1 Introduction. 2 Two Phases. J.L. Kirtley Jr.
|
|
|
- Ashlynn Kelly
- 10 years ago
- Views:
Transcription
1 Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science Introduction to Power Systems Class otes Chapter 3 Polyphase etworks J.L. Kirtley Jr. 1 Introduction Most electric power applications employ three phases. That is, three separate power carrying circuite, with voltages and currents staggered symmetrically in time are used. Two major reasons for the use of three phase power are economical use of conductors and nearly constant power flow. Systems with more than one phase are generally termed polyphase. Three phase systems are the most common, but there are situations in which a different number of phases may be used. Two phase systems have a simplicity that makes them useful for teaching vehicles and for certain servomechanisms. This is why two phase machines show up in laboratories and textbooks. Systems with a relatively large number of phases are used for certain specialized applications such as controlled rectifiers for aluminum smelters. Six phase systems have been proposed for very high power transmission applications. Polyphase systems are qualitatively different from single phase systems. In some sense, polyphase systems are more complex, but often much easier to analyze. This little paradox will become obvious during the discussion of electric machines. It is interesting to note that physical conversion between polyphase systems of different phase number is always possible. This chapter starts with an elementary discussion of polyphase networks and demonstrates some of their basic features. It ends with a short discussion of per-unit systems and power system representation. 2 Two Phases The two-phase system is the simplest of all polyphase systems to describe. Consider a pair of voltage sources sitting side by side with: c2003 James L. Kirtley Jr. v 1 = V cos ωt (1) v 2 = V sinωt (2) 1
2 Suppose this system of sources is connected to al balanced load, as shown in Figure 1. To compute the power flows in the system, it is convenient to re-write the voltages in complex form: i 1 i 2 v v 1 v v 1 Z 2 Z 2 Figure 1: Two-Phase System v 1 v 2 = Re V e = Re jv e = Re V e jωt jωt π j(ωt 2 ) (3) (4) (5) V 1 V 2 Figure 2: Phasor Diagram for Two-Phase Source If each source is connected to a load with impedance: then the complex amplitudes of currents are: Z = Z e jψ I 1 = V jψ e Z I 2 = V jψ j e e π 2 Z Each of the two phase networks has the same value for real and reactive power: P jq = 2 V 2 e jψ (6) 2 Z
3 or: P = Q = V 2 cos ψ (7) 2 Z V 2 sinψ (8) 2 Z The relationship between complex power and instantaneous power flow was worked out in Chapter 2 of these notes. For a system with voltage of the form: v = Re V e jφ e jωt instantaneous power is given by: p = P [1 cos2(ωt φ)] Q sin2(ωt φ) For the case under consideration here, φ = 0 for phase 1 and φ = π 2 for phase 2. Thus: p 1 = p 2 = V 2 cos ψ [1 cos 2ωt] V 2 sinψ sin2ωt 2 Z 2 Z V 2 cos ψ [1 cos(2ωt π)] V 2 sinψ sin(2ωt π) 2 Z 2 Z ote that the time-varying parts of these two expressions have opposite signs. Added together, they give instantaneous power: V 2 p = p 1 p 2 = cosψ Z At least one of the advantages of polyphase power networks is now apparent. The use of a balanced polyphase system avoids the power flow pulsations due to ac voltage and current, and even the pulsations due to reactive energy flow. This has obvious benefits when dealing with motors and generators or, in fact, any type of source or load which would like to see constant power. 3 Three Phase Systems ow consider the arrangement of three voltage sources illustrated in Figure 3. The three phase voltages are: v a = V cos ωt = Re V e jωt (9) ) v b = V cos(ωt 2 π 3 ) = Re V e j(ωt2 π 3 (10) 2π 2π v c = V cos(ωt 3 ) = Re V e j(ωt ) 3 (11) These three phase voltages are illustrated in the time domain in Figure 4 and as complex phasors in Figure 5. ote the symmetrical spacing in time of the voltages. As in earlier examples, the instantaneous voltages may be visualized by imagining Figure 5 spinning counterclockwise with 3
4 v c v b V e j 2 π 3 V e j 2 π 3 V v a Figure 3: Three- Phase Voltage Source Va, Vb, Vc t Figure 4: Three Phase Voltages angular velocity ω. The instantaneous voltages are just projections of the vectors of this pinwheel onto the horizontal axis. Consider connecting these three voltage sources to three identical loads, each with complex impedance Z, as shown in Figure 6. If voltages are as given by (9-11), then currents in the three phases are: V i a = Re e jωt (12) Z V j(ωt 2 π ) i b = Re e 3 (13) Z V j(ωt e 2 π ) i c = Re 3 (14) Z 4
5 V c V b V a Figure 5: Phasor Diagram: Three Phase Voltages i c i b i a v a v b v c Z v c Z v b Z va i n Figure 6: Three- Phase Source Connected To Balanced Load Complex power in each of the three phases is: P jq = V 2 (cos ψ j sinψ) (15) 2 Z Then, remembering the time phase of the three sources, it is possible to write the values of instantaneous power in the three phases: p a = p b = p c = V 2 {cosψ [1 cos 2ωt] sinψ sin2ωt} (16) 2 Z 2 V 2π 2π cos ψ 1 cos(2ωt ) sinψ sin(2ωt ) (17) 2 Z V cos ψ 1 cos(2ωt 2π ) sinψ sin(2ωt 2π ) (18) 2 Z 3 3 The sum of these three expressions is total instantaneous power, which is constant: p = p a p b p c = 3 V 2 cos ψ (19) 2 Z 5
6 It is useful, in dealing with three phase systems, to remember that 2π 2π cos x cos(x ) cos(x ) = regardless of the value of x. ow consider the current in the neutral wire, i n in Figure 6. This current is given by: V i n = i a i b i c = Re e jωt e j(ωt2π ) j(ωt 2π ) 3 e 3 = 0 (20) Z This shows the most important advantage of three-phase systems over two-phase systems: a wire with no current in it does not have to be very large. In fact, the neutral connection may be eliminated completely in many cases. The network shown in Figure 7 will work as well as the network in Figure 6 in most cases in which the voltages and load impedances are balanced. v a i a v a Z v b i b v b Z v c i c v c Z Figure 7: Ungrounded Three-Phase Source and Load There is a fundamental difference between grounded and undgrounded systems if perfectly balanced conditions are not maintained. In effect, the ground wire provides isolation between the phases by fixing the neutral voltage a the star point to be zero. If the load impedances are not equal the load is said to be unbalanced. If the system is grounded there will be current in the neutral. If an unbalanced load is not grounded, the star point voltage will not be zero, and the voltages will be different in the three phases at the load, even if the voltage sources all have the same magnitude. 4 Line-Line Voltages A balanced three-phase set of voltages has a well defined set of line-line voltages. If the line-toneutral voltages are given by (9-11), then line-line voltages are: j 2 π jωt v ab = v a v b = Re V 1 e 3 e (21) v bc = v b v c = v ca = v c v a = j 2π j 2π jωt Re V e 3 e 3 e j 2 π Re V e 3 1 e jωt (22) (23) 6
7 and these reduce to: = Re j π v ab 3V e 6 e v bc = Re 3 V e j π e v ca = j Re 3V e 5π 6 e jωt jωt 2 jωt (24) (25) (26) The phasor relationship of line-to-neutral and line-to-line voltages is shown in Figure 8. Two things should be noted about this relationship: The line-t o-line voltage set has a magnitude that is larger than the line-ground voltage by a factor of 3. Line-to-line voltages are phase shifted by 30 ahead of line-to-neutral voltages. Clearly, line-to-line voltages themselves form a three-phase set just as do line-to-neutral voltages. Power system components (sources, transformer windings, loads, etc.) may be connected either between lines and neutral or between lines. The former connection of often called wye, the latter is called delta, for obvious reasons. V c V ca Vca V ab V c V a V a V bc V b V ab V b V bc Figure 8: Line-eutral and Line-Line Voltages It should be noted that the wye connection is at least potentially a four-terminal connection, while the delta connection is inherently three-terminal. The difference is the availability of a neutral point. Under balanced operating conditions this is unimportant, but the difference is apparent and important under unbalanced conditions. 4.1 Example: Wye and Delta Connected Loads Loads may be connected in either line-to-neutral or line-to-line configuration. An example of the use of this flexibility is in a fairly commonly used distribution system with a line-to-neutral voltage of 120 V, RMS. In this system the line-to-line voltage is 208 V, RMS. Single phase loads may be connected either line-to-line or line-to-neutral. 7
8 V a - - V V ca ab - V - b - Vc - V bc Figure 9: Wye And Delta Connected Voltage Sources a a Z a Z ca Z ab Z b c Z c b c Z bc b Figure 10: Wye And Delta Connected Impedances Suppose it is necessary to build a resistive heater to deliver 6 kw, to be made of three elements which may be connected in either wye or delta. Each of the three elements must dissipate 2000 W. V 2 Thus, since P = R, the wye connected resistors would be: R y = = 7.2Ω 2000 while the delta connected resistors would be: R Δ = = 21.6Ω 2000 As is suggested by this example, wye and delta connected impedances are often directly equivalent. In fact, ungrounded connections are three-terminal networks which may be represented in two ways. The two networks shown in Figure 10, combinations of three passive impedances, are directly equivalent and identical in their terminal behavior if the relationships between elements are as given in (27-32). Z ab Z a Z b Z b Z Z Z c c a = (27) Z c 8
9 Z bc = Z a Z b Z b Z c ZcZ a Z a (28) Z a Z b Z b Zc Z c Z Z a a (29) c = Z b Z a = Z ab Zc a Z ab Z bc Z ca (30) Z b = Z ab Z bc Z ab Z bc Z ca (31) Z c = Z b cz ca Z ab Z bc Z ca (32) A special case of the wye-delta equivalence is that of balanced loads, in which: Z a = Z b = Z c = Z y and in which case: Z ab = Z bc = Z ca = Z Δ Z Δ = 3Z y 4.2 Example: Use of Wye-Delta for Unbalanced Loads The unbalanced load shown in Figure 11 is connected to a balanced voltage source. The problem is to determine the line currents. ote that his load is ungrounded (if it were grounded, this would be a trivial problem). The voltages are given by: v a = V cos ωt v b 2π = V cos(ωt ) 3 v c 2π = V cos(ωt ) 3 To solve this problem, convert both the source and load to delta equivalent connections, as shown in Figure 12. The values of the three resistors are: r ab = r ca = = r bc = = 8 1 The complex amplitudes of the equivalent voltage sources are: V j 2 π j V 3e π ab = V a V b = V 1 e 3 = 6 V π j 2 π j 2 π j V bc = V b V c = V e 3 e 3 = 3e 2 V 3e j 5 π j 2 π V ca = V c V a = V e 3 1 = 6 9
10 I a - V a R a = 1 V - - c Vb R b = 2 R c = 2 I b I c Figure 11: Unbalanced Load V ca - Vab - I a R = 4 ab R = 4 ca - V bc I b R = 8 bc I c Figure 12: Delta Equivalent 10
11 Currents in each of the equivalent resistors are: V ab V bc V I ca 1 = I 2 = I 3 = r ab The line curents are then just the difference between current in the legs of the delta: j π 5π 3 3V e 6 j e 6 I a = I 1 I 3 = 4 4 = V 4 j j e π π 3V 2 e I b = I 2 I 1 = 8 4 = j V 8 4 j 5π j π e 3 1 3V 6 e 2 I c = I 3 I 2 = 4 8 = j V 8 4 These are shown in Figure 13. r bc r ca V 4V Im( ) 1 V 4 1 V 4 Re( ) Figure 13: Line Currents 5 Transformers Transformers are essential parts of most power systems. Their role is to convert electrical energy at one voltage to some other voltage. We will deal with transformers as electromagnetic elements later on in this subject, but for now it will be sufficient to use a simplified model for the transformer which we will call the ideal transformer. This is a two-port circuit element, shown in Figure 14. i 1 i 2 1 : 2 v 1 v 2 Figure 14: Ideal Transformer The ideal transformer as a network element constrains its terminal variables in the following way: 11
12 v 1 v 2 = (33) i 1 = 2 i 2 (34) As it turns out, this is not a terribly bad model for the behavior of a real transformer under most circumstances. Of course, we will be interested in fine points of transformer behavior and behavior under pathological operating conditions, and so will eventually want a better model. For now, it is sufficient to note just a few things about how the transformer works. 1. In normal operation, we select a transformer turns ratio 1 2 so that the desired voltages appear at the proper terminals. For example, to convert 13.8 kv distribution voltage to the 120/240 volt level suitable for residential or commercial single phase service, we would use a transformer with turns ratio of 240 = To split the low voltage in half, a center tap on the low voltage winding would be used. 2. The transformer, at least in its ideal form, does not consume, produce nor store energy. ote that, according to (33) and (34), the sum of power flows into a transformer is identically zero: p 1 p 2 = v 1 i 1 v 2 i 2 = 0 (35) 3. The transformer also tends to transform impedances. To show how this is, look at Figure 15. Here, some impedance is connected to one side of an ideal transformer. See that it is possible to find an equivalent impedance viewed from the other side of the transformer. I 1 V 1 I 1 : 2 2 Z Figure 15: Impedance Transformation oting that 1 I 2 = 2 I 1 and that V 2 = ZI 2 Then the ratio between input voltage and current is: V 1 = V 2 = I 2 1 (36) 2 12
13 6 Three-Phase Transformers A three-phase transformer is simply three single phase transformers. The complication in these things is that there are a number of ways of winding them, and a number of ways of interconnecting them. We will have more to say about windings later. For now, consider interconnections. On either side of a transformer connection (i.e. the high voltage and low voltage sides), it is possible to connect transformer windings either line to neutral (wye), or line to line (delta). Thus we may speak of transformer connections being wye-wye, delta-delta, wye-delta, or delta-wye. Ignoring certain complications that we will have more to say about shortly, connection of transformers in either wye-wye or delta-delta is reasonably easy to understand. Each of the line-to-neutral (in the case of wye-wye), or line-to-line (in the case of delta-delta) voltages is transformed by one of the three transformers. On the other hand, the interconnections of a wye-delta or delta-wye transformer are a little more complex. Figure 16 shows a delta-wye connection, in what might be called wiring diagram form. A more schematic (and more common) form of the same picture is shown in Figure 17. In that picture, winding elements that appear parallel are wound on the same core segment, and so constitute a single phase transformer. X c H c X b H b X a H a Figure 16: Delta-Wye Transformer Connection ow: assume that and are numbers of turns. If the individual transformers are considered to be ideal, the following voltage and current constraints exist: v ay = v by = v cy = i aδ = i bδ = i cδ = (v aδ v bδ ) (37) (v bδ v cδ ) (38) (v cδ v aδ ) (39) (i ay i cy ) (40) (i by i ay ) (41) (i cy i by ) (42) 13
14 A A Y C B C Y B Y Figure 17: Schematic of Delta-Wye Transformer Connection where each of the voltages are line-neutral and the currents are in the lines at the transformer terminals. ow, consider what happens if a Δ Y transformer is connected to a balanced three- phase voltage source, so that: v aδ = Re V e jωt ) v bδ = Re V e j(ωt2 π 3 ) v cδ = Re V e j(ωt2 π 3 Then, complex amplitudes on the wye side are: V = Y ay V 1 e j 2 π 3 = 3 j V e π 6 = Y j V e 3 e 3 = 3 j V 2π V e π by 2 j 2π j = 5π Y V e j 2 π V cy 3 1 = 3 V e 6 Two observations should be made here: The ratio of voltages (that is, the ratio of either line-line or line-neutral) is different from the turns ratio by a factor of 3. All wye side voltages are shifted in phase by 30 with respect to the delta side voltages. 6.1 Example Suppose we have the following problem to solve: 14
15 A balanced three- phase wye-connected resistor is connected to the Δ side of a Y Δ transformer with a nominal voltage ratio of v Δ = v Y What is the impedance looking into the wye side of the transformer, assuming drive with a balanced source? The situation is shown in Figure 18. R R R Figure 18: Example It is important to remember the relationship between the voltage ratio and the turns ratio, which is: v Δ = = Δ v Y 3Y so that: δ = 3 ext, the Y Δ equivalent transform for the load makes the picture look like figure 19 In this situation, each transformer secondary winding is conected directly across one of the three resistors. Currents in the resistors are given by: Line currents are: i 1 = i 2 = i 3 = v abδ v bcδ v caδ i aδ = i bδ = i cδ = i 1 i 3 = i 2 i 1 = i 3 i 2 = v abδ v caδ v bcδ v abδ v caδ v bcδ 15 = i 1Δ i 3Δ = i 2Δ i 1Δ = i 3Δ i 2Δ
16 i a i cy v cy i ay v ay v by iby i c vca v v ab bc i 3 i 2 i b i 1 Figure 19: Equivalent Situation Solving for currents in the legs of the transformer Δ, subtract, for example, the second expression from the first: 2i 1Δ i 2Δ i 3Δ = 2v abδ v bcδ v caδ ow, taking advantage of the fact that the system is balanced: to find: i 1Δ i 2Δ i 3Δ = 0 v abδ v bcδ v caδ = 0 i 1Δ = i 2Δ = i 3Δ = Finally, the ideal transformer relations give: v abδ v bcδ v caδ v abδ = v ay i ay = i 1Δ v bcδ = v by i by = i 2Δ v caδ = v cy i cy = i 3Δ so that: 2 Δ 1 i ay = v ay 16
17 2 Δ 1 i by = v by 2 Δ 1 i cy = v cy The apparent resistance (that is, apparent were it to be connected in wye) at the wye terminals of the transformer is: 2 Y R eq = Expressed in terms of voltage ratio, this is: 2 v 2 Y R eq = = R 3 vδ It is important to note that this solution took the long way around. Taken consistently (uniformly on a line-neutral or uniformly on a line-line basis), impedances transform across transformers by the square of the voltage ratio, no matter what connection is used. 7 Polyphase Lines and Single-Phase Equivalents By now, one might suspect that a balanced polyphase system may be regarded simply as three single-phase systems, even though the three phases are physically interconnected. This feeling is reinforced by the equivalence between wye and delta connected sources and impedances. One more step is required to show that single phase equivalence is indeed useful, and this concerns situations in which the phases have mutual coupling. In speaking of lines, we mean such system elements as transmission or distribution lines: overhead wires, cables or even in-plant buswork. Such elements have impedance, so that there is some voltage drop between the sending and receiving ends of the line. This impedance is more than just conductor resistance: the conductors have both self and mutual inductance, because currents in the conductors make magnetic flux which, in turn, is linked by all conductors of the line. A schematic view of a line is shown in Figure 20. Actually, only the inductance components of line impedance are shown, since they are the most interesting parts of line impedance. Working in complex amplitudes, it is possible to write the voltage drops for the three phases by: V a1 V a2 = jωli a jωm (I b I c ) (43) V b1 V b2 = jωli b jωm (I a I c ) (44) V c1 V c2 = jωli c jωm (I a I b ) (45) If the currents form a balanced set: Then the voltage drops are simply: I a I b I c = 0 (46) V a1 V a2 V b1 V b2 V c1 V c2 = jω (L M) I a = jω (L M) I b = jω (L M) I c 17
18 v a1 v b1 v c1 i i a b i c L L L M M M v v v a2 b2 c2 Figure 20: Schematic Of A Balanced Three-Phase Line With Mutual Coupling V c - V a - - V b L L L M M M R R R Voltage Source Primary Secondary Transmission Line Load Transformer Figure 21: Example In this case, an apparent inductance, suitable for the balanced case, has been defined: L 1 = L M (47) which describes the behavior of one phase in terms of its own current. It is most important to note that this inductance is a valid description of the line only if (46) holds, which it does, of course, in the balanced case. 7.1 Example To show how the analytical techniques which come from the network simplification resulting from single phase equivalents and wye-delta transformations, consider the following problem: A three-phase resistive load is connected to a balanced three-phase source through a transformer connected in delta-wye and a polyphase line, as shown in Figure 21. The problem is to calculate power dissipated in the load resistors. The three- phase voltage source has: jωt v a = Re 2V RMS e j(ωt 2π ) v b = Re 2V RMS e 3 j(ωt 2π ) v c = Re 2V RMS e 3 18
19 This problem is worked by a succession of simple transformations. First, the delta connected R resistive load is converted to its equivalent wye with R Y = 3. ext, since the problem is balanced, the self- and mutual inductances of the line are directly equivalent to self inductances in each phase of L 1 = L M. ow, the transformer secondary is facing an impedance in each phase of: Z Y s = jωl 1 R Y The delta-wye transformer has a voltage ratio of: v p v s = 3Y so that, on the primary side of the transformer, the line and load impedance is: where the equivalent elements are: Z p = jωl eq R eq L eq = R eq = 1 2 Δ (L M) Δ R 3 3 Magnitude of current flowing in each phase of the source is: 2VRMS I = (ωl ) 2 R 2 eq Dissipation in one phase is: eq P 1 = = I R eq V RMS 2 R eq (ωl eq ) 2 R2 eq And, of course, total power dissipated is just three times the single phase dissipation. 8 Introduction To Per-Unit Systems Strictly speaking, per-unit systems are nothing more than normalizations of voltage, current, impedance and power. These normalizations of system parameters because they provide simplifications in many network calculations. As we will discover, while certain ordinary parameters have very wide ranges of value, the equivalent per-unit parameters fall in a much narrower range. This helps in understanding how certain types of system behave. 19
20 i 1 V v Z 1 Figure 22: Example 8.1 ormalization Of Voltage And Current The basis for the per-unit system of notation is the expression of voltage and current as fractions of base levels. Thus the first step in setting up a per-unit normalization is to pick base voltage and current. Consider the simple situation shown in Figure 22. For this network, the complex amplitudes of voltage and current are: V = IZ (48) We start by defining two base quantities, V B for voltage and I B for current. In many cases, these will be chosen to be nominal or rated values. For generating plants, for example, it is common to use the rated voltage and rated current of the generator as base quantities. In other situations, such as system stability studies, it is common to use a standard, system wide base system. The per-unit voltage and current are then simply: v = V V B (49) i = I I B (50) Applying (49) and (50) to (48), we find: v = iz (51) where the per-unit impedance is: I B z = Z V B (52) This leads to a definition for a base impedance for the system: V B Z B = I B (53) Of course there is also a base power, which for a single phase system is: P B = V B I B (54) as long as V B and I B are expressed in RMS. It is interesting to note that, as long as normalization is carried out in a consistent way, there is no ambiguity in per-unit notation. That is, peak quantities normalized to peak base quantities will be the same, in per-unit, as RMS quantities normalized to RMS bases. This advantage is even more striking in polyphase systems, as we are about to see. 20
21 8.2 Three Phase Systems When describing polyphase systems, we have the choice of using either line-line or line-neutral voltage and line current or current in delta equivalent loads. In order to keep straight analysis in ordinary variable, it is necessary to carry along information about which of these quantities is being used. There is no such problem with per-unit notation. We may use as base quantities either line to neutral voltage V Blg or line to line voltage V Bll. Taking the base current to be line current I Bl, we may express base power as: P B = 3V Blg I Bl (55) Because line-line voltage is, under normal operation, 3 times line-neutral voltage, an equivalent statement is: P B = 3VBll I Bl (56) If base impedance is expressed by line-neutral voltage and line current (This is the common convention, but is not required), V Blg Z B = (57) I Bl Then, base impedance is, written in terms of base power: P V 2 V 2 B Blg Z Bll B = 3I 2 = 3 = (58) P B P B B ote that a single per-unit voltage applied equally well to line-line, line-neutral, peak and RMS quantities. For a given situation, each of these quantities will have a different ordinary value, but there is only one per-unit value. 8.3 etworks With Transformers One of the most important advantages of the use of per-unit systems arises in the analysis of networks with transformers. Properly applied, a per-unit normalization will cause nearly all ideal transformers to dissapear from the per-unit network, thus greatly simplifying analysis. To show how this comes about, consider the ideal transformer as shown in Figure 23. The I 1 I 2 1 : V 1 V 2 Figure 23: Ideal Transformer With Voltage And Current Conventions oted ideal transformer imposes the constraints that: V 2 = V 1 I 2 = 1 I 1 21
22 ormalized to base quantities on the two sides of the transformer, the per-unit voltage and current are: v 1 = i 1 = v 2 = i 2 = V 1 V B1 I 1 I B1 V 2 V B2 I 2 I B2 ow: note that if the base quantities are related to each other as if they had been processed by the transformer: V B2 = V B1 (59) I B1 I B2 = (60) then v 1 = v 2 and i 1 = i 2, as if the ideal transformer were not there (that is, consisted of an ideal wire). Expressions (59) and (60) reflect a general rule in setting up per-unit normalizations for systems with transformers. Each segment of the system should have the same base power. Base voltages transform according to transformer voltage ratios. For three-phase systems, of course, the voltage ratios may differ from the physical turns ratios by a factor of 3 if delta-wye or wye-delta connections are used. It is, however, the voltage ratio that must be used in setting base voltages. 8.4 Transforming From One Base To Another Very often data such as transformer leakage inductance is given in per-unit terms, on some base (perhaps the units rating), while in order to do a system study it is necessary to express the same data in per-unit in some other base (perhaps a unified system base). It is always possible to do this by the two step process of converting the per-unit data to its ordinary form, then re-normalizing it in the new base. However, it is easier to just convert it to the new base in the following way. ote that impedance in Ohms (ordinary units) is given by: Z = z 1 Z B1 = z 2 Z B2 (61) Here, of course, z 1 and z 2 are the same per-unit impedance expressed in different bases. This could be written as: V B1 2 V B2 2 z 1 = z 2 (62) This yields a convenient rule for converting from one base system to another: P B1 P B2 P B1 V 2 B2 z 1 = z 2 (63) P B2 V B1 22
23 Load G T 1 1 L T 2 3-Phase Fault Figure 24: One-Line Diagram Of Faulted System 8.5 Example: Fault Study To illustrate some of the concepts with which we have been dealing, we will do a short circuit analysis of a simple power system. This system is illustrated, in one-line diagram form, in Figure 24. A one-line diagram is a way of conveying a lot of information about a power system without becoming cluttered with repetitive pieces of data. Drawing all three phases of a system would involve quite a lot of repetition that is not needed for most studies. Further, the three phases can be re-constructed from the one-line diagram if necessary. It is usual to use special symbols for different components of the network. For our network, we have the following pieces of data: Symbol Component Base P Base V Impedance (MVA) (kv) (per-unit) G 1 Generator j.18 T 1 Transformer /138 j.12 L 1 Trans. Line j.05 T 2 Transformer /34.5 j.08 A three-phase fault is assumed to occur on the 34.5 kv side of the transformer T 2. This is a symmetrical situation, so that only one phase must be represented. The per-unit impedance diagram is shown in Figure 25. It is necessary to proceed now to determine the value of the components in this circuit. x g x T 1 x l r l x T 2 e g Figure 25: Impedance Diagram For Fault Example First, it is necessary to establish a uniform base an per-unit value for each of the system components. Somewhat arbitrarily, we choose as the base segment the transmission line. Thus all of the parameters must be put into a base power of 100 MVA and voltage bases of 138 kv on the 23
24 line, 13.8 kv at the generator, and 34.5 kv at the fault. Using (62): x g = x T 1 = x T 2 = r l = x l = =.09per-unit =.06per-unit =.16per-unit =.02per-unit =.05per-unit Total impedance is: z z = j (x g x T 1 x l x T 2 ) r l = j.36.02per-unit =.361per-unit ow, if e g is equal to one per-unit (generator internal voltage equal to base voltage), then the per-unit current is: 1 i = =.277per-unit.361 This may be translated back into ordinary units by getting base current levels. These are: On the base at the generator: 100MVA I B = kV = 4.18kA On the line base: On the base at the fault: 100MVA I B = 3 138kV = 418A 100MVA I B = kV = 1.67kA Then the actual fault currents are: At the generator I f = 11, 595A On the transmission line I f = 1159A At the fault I f = 4633A 24
25 MIT OpenCourseWare / Introduction to Electric Power Systems Spring 2011 For information about citing these materials or our Terms of Use, visit:
1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr.
Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science 6.06 Introduction to Power Systems Class Notes Chapter 4 Introduction To Symmetrical Components J.L. Kirtley
BALANCED THREE-PHASE CIRCUITS
BALANCED THREE-PHASE CIRCUITS The voltages in the three-phase power system are produced by a synchronous generator (Chapter 6). In a balanced system, each of the three instantaneous voltages have equal
Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1
Experiment no 1 Power measurement in balanced 3 phase circuits and power factor improvement 1 Power in Single Phase Circuits Let v = m cos(ωt) = cos(ωt) is the voltage applied to a R-L circuit and i =
Chapter 24. Three-Phase Voltage Generation
Chapter 24 Three-Phase Systems Three-Phase Voltage Generation Three-phase generators Three sets of windings and produce three ac voltages Windings are placed 120 apart Voltages are three identical sinusoidal
Three-phase AC circuits
Three-phase AC circuits This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,
Three phase circuits
Three phase circuits THREE PHASE CIRCUITS THREE-PHASE ADVANTAGES 1. The horsepower rating of three-phase motors and the kva rating of three-phase transformers are 150% greater than single-phase motors
Lecture Notes ELE A6
ecture Notes EE A6 Ramadan El-Shatshat Three Phase circuits 9/12/2006 EE A6 Three-phase Circuits 1 Three-phase Circuits 9/12/2006 EE A6 Three-phase Circuits 2 Advantages of Three-phase Circuits Smooth
How To Wire A Three Phase, Single Phase, Wye Transformer
Three-Phase Transformers When more power is needed - three transformers can be tied together. This is called three-phase. Here s a simple way of comparing single-phase to threephase power. Single-Phase
(3 )Three Phase Alternating Voltage and Current
EEE 2015 EECTRCS (3) Monophase 1 Three phase Three phase electric power is a common method of alternating current electric power generation, transmission, and distribution. t is a type of polyphase system
3-Phase AC Calculations Revisited
AN110 Dataforth Corporation Page 1 of 6 DID YOU KNOW? Nikola Tesla (1856-1943) came to the United States in 1884 from Yugosiavia. He arrived during the battle of the currents between Thomas Edison, who
Three Phase Circuits. Three Phase Circuits
Three Phase Circuits 1 Three Phase Circuits Chater Objectives: Be familiar with different three-hase configurations and how to analyze them. Know the difference between balanced and unbalanced circuits
Chapter 12 Three-Phase Circuit
Chapter 12 Three-Phase Circuit 馮 武 雄 教 授 長 庚 大 學 電 子 系 1 Chapter 12 Three-Phase Circuits 12.1 What is a Three-Phase Circuit? 12.2 Balance Three-Phase oltages 12.3 Balance Three-Phase Connection 12.4 Power
BALANCED THREE-PHASE AC CIRCUIT
BAANCED THREE-PHASE AC CRCUT Balanced Three-Phase oltage Sources Delta Connection Star Connection Balanced 3-hase oad Delta Connection Star Connection Power in a Balanced Phase Circuit ntroduction Three
Basic Electrical Technology Dr. L. Umanand Department of Electrical Engineering Indian Institute of Science, Bangalore. Lecture - 33 3 phase System 4
Basic Electrical Technology Dr. L. Umanand Department of Electrical Engineering Indian Institute of Science, Bangalore Lecture - 33 3 phase System 4 Hello everybody. So, in the last class we have been
Coupled Inductors. Introducing Coupled Inductors
Coupled Inductors From power distribution across large distances to radio transmissions, coupled inductors are used extensively in electrical applications. Their properties allow for increasing or decreasing
Equipment: Power Supply, DAI, Variable resistance (8311), Variable inductance (8321)
Lab 4: 3-phase circuits. Objective: to study voltage-current relationships in 3-phase circuits; to learn to make delta and Y connections; to calculate and measure real, apparent, and reactive powers. Equipment:
Chapter 11 Balanced Three-Phase Circuits
Chapter 11 Balanced Three-Phase Circuits 11.1-2 Three-Phase Systems 11.3 Analysis of the Y-Y Circuit 11.4 Analysis of the Y- Circuit 11.5 Power Calculations in Balanced Three-Phase Circuits 11.6 Measuring
Radial Distribution Test Feeders
Radial Distribution Test Feeders Distribution System Analysis Subcommittee Report Abstract: Many computer programs are available for the analysis of radial distribution feeders. In 1992 a paper was published
How To Understand And Understand The Theory Of Electricity
DIRECT CURRENT AND ALTERNATING CURRENT SYSTEMS N. Rajkumar, Research Fellow, Energy Systems Group, City University Northampton Square, London EC1V 0HB, UK Keywords: Electrical energy, direct current, alternating
Chapter 12: Three Phase Circuits
Chapter 12: Three Phase Circuits 12.1 What Is a Three Phase Circuit? 12.2 Balance Three Phase Voltages 12.3 Balance Three Phase Y to Y Connection 12.4 Other Balance Three Phase Connections 12.5 Power in
The generation and supply of electricity within the U.K is achieved through the use of a 3-phase system.
Three Phase Electricity Supplies and Systems The generation and supply of electricity within the U.K is achieved through the use of a 3-phase system. This consists of 3 separate phase conductors along
THREE PHASE CIRCUITS
THREE PHASE CIRCUITS A. PREPARATION 1. Three Phase Voltages and Systems 2. The Determination of Phase Sequence 3. Blondel's Theorem and Its Consequences 4. References B. EXPERIMENT 1. Equipment List 2.
AC Generators. Basic Generator
AC Generators Basic Generator A basic generator consists of a magnetic field, an armature, slip rings, brushes and a resistive load. The magnetic field is usually an electromagnet. An armature is any number
Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques
Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques Howard W. Penrose, Ph.D On behalf of ALL-TEST Pro, LLC Old Saybrook, CT Introduction Field and shop testing of
Motor Protection Voltage Unbalance and Single-Phasing
Motor Protection Voltage Unbalance and Single-Phasing Cooper Bussmann contributes the following information, which is an excerpt from their 190-page handbook SPD Selecting Protective Devices Based on the
Transformer circuit calculations
Transformer circuit calculations This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,
PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA
PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA What are phasors??? In normal practice, the phasor represents the rms maximum value of the positive half cycle of the sinusoid
Outline. Systems and Signals 214 / 244 & Energy Systems 244 / 344. Ideal Inductor. Ideal Inductor (cont... )
Outline Systems and Signals 214 / 244 & Energy Systems 244 / 344 Inductance, Leakage Inductance, Mutual Inductance & Transformers 1 Inductor revision Ideal Inductor Non-Ideal Inductor Dr. P.J. Randewijk
TRANSFORMER: THREE PHASE
CONTENTS Transformer : Three Phase 1211 C H A P T E R 33 Learning Objectives Three-phase Transformers Three-phase Transformer Connections Star/Star or Y/Y Connection Delta-Delta or Connection Wye/Delta
Loading Considerations When Paralleling Transformers
Application Guide 7400DB0701 02/2007 Nashville, TN, USA Loading Considerations When Paralleling Transformers Class 7400 Retain for future use. Introduction Principles of Paralleling This application guide
2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?
Extra Questions - 2 1. A straight length of wire moves through a uniform magnetic field. The e.m.f. produced across the ends of the wire will be maximum if it moves: a) along the lines of magnetic flux
Three-Phase AC Power Circuits
Electricity and New Energy Three-Phase AC Power Circuits Student Manual 86360-F0 Order no.: 86360-00 Revision level: 10/2014 By the staff of Festo Didactic Festo Didactic Ltée/Ltd, Quebec, Canada 2010
Linear DC Motors. 15.1 Magnetic Flux. 15.1.1 Permanent Bar Magnets
Linear DC Motors The purpose of this supplement is to present the basic material needed to understand the operation of simple DC motors. This is intended to be used as the reference material for the linear
Induced voltages and Inductance Faraday s Law
Induced voltages and Inductance Faraday s Law concept #1, 4, 5, 8, 13 Problem # 1, 3, 4, 5, 6, 9, 10, 13, 15, 24, 23, 25, 31, 32a, 34, 37, 41, 43, 51, 61 Last chapter we saw that a current produces a magnetic
Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.
By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt
The following table shows approximate percentage wise the
SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are
Figure. 1 - Split Phase 240/120V circuit (180 phase shift)
This technical note describes the option of connecting the 60Hz XW Inverter/Charger to a three-phase source by using a transformer to convert the AC source to split-phase 240/120V. INTRODUCTION: Split-phase
Unit 33 Three-Phase Motors
Unit 33 Three-Phase Motors Objectives: Discuss the operation of wound rotor motors. Discuss the operation of selsyn motors. Discuss the operation of synchronous motors. Determine the direction of rotation
EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT
EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT 4 Understand single-phase alternating current (ac) theory Single phase AC
ECE 431. Experiment #1. Three-Phase ac Measurements. PERFORMED: 26 January 2005 WRITTEN: 28 January 2005. Jason Wells
ECE 41 Experiment #1 Three- ac Measurements PERFORMED: 6 January 005 WRTTEN: 8 January 005 Jason Wells LEADER: Jason Wells RECORDER: Nathaniel Hakes 1 ntroduction The primary objectives of the experiment
SYNCHRONOUS MACHINES
SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical
GE Multilin technical note
Digital Energy Multilin GE Multilin technical note eutral voltage unbalance function at grounded wye capacitor banks GE publication number: GET-8544 Copyright 00 GE Multilin eutral voltage unbalance function
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
DOE FUNDAMENTALS HANDBOOK ELECTRICAL SCIENCE Volume 3 of 4
DOE-HDBK-1011/3-92 JUNE 1992 DOE FUNDAMENTALS HANDBOOK ELECTRICAL SCIENCE Volume 3 of 4 U.S. Department of Energy Washington, D.C. 20585 FSC-6910 Distribution Statement A. Approved for public release;
Measurement of Power in single and 3-Phase Circuits. by : N.K.Bhati
Measurement of Power in single and 3-Phase Circuits by : N.K.Bhati A specifically designed programme for Da Afghanistan Breshna Sherkat (DABS) Afghanistan 1 Areas Covered Under this Module 1. Power in
Earth Fault Detection Basics in Theory
Earth Fault Detection Basics in Theory Author: Dipl.-Ing. Ingo Kühnen Woodward Power Solutions Krefelder Weg 47 47906 Kempen, Germany Kempen, 16.04.2010 Earth_Fault_Detection_20100416.doc page 1 1. Star
ACCURACY OF POTENTIALTRANSFORMERS
8 VOLTAGE TRANSFORMERS Two types of voltage transformer are used for protective-relaying purposes, as follows: (1) the "instrument potential transformer," hereafter to be called simply "potential transformer,"
Static Analysis of Power Systems. Lennart Söder and Mehrdad Ghandhari
Static Analysis of Power Systems Lennart Söder and Mehrdad Ghandhari Electric Power Systems Royal Institute of Technology August 200 ii Contents Introduction 2 Power system design 3 2. The development
The electrical energy produced at the gen
300 300 Principles of Power System CHAPTER CHAPTER 12 Distribution Systems General 12.1 Distribution System 12.2 Classification of Distribution Systems 12.3 A.C. Distribution 12.4 D.C. Distribution 12.5
Rule 5.500 Fast Track Analysis for National Life Insurance Co.
Rule 5.500 Fast Track Analysis for National Life Insurance Co. For a 500 kw Solar array to be located at 155 Northfield Street in Montpelier, Vermont Green Mountain Power Pam Allen Date: 5/31/13 SECTION
SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations
SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3 3.0 Introduction Fortescue's work proves that an unbalanced system of 'n' related phasors can be resolved into 'n' systems of balanced phasors called the
THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating.
THE PER-UNIT SYSTEM An interconnected power system typically consists of many different voltage levels given a system containing several transformers and/or rotating machines. The per-unit system simplifies
Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE
Understanding Power Factor and How it Affects Your Electric Bill Presented by Scott Peele PE Understanding Power Factor Definitions kva, kvar, kw, Apparent Power vs. True Power Calculations Measurements
Solution Derivations for Capa #11
Solution Derivations for Capa #11 Caution: The symbol E is used interchangeably for energy and EMF. 1) DATA: V b = 5.0 V, = 155 Ω, L = 8.400 10 2 H. In the diagram above, what is the voltage across the
Chapter 9 Balanced Faults
Chapter 9 alanced Faults 9.1 Introduction The most common types of fault are (in order) single-line-to-ground fault, line-to-line fault, and double-line-to-ground fault. All of these are unbalanced faults.
Three-Phase Electric Power Distribution for Computer Data Centers
Three-hase Electric ower Distribution for Computer Data Centers WHITE AER E901 Geist January 008 Summary This paper will describe the characteristics of three-phase power and outline the advantages of
SHORT CIRCUIT CURRENT CALCULATION AND PREVENTION IN HIGH VOLTAGE POWER NETS
Bachelor's Thesis Electrical Engineering June 2014 SHORT CIRCUIT CURRENT CALCULATION AND PREVENTION IN HIGH VOLTAGE POWER NETS MD FARUQUL ALAM SALMAN SAIF HAMID ALI School of Engineering Blekinge Tekniska
Product Data Bulletin
Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system
EET272 Worksheet Week 9
EET272 Worksheet Week 9 answer questions 1-5 in preparation for discussion for the quiz on Monday. Finish the rest of the questions for discussion in class on Wednesday. Question 1 Questions AC s are becoming
Short Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
Simulation of Ungrounded Shipboard Power Systems in PSpice
Simulation of Ungrounded Shipboard Power Systems in PSpice Haibo Zhang IEEE Student Member Karen L.Butler IEEE Member Power System Automation Lab Electrical Engineering Department Texas A&M University
Definition AC Power Distribution
COMMON AC POWER DISTRIBUTION CONFIGURATIONS The input voltage needed to power electronic equipment is provided by the manufacture in the product specifications. Matching this requirement to the facility
DESIGNING MODERN ELECTRICAL SYSTEMS WITH TRANSFORMERS THAT INHERENTLY REDUCE HARMONIC DISTORTION IN A PC-RICH ENVIRONMENT
DESIGNING MODERN ELECTRICAL SYSTEMS WITH TRANSFORMERS THAT INHERENTLY REDUCE HARMONIC DISTORTION IN A PC-RICH ENVIRONMENT by Philip J. A. Ling, P.Eng. Cyril J. Eldridge, B. Sc. POWERSMITHS INTERNATIONAL
E.G.Strangas MSU Electrical Machines and Drives Laboratory
Notes for an Introductory Course On Electrical Machines and Drives E.G.Strangas MSU Electrical Machines and Drives Laboratory Contents Preface ix 1 Three Phase Circuits and Power 1 1.1 Electric Power
Circuits with inductors and alternating currents. Chapter 20 #45, 46, 47, 49
Circuits with inductors and alternating currents Chapter 20 #45, 46, 47, 49 RL circuits Ch. 20 (last section) Symbol for inductor looks like a spring. An inductor is a circuit element that has a large
EE 221 Circuits II. Chapter 13 Magnetically Coupled Circuits
EE Circuits II Chapter 3 Magnetically Coupled Circuits Magnetically Coupled Circuits 3. What is a transformer? 3. Mutual Inductance 3.3 Energy in a Coupled Circuit 3.4 inear Transformers 3.5 Ideal Transformers
8 Speed control of Induction Machines
8 Speed control of Induction Machines We have seen the speed torque characteristic of the machine. In the stable region of operation in the motoring mode, the curve is rather steep and goes from zero torque
INDUCTION REGULATOR. Objective:
INDUCTION REGULATOR Objective: Using a wound rotor induction motor an Induction Regulator, study the effect of rotor position on the output voltage of the regulator. Also study its behaviour under load
Eðlisfræði 2, vor 2007
[ Assignment View ] [ Print ] Eðlisfræði 2, vor 2007 30. Inductance Assignment is due at 2:00am on Wednesday, March 14, 2007 Credit for problems submitted late will decrease to 0% after the deadline has
PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP
PacifiCorp Original Sheet No. 476 APPENDIX 2 TO SGIP SMALL GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: Designated Contact Person: Address: Telephone Number: An Interconnection
Alternating current three-phase circuits
Unit. C HEE-PHE CCU lternating current three-phase circuits Unit. C HEE-PHE CCU COE: hree-phase systems characteristics Generation of three-phase voltages hree-phase loads -Y and Y- transformation nstantaneous
How To Balance Three Phase Power In A Balanced System
Three-Phase Circuits Three-Phase Circuit Three-Phase Circuits What is a Three-Phase Circuit? Balance Three-Phase oltages Balance Three-Phase Connection Power in a Balanced System Unbalanced Three-Phase
Chapter 29 Alternating-Current Circuits
hapter 9 Alternating-urrent ircuits onceptual Problems A coil in an ac generator rotates at 6 Hz. How much time elapses between successive emf values of the coil? Determine the oncept Successive s are
AP1 Electricity. 1. A student wearing shoes stands on a tile floor. The students shoes do not fall into the tile floor due to
1. A student wearing shoes stands on a tile floor. The students shoes do not fall into the tile floor due to (A) a force of repulsion between the shoes and the floor due to macroscopic gravitational forces.
V out. Figure 1: A voltage divider on the left, and potentiometer on the right.
Living with the Lab Fall 202 Voltage Dividers and Potentiometers Gerald Recktenwald v: November 26, 202 [email protected] Introduction Voltage dividers and potentiometers are passive circuit components
Physics 9e/Cutnell. correlated to the. College Board AP Physics 1 Course Objectives
Physics 9e/Cutnell correlated to the College Board AP Physics 1 Course Objectives Big Idea 1: Objects and systems have properties such as mass and charge. Systems may have internal structure. Enduring
4.5 Transformer Connections
ELECTRIC POWER SYSTEMS IN COMMERCIAL BUILDINGS IEEE Std 241-1990 5) Flat Billing Ñ Certain applications involve service to the load of a Þxed characteristic. For such loads, the supplying utility may offer
Eðlisfræði 2, vor 2007
[ Assignment View ] [ Pri Eðlisfræði 2, vor 2007 28. Sources of Magnetic Field Assignment is due at 2:00am on Wednesday, March 7, 2007 Credit for problems submitted late will decrease to 0% after the deadline
Mutual Inductance and Transformers F3 3. r L = ω o
utual Inductance and Transformers F3 1 utual Inductance & Transformers If a current, i 1, flows in a coil or circuit then it produces a magnetic field. Some of the magnetic flux may link a second coil
LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University
LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University PURPOSE: The purpose of this lab is to introduce PSS/E. This lab will introduce the following aspects of PSS/E: Introduction to
PHASE CONVERSION TECHNOLOGY OVERVIEW
Dr. Larry Meiners, Ph.D. PHASE CONVERSION TECHNOLOGY OVERVIEW Introduction A wide variety of commercial and industrial electrical equipment requires three-phase power. Electric utilities do not install
12. Transformers, Impedance Matching and Maximum Power Transfer
1 1. Transformers, Impedance Matching and Maximum Power Transfer Introduction The transformer is a device that takes AC at one voltage and transforms it into another voltage either higher or lower than
HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80
Buck-Boost Transformers Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...
ET 332b Ac Electric Machines and Power Systems
Instructor: Dr. Carl Spezia, PE Office: Engr. D110 Phone: 453-7839 E-mail: [email protected] ET 332b Ac Electric Machines and Power Systems Office Hours: 9:00 am - 10:00 am M-W-F 2:00 pm - 3:00 pm M-W-F
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing
13 ELECTRIC MOTORS. 13.1 Basic Relations
13 ELECTRIC MOTORS Modern underwater vehicles and surface vessels are making increased use of electrical actuators, for all range of tasks including weaponry, control surfaces, and main propulsion. This
Power Quality Standards for Electric Service
Power Quality Standards for Electric Service Effective June 1, 2008 A transition period will exist from June 1 through December 31, 2008 in which installations may be approved and connected as long as
Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science
Massachusetts Institute of Technology Department of Electrical Engineering and Computer Science 6.685 Electric Machines Class Notes 4: Elementary Synchronous Machine Models c 005 James L. Kirtley Jr. 1
Telecommunication Line Protectors
TN CR 0025 Telecommunication Line s 1.1 The nature of telecom surges The telecom services considered in this report are transported on twisted pair. Each service has two wires, or lines, sometimes called
Triplen Harmonics Mitigation 3 Phase Four-Wire Electrical Distribution System Using Wye- Zig-Zag Transformers
Journal Journal of of Emerging Emerging Trends Trends in in Engineering Engineering and and Applied Applied Sciences Sciences (JETEAS) (JETEAS) 1 1 (1): (1): 72-78 72-78 Scholarlink Research Institute
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated
Current Probes, More Useful Than You Think
Current Probes, More Useful Than You Think Training and design help in most areas of Electrical Engineering Copyright 1998 Institute of Electrical and Electronics Engineers. Reprinted from the IEEE 1998
Scholars Research Library
Available online at www.scholarsresearchlibrary.com Scholars Research Library Archives of Applied Science Research, 2010, 2 (2):380-387 (http://scholarsresearchlibrary.com/archive.html) ISSN 0975-508X
PHY3128 / PHYM203 (Electronics / Instrumentation) Transmission Lines. Repeated n times I L
Transmission Lines Introduction A transmission line guides energy from one place to another. Optical fibres, waveguides, telephone lines and power cables are all electromagnetic transmission lines. are
2 A bank account for electricity II: flows and taxes
PHYS 189 Lecture problems outline Feb 3, 2014 Resistors and Circuits Having introduced capacitors, we now expand our focus to another very important component of a circuit resistors. This entails more
Power Factor Correction for Power Systems First Semester Report Spring Semester 2007
Power Factor Correction for Power Systems First Semester Report Spring Semester 2007 by Pamela Ackerman Prepared to partially fulfill the requirements for EE401 Department of Electrical and Computer Engineering
Chapter 35 Alternating Current Circuits
hapter 35 Alternating urrent ircuits ac-ircuits Phasor Diagrams Resistors, apacitors and nductors in ac-ircuits R ac-ircuits ac-ircuit power. Resonance Transformers ac ircuits Alternating currents and
Power Technology Issue 104. Modeling of Two-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E
SIEMENS Siemens Energy, Inc. Power Technology Issue 104 Modeling of TwoWinding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E Carlos GrandeMoran, Ph.D. Principal Consultant
