display LA and the line-resistance or 3-L alternate. Enter with Set in parameterizing sensor. Set cable resistance or 3-wire configuration (3-L). 2-wire configuration, cable resistance compensation: Short-circuit the wires nearby the sensor and measure the cable resistance. Set parameter LA on this value. We recommend 3-wire connection. Parameterizing of the alarms (AL1 / AL2): Choose menu item with up/down until AL 1 and limit (limit value) alternate in display, e.g. AL1 und 130 for 130 C. Begin to parameterize with Set. Adjust limit with up/down. Adjust hysteresis. Negative hysteresis = MAX-switching point, the relay switches when the adjusted limit is reached and switches back when the signal is fallen by the hysteresis. E.g. limit 130 C and hysteresis -5 C: Relais switches at 130 C and switches back at 125 C. Positive hysteresis vice versa = MIN-switching point. Alarm delay time dal: An alarm is suppressed for the adjusted time, short-timed exceeding of the limit does not cause an alarm. Switch-back delay dof: An alarm is only switched off after the signal is below the limit and after delay of this time, e.g. a cooling ventilator can cool further on for this time to avoid, that it has to switch be switched on again after a short time. Function of relay: r-closed-current circuit mode, relay is picked up in GOOD-state (=limit not reached) and releases when the limit is exceeded. Advantage: errors and faults normally cause an alarm. Disadvantage: alarm also when supply-voltage is switched off and after switching on until the relay has picked up. Unfavourable e.g. with transformers, particularly, when the supply-voltage of the TR 122 D(A) comes from a monitored transformer. A-Operating-current mode: relay is released in GOOD-state and picks up when the limit is exceeded. No alarm at errors and when supply-voltage switched off. Used normally to switch ventilators or heatings or for tripping of transformers. r-l / A-L: A alarm switches locked. Reset with "Reset" only after value within the limit (with hysteresis) and end of the switch-back delay. Ready for Reset is indicated with A1L in the display mode. Page 6 von 14

Error report: With Err it can be selected, if the relay switches in the alarm state in case of sensor-error Er1-2 (short circuit or break). (on / off) Analog output (ovt): (TR 122 DA only) Here the analog output can be parameterized and scaled. Enter with Set. Select between current-output 0- or 4-20mA. Go on to scaling ZERO with button Set. Scale the value for Zero (0/4 ma) and confirm with Set. Scale the value for Full-Scale (20mA). Finish parameterizing of output with Set. Sensor simulation (Si): A measured temperature can be simulated with the buttons up/down. All functions of the unit work as if this temperature was really measured. If there is no button pushed for 15 minutes, the device automatically switches back into the display mode. Cod: After setting all parameters they can be protected by activating the code lock. After pushing Set, the display indicates Pin. Adjust with buttons up/down Pin 504 (factory setting). After pushing Set, code lock can be activated or switched off. After pushing Set again, an individual Pin can be selected (write down). When code lock is activated all parameters can be seen but not be changed anymore. Setting of the lock: off : all parameters can be changed EL : only the limits (alarms) can be changed on : no parameters can be changed In case of problems with the code lock (forgotten Pin) the lock can be switched off and the Pin can be set back to 504, by pushing button set while connecting the device to supply-voltage until Cod / off is indicated in the display. Tips: - After finishing one menu item it is switched automatically on the next one. - When the right decimal point in the 7 segment display is on, the display mode has been left, and the menu items can be chosen with up/down (menu mode). - When the right decimal point blinks, you are in the parameter setting mode and can change the setting with up/down. - Long pushing on up/down speeds up the changes in the display. - Pushing button up and down at the same time sets values to zero. - With reset (press set/reset for 2s) the display mode can be reached from every position (exception: simulation) of the parameter setting mode (the last selected value in is being stored). Page 7 von 14

Indication of the Digital Display: A1, A2 = alarm 1, alarm 2 active A12 = alarm 1 and alarm 2 active A1L, A2L = alarm locked, for setting back reset is necessary LA = 2-wire cable resistance 3-L = 3-wire configuration AL1, AL2 = alarm limit H = hysteresis dal = alarm delay (time delay until alarm) dof = switch back delay (time delay until alarm switches back to good) rel = function of relay r = closed-circuit current mode A = operating current mode r-l, = closed-circuit current with interlocked switching (Locked) A-L = operating current with interlocked switching (Locked) ovt = analog output: 0-20 ma, 4-20mA scalable,,, = value, at which 20 ma is put out = value, at which 0/4 ma is put out on, off = on/off Si = simulation Cod = code (pin) EL = Easy Limit, only limits adjustable Pin = PIN (factory-setting = 504) Page 8 von 14

Operation: Pr1 / Temperature-Measuring with Pt 100 (RTD) Operation with pushbuttons: Display mode Up Down Set Reset = >2s Set 2 s = Max 2 s = Min Sensor AL1-199 AL2-199 Parameter setting mode LA Typ 0..99.9 3-l Menu mode AL1 AL2 Limit alarm 1 Limit -199.. 850 Limit... H -199...999 dal 0..999 s dof 0..999 s rel r A r-l A-L Err on off * ovt Typ Typ 0-4- -199,,, Zero -199 Fullscale up/down at the same time sets values on zero. code-reset = 2 s set while switching on power-supply. (Pin = 504) Cod Si on/ EL/ off Pin -199 0.. 999 o.k. on/ EL/ off Pin 0.. 999 error messages: Er 1 = sensor short circuit Er 2 = sensor break Err = general error EEE = sensor values too high -EE = sensor values too low 3x Err 3x on/el/off * TR 122 DA only Page 9 von 14

Operation: Pr2 / Measuring of Resistance Operation with pushbuttons: Display mode Up Down Set Reset = >2s Set 2 s = Max 2 s = Min R AL1 0 AL2 0 Parameter setting mode Menu mode LA AL1 Typ 0..99.9 3-l Limit alarm 1 Limit 0... 850 H 0.. 850 dal 0..999 s dof 0..999 s rel r A r-l A-L Err on off AL2 Limit... * ovt Typ Typ 0-4- 0,,, Zero 0 Fullscale up/down at the same time sets values on zero. code-reset = 2 s set while switching on power-supply. (Pin = 504) Cod Si on/ EL/ off Pin 0 0.. 999 o.k. on/ EL/ off Pin 0.. 999 error messages: Er 1 = sensor short circuit Er 2 = sensor break Err = general error EEE = sensor values too high -EE = sensor values too low 3x Err 3x on/el/off * TR 122 DA only Page 10 von 14

Action Chart: ϑ sensor ϑ 1 ϑ 2 t Relay (r), LED t M dal t M dof Relay locked (rl) Reset t t ϑ M 1 = measuring time = LIMIT ϑ 2 = LIMIT + Hysteresis Reaction time of the unit measuring time t M If the temperature is changing constantly, the measuring time t M is about 2 s. If the temperature is changing rapidly, e.g. through simulation of the temperature with an external potentiometer, the measuring time t M is about 4 6 s. In case of sensor error the measuring time t M raises to 7 10 s. Factory Setting: In case of program change all parameters are set back upon factory setting. Menuitem Parameter LA (line compensation) Pr1 Value Pr2 3-l 3-l Limit 1 150 200 H (Hysteresis) -2.0-2.0 Alarm 1 dal (Alarm-delay) 0 0 AL 1 dof (Delay-Alarm off) 0 0 rel (Relaisfunktion) r r Err (Sensor-Error) on on Limit 2 100 100 H (Hysteresis) -2.0-2.0 Alarm 2 dal (Alarm-delay) 0 0 AL 2 dof (Delay-Alarm off) 0 0 rel (Relaisfunktion) r r Err (Sensor-Error) on on si 0.0 0.0 Type 0-4- ovt (Zero) 0.0 0.0,,, (Fullscale) 200 200 Off / EL / on off off Cod Pin 504 504 My Data Page 11 von 14

Error search and measures Display EEE -EE sensor break or temperature too high sensor interruption or temperature too low Unit cannot be programmed Code lock The code lock gives protection against unauthorized manipulation of the unit. When code lock is activated the parameters cannot be changed. The pin can be set by the user. Pin unknown? Make code-reset: When switching in supply-voltage keep pushed button Set for 2 s. Display indicates: "888"; "Cod"; "off"; "888" release button Set. Code = off, Pin = 504. Indicated temperature does not correspond to the sensor temperature Check connected sensor type Check cable resistance Display indicates Er1 or Er2 Er1 Sensor short circuit Er2 Sensor interruption Technical data Rated supply voltage Us: AC/DC 24 240 V, 0 / 50 / 60 Hz < 3 W < 5 VA Tolerance DC 20,4-297 V, AC 20-264 V Relay output: Switching voltage Switching current Switching capacity 2 x 1 change-over contact (CO) max. AC 415 V max. 5 A max. 1250 VA (ohmic load) max. 48 W at DC 24 V Reduction factor for cos ϕ 0,7 0,5 Nominal operational current Ie: AC15 Ie = 1 A Ue = 400 V Ie = 2 A Ue = 250 V DC13 Ie = 2 A Ue = 24 V Ie = 0,2 A Ue = 125 V Ie = 0,1 A Ue = 250 V Recommended fuses for contacts T 3,15 A (gl) Expected life mechanical 1 x 10 7 switching cycles Expected life electrical 1 x 10 5 switching cycles at AC 250 V / 5 A 2 x 10 5 switching cycles at AC 250 V / 3 A 6 x 10 5 switching cycles at AC 250 V / 1 A Page 12 von 14

Test conditions EN 50178 / EN 60 947 Rated impulse voltage 4000 V Contamination level 3 Rated insulation voltage Ui 250 V On-time 100 % Rated ambient temperature range -20 C... +60 C EN 60068-2-1 dry heat EMV interference resistance EN 61000-6-2 EMV emitted interference EN 61000-6-3 Vibration resistance EN 60068-2-6 2 25 Hz ±1,6 mm 25... 150 Hz 5 g Sensor connection: Measuring time t M Pt 100 (RTD) according to EN 60751: < 2,5 s < 5 s in case of changes > 5 K or < 1 K < 15 s in case of sensor error Measuring range C Short circuit Ohm Break Ohm Sensor resistance + line resistance Ohm Sensor min max < > max Pt 100-199 860 15 400 500 Tolerance Sensor current Temperature drift Analog output: Current output 0/4-20 ma Temperature drift Error from impedance At error short circuit Er1: Other errors ±0,3 % of measured value ±0,5 K 0,8 ma <0,04 C/K not electrically insulated from the inputs max. 500 Ω, Precision 0,3 % of Full-Scale < 0,015 %/K (250 Ω - load)/250 Ω * 0,3 % of current output 0 ma output 22 ma Housing: Design S12 Dimensions (height x width x depth) 82 x 42 x 121 mm Wire connection, one wire 12-pole, each 2 x 1,5 mm 2 Protection class housing IP 40 Protection class terminal IP 20 Mounting position any Installation Snap mounting on DIN-rail 35 mm According to EN 60715 or screws M4 Weight app. 250 g Subject to technical changes Page 13 von 14

Design S12: Dimensions in mm 5 38 17,5 1 5 36 23,5 82 104,5 41,5 80 61 41 10 7,5 17 11,5 1 16 2 5 2 1 2 3 4 5 6 7 8 9 10 11 12 6 Jackets for coding - pins 82 34 1 3 41,5 1 Cable bushing 2 Mounting bore - hole Base 3 Unlatching (only with rail - mounting) 14 27,5 116 This and other operating manuals, as far as available also in other languages, you find on our homepage: www.ziehl.com Page 14 von 14