PV and Inverter based DER Ground Referencing Requirements and Sample Calculations

Similar documents
FIT TIER 2 Application

Physical Address: City: State: Zip Code:

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP

Application Guidelines for Transformer Connection and Grounding for Distributed Generation: An Update

Rule Fast Track Analysis for National Life Insurance Co.

ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only

Effective: September 10, 2006 Vermont Attachment 1 to Rule Public Service Board Page 1 of 6

Green Power Connection Net Energy Metering Engineering Review Process in Delaware and Speeding Up the Application Fee Process

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

AUSTIN ENERGY INTERCONNECTION GUIDE FOR CUSTOMER-OWNED POWER PRODUCTION FOR FACILITIES UP TO 10MW A INTERCONNECTION CLASSIFICATIONS...

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA

Interconnection Application For Residential and Commercial Power Systems 10 kw or Smaller

Solar Power Plant Design and Interconnection

APPLICATION NOTE. Increasing PV Hosting Capacity on LV Secondary Circuits with the Gridco System empower TM Solution

PSEG-LONG ISLAND SMART GRID SMALL GENERATOR INTERCONNECTION SCREENING CRITERIA FOR OPERATING IN PARALLEL WITH LIPA S DISTRIBUTION SYSTEM

Step Voltage Regulators

Fault Analysis I PowerWorld Corporation

Introduction to PowerWorld Simulator: Interface and Common Tools

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP

Unitil Energy Systems, Inc. Interconnection Standards For Inverters Sized Up To 100 kva

TERMS AND CONDITIONS

Application for Small Generator Facility Interconnection Tier 2, Tier 3 or Tier 4 Interconnection

Definition AC Power Distribution

1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr.

Shunt Capacitor Bank Fundamentals and Protection

SOUTH CAROLINA. Standard for Interconnecting Small Generation 100 kw or Less with Electric Power Systems (EPS) (Interconnection Standard)

Power over Ethernet plus Isolation requirements. David Law 3Com

Title 20 PUBLIC SERVICE COMMISSION. Subtitle 50 SERVICE SUPPLIED BY ELECTRIC COMPANIES. Chapter 02 Engineering

Session 10: General Overview of Interconnection Standards & Grid Codes for High Penetration PV October 21, 2015 Santiago, Chile

Interconnection of Generators to EDI s Distribution System

System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

Short Circuit Current Calculations

The following table shows approximate percentage wise the

Chapter 9 Balanced Faults

Radial Distribution Test Feeders

IEEE Smart Grid Series of Standards IEEE 2030 TM (Interoperability) and IEEE 1547 TM (Interconnection) Status. #GridInterop

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

Equipment: Power Supply, DAI, Variable resistance (8311), Variable inductance (8321)

LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University

Earth Fault Detection Basics in Theory

Typical Data Requirements Data Required for Power System Evaluation

TABLE OF CONTENTS 1.0 INTRODUCTION PURPOSE DEVIATION INTERTIE PROTECTION REQUIREMENTS... 4

QUESTIONS and ANSWERS RFB , Metal Clad Switchgear and Power Control Room

N.J.A.C. 14:8-4 NET METERING FOR CLASS I RENEWABLE ENERGY SYSTEMS

4.1.1 Generator Owner Transmission Owner that owns synchronous condenser(s)

TECHNICAL INTERCONNECTION REQUIREMENTS FOR DISTRIBUTED GENERATION. Micro Generation & Small Generation, 3-phase, less than 30 kw

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS

How To Choose A Transformer

Loading Considerations When Paralleling Transformers

Design of electrical power system for a 1000MW nuclear power generating station

Buck - Boost Transformers

SPECIFICATION COG-2007

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

AC and DC Drive System Installation Information

4.5 Transformer Connections

Application of Four-Pole Circuit Breakers within Data Centers

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Distribution Operations with High-penetration of Beyond the Meter Intermittent Renewables. Bob Yinger Southern California Edison April 15, 2014

Modeling and Testing of Unbalanced Loading and Voltage Regulation

Paralleling Power Sources Which Share a Common Neutral

Overcurrent Protection for the IEEE 34 Node Radial Test Feeder

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V V V (at 50 Hz)

VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES

Beware of Simplistic Voltage Drop Calculations. By Aaron Hesse, PE, Coffman Engineers, Spokane, Washington INTRODUCTION

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80

Creating a One-line Diagram

Residential Solar Service Agreement (RSSA) Customer Sited Solar Photovoltaic Systems

Figure. 1 - Split Phase 240/120V circuit (180 phase shift)

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

Distributed Generation: Feeder Hosting Capacity. Dean E. Philips, P.E. FirstEnergy Service Corp Manager, Distribution Planning & Protection

1 Introduction. 2 Two Phases. J.L. Kirtley Jr.

Unified requirements for systems with voltages above 1 kv up to 15 kv

Application Bulletin NEC Reference Guide for SolarBridge-Enabled AC Module Installers

Measurement, Modeling and Simulation of Capacitor Bank Switching Transients

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

Integration Capacity Analysis Workshop 11/10/15 California IOU s Approach

Triplen Harmonics Mitigation 3 Phase Four-Wire Electrical Distribution System Using Wye- Zig-Zag Transformers

Transmission Planning Standards for the Baltimore Gas & Electric Company Transmission System

Electric Power Systems An Overview. Y. Baghzouz Professor of Electrical Engineering University of Nevada, Las Vegas

Generation Interconnection System Impact Study Report. For. PJM Generation Interconnection Request Queue Position X1-114.

INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

Low Voltage Transformer Through-Fault Protection: A System Approach

Three-phase AC circuits

Power Quality Standards for Electric Service

ZONE SELECTIVE INTERLOCKING (ZSI) APPLICATION AND TESTING GUIDE SIEMENS WL UL489 AND UL1066 AIR CIRCUIT BREAKERS

Colorado Springs Utilities Interconnection Guidelines For Transmission to Transmission Interconnections Version 1 12/04/2007

Chapter 24. Three-Phase Voltage Generation

BALANCED THREE-PHASE CIRCUITS

Power System Analysis

Transformer Design & Design Parameters

Transcription:

PV and Inverter based DER Ground Referencing Requirements and Sample Calculations Scope This document lists technical requirements, and provides sample calculations, for ground referencing of inverter based Distributed Energy Resources (DER) on Xcel Energy s 4 wire system medium voltage (MV) electric distribution system. DER units with AC nameplate capacities from 100kW to 10MW are covered in the scope. This document assumes a proper ground reference is being created by either a separate grounding transformer or a wye grounded:delta (MV:LV) interconnection transformer. Inverters which have an internal grounded wye isolation transformer are not covered in this document. The information in this document is to be applied at the Point of Common Coupling. Background Ground referencing electric distribution systems is standard practice in large part to avoid damaging overvoltages, for line to ground connected loads, which can result from ground fault conditions on ungrounded systems. Figure A below shows the range of expected line voltages for different system ground referencing methods. Line surge arrestors and customer equipment connected phase to ground are usually not designed to withstand the phase to phase voltages that can occur during ungrounded system fault conditions. Figure A Neutral shift during ground fault conditions During a ground fault condition, in situations where the Xcel Energy s protective device opens and before the DER trips off line, the distribution system has lost the system ground reference. It is important that any DER source energizing this portion of the distribution system provides a ground reference in order to prevent overvoltages. Sample Calculations Page: 1 of 8

Std IEEE 1547 2003 states that the grounding scheme of the DR interconnection shall not cause overvoltages that exceed the rating of the equipment connected to the Area EPS. The below requirements for inverter ground referencing are adopted from IEEE P1547.8/D8 2014 which is the draft document titled Draft Recommended Practice for Establishing Methods and Procedures that Provide Supplemental Support for Implementation Strategies for Expanded use of IEEE Standard 1547. Although this document as a whole is in draft form and not yet approved, Xcel Energy believes the provision below on inverter ground referencing identifies a best practice. Requirements For DG Facilities with an Inverter Interface: 1.) 0.6. 10% Note: 1 p.u. is based on 2.) 4 3) Ground referencing equipment shall be designed to withstand a minimum of 4% and remain connected Note: can be approximated as 4) Ground referencing equipment shall have 5 second withstand ratings that exceed maximum available short circuit current for close in faults Additional Notes: a) Sum of MVA ratings of DER inverter nameplates and high side (medium voltage) kv rating of interconnection transformer or grounding bank, depending on which unit creates the ground source, are used in determining required zero sequence impedance ( ) for composite facility b) The MVA and high side kv rating of the interconnection transformer or grounding bank, depending on which unit creates the ground source, is used for determining grounding bank and neutral reactor sizing c) The impedance of the interconnection transformer is needed for neutral reactor sizing Sample Calculations Page: 2 of 8

Example Calculations The below examples assume a ground reference is created by a proper transformer configuration and that the PV facility is interconnected to Xcel Energy s 4 wire electric distribution system. For simplicity, the example online diagrams below exclude system components not relevant to grounding requirements; these drawings are not intended to be used as example onelines for system design. Example 1 Separate Zig Zag Grounding Transformer A PV facility with 1 MVA inverter total AC nameplate is interconnected to a 13.8kV feeder through a 1 MVA interconnection transformer that does not create a ground reference. A separate zig zag transformer is connected at 13.8kV to meet ground referencing requirements. (Note: Secondary ground bank connections are also acceptable when the interconnection transformer is wye grounded:wye grounded. The kv used for determine would be 480V in that case.) i) Find base impedance: 13.8 190 Ω 1 Notes: kv is high side voltage of grounding transformer. is aggregate facility (i.e. 5 MVA would be used for five 1 MVA facilities) Find zero sequence reactance requirement: 0.6 190 Ω 10% 114 Ω 10% The zig zag grounding transformer will require a per phase zero sequence reactance of 114 Ω 10% to meet Requirement 1. ii) For Requirements 2, verify 4 iii) For Requirement 3, assuming 114 Ω determines the continuous current associate with 4%. Find base current value. 41.8 Ω Sample Calculations Page: 3 of 8

Find per unit zero sequence current,.. 0.067... Find zero sequence current in amps,. 41.8 0.067 2.8 Verify that the transformer per phase rating exceeds this value. Find neutral current 3 3 2.8 8.4 Verify that the transformer continuous neutral rating exceeds this value. iv) For Requirement 4, request system impedance from the Area engineer and determine ground bank s short circuit contribution for close in single line to ground faults. The grounding transformer 5 second withstand rating shall exceed the maximum anticipated ground fault current contribution from the transformer. Sample Calculations Page: 4 of 8

Example 2 Wye grounded:delta Interconnection Transformer with Neutral Reactor A PV facility with 1 MVA inverter total AC nameplate is interconnected to a 13.8kV feeder through a 1 MVA interconnection transformer through a wye grounded:delta interconnection transformer (grounded wye winding is connected to 13.8kV system). The interconnection transformer has nameplate impedance of 5%. A neutral reactor is required to meet ground referencing requirements. i) Find base impedance: 13.8 190 Ω 1 Notes: kv is high side voltage of grounding transformer. is aggregate facility (i.e. 5 MVA would be used for five 1 MVA facilities) Find zero sequence reactance requirement: 0.6 190 Ω 10% 114 Ω 10% Find interconnection zero sequence reactance contribution:, 0.05 190 Ω 9.5 Ω Find neutral reactor zero sequence contribution to meet requirement by subtracting interconnection transformer contribution: 114 9.5 Ω 104.5 Ω 10% Determine neutral reactor size (note: 3 ): 104.5 Ω 34.8 Ω 10% 3 3 A neutral reactor with reactance of 34.8 Ω 10%, inserted into the neutral of the interconnection transformer, will meet ground referencing Requirement 1. Requirements 2 through 4 should be checked using transformer nameplate information. ii) For Requirements 2, verify 4 iii) For Requirement 3, assuming 114 Ω determines the continuous current associate with 4%. Sample Calculations Page: 5 of 8

Find base current value. 41.8 Ω Find per unit zero sequence current,.. 0.067... Determine zero sequence current in amps,. 41.8 0.067 2.8 Find neutral reactor current 3 3 2.8 8.4 Verify that the neutral reactor continuous rating exceeds this value. iv) For Requirement 4, request system impedance from the Area engineer and determine ground bank s short circuit contribution for close in single line to ground faults. The grounding transformer 5 second withstand rating shall exceed the maximum anticipated ground fault current contribution from the transformer. Sample Calculations Page: 6 of 8

Example 3 Separate Wye grounded:delta Grounding Transformer A PV facility with 1 MVA inverter total AC nameplate is interconnected to a 13.8kV feeder through a 1 MVA wye grounded:wye grounded interconnection transformer. A separate wye grounded:delta transformer is connected at 480V to meet ground referencing requirements. i) Find base impedance: 0. 48 0.2304 Ω 1 Notes: kv is high side voltage of grounding transformer. is aggregate facility (i.e. 5 MVA would be used for five 1 MVA facilities) Find zero sequence reactance requirement: 0.6 0.23 Ω 10% 0.14 Ω 10% The grounding transformer will require a per phase zero sequence reactance of 0.14 Ω 10% to meet Requirement 1. ii) For Requirements 2, verify 4 iii) For Requirement 3, assuming 0.14 Ω determines the continuous current associate with 4%. Find base current value. 1202.8. Ω Find per unit zero sequence current,.. 0.067... Find zero sequence current in amps,. 1202.8 0.067 80.6 Verify that the transformer per phase rating exceeds this value. Sample Calculations Page: 7 of 8

Find neutral current 3 3 80.6 241.8 Verify that the transformer continuous neutral rating exceeds this value. iv) For Requirement 4, refer to the system impedance from the Engineering Scoping Study Results and determine ground bank s short circuit contribution for close in single line toground faults. Alternatively this may be requested from Area Engineering. The grounding transformer 5 second withstand rating shall exceed the maximum anticipated ground fault current contribution from the transformer. Sample Calculations Page: 8 of 8