HIGH BAY Beta Lighting High Bay luminaires provide HID or CFL illumination for high-ceiling commercial and industrial applications. This section includes details of each luminaire including reflector type, optical description, lamp selection, voltage, finishes, options and accessories. 16" Glass Prismatic Aisle Light 16" Prismatic 250 Beta Lighting 800-236-6800 www.beta-lighting.com
SECTION CONTENTS PAGE CONTENTS 252-253 Optical Distributions 254-255 Key Features and Benefits and Master Nomenclature Max Catalog Wattage Housing Prefix 256-257 16" Glass Prismatic 400W Die-Cast BHB-G16-DC 258-259 Aisle Light 450W Die-Cast BHB-ALR-DC 260-261 16" Prismatic 450W Die-Cast BHB-P16-DC 262-263 22" Prismatic 1000W Die-Cast BHB-P22-DC 264-265 22" Translucent Reflector 1000W Die-Cast BHB-T22-DC 266-267 16" Aluminum 450W Die-Cast BHB-A16-DC 268-269 22" Aluminum 1000W Die-Cast BHB-A22-DC 270-271 22" CFL Prismatic (4) 57W Formed Steel BHB-P22-FS 272-273 22" CFL Aluminum (4) 57W Formed Steel BHB-A22-FS 274-275 High Bay Mounting Options and Accessories 22" Prismatic 22" Translucent 16" Aluminum 22" Aluminum www.beta-lighting.com 800-236-6800 Beta Lighting 251
HIGH BAY OPTICAL DISTRIBUTIONS G: Glass Prismatic This clear, borosilicate glass prismatic reflector provides 93-percent efficiency and a minimum of 22-percent uplight. These luminaires are ideal for industrial applications where a heavy concentration of cutting fluids are used, as well as commercial and retail applications. P: Acrylic Prismatic This prismatic reflector provides over 90-percent efficiency and just under 20-percent uplight. These luminaires are ideal for industrial, commercial and retail applications. 252 Beta Lighting 800-236-6800 www.beta-lighting.com
HIGH BAY OPTICAL DISTRIBUTIONS A: Aluminum Reflector This hydro-formed aluminum reflector provides 80-percent efficiency. These luminaires are ideal for industrial, commercial and retail applications. AL: Aisle Light This metalized, thermal-formed elliptical-shaped reflector produces an asymmetric wide light distribution emphasizing both vertical and horizontal illuminance. These luminaires are ideal for aisle-lighting applications. www.beta-lighting.com 800-236-6800 Beta Lighting 253
HIGH BAY KEY FEATURES AND BENEFITS Optical Systems Computer-designed reflectors engineered for maximum performance and control Reflector systems make use of the latest high-efficiency materials to further optimize lighting results Lamp Mogul base HID lamp or 4-pin compact Fluorescent lamps included Housing Die-cast aluminum housing Unique design to lower ballast temperatures Electrical HID: High power factor ballasts are standard CFL: Self-sensing electronic ballasts are standard Ballast and other electrical components are strategically located and heat sunk to the aluminum housing for maximum longevity Electrical characteristics of every luminaire are tested prior to packing and shipping Finish Ballast housing: Exclusive Colorfast DeltaGuard finish with 7-year warranty Labels UL listed for damp locations ANSI lamp wattage label supplied 254 Beta Lighting 800-236-6800 www.beta-lighting.com
BHB SERIES Glass Prismatic Acrylic Prismatic 16" and 22" Translucent Reflector Aluminum Reflector 16" and 22" Aisle Light Beta High Bay Fixtures BHB Series See following pages for specific product availability. ORDER CODE LOGIC BHB P22 DC HSB O 400 PMH R7 Product Family Housing Indicator Ballast Housing Mounting Options Lamp Rating (PMH, MHX or HPS) Lamp Selections Ballast Voltage BHB G16 = 16" Glass Prismatic DC = Die-Cast ALR = Aisle Light Reflector FS = Formed Steel HCP = Hook, Cord & Plug P16 = 16" Prismatic Reflector HSB = Hinged Splice P22 = 22" Prismatic Reflector Box O = Open Rated 026 CFL EB = Electronic Ballast E = Enclosed Rated 032 CFL DT = Dual-tap S = S Rated 042 CFL MT = Multi-tap 057 CFL 12 = 120 Volt 150 PMH/HPS 20 = 208 Volt 175 MHX 24 = 240 Volt 4 = 4 lamps 200 PMH 27 = 277 Volt 6 = 6 lamps 250 PMH/MHX/HPS R7 = 277 Volt Reactor 8 = 8 lamps 300 PMH or Lamp Quantity (CFL) T22 = 22" Translucent Reflector A16 = 16" Aluminum Reflector A22 = 22" Aluminum Reflector 34 = 347 Volt 320 PMH (Canada) 350 PMH 400 PMH/MHX/HPS 450 PMH L5-15R = Locking Receptacle 120V WG-A = 16" (For Aluminum reflector) L6-15R = Locking Receptacle 208V/240V WG-A/OC = 16" w/re-lamp Opening L7-15R = Locking Receptacle 277V 48 = 480 Volt 5_ = 50 Hz 750 PMH Accessories (Field Installed) 10X PMH/MHX/HPS (International) Options (Factory Installed) (For Aluminum reflector) L8-20R = Locking Receptacle 480V WG-AJ = 22" (For Aluminum reflector) AD = Acrylic Drop Prismatic Lens PH-1 = Power Hook w/120v Receptacle WG-AJ/OC = 22" w/re-lamp Opening AF = Air Filter PH-2 = Power Hook w/277v Receptacle (For Aluminum reflector) BN = Ballast Noise Suppressor PH-3 = Power Hook w/208v Receptacle WG-AP = 16" (For Prismatic reflector) CL = Conical Lens PH-4 = Power Hook w/240v Receptacle WG-AP/OC = 16" w/re-lamp Opening DM = Dimming PH-5 = Power Hook w/480v Receptacle (For Prismatic reflector) EM = Emergency Battery Pack SC-5 = Safety Cable with Hang Fast WG-AR = 22" (For Prismatic reflector) F = Fuse SL-C = Steady-Lock for Cable or Chain WG-AR/OC = 22" w/re-lamp Opening FA = Flat Acrylic Lens SL-E = Steady-Lock for Eyebolt Q (For Prismatic reflector) FAW = Flat Acrylic Lens with Q = Quartz Standby Lamp Abbreviations: PMH = Pulse Start Metal Halide, MHX = Metal Halide, HPS = High Pressure Sodium, CFL = Compact Fluorescent A 5_ indicates a 50 Hertz ballast. See page 11 for the second number designator to specify voltage required.the table above is for reference only see specific product pages for actual ordering options. SS = Stainless Steel Hardware TG = Tempered Glass Flat Lens TGW = Tempered Glass Flat Lens with TL = Two-Level 360 Integrated Motion Sensor www.beta-lighting.com 800-236-6800 Beta Lighting 255
BHB-P16-DC 16" PRISMATIC HIGH BAY Optical System This prismatic reflector provides 92-percent efficiency and approximately 19-percent uplight. Lamp Maximum wattage: 450W PSMH, 400W MH, 400W HPS Mogul base HID lamp included: coated PSMH & MH, clear HPS Housing and Reflector Die-cast aluminum ballast housing Clear, acrylic prismatic reflector Electrical High power factor ballasts are standard Ballast housing designed to reduce thermal load on electrical components Finish Ballast housing: Exclusive Colorfast DeltaGuard finish with 7-year warranty Labels UL listed for damp locations ANSI lamp wattage label supplied AVAILABLE FINISH COLOR: WH White Standard Color CE DELTAGUARD 7-Y E A R W A R R A N T Y FI NIS H 260 Beta Lighting 800-236-6800 www.beta-lighting.com
DIE-CAST HOUSING BHB-P16-DC 4000 8000 12000 0 120 90 60 30 Candlepower distribution curve of 400W MH. Efficiency = 90.9%; SC - 1.7 Candlepower Summary Angle Mean CP Lumens 0 6213 5 6343 607 15 6664 1907 25 7541 3543 35 9389 5802 45 8643 6389 55 3872 3677 65 1863 1954 75 1500 1604 85 1537 1674 95 1524 1651 105 1352 1423 115 1081 1066 125 729 658 135 455 366 145 404 253 155 288 130 165 53 22 175 20 2 180 14 Zonal Lumens and Percentages Zone Lumens % Lamp % Fixture 0-30 6056 16.82 18.51 0-40 11858 32.94 36.23 0-60 21924 60.90 66.99 0-90 27155 75.43 82.98 40-90 15297 42.49 46.74 60-90 5231 14.53 15.98 90-180 5571 15.48 17.02 0-180 32727 90.91 100.00 A B A = 16.2" (277 mm) B = 19.0" (483 mm) See page 255 for order code logic. 16" PRISMATIC DIE-CAST HIGH BAY (Example: BHB-P16-DC-HSB-O-400PMH-MT) Product Housing Ballast Mounting Lamp Lamp Ballast Options Family Indicator Housing Options Rating Selection Voltage (Factory Installed) BHB P16 DC HCP E 150 PMH/HPS MT AD HSB O 175 MHX 12 AF S 200 PMH 20 BN Formerly BBA 250 PMH/MHX/HPS 24 CL 300 PMH 27 F 320 PMH R7 FA 350 PMH 34 FAW 400 PMH/MHX/HPS 48 Q 450 PMH 5_ TL Ballast & Lamp Footnotes All fixtures are standard with multi-tap (MT) ballast R7 (277V reactor ballast) For PMH only, must be specified All fixtures available in 480V ballast International 50 Hertz ballasts available; see page 11 for specification information Coated lamp standard with PMH and MHX fixtures; clear lamp for HPS Lamp Rating Definitions and Ordering Guidelines: E (Enclosed) Lamp provided can be used in enclosed fixture only, must order fixture with lens (AD, CL, FA or FAW) option (200W maximum) O (Open) Lamp provided can be used in both open and enclosed fixtures S (S Rated) For use with 400W MHX only; lamp approved by lamp supplier to operate without enclosure, however this does not meet NEC Article 410.73 (F)(5) consult local inspector prior to ordering PMH 150W & 200W PMH wattages can be ordered with O or E; if E is selected the fixture must be ordered with lens (AD, CL, FA or FAW) option; 250W, 300W, 320W, 350W, 400W & 450W PMH cannot be enclosed must order with O PMH fixtures ordered with O and a lens option will be provided with open rated lamp and socket, as well as selected lens option MHX 175W MHX available with lens only must order with E; 250W MHX must be ordered with an O; 400W MHX must be ordered with S or an O 250W & 400W fixtures can not be enclosed HPS All HPS wattages must be ordered with O and can be ordered with or without lens (AD, CL, FA or FAW) option; 250W & 400W HPS can not be enclosed Ambient Temperature Limits on pages 426-427 Mounting Footnotes see page 274 for details HCP (Hook, Cord & Plug) Heavy-duty steel hook with safety-lock spring and 30-inch (762 mm) cord with NEMA locking type plug; must specify voltage other than MT HSB (Hinged Splice Box) Multiple knockouts are available for both surface wiring or pendant mounting Modular Wiring is available consult factory Option Footnotes AD (Acrylic Drop Prismatic Lens) Reduces lamp brightness and provides a smoother pattern of light; measures 3.2" (81 mm) deep; 200W maximum AF (Air Filter) Helps prevent dirt contaminants from entering the optical chamber (for use with lens options); 175W maximum BN (Ballast Noise Suppressor) Reduces the noise emitted by the ballast (450W maximum); 35 C ambient maximum for 400W & 450W CL (Conical Lens) Reduces lamp brightness and provides a smoother pattern of light; measures 1.7" (43 mm) deep; 200W maximum F (Fuse) Must specify voltage other than MT FA (Flat Acrylic Lens) Flat acrylic lens to enclose lamp, 200W maximum FAW (Flat Acrylic Lens & ) Flat acrylic lens with wire guard for added protection; 200W maximum Q (Quartz Standby) Delay-relay type and includes 100W T4 dual-contact quartz lamp (not available with 277V reactor ballast) TL (Two-Level) 2-level integrated 360 motion sensor; time control is externally adjustable from 30-seconds to 20-minutes; not available with 277V reactor ballast Accessories (Field Installed) See page 275 for details L_- _ Locking Type Receptacle PH- _ Power Hook WG-AP 16" Prismatic No Lens WG-AP/OC 16" Prismatic Re-lamp Opening SC-5 Safety Cable with Hang Fast www.beta-lighting.com 800-236-6800 Beta Lighting 261
BHB-P22-DC 22" PRISMATIC HIGH BAY Optical System This prismatic reflector provides 94-percent efficiency and approximately 17-percent uplight. Lamp Maximum wattage: 750W PSMH, 1000W MH, 400W HPS Mogul base HID lamp included: coated PSMH & MH, clear HPS Housing and Reflector Die-cast aluminum ballast housing Clear, acrylic prismatic reflector Electrical High power factor ballasts are standard Ballast housing designed to reduce thermal load on electrical components Finish Ballast housing: Exclusive Colorfast DeltaGuard finish with 7-year warranty Labels UL listed for damp locations ANSI lamp wattage label supplied AVAILABLE FINISH COLOR: WH White Standard Color CE DELTAGUARD 7-Y E A R W A R R A N T Y FI NIS H 262 Beta Lighting 800-236-6800 www.beta-lighting.com
DIE-CAST HOUSING BHB-P22-DC 5000 10000 15000 20000 0 90 60 30 Candlepower distribution curve of 400W MH. Efficiency = 96.4%; SC - 1.7 Candlepower Summary Angle Mean CP Lumens 0 5413 5 5642 551 15 6616 1918 25 9149 4262 35 12340 7572 45 8074 6338 55 3123 2830 65 1198 1292 75 1308 1379 85 1523 1661 95 1660 1811 105 1600 1693 115 1312 1309 125 887 901 135 608 476 145 562 349 155 544 253 165 567 158 175 425 43 180 407 Zonal Lumens and Percentages Zone Lumens % Lamp % Fixture 0-30 6731 18.7 19.4 0-40 14303 39.7 41.2 0-60 23471 65.2 67.6 0-90 27805 77.2 80.1 90-120 4813 13.4 13.9 90-130 5613 15.6 16.2 90-150 6438 17.9 18.6 90-180 6892 19.1 19.9 0-180 34697 96.4 100.0 A B A = 22.25" (565 mm) B = 21.6" (549 mm) For 750 & 1000W: A = 25.0" (635 mm) B = 22.1" (561 mm) See page 255 for order code logic. 22" PRISMATIC DIE-CAST HIGH BAY (Example: BHB-P22-DC-HSB-O-400PMH-MT) Product Housing Ballast Mounting Lamp Lamp Ballast Options Family Indicator Housing Options Rating Selection Voltage (Factory Installed) BHB P22 DC HCP E 200 PMH MT AD HSB O 250 PMH/MHX/HPS 12 AF S 300 PMH 20 BN Formerly BBB 320 PMH 24 CL 350 PMH 27 F 400 PMH/MHX/HPS R7 FA 450 PMH 34 FAW 750 PMH 48 Q 10X MHX 5_ TL Ballast & Lamp Footnotes All fixtures are standard with multi-tap (MT) ballast R7 (277V reactor ballast) For PMH only, must be specified All fixtures available in 480V ballast International 50 Hertz ballasts available; see page 11 for specification information Coated lamp standard with PMH and MHX fixtures; clear lamp for HPS Lamp Rating Definitions and Ordering Guidelines: E (Enclosed) Lamp provided can be used in enclosed fixture only, must order fixture with lens (AD, CL, FA or FAW) option (450W maximum) O (Open) Lamp provided can be used in both open and enclosed fixtures S (S Rated) For 400W & 1000W MHX and 750W PMH only; lamp approved by lamp supplier to operate without enclosure, however this does not meet NEC Article 410.73 (F)(5) consult local inspector prior to ordering PMH 200W, 250W, 300W, 320W, 350W, 400W & 450W PMH can be ordered with O or E; if E is selected, the fixture must be ordered with lens (AD, CL, FA or FAW) option; 750W PMH must be ordered with S, but cannot be enclosed with lens PMH fixtures ordered with O and a lens option will be provided with open rated lamp and socket, as well as selected lens option MHX 250W MHX can be ordered with O or E; 400W MHX can be ordered with E, O or S if E is selected, the fixture must be ordered with lens (AD, CL, FA or FAW) option; 1000W MHX can be ordered with an O or S, but can not be enclosed with lens MHX fixtures ordered with O and lens option will be provided with open rated lamp and socket, as well as selected lens option HPS All HPS wattages must be ordered with O and can be ordered with or without lens (AD, CL, FA or FAW) option Ambient Temperature Limits on pages 426-427 Mounting Footnotes see page 274 for details HCP (Hook, Cord & Plug) Heavy-duty steel hook with safety-lock spring and 30-inch (762 mm) cord with NEMA locking type plug; must specify voltage other than MT HSB (Hinged Splice Box) Multiple knockouts are available for both surface wiring or pendant mounting Modular Wiring is available consult factory Option Footnotes AD (Acrylic Drop Prismatic Lens) Reduces lamp brightness and provides a smoother pattern of light; measures 2.3" (58 mm) deep; 450W maximum AF (Air Filter) Helps prevent dirt contaminants from entering the optical chamber (for use with lens options); 250W maximum BN (Ballast Noise Suppressor) Reduces the noise emitted by the ballast (450W maximum); 35 C ambient maximum for 400W & 450W CL (Conical Lens) Reduces lamp brightness and provides a smoother pattern of light; measures 2.0" (51 mm) deep; 450W maximum F (Fuse) Must specify voltage other than MT FA (Flat Acrylic Lens) Flat acrylic lens to enclose lamp; 450W maximum FAW (Flat Acrylic Lens & ) Flat acrylic lens with wire guard for added protection; 450W maximum Q (Quartz Standby) Delay-relay type and includes 100W T4 dual-contact quartz lamp (not available with 277V reactor ballast) TL (Two-Level) 2-level integrated 360 motion sensor; time control is externally adjustable from 30-seconds to 20-minutes; not available with 277V reactor ballast Accessories (Field Installed) See page 275 for details L_- _ Locking Type Receptacle PH- _ Power Hook SC-5 Safety Cable with Hang Fast WG-AR WG-AR/OC Re-lamp Opening www.beta-lighting.com 800-236-6800 Beta Lighting 263
BHB-T22-DC 22" TRANSLUCENT REFLECTOR HIGH BAY Optical System This translucent prismatic reflector provides 90-percent efficiency and approximately 10-percent uplight. Lamp Maximum wattage: 750W PSMH, 1000W MH, 400W HPS Mogul base clear HID lamp included Housing and Reflector Die-cast aluminum ballast housing Translucent, acrylic prismatic reflector Electrical High power factor ballasts are standard Ballast housing designed to reduce thermal load on electrical components Finish Ballast housing: Exclusive Colorfast DeltaGuard finish with 7-year warranty Labels UL listed for damp locations ANSI lamp wattage label supplied AVAILABLE FINISH COLOR: WH White Standard Color CE DELTAGUARD 7-Y E A R W A R R A N T Y FI NIS H 264 Beta Lighting 800-236-6800 www.beta-lighting.com
DIE-CAST HOUSING BHB-T22-DC 12259 24518 36777 49036 120 90 60 30 Candlepower distribution curve of 1000W MH. Efficiency = 89.7%; SC - 1.6 Candlepower Summary Angle Mean CP Lumens 0 10506 5 10213 989 15 10343 2937 25 10722 4918 35 10471 6655 45 10438 7948 55 5562 5353 65 2907 2919 75 1536 1633 85 535 652 95 454 496 105 533 560 115 587 579 125 595 532 135 573 440 145 564 394 155 1173 494 165 450 150 175 360 35 180 359 Zonal Lumens and Percentages Zone Lumens % Lamp % Fixture 0-30 8844 21.06 23.47 0-40 15498 36.90 41.13 0-60 28799 68.57 76.43 0-90 34002 80.96 90.24 40-90 18503 44.06 49.11 60-90 5203 12.39 13.81 90-180 3679 8.76 9.76 0-180 37682 89.72 100.00 A B A = 22.25" (565 mm) B = 21.6" (549 mm) For 750 & 1000W: A = 25.0" (635 mm) B = 22.1" (561 mm) See page 255 for order code logic. 22" TRANSLUCENT REFLECTOR DIE-CAST HIGH BAY (Example: BHB-T22-DC-HSB-O-400PMH-MT) Product Housing Ballast Mounting Lamp Lamp Ballast Options Family Indicator Housing Options Rating Selection Voltage (Factory Installed) BHB T22 DC HCP E 200 PMH MT AD HSB O 250 PMH/MHX/HPS 12 AF S 300 PMH 20 BN Formerly BBX 320 PMH 24 CL 350 PMH 27 F 400 PMH/MHX/HPS R7 FA 450 PMH 34 FAW 750 PMH 48 Q 10X MHX 5_ TL Ballast & Lamp Footnotes All fixtures are standard with multi-tap (MT) ballast R7 (277V reactor ballast) For PMH only, must be specified All fixtures available in 480V ballast International 50 Hertz ballasts available; see page 11 for specification information Clear lamp is standard with all fixtures Lamp Rating Definitions and Ordering Guidelines: E (Enclosed) Lamp provided can be used in enclosed fixture only, must order fixture with lens (AD, CL, FA or FAW) option (450W maximum) O (Open) Lamp provided can be used in both open and enclosed fixtures S (S Rated) For use with 400W & 1000W MHX and 750W PMH only; lamp approved by lamp supplier to operate without enclosure, however this does not meet NEC Article 410.73 (F)(5) consult local inspector prior to ordering PMH 200W, 250W, 300W, 320W, 350W, 400W and 450W PMH can be ordered with O or E; if E is selected, the fixture must be ordered with lens (AD, CL, FA or FAW) option; 750W PMH must be ordered with S, but can not be enclosed with lens PMH fixtures ordered with O and a lens option will be provided with open rated lamp and socket, as well as selected lens option MHX 250W MHX can be ordered with O or E; 400W MHX can be ordered with E, O or S if E is selected, the fixture must be ordered with lens (AD, CL, FA or FAW) option; 1000W MHX can be ordered with an O or S, but can not be enclosed with lens MHX fixtures ordered with O and lens option will be provided with open rated lamp and socket, as well as selected lens option HPS All HPS wattages must be ordered with O and can be ordered with or without lens (AD, CL, FA or FAW) option Ambient Temperature Limits on pages 426-427 Mounting Footnotes see page 274 for details HCP (Hook, Cord & Plug) Heavy-duty steel hook with safety-lock spring and 30-inch (762 mm) cord with NEMA locking type plug; must specify voltage other than MT HSB (Hinged Splice Box) Multiple knockouts are available for both surface wiring or pendant mounting Modular Wiring is available consult factory Option Footnotes AD (Acrylic Drop Prismatic Lens) Reduces lamp brightness and provides a smoother pattern of light; measures 2.3" (58 mm) deep; 450W maximum AF (Air Filter) Helps prevent dirt contaminants from entering the optical chamber (for use with lens options); 250W maximum BN (Ballast Noise Suppressor) Reduces the noise emitted by the ballast (450W maximum); 35 C ambient maximum for 400W & 450W CL (Conical Lens) Reduces lamp brightness and provides a smoother pattern of light; measures 2.0" (51 mm) deep; 450W maximum F (Fuse) Must specify voltage other than MT FA (Flat Acrylic Lens) Flat acrylic lens to enclose lamp; 450W maximum FAW (Flat Acrylic Lens & ) Flat acrylic lens with wire guard for added protection; 450W maximum Q (Quartz Standby) Delay-relay type and includes 100W T4 dual-contact quartz lamp (not available with 277V reactor ballast) TL (Two-Level) 2-level integrated 360 motion sensor; time control is externally adjustable from 30-seconds to 20-minutes; not available with 277V reactor ballast Accessories (Field Installed) See page 275 for details L_- _ Locking Type Receptacle PH- _ Power Hook SC-5 Safety Cable with Hang Fast WG-AR No Lens WG-AR/OC with Re-lamp Opening www.beta-lighting.com 800-236-6800 Beta Lighting 265
BHB-A16-DC 16" ALUMINUM HIGH BAY Optical System This hydro-formed aluminum reflector provides 80-percent efficiency. Lamp Maximum wattage: 450W PSMH, 400W MH, 400W HPS Mogul base clear HID lamp included Housing and Reflector Die-cast aluminum ballast housing Hydro-formed aluminum reflector 175W & 250W MH fixtures are supplied with a clear, flat tempered glass lens enclosure Electrical High power factor ballasts are standard Ballast housing designed to reduce thermal load on electrical components Finish Ballast housing: Exclusive Colorfast DeltaGuard finish with 7-year warranty Labels UL listed for damp locations ANSI lamp wattage label supplied AVAILABLE FINISH COLOR: WH White Standard Color CE DELTAGUARD 7-Y E A R W A R R A N T Y FI NIS H 266 Beta Lighting 800-236-6800 www.beta-lighting.com
DIE-CAST HOUSING BHB-A16-DC 180 4000 8000 12000 16000 120 90 60 30 Candlepower distribution curve of 400W MH. Efficiency = 77.18%; SC - 1.6 Candlepower Summary Angle Mean CP Lumens 0 8239 5 6272 629 15 6421 1911 25 9559 4370 35 11551 7396 45 11564 8084 55 1638 1977 65 429 465 75 80 104 85 19 23 95 7 9 105 12 13 115 17 19 125 47 49 135 193 194 145 960 560 155 856 380 165 143 57 175 32 4 180 30 Zonal Lumens and Percentages Zone Lumens % Lamp % Fixture 0-30 6909 20.32 26.33 0-40 14305 42.07 54.52 0-60 24365 71.66 92.86 0-90 24957 73.41 95.11 40-90 10652 31.33 40.60 60-90 592 1.74 2.26 90-180 1281 3.77 4.89 0-180 26239 77.18 100.00 A B A = 16.4" (417 mm) B = 18.8" (478 mm) See page 255 for order code logic. 16" ALUMINUM DIE-CAST HIGH BAY (Example: BHB-A16-DC-HSB-O-400PMH-MT) Product Housing Ballast Mounting Lamp Lamp Ballast Options Family Indicator Housing Options Rating Selection Voltage (Factory Installed) BHB A16 DC HCP E 150 PMH/HPS MT AF HSB O 175 PMH/MHX 12 BN S 200 PMH 20 F Formerly BBC 250 PMH/MHX/HPS 24 Q 300 PMH 27 TG 320 PMH R7 TGW 350 PMH 34 TL 400 PMH/MHX/HPS 48 450 PMH 5_ Ballast & Lamp Footnotes All fixtures are standard with multi-tap (MT) ballast R7 (277V reactor ballast) For PMH only, must be specified All fixtures available in 480V ballast International 50 Hertz ballasts available; see page 11 for specification information Clear lamp is standard with all fixtures Lamp Rating Definitions and Ordering Guidelines: E (Enclosed) Lamp provided can be used in enclosed fixture only, must order fixture with tempered glass lens (TG or TGW) option (400W maximum) O (Open) Lamp provided can be used in both open and enclosed fixtures S (S Rated) For use with 400W MHX only; lamp approved by lamp supplier to operate without enclosure, however this does not meet NEC Article 410.73 (F)(5) consult local inspector prior to ordering PMH All PMH wattages except 450W PMH can be ordered with O or E; if E is selected, the fixture must be ordered with lens (TG or TGW) option (450W PMH available as O only) PMH fixtures ordered with O and lens option will be provided with open rated lamp and socket, as well as selected lens option MHX 175W MHX available with lens only must order with E; 250W MHX can be ordered with O or E; 400W MHX can be ordered with E, O or S if E is selected, the fixture must be ordered with lens (TG or TGW) option MHX fixtures ordered with O and lens option will be provided with open rated lamp and socket, as well as selected lens option HPS All HPS wattages must be ordered with O and can be ordered with or without lens (TG or TGW) option Ambient Temperature Limits on pages 426-427 Mounting Footnotes see page 274 for details HCP (Hook, Cord & Plug) Heavy-duty steel hook with safety-lock spring and 30-inch (762 mm) cord with NEMA locking type plug; must specify voltage other than MT HSB (Hinged Splice Box) Multiple knockouts are available for both surface wiring or pendant mounting Modular Wiring is available consult factory Option Footnotes AF (Air Filter) Helps prevent dirt contaminants from entering the optical chamber (for use with lens options) BN (Ballast Noise Suppressor) Reduces the noise emitted by the ballast (450W maximum); 35 C ambient maximum for 400W & 450W F (Fuse) Must specify voltage other than MT Q (Quartz Standby) Delay-relay type and includes 100W T4 dual-contact quartz lamp (not available with 277V reactor ballast) TG (Tempered Glass Lens) Flat tempered glass lens to enclose lamp; 400W maximum TGW (Tempered Glass Lens & ) Flat tempered glass lens with wire guard for added protection; 400W maximum TL (Two-Level) 2-level integrated 360 motion sensor; time control is externally adjustable from 30-seconds to 20-minutes; not available with 277V reactor ballast Accessories (Field Installed) See page 275 for details L_- _ Locking Type Receptacle PH- _ Power Hook WG-A No Lens WG-A/OC Re-lamp Opening SC-5 Safety Cable with Hang Fast www.beta-lighting.com 800-236-6800 Beta Lighting 267
BHB-P22-FS 22" CFL PRISMATIC HIGH BAY Optical System This prismatic reflector provides 90-percent efficiency and approximately 15-percent uplight. Lamp Maximum wattage lamp: 57W CFL* * Triple Biax 26W, 32W & 42W; High output biax 57W 4-pin compact fluorescent lamps included Housing and Reflector Formed steel ballast housing Clear, acrylic prismatic reflector Electrical Electronic ballasts are standard Ballast housing vented to reduce thermal load on electrical components Finish Ballast housing: Exclusive Colorfast DeltaGuard finish with 7-year warranty Labels UL listed for damp locations ANSI lamp wattage label supplied Discontinued AVAILABLE FINISH COLOR: WH White Standard Color CE DELTAGUARD 7-Y E A R W A R R A N T Y FI NIS H 270 Beta Lighting 800-236-6800 www.beta-lighting.com
FORMED STEEL HOUSING BHB-P22-FS Product Housing Ballast Mounting Number Lamp Ballast Options Family Indicator Housing Options of Lamps Selection Voltage (Factory Installed) BHB P22 FS HCP 4 026 CFL EB AD HSB 6 026 CFL DT CL 8 026 CFL 12 DM 4 032 CFL 20 EM 6 032 CFL 24 F 8 032 CFL 27 FA 4 042 CFL 34 FAW 6 042 CFL 5_ TL 8 042 CFL 4 057 CFL Ballast & Lamp Footnotes All fixtures are standard with self-sensing (120V-277V) electronic ballast (EB) Dual-tap (DT) ballast for EM option only when used with HSB mounting option International 50 Hertz ballasts available; see page 11 for specification information Triple Biax 4-pin lamp, 82 CRI, 3500K: 26W, 32W & 42W High Output Biax 4-pin lamp, 82 CRI, 3500K: 57W Ambient Temperature Limits on pages 426-427 A 1550 3050 4600 0 150 120 90 30 60 B Candlepower distribution curve for eight 42W Compact Fluorescent with no lens. Efficiency = 81.0%; SC - 1.5 A = 22.7" (576 mm) B = 18.7" (475 mm) Candlepower Summary Angle Mean CP Lumens 0 4329 5 4487 451 15 5488 1567 25 6129 2802 35 5406 3345 45 3928 2990 55 1830 1761 65 1297 1311 75 1296 1364 85 1205 1311 95 1072 1163 105 871 923 115 688 684 125 515 463 135 347 273 145 246 157 155 204 95 165 185 53 175 186 18 180 191 22" CFL PRISMATIC FORMED STEEL HIGH BAY (Example: BHB-P22-FS-HSB-6-042CFL-EB) Mounting Footnotes see page 274 for details HCP (Hook, Cord & Plug) Heavy-duty steel hook with safety-lock spring and 30-inch (762 mm) cord with NEMA locking type plug; must specify voltage other than EB or DT HSB (Hinged Splice Box) Multiple knockouts are available for both surface wiring or pendant mounting Option Footnotes Zonal Lumens and Percentages Zone Lumens % Lamp % Fixture 0-30 4820 18.83 23.25 0-40 8165 31.89 39.39 0-60 12915 50.45 62.31 0-90 16900 66.02 81.53 40-90 8735 34.12 42.14 60-90 3985 15.57 19.23 90-180 3828 14.96 18.47 0-180 20729 80.97 100.00 See page 255 for order code logic. AD (Acrylic Drop Prismatic Lens) Reduces lamp brightness and provides a smoother pattern of light; measures 2.3" (58 mm) deep CL (Conical Lens) Reduces lamp brightness and provides a smoother pattern of light; measures 2.0" (51 mm) deep DM (Dimming) Power Line Dimming Advance Mark X Ballast; available for 4 lamp 26W & 32W fixtures; must specify 120V or 277V; 6 or 8 lamp 42W also available (overall fixture height will change consult factory) EM (Emergency Battery Pack) Overall fixture height will change consult factory; for 120V, 277V or DT ballasts only F (Fuse) Must specify voltage other than EB or DT FA (Flat Acrylic Lens) Flat acrylic lens to enclose lamp FAW (Flat Acrylic Lens & ) Flat acrylic lens with wire guard for added protection TL (Two-Level) 2-level integrated 360 motion sensor; time control is externally adjustable from 30-seconds to 20-minutes Discontinued Accessories (Field Installed) See page 275 for details L_- _ Locking Type Receptacle PH- _ Power Hook WG-AR No Lens WG-AR/OC Re-lamp Opening SC-5 Safety Cable with Hang Fast www.beta-lighting.com 800-236-6800 Beta Lighting 271
BHB-A22-FS 22" CFL ALUMINUM HIGH BAY Optical System This hydro-formed aluminum reflector provides 71-percent efficiency. Lamp Maximum wattage lamp: 57W CFL* * Triple Biax 26W, 32W & 42W; High output biax 57W 4-pin compact fluorescent lamps included Housing and Reflector Formed steel ballast housing Hydro-formed aluminum reflector Electrical Electronic ballasts are standard Ballast housing vented to reduce thermal load on electrical components Finish Ballast housing: Exclusive Colorfast DeltaGuard finish with 7-year warranty Labels UL listed for damp locations ANSI lamp wattage label supplied Discontinued AVAILABLE FINISH COLOR: WH White Standard Color CE DELTAGUARD 7-Y E A R W A R R A N T Y FI NIS H 272 Beta Lighting 800-236-6800 www.beta-lighting.com
FORMED STEEL HOUSING BHB-A22-FS Product Housing Ballast Mounting Number Lamp Ballast Options Family Indicator Housing Options of Lamps Selection Voltage (Factory Installed) BHB A22 FS HCP 4 026 CFL EB AD HSB 6 026 CFL DT CL 8 026 CFL 12 DM 4 032 CFL 20 EM 6 032 CFL 24 F 8 032 CFL 27 FA 4 042 CFL 34 FAW 6 042 CFL 5_ TL 8 042 CFL 4 057 CFL Ballast & Lamp Footnotes All fixtures are standard with self-sensing (120V-277V) electronic ballast (EB) Dual-tap (DT) ballasts for EM option only when used with HSB mounting option International 50 Hertz ballasts available; see page 11 for specification information Triple Biax 4-pin lamp, 82 CRI, 3500K: 26W, 32W & 42W High Output Biax 4-pin lamp, 82 CRI, 3500K: 57W Ambient Temperature Limits on pages 426-427 A 1900 3800 5700 0 150 120 90 30 60 B Candlepower distribution curve for eight 42W CFL. Efficiency = 69.7%; SC - 1.8 A = 22.7" (576 mm) B = 18.2" (462 mm) Candlepower Summary Angle Mean CP Lumens 0 3619 5 3856 396 15 5242 1509 25 6668 3096 35 7608 4702 45 6329 4760 55 2901 2647 65 613 692 75 29 40 85 8 8 90 0 22" CFL ALUMINUM FORMED STEEL HIGH BAY (Example: BHB-A22-FS-HSB-8-042CFL-EB) Mounting Footnotes see page 274 for details HCP (Hook, Cord & Plug) Heavy-duty steel hook with safety-lock spring and 30-inch (762 mm) cord with NEMA locking type plug; must specify voltage other than EB or DT HSB (Hinged Splice Box) Multiple knockouts are available for both surface wiring or pendant mounting Option Footnotes Zonal Lumens and Percentages Zone Lumens % Lamp % Fixture 0-30 4999 19.53 28.01 0-40 9701 37.90 54.35 0-60 17108 66.83 95.85 0-90 17849 69.72 100.00 40-90 8147 31.83 45.65 60-90 740 2.89 4.15 90-180 0.00.00 0-180 17849 69.72 100.00 See page 255 for order code logic. AD (Acrylic Drop Prismatic Lens) Reduces lamp brightness and provides a smoother pattern of light; measures 2.3" (58 mm) deep CL (Conical Lens) Reduces lamp brightness and provides a smoother pattern of light; measures 2.0" (51 mm) deep DM (Dimming) Power Line Dimming Advance Mark X Ballast; available for 4 lamp 26W & 32W fixtures; must specify 120V or 277V; 6 or 8 lamp 42W also available (overall fixture height will change consult factory) EM (Emergency Battery Pack) Overall fixture height will change consult factory; for 120V, 277V or DT ballasts only F (Fuse) Must specify voltage other than EB or DT FA (Flat Acrylic Lens) Flat acrylic lens to enclose lamp FAW (Flat Acrylic Lens & ) Flat acrylic lens with wire guard for added protection TL (Two-Level) 2-level integrated 360 motion sensor; time control is externally adjustable from 30-seconds to 20-minutes Discontinued Accessories (Field Installed) See page 275 for details L_- _ Locking Type Receptacle PH- _ Power Hook SC-5 Safety Cable with Hang Fast WG-AJ No Lens WG-AJ/OC Re-lamp Opening www.beta-lighting.com 800-236-6800 Beta Lighting 273
SECURITY HIGH BAY & MOUNTING PERIMETER OPTIONS ACCESSORIES (FIELD INSTALLED) OPTIONS (FACTORY INSTALLED) Acrylic Drop Prismatic Lens Option Code: AD Lens disperses light evenly and reduces brightness Secures to reflector with V-band collar Conical Lens Option Code: CL Diffuses light, reduces brightness and glare Secures to reflector with V-band collar Hook, Cord & Plug Mounting Code: HCP To suspend luminaire from a ceiling eye hanger (by others) Includes a heavy-duty steel hook with retainer spring Supplied with a 30" (762 mm) cord and voltage specific NEMA standard locking-type plug Hinged Splice Box Mounting Code: HSB Galvanized steel splice box with hinge for quick access to wiring For either surface wiring or pendant mount from rigid conduit Includes two 3/4" and six 1/2" knockouts on the sides and two 3/4" knockouts and mounting holes for standard junction boxes on top Measures 4"W x 3.75" L x 1.5"H (102 mm W x 95 mm L x 38 mm H) Flat Acrylic Lens Option Code: FA Provides lamp containment Secures to reflector with V-band collar Two-Level Integrated 360-degree Motion Sensor Option Code: TL Tempered Glass Flat Lens Option Code: TG Provides lamp containment A16, A22, ALR: Secures to reflector with support ring and clip system; one clip remains attached to the reflector to hold the lens while relamping G16: L-clips secure TG to three supporting arms Discontinued Passive infrared technology can detect temperature changes as an occupant moves within the sensor s 360-degree field of view Time control is externally adjustable from 30 seconds to 20 minutes Switches when occupant approaches from 15 to 20 feet beneath fixture Easy installation no additional wiring is required 274 Beta Lighting 800-236-6800 www.beta-lighting.com
HIGH BAY ACCESSORIES (FIELD INSTALLED) Catalog Number: (For Aluminum reflector) WG-A (16") WG-A/OC (16" with re-lamp opening) WG-AJ (22") WG-AJ/OC (22" with re-lamp opening) (For Prismatic reflector) WG-AP (16") WG-AP/OC (16" with re-lamp opening) WG-AR (22") WG-AR/OC (22" with re-lamp opening) Steel guard protects optical system where lamp hazards are high Attaches easily to reflector with supplied hardware For use with non-lensed fixtures Safety Cable with Hang Fast Catalog Number: SC-5 Provides added safety for fixture Recommended for Hook, Cord & Plug mount luminaires Attaches to ballast housings 5' (1.5 m) long safety cable Steady-Lock for Cable or Chain Catalog Number: SL-C Helps maintain proper fixture orientation for ALF ALR Recommended with (2) SC-5 or (2) SC-5C Locking Receptacle Catalog Number: L5-15R (120V) L6-15R (208 or 240V) L7-15R (277V) L8-20R (480V) Prevents unintended cord disconnection For use with any Hook, Cord & Plug mount luminaire NEMA standard receptacle Power Hook Catalog Number: PH-1 (120V Receptacle) PH-2 (277V Receptacle) PH-3 (208V Receptacle) PH-4 (240V Receptacle) PH-5 (480V Receptacle) Includes an eye hanger to support luminaire For use with any Hook, Cord & Plug mount luminaire Provides 3 threaded knockouts for 1/2" conduit Steady-Lock for Eyebolt Catalog Number: SL-E Helps maintain proper fixture orientation for ALR Included with ALR Hook, Cord and Plug mount Discontinued www.beta-lighting.com 800-236-6800 Beta Lighting 275