Troubleshooting and Lessons Learned Using Protective Relay Event Analysis. GE Digital Energy Multilin

Similar documents
Motor Protection Principles. Craig Wester GE Multilin

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations

Introduction to Paralleling of LTC Transformers by the Circulating Current Method

1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr.

Eaton s E-Series protective relay family

The following table shows approximate percentage wise the

Instrument Transformer Wiring Troubleshooting Guide Three Phase Meters Revision 0, Initial Issue, April 26, 1993

Open Phase Conditions in Transformers Analysis and Protection Algorithm

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

Generator Differential Relay Electrical Apparatus

GE Protection and Control Business Department. Page 1 Date 5/11/99

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

E-Series protective relay family

Basics of Electricity

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

Eaton s Electrical Services & Systems. Technical Training Safety Training

Scholars Research Library

SYNCHRONOUS MACHINES

Chapter 12: Three Phase Circuits

VOLTAGE REGULATOR AND PARALLEL OPERATION

Step Voltage Regulators

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only

Effective: September 10, 2006 Vermont Attachment 1 to Rule Public Service Board Page 1 of 6

Shunt Capacitor Bank Fundamentals and Protection

GENERATOR DIFFERENTIAL PROTECTION RELAY STABILITY VIS-A -VIS SELECTION OF CTS MR. H. C. MEHTA & MR. JAY MEHTA Power Linker Group Co.

Chapter 12 Three-Phase Circuit

Science and Reactor Fundamentals Electrical CNSC Technical Training Group. Table of Contents

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

GE Multilin technical note

Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering

Power Plant Electrical Distribution Systems

SPECIFICATION COG-2007

SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

Power Quality Paper #3

Cahier technique no. 196

EET272 Worksheet Week 8

PHASE CONVERSION TECHNOLOGY OVERVIEW

System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems

Impact of Distributed Resources on Distribution Relay Protection

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

Unit 33 Three-Phase Motors

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP

FREQUENCY CONTROLLED AC MOTOR DRIVE

Advanced Protection of Distribution Networks with Distributed Generators

TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v Spring web.itu.edu.tr/yumakk. Distance Protection

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS

Transmission Protection Overview

ABB PSPS Erich Steinmann; Generator control-2013

Three phase circuits

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

Product Data Bulletin

Motor Fundamentals. DC Motor

Loss of ac Voltage Considerations For Line Protection

SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION

Three-phase AC circuits

21 st Century Facilities

SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks

BALANCED THREE-PHASE CIRCUITS

INTRODUCTION TO SYNCHRONIZING AUTOMATIC SYNCHRONIZING CONSIDERATIONS AND APPLICATIONS

4.1.1 Generator Owner Transmission Owner that owns synchronous condenser(s)

High Efficiency Motor Protection. Industry White Paper

Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

Protection of Phase Angle Regulating Transformers

G650. Protection, control and monitoring for generator interconnection. Digital Energy Multilin. Communications

Voltage Unbalance and Motors

Chapter 11 Balanced Three-Phase Circuits

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

8 Speed control of Induction Machines

Transmission Line Protection Principles

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

300 MW Variable Speed Drives for Pump-Storage Plant Application Goldisthal

Engineering innovation

Power Factor Correction for Power Systems First Semester Report Spring Semester 2007

Line Reactors and AC Drives

AND8008/D. Solid State Control Solutions for Three Phase 1 HP Motor APPLICATION NOTE

Agilent Technologies. Troubleshooting Three-Phase AC Motors with U1210 Series Handheld Clamp Meters. Application Note

Grounding of AC generators and switching the neutral in emergency and standby power systems

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT

PROGRAM CRITERIA FOR ELECTRICAL ENGINEERING TECHNOLOGY

Paralleling Power Sources Which Share a Common Neutral

Challenges of Protection and Control System Verification on DP3 vessels with Focus on Ride Through Fault and Blackout

Short Circuit Current Calculations

Lecture Notes ELE A6

Measurement, Modeling and Simulation of Capacitor Bank Switching Transients

3-Phase AC Calculations Revisited

TABLE OF CONTENTS 1.0 INTRODUCTION PURPOSE DEVIATION INTERTIE PROTECTION REQUIREMENTS... 4

Basic Electrical Technology Dr. L. Umanand Department of Electrical Engineering Indian Institute of Science, Bangalore. Lecture phase System 4

Typical Data Requirements Data Required for Power System Evaluation

ZONE SELECTIVE INTERLOCKING (ZSI) APPLICATION AND TESTING GUIDE SIEMENS WL UL489 AND UL1066 AIR CIRCUIT BREAKERS

Synchronous motor. Type. Non-excited motors

1/29/2013. School. Generation Track. Overview Lecture. Generator Design, Connections, and Grounding

Modeling and Testing of Unbalanced Loading and Voltage Regulation

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

FREJA Win Software for FREJA relay testing system

Transcription:

Troubleshooting and Lessons Learned Using Protective Relay Event Analysis GE Digital Energy Multilin 1

Seminar Presenter Terrence Smith Terrence.Smith@GE.com 423-304-0843 2

Seminar Agenda Overhead distribution ground fault inside industrial facility causes a generator stator fault Incorrect current transformer wiring causes bus fault during power transformer energization Fault on distribution system causes unusual transformer high side currents Incorrect current transformer wiring causes motor thermal overload trip Generator loss of excitation and reverse power trips Overcurrent trip on paralleling switchgear Synchronous motor trip on power factor Substation heat pumps drops bus voltage by 1kV causes capacitor bank trip 3

Review Of Symmetrical Components 4

Symmetrical and Non-Symmetrical Systems: Symmetrical System: Counter-clockwise rotation All current vectors have equal amplitude All voltage phase vectors have equal amplitude All current and voltage vectors have 120 degrees phase shifts and a sum of 0v. Non-Symmetrical System: Fault or Unbalanced condition If one or more of the symmetrical system conditions is not met 9 units 3 units 3 units 120 120 120 3 units 100 4 units 120 140 3 units 5

Symmetrical Components: Positive Sequence (Always Present) C 120 B 120 A 120 A-B-C Counter-clockwise phase rotation All phasors with equal magnitude All phasors displaced 120 degrees apart Zero Sequence A B C No Rotation Sequence All phasors with equal magnitude All phasors are in phase Negative Sequence C B 120 120 A 120 A-C-B counter-clockwise phase rotation All phasors with equal magnitude All phasors displaced 120 degrees apart 6

Symmetrical Components: Positive Sequence Component: Negative Sequence Component: I 1 = ⅓ (I a + I b + 2 I c ) I 2 = ⅓ (I a + 2 I b + I c ) V 1 = ⅓ (V a + V b + 2 V c ) V 2 = ⅓ (V a + 2 V b + V c ) C 2 = 240 B A = 120 Zero Sequence Component: I 0 = ⅓ (I a + I b + I c ) V 0 = ⅓ (V a + V b + V c ) A B C Unbalanced Line-to-Neutral Phasors: I a = I 1 + I 2 + I 0 I b = 2 I 1 + I 2 + I 0 I c = I 1 + 2 I 2 + I 0 V a = V 1 + V 2 + V 0 V b = 2 V 1 + V 2 + V 0 V c = V 1 + 2 V 2 + V 0 =Phasor @ +120 2 =Phasor @ 240 7

Calculating Symmetrical Components: V c I c Positive Negative Zero 3V 1 3V 0 =0 I b V a V a *V b 2 *V c 2 *V b V c V a I a *V c V b 3V 2 =0 V a V b Three-Phase Balanced / Symmetrical System V c Positive Negative Zero I c I b V a I a *Ib 3I 1 3I 2 I a 3I 0 I c I b I a 2 *I c 2 *I b *I c I a V b Open-Phase Unbalanced / Non-Symmetrical System 8

Symmetrical Components Example: Perfectly Balanced & ABC Rotation Result: 100% I1 (Positive Sequence Component) 9

Symmetrical Components Example: B-Phase Rolled & ABC Rotation I 2 Result: 33% I1, 66% I0 and 66% I2 10

Symmetrical Components Example: B-Phase & C-Phase Rolled & ABC Rotation Result: 100% I2 (Negative Sequence Component) 11

Summary of Symmetrical Components: Under a no-fault condition, the power system is considered to be essentially symmetrical therefore, only positive sequence currents and voltages exist. At the time of a fault, positive, negative and possibly zero sequence currents and voltages exist. o o All positive, negative and zero sequence currents can be calculated using real world phase voltages and currents along with Fortescue s formulas. In = Ia + Ib + Ic = 3 I0 12

Power System Faults Fault Analysis Relay Data Sample 1 = No Fault Data Sample 2 = Fault 13

Power System Faults Fault Analysis For Normal Conditions: Data Sample 1 Phasor Diagram: Waveform Capture: 300 A 120 120 300 A 120 300 A Data Sample 1 = No Fault 14

Power System Faults Fault Analysis - Example For Fault Condition: Negative Sequence Component, I 2 : I 2 = 1/3(I a + 2 I b + I c ) = 1/3(600 A) I 2 = 200 Amps 2 I b = 300 A I c = 300 A I 2 = 1/3(600 A) I 2 = 200 A 600 A I a = 900 A 15

Power System Faults Fault Analysis - Example For Fault Condition: Zero Sequence Component, I 0 : I 0 = 1/3(I a +I b +I c ) 900 A I b I c 300 A 300 A 16

Power System Faults Fault Analysis - Example For Fault Condition: Zero Sequence Component, I 0 : I 0 = 1/3(I a +I b +I c ) I b = 300 A = 1/3(600 A) I 0 = 200 Amps I c = 300 A I 0 = 1/3(600 A) I 0 = 200 A 600 A I a = 900 A 17

Power System Faults Fault Analysis - Example For Fault Condition: Verifying Fault Current on Phase A: I a = I 1 + I 2 + I 0 = 500 A + 200 A + 200 A I a = 900 Amps = actual fault current measured on Phase A Fault, I a At the time of a fault, positive (I 1 ), negative (I 2 ) and possibly zero (I 0 ) sequence currents exist. 18

Sequence Networks Where is sequence voltage highest? What generates negative and zero sequence currents? 19

How do we connect so that I1=I2=I0? The sequence networks have to be in series for a phase to ground fault on a solidly grounded system. 20

Common Fault Types: 21

Transformer Interconnections: 22

Analysis of Interesting Events Using Waveforms 23

Snake Causes a Distribution Fault 24

Snake Causes a Distribution Fault Relays at all three locations tripped. All three had different times. Are these events related??? 25

Relays at all three locations tripped. All three had different times. Are these events related??? CB01 Why B phase on one and C on the other? CB402 26

What about the Generator??? C phase terminal fault current, but CG Stator fault close to the terminal Small C phase neutral fault current 27

What happened here?? C phase to ground fault because of the snake Zone interlocking scheme failed because of a settings error Generator failed due to the extra stress caused by the fault. Biggest Challenge was synchronizing the time differences in the relays. 28

Challenges to Time Synch 29

Modern Time Synchronization Add 1588 capabilities for future expansion while supporting inservice IRIG-B devices 30

1588 Protocol over a wide area with legacy devices 31

Generator Relay Failure to Trip on Loss of Excitation 32

The Story We lost the exciter The relay failed to trip on loss of excitaton 33

This ring down in current looks like loss of excitation (40) But 40 function does not operate! 34

Let s look at the phasors Why is current in opposite direction from voltage? 35

Machine limits Increasing pressure (cooling) Limited by OEL Overexcited Reactive Power Underexcited Real Power Limited by SCL Limited by MEL 36

Loss of field VT 18900 120 157.5 8000 1600 5 CT 2 base kv CTR 18kV 1600 Zbase (sec) 15. 54 base MVA VTR 211MVA 157.5 X (sec) X Zbase (sec) 0.216 15.54 3. 36 X d d d (sec) X Zbase (sec) 1.967 15.54 30. 57 d 2 37

Something with your current is not right! Ok, then why don t I trip on Differential? 38

Once I account for transformer, currents sum to zero 39

So what's wrong with 40 function? 40

Fault on Distribution System Causes Unusual Transformer High Side Currents 41

The Story Distribution transformer feeding medium voltage overhead distribution. In oscillography, we see two phases of fault current on the high side of the transformer for a single phase to ground fault on the low side 42

43

44

45

Pre-Fault Values F1 Symmetrical components M1 Symmetrical components Pre-fault all positive seq. 46

Fault Values F1 Pos, Neg, and no Zero M1 Pos, Neg, and Zero Why are the sequence values of M1 and F1 different?????? 47

The Fault Network as Seen From F1 48

The Fault Network as Seen From M1 49

What Effect Does this Fault Have on Voltage? 50

What Effect Does this Fault Have on Voltage? 51

Incorrect current transformer wiring causes bus fault during power transformer energization 52

The Story I have energized the transformer As soon as I pickup load, I get a transformer differential. 53

Oscillography Percent Differential Operates 54

Oscillography 55

What I expect to see for ABC rotation: Typically H Winding leads X winding by 30 degrees 56

What I expect to see for ABC rotation: We compensate the measured currents with settings Typically H Winding leads X winding by 30 degrees 57

What I expect to see for ABC rotation: 58

But this isn t ABC rotation: 59

But this isn t ABC rotation: Typically H Winding lags X winding by 30 degrees on ACB rotation 60

Trip occurred because of setting Typically H Winding lags X winding by 30 degrees on ACB rotation 61

What happens if I swap phases on my H winding: A a C c Swapping phases on the High side changes my transformer from 30 lag to 30 lead 62

Reversed Phase Causes Motor Thermal Overload Trip 63

The Story New switchgear feeding motor When we start the motor, it trips after about 10 minutes. 64

Waveforms Clearly, there is a phase reversed Why would this take 10 minutes to trip 65

Thermal Model Thermal Capacity Used Thermal Capacity Used (TCU) is a criterion selected in thermal model to evaluate thermal condition of the motor. TCU is defined as percentage of motor thermal limit utilized during motor operation. A running motor will have some level of thermal capacity used due to Motor Losses. Thermal Trip when Thermal Capacity Used equals 100% 66

Thermal Model - Current Unbalance Bias Negative sequence currents (or unbalanced phase currents) will cause additional rotor heating that will be accounted for in Thermal Model. Positive Sequence Main causes of current unbalance Blown fuses Loose connections Stator turn-to-turn faults System voltage distortion and unbalance Faults Negative Sequence 67

Thermal Model - Current Unbalance Bias Equivalent heating motor current is employed to bias thermal model in response to current unbalance. I EQ I 2 M (1 K (I 2 I 1 ) 2 ) Im - real motor current; K - unbalance bias factor; I 1 & I 2 - positive and negative sequence components of motor current. K factor reflects the degree of extra heating caused by the negative sequence component of the motor current. IEEE guidelines for typical and conservative estimates of K. K 175 2 I LRC TYPICAL K 230 2 I LRC CONSERVATIVE 68

Is the reversed phase the only error here? 69

VAB voltage relative to VAG For an ABC rotation, VAG lags VAB by 30 degrees 70

Is the reversed phase the only error here? For an ABC rotation, VAG lags VAB by 30 degrees 71

How to fix For an ABC rotation, VAG lags VAB by 30 degrees What is really A phase is wired to B phase and is rolled 180 degrees 72

How to fix Move wire from B to A and roll 180 degrees Move wire from C to B and roll 180 degrees Move wire from A to C and don t roll. 73

Lessons Learned This relay had a rolled phase, but also a lot of other issues During start up, verify metered values Negative sequence voltage and current should be small relative to positive sequence quantities Power factor should be as expected 80-90% lagging for induction machines and loads. Phase relationships should be as expected (across transformers) 74

Low Impedance Bus Differential Trip When the Second Breaker is Closed on the Bus 75

The Story We are installing a bus differential When we pick up load, we trip 76

77

87B Bus Differential Configuration 78

Let s look at the phasors How do we fix this monstrosity? 79

Corrective action required We must maintain ABC rotation 80

Paralleling Switchgear Trip 81

The Story This relay trips every time I close the breaker It is tripping on Overcurrent. You need to send me a new relay because this one is obviously bad. 82

Events 83

Waveforms 84

How Microprocessor Relays Fail Power Supplies Failures there most likely mean the relay is dead with no lights. Processor failures Failures there cause an alarm which takes the relay out of service and illuminates an alarm LED. DSP failures Failures there are rare, would typically raise an alarm and would show distorted metering values. Safe to say, this relay has NO problems, it is doing what it is suppose to do. 85

Where is this relay and when is it tripping? So what are you actually paralleling? 86

So what are you actually paralleling? 230KV Transmission System 13KV Distribution System 87

Equivalent Circuit Since Parallel: ZdistIdist=ZtranItran Zdist/Ztran=Itran/Idist If Zdist>>Ztran Then Itran>>Idist 88

Possible Solutions Can t really raise the TOC pickup setting on the tie breaker 750 and can t really make the time delay longer Could add controls to trip a selected breaker after all three are closed. Never parallel these two sources. Add mechanical interlocks to prevent parallel of all three sources. 89

Synchronous Motor Trip on Power Factor 90

The Story Synchronous motor is tripping on power factor pull-out Four of these compressors at the facility and is only happening to this compressor Started happening after we had the motor rebuilt. 91

Synchronous Motor Theory 92

Machine Excitation Synchronous Motor Operation Typical Generator Operation Induction Motor Operation Under-Excited Generator Operation 93

Synchronous Machines In an induction motor, the more load you have, the larger your slip. In a synchronous motor, slip=0. The more load you have (without increasing excitation) the greater your (negative) power factor. To prevent slipping a pole (pull-out protection) you use power factor protection to trip when your load changes beyond what your exciter can keep up with. 94

Reciprocal Compressors 95

Reciprocal Compressors 96

The Problem Compressor Loaded Cycle 97

The Problem Compressor Un- Loaded Cycle Within 60 Degrees of slipping a pole! 98

Problem This cannot be fixed with relay settings. Must talk to motor manufacture about why this compressor behaves this way. A mechanical problem was causing the issue. 99

Substation heat pumps drops bus voltage by 1kV causes capacitor bank trip 100

The Story This relay is tripping on B phase voltage differential. Two relays in the station and they are both tripping on B phase voltage differential. The redundant relays are not tripping. 101

Six Capacitor Banks 2 Relays 144KV Line to Line 0 0 0 300/5 16.7KV 600KVAR 9 Elements/Can 83.13KV/115V 0.8KV 167KVAR Protective Relay 87 102

Pre-Fault Values of the Trip 95,924-274(350.7130)=171=0.002pu 103

Fault Values of the Trip 94047-274(350.6185)=2022=0.022 Trip is set to 0.02 with a 50ms Delay 104

Event Records 105

Event Records 106

One of these things isn t like the others! 107

108

109

110

111

What can I do to prevent nuisance trips when the heat pump kicks on? Capacitor Bank Protection is set very sensitive. In this case at 2%. Can interlock the heat pump contactor with an 89B contact (humor intended) Can add a standard VT to provide voltages for protection. 112

How would this effect other relaying Phase and Ground Distance Protection: Could cause an element to over-reach if a fault occurred at the same instance of a heat pump start. Probably wouldn t affect steady state conditions unless extremely heavily loaded line. 113

How would this effect other relaying Bus Under-voltage: Probably would be unaffected because of the duration. 114

Lessons Learned Capacitor Bank Protection requires very sensitive settings. VT error can influence those setting. We still spend most of our time talking about instrument transformers. 115

Questions? 116