Instrument Transformer Wiring Troubleshooting Guide Three Phase Meters Revision 0, Initial Issue, April 26, 1993
|
|
|
- Nelson McDaniel
- 9 years ago
- Views:
Transcription
1 R Instrument Transformer Wiring Troubleshooting Guide Three Phase Meters Revision 0, Initial Issue, April 26, 1993 CONTENTS I. How to Use This Guide II. Common Problems for 3-Wire and 4-Wire Systems III. 3-Wire System Troubleshooting IV. 4-Wire System Troubleshooting V. Actual Field Examples I. HOW TO USE THIS GUIDE 1. Symptoms listed are "ideal"; some judgment must be exercised. For example, if KW reading is 25 but you know that it should be about 300 KW, go to where this guide lists "KW=0" as one of the symptoms. 2. Section II "Common Problems for 3-Wire and 4-Wire Systems" addresses symptoms and possible causes which occur regardless of system type; this section should be checked first. If the symptoms are more complicated, proceed to Section III for 3-wire systems or Section IV for 4-wire systems as appropriate. 3. Always assume that the problem is in the wiring to the Circuit Monitor; do not assume a defective Circuit Monitor. Experience has shown that this is almost always a good assumption. 4. This guide addresses mostly only a single wiring problem at a time. It is nearly impossible to address all combinations of multiple wiring mistakes or other problems which can occur such as blown PT fuses, missing PT neutral ground connection, etc. 5. When calling in for troubleshooting assistance, it is imperative that all instantaneous Circuit Monitor readings be provided. Specifically, this includes line-to-line voltages, line-to-neutral voltages, phase currents, phase power factors, KW, KVAR, and KVA. Printouts of logged readings or waveform capture data, if available, can be extremely useful as well. What is "Normal"? See the next page. 1
2 What is "Normal"? Most power systems have a lagging (inductive) power factor. The Circuit Monitor and PowerLogic software displays lagging power factor as negative, leading (capacitive) power factor as positive. The only time a leading power factor would be expected would be if the customer had power factor correction capacitors switched in or over-excited synchronous motors with enough capacitive KVARS on-line to overcorrect the power factor to leading. "Normal" lagging power system readings are as follows: Positive KW = ( 3 * V AB * I3φ Avg * PF 3φ Avg )/ Negative KVAR = ( ( KVA ) ( KW ) )/1000 KVA (always positive) = ( 3 * V AB * I3φ Avg )/1000 = lagging (negative) in the range to 1.00 (for 4W systems, all phase PF's about the PF Avg 3φ same) Phase currents approximately equal Phase voltages approximately equal Quick Check A quick check for proper Circuit Monitor readings consists of KW comparison (calculated per equation above and compared to the Circuit Monitor reading) and a reasonable lagging 3-phase average power factor reading. If these checks are OK, there is no reason to do anything more. If your calculations indicate that Circuit Monitor readings are correct but the customer disagrees, check CT ratio, PT ratio, and system type (3-wire or 4-wire) programmed into Circuit Monitor versus what is actually installed. If this is not the problem, ask customer what he based his estimate of the "correct" reading on. Be aware that there is a surprisingly high percentage of mis-wired watt-hour and power factor meters installed which make the Circuit Monitor appear wrong. Many times old meters that "never have worked right" have been in reality mis-wired from the start and the new Circuit Monitor is using the same instrument transformers. Updates to this Guide This guide will be updated as new types of problems and/or fixes are uncovered. Updates will also be incorporated if features of subsequent Circuit Monitor or software versions facilitate simpler or more detailed troubleshooting. For example, the Series 2000 Circuit Monitor has two 4-wire mode metering functions which were not available in original Circuit Monitor design that may be very helpful in troubleshooting. These are per phase power readings and neutral current reading (neutral current may be calculated or measured from a neutral CT). 2
3 II. Common Problems for 3-Wire and 4-Wire Systems Case A and 4-Wire Zero amps Zero KW, KVAR, KVA Case B and 4-Wire Negative KW of expected magnitude Positive KVAR Normal lagging power factor 1. CT secondaries shorted 2. Less than 2% load on Circuit Monitor based on CT ratio (example: with 100/5 CT's, at least 2 amps must flow through CT window for Circuit Monitor to "wake up") 1. All three CT polarities backwards; could be CT's physically mounted with primary polarity mark (H1)toward the load instead of toward source or secondary leads (X1 and X2) swapped 2. All three PT polarities backwards; again, could be on primary or secondary Note: Experience shows CT's are usually the problem. Case C and 4-Wire Frequency is some ridiculous value; may or may not be a multiple of 60 Hz 1. PT's primary and/or secondary neutral common not grounded (values as high as 275 Hz and as low as 10 Hz have been seen) 2. System grounding problem at the power distribution transformer (such as utility transformer); this is not likely 4
4 III. 3-Wire System Troubleshooting Case A Currents and voltages approximately balanced KW = near 0 KVAR = near 0 PF can be any value, probably fluctuating Case B Phase B current is 3 higher than A and C KVA = about half of the expected magnitude KW and KVAR can be positive or negative, less than about half of the expected magnitude PF can be any value, probably a low leading value 1. CT secondary leads are swapped (A phase lead on C phase terminal and vice versa) 2. PT secondary leads are swapped (A phase lead on C phase terminal and vice versa) 1. One CT polarity is backwards Case C V CA is 3 higher than V AB and V BC KVA = about half of the expected magnitude KW and KVAR can be positive or negative, less than about half of the expected magnitude PF can be any value, probably a low leading value 1. One PT polarity is backwards Case D 5
5 KW = 0 or low, with magnitude less than KVAR KVAR = positive or negative with magnitude of close to what is expected for KW KVA = expected magnitude PF = near 0 up to about 0.7 lead 1. Either the two voltage leads are swapped or the two current leads are swapped AND one instrument transformer has backwards polarity (look for V CA = 3 high or phase B current = 3 high) 2. The Circuit Monitor is metering a purely capacitive load (this is unusual); in this case KW and KVAR will be positive and PF will be near 0 lead Case E One phase current reads 0 KVA = about 1/2 of the expected value KW, KVAR, and power factor can be positive or negative of any value 1. The CT on the phase that reads 0 is short-circuited. 2. Less than 2% current (based on CT ratio) flowing thru the CT on the phase that reads 0 6
6 IV. 4-Wire System Troubleshooting Case A KW = 1/3 of the expected value KVAR = 1/3 of the expected value KVA = 1/3 of the expected value All else is normal Case B KW = 1/3 of the expected value KVAR = 1/3 of the expected value KVA = 1/3 of the expected value 2 of the 3 line-to-line voltages are 3 low All else is normal Case C One line-to-neutral voltage is zero 2 of the 3 line-to-line voltages are 3 low KW = 2/3 of the expected value KVAR = 2/3 of the expected value KVA = 2/3 of the expected value One phase power factor may look abnormal 1. One CT polarity is backwards Note: the only way this problem will usually be detected is by the Quick Check procedure. It is very important to always calculate KW. In this case, it is the only symptom and will go unnoticed unless the calculation is done or someone notices backwards CT on a waveform capture. 1. One PT polarity is backwards Note: the line-to-line voltage reading that does not reference the PT with backwards polarity will be the only correct reading. Example: V AB =277, V BC =480, V CA =277 In this case, the A-phase PT polarity is backwards. V BC is correct because it does not reference V A. 1. PT metering input missing (blown fuse, open phase disconnect, etc.) on the phase that reads zero Note: the line-to-line voltage reading that does not reference the missing PT input will be the only correct reading. Example: V AB =277, V BC =277, V CA =480 In this case, the B-phase PT input is missing. V CA is correct because it does not reference V B. 7
7 Case D KW = 2/3 of the expected value KVAR = 2/3 of the expected value KVA = 2/3 of the expected value One phase current reads 0 All else is normal Case E KW = near 0 KVAR = near 0 KVA = near 0 One phase power factor reads lagging (normal magnitude) One phase power factor reads leading One phase power factor reads very low 3-phase average power factor flip-flopping lead and lag Voltages and currents are normal Case F KW = negative and less than KVAR KVAR = negative and close to value expected for KW KVA = expected value All power factors low and leading Voltages and currents are normal 1. The CT on the phase that reads 0 is short-circuited. 2. Less than 2% current (based on CT ratio) flowing thru the CT on the phase that reads Two CT secondary leads are swapped (A phase on B phase terminal, for example) 2. Two PT secondary leads are swapped (A phase on B phase terminal, for example) Note: in either case, the phase input that is not swapped will read normal lagging power factor. 1. All three PT lead connections "rotated" counterclockwise: A-phase wire on C-phase terminal, B-phase wire on A-phase terminal, C-phase wire on B-phase terminal. 2. All three CT lead connections "rotated" clockwise: A-phase wire on B-phase terminal, B-phase wire on C-phase terminal, C-phase wire on A-phase terminal. 8
8 Case G KW = negative and less than KVAR KVAR = positive and close to the value expected for KW Note: looks like KW and KVAR swapped places KVA = expected value All power factors low and lagging Voltages and currents are normal 1. All three PT lead connections "rotated" clockwise: A-phase wire on B-phase terminal, B-phase wire on C-phase terminal, C-phase wire on A-phase terminal. 2. All three CT lead connections "rotated" counterclockwise: A-phase wire on C-phase terminal, B-phase wire on A-phase terminal, C-phase wire on B-phase terminal. 9
9 V. Actual Field Examples A. 4-wire system KW = 25 KVAR = -15 KVA = 27 I A = 904A I B = 910A I C = 931A I3φ Avg = 908A V AB = 495V V BC = 491V V CA = 491V V AN = 287V V BN = 287V V CN = 284V PF A = PF B = 0.96 PF C = 0.27 PF 3φ Avg = to.22 fluctuating Troubleshooting Diagnosis - Power factors cannot be correct - None of the Section II symptoms exist so proceed to the 4-wire troubleshooting Section IV - Cannot calculate KW because 3-phase power factor cannot be right so calculate KVA instead - Calculated KVA = ( 3 * V AB * I Avg 3φ )/1000 = (1.732 * 495 * 908)/1000 = 778 KVA - Circuit Monitor reading is essentially zero compared to this value - 4-wire Case E looks similar - Since the PT's were connected to other Circuit Monitors which were reading correctly, suspect two CT leads swapped - since A-phase power factor is the only one that has a normal looking lagging value, suspect B and C phase CT leads may be swapped - after swapping B and C phase CT leads, all readings went to the expected values; problem solved 10
Lecture Notes ELE A6
ecture Notes EE A6 Ramadan El-Shatshat Three Phase circuits 9/12/2006 EE A6 Three-phase Circuits 1 Three-phase Circuits 9/12/2006 EE A6 Three-phase Circuits 2 Advantages of Three-phase Circuits Smooth
VOLTAGE REGULATOR AND PARALLEL OPERATION
VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by
Three phase circuits
Three phase circuits THREE PHASE CIRCUITS THREE-PHASE ADVANTAGES 1. The horsepower rating of three-phase motors and the kva rating of three-phase transformers are 150% greater than single-phase motors
BALANCED THREE-PHASE CIRCUITS
BALANCED THREE-PHASE CIRCUITS The voltages in the three-phase power system are produced by a synchronous generator (Chapter 6). In a balanced system, each of the three instantaneous voltages have equal
Chapter 11 Balanced Three-Phase Circuits
Chapter 11 Balanced Three-Phase Circuits 11.1-2 Three-Phase Systems 11.3 Analysis of the Y-Y Circuit 11.4 Analysis of the Y- Circuit 11.5 Power Calculations in Balanced Three-Phase Circuits 11.6 Measuring
THREE-PHASE POWER SYSTEMS ECE 454/554: Power Systems Laboratory
THREE-PHSE POER SYSTEMS ECE 5/55: Power Systems Laboratory Contributors: Dr... El-Keib Mr. Clifton Black Dr. Tim. Haskew Mr. Johnny Carlisle Mr. Neil Hutchins Objectives Learn how to perform measurements
Basic Electrical Technology Dr. L. Umanand Department of Electrical Engineering Indian Institute of Science, Bangalore. Lecture - 33 3 phase System 4
Basic Electrical Technology Dr. L. Umanand Department of Electrical Engineering Indian Institute of Science, Bangalore Lecture - 33 3 phase System 4 Hello everybody. So, in the last class we have been
Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE
Understanding Power Factor and How it Affects Your Electric Bill Presented by Scott Peele PE Understanding Power Factor Definitions kva, kvar, kw, Apparent Power vs. True Power Calculations Measurements
Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1
Experiment no 1 Power measurement in balanced 3 phase circuits and power factor improvement 1 Power in Single Phase Circuits Let v = m cos(ωt) = cos(ωt) is the voltage applied to a R-L circuit and i =
Module Title: Electrotechnology for Mech L7
CORK INSTITUTE OF TECHNOLOGY INSTITIÚID TEICNEOLAÍOCHTA CHORCAÍ Autumn Examinations 2012 Module Title: Electrotechnology for Mech L7 Module Code: ELEC7007 School: School of Mechanical, Electrical and Process
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated
3-Phase AC Calculations Revisited
AN110 Dataforth Corporation Page 1 of 6 DID YOU KNOW? Nikola Tesla (1856-1943) came to the United States in 1884 from Yugosiavia. He arrived during the battle of the currents between Thomas Edison, who
Power Factor Correction for Power Systems First Semester Report Spring Semester 2007
Power Factor Correction for Power Systems First Semester Report Spring Semester 2007 by Pamela Ackerman Prepared to partially fulfill the requirements for EE401 Department of Electrical and Computer Engineering
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS
Radial Distribution Test Feeders
Radial Distribution Test Feeders Distribution System Analysis Subcommittee Report Abstract: Many computer programs are available for the analysis of radial distribution feeders. In 1992 a paper was published
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing
POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS
A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS By: Robert G. Ellis, P. Eng., Rockwell Automation Medium Voltage Business CONTENTS INTRODUCTION...
Chapter 12: Three Phase Circuits
Chapter 12: Three Phase Circuits 12.1 What Is a Three Phase Circuit? 12.2 Balance Three Phase Voltages 12.3 Balance Three Phase Y to Y Connection 12.4 Other Balance Three Phase Connections 12.5 Power in
Chapter 24. Three-Phase Voltage Generation
Chapter 24 Three-Phase Systems Three-Phase Voltage Generation Three-phase generators Three sets of windings and produce three ac voltages Windings are placed 120 apart Voltages are three identical sinusoidal
ECE 431. Experiment #1. Three-Phase ac Measurements. PERFORMED: 26 January 2005 WRITTEN: 28 January 2005. Jason Wells
ECE 41 Experiment #1 Three- ac Measurements PERFORMED: 6 January 005 WRTTEN: 8 January 005 Jason Wells LEADER: Jason Wells RECORDER: Nathaniel Hakes 1 ntroduction The primary objectives of the experiment
Essential Electrical Concepts
Essential Electrical Concepts Introduction Modern vehicles incorporate many electrical and electronic components and systems: Audio Lights Navigation Engine control Transmission control Braking and traction
Equipment: Power Supply, DAI, Variable resistance (8311), Variable inductance (8321)
Lab 4: 3-phase circuits. Objective: to study voltage-current relationships in 3-phase circuits; to learn to make delta and Y connections; to calculate and measure real, apparent, and reactive powers. Equipment:
AC Power. by Prof. Dr. Osman SEVAİOĞLU Electrical and Electronics Engineering Department
by Prof. Dr. Osman SEVAİOĞLU Electrical and Electronics Engineering Department EE 209 Fundamentals of Electrical and Electronics Engineering, Prof. Dr. O. SEVAİOĞLU, Page 1 Voltage Waveform Consider the
Short Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only
ATTACHMENT F CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 150 KW Also Serves as Application for Category
DUAL%CHANNEL BROADBAND%LINEAR%AMPLIFIER Model&A800D
ELECTRONICS AB DUAL%CHANNEL BROADBAND%LINEAR%AMPLIFIER Model&A800D & HIGH&VOLTAGE& FIXED&GAIN& BROADBAND & 800Vpp&60mA& 100x& DC&to&ca&200&kHz & LOW&OUTPUT&IMPEDANCE& HIGH&SLEW&RATE &
Diode Applications. As we have already seen the diode can act as a switch Forward biased or reverse biased - On or Off.
Diode Applications Diode Switching As we have already seen the diode can act as a switch Forward biased or reverse biased - On or Off. Voltage Rectifier A voltage rectifier is a circuit that converts an
Open Phase Conditions in Transformers Analysis and Protection Algorithm
Open Phase Conditions in Transformers Analysis and Protection Algorithm Amir Norouzi GE Digital Energy Markham, ON [email protected] Abstract This paper first provides an in-depth analysis of open phase
TESLA Recorder Power Metering Setup Configuration for 3 and 2 Element Watt/VAR Metering
TESLA Recorder Power Metering Setup Configuration for 3 and 2 Element Watt/VAR Metering Introduction This application note will assist the user to set up 3-phase metering to monitor Watt, VAR and VA power
2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?
Extra Questions - 2 1. A straight length of wire moves through a uniform magnetic field. The e.m.f. produced across the ends of the wire will be maximum if it moves: a) along the lines of magnetic flux
INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012
INTRODUCTION TO SYSTEM PROTECTION Hands-On Relay School 2012 CONGRATULATIONS On choosing the field of system protection. It is an exciting, challenging profession. System protection has changed considerably
SYNCHRONOUS MACHINES
SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical
Understanding Power Flow and Naming Conventions In Bi-directional Metering Applications
Understanding Power Flow and Naming Conventions In Bi-directional Metering Applications By Michael Bearden Introduction In 1982 Raymond Ray Stevens published a paper Power Flow Direction Definitions for
Power Factor The Basics
Power Factor The Basics OK. I ve heard a lot about this power factor stuff. What exactly is it? We hope to give you an easy explanation of what power factor is, and to answer the following most asked questions:
Simulation of Ungrounded Shipboard Power Systems in PSpice
Simulation of Ungrounded Shipboard Power Systems in PSpice Haibo Zhang IEEE Student Member Karen L.Butler IEEE Member Power System Automation Lab Electrical Engineering Department Texas A&M University
Reading assignment: All students should read the Appendix about using oscilloscopes.
10. A ircuits* Objective: To learn how to analyze current and voltage relationships in alternating current (a.c.) circuits. You will use the method of phasors, or the vector addition of rotating vectors
SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS
SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE S By Jack Farrow, May, 2004 WELDING TECHNOLOGY CORPORATION ABSTRACT Information on how to select the correct size of substation transformer and 480V bus to
Table of Contents. The Basics of Electricity 2. Using a Digital Multimeter 4. Testing Voltage 8. Testing Current 10. Testing Resistance 12
Table of Contents The Basics of Electricity 2 Using a Digital Multimeter 4 IDEAL Digital Multimeters An Introduction The Basics of Digital Multimeters is designed to give you a fundamental knowledge of
Power System Harmonics
Pacific Gas and Electric Company Power System Harmonics What are power system harmonics? Ideally, voltage and current waveforms are perfect sinusoids. However, because of the increased popularity of electronic
SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original
SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according
BALANCED THREE-PHASE AC CIRCUIT
BAANCED THREE-PHASE AC CRCUT Balanced Three-Phase oltage Sources Delta Connection Star Connection Balanced 3-hase oad Delta Connection Star Connection Power in a Balanced Phase Circuit ntroduction Three
TRANSFORMER LOSS COMPENSATION FOR METERMEN PRESENTED BY: MICHAEL K. BEARDEN
TRANSFORMER LOSS COMPENSATION FOR METERMEN PRESENTED BY: MICHAEL K. BEARDEN WHAT are transformer losses? TRANSFORMER LOSS COMPENSATION THE WHAT, WHEN, WHO, WHERE AND HOW Transformer losses can be viewed
ENGINEERING REPORT. XYZ Corporation 100 Anyplace Drive Chicago, Illinois 60613
ENGINEERING REPORT XYZ Corporation 100 Anyplace Drive Chicago, Illinois 60613 PERFORMED BY: MIDWEST ELECTRICAL CONSULTANTS, INC 18055 UPLAND DRIVE TINLEY PARK, ILLINOIS 60487 (708) 444-0001 fax: 444-0003
RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:
Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog
SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks
SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks Introduction SCADA (Supervisory Controlled and Data Acquisition) controlled multi-step metalenclosed automatic capacitor
ε: Voltage output of Signal Generator (also called the Source voltage or Applied
Experiment #10: LR & RC Circuits Frequency Response EQUIPMENT NEEDED Science Workshop Interface Power Amplifier (2) Voltage Sensor graph paper (optional) (3) Patch Cords Decade resistor, capacitor, and
11. MEASUREMENT OF POWER CONSUMPTION OF THE NONBALANCED THREE-PHASE LOAD
. MEASEMENT OF OE CONSMTION OF THE NONBALANCED THEE-HASE LOAD Task of the measurement. Measure the active power and the reactive power of the nonsymmetrical -phase load in Y-connection. Do not connect
Drive circuit basics + V. τ e. Industrial Circuits Application Note. Winding resistance and inductance
ndustrial Circuits Application Note Drive circuit basics For a given size of a stepper motor, a limited space is available for the windings. n the process of optimizing a stepper motor drive system, an
Rule 5.500 Fast Track Analysis for National Life Insurance Co.
Rule 5.500 Fast Track Analysis for National Life Insurance Co. For a 500 kw Solar array to be located at 155 Northfield Street in Montpelier, Vermont Green Mountain Power Pam Allen Date: 5/31/13 SECTION
Automatic Voltage Regulator User s Manual
Resp. dept. R&D We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. Copyright
4 LEAD DEDICATED SINGLE PHASE LIMA MAC GENERATOR MODELS 250MSL1185 AND 250MSL1152
4 LEAD DEDICATED SINGLE PHASE LIMA MAC GENERATOR MODELS 250MSL1185 AND 250MSL1152 SERVICE PROCEDURE ELECTRICAL COMPONENT TESTING HI POTENTIAL TETS None of the windings, either rotating or stationary should
AC Generators. Basic Generator
AC Generators Basic Generator A basic generator consists of a magnetic field, an armature, slip rings, brushes and a resistive load. The magnetic field is usually an electromagnet. An armature is any number
Equipment: Power Supply, DAI, Transformer (8341), Variable resistance (8311), Variable inductance (8321), Variable capacitance (8331)
Lab 5: Single-phase transformer operations. Objective: to examine the design of single-phase transformers; to study the voltage and current ratios of transformers; to study the voltage regulation of the
Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer
Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer A Short Circuit analysis is used to determine the magnitude of short
Prepared By: Sheilani Binti Shaari Department of Electrical Engineering/PKB
Prepared By: Sheilani Binti Shaari Department of Electrical Engineering/ Course Learning Outcome (CLO) Upon completion of this course, students should be able to: Apply the principles of three phase systems,
Equipment: Power Supply, DAI, Synchronous motor (8241), Electrodynamometer (8960), Tachometer, Timing belt.
Lab 9: Synchronous motor. Objective: to examine the design of a 3-phase synchronous motor; to learn how to connect it; to obtain its starting characteristic; to determine the full-load characteristic of
LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units
Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two
Metering Devices IQ Analyzer 6400/6600 Series
Metering Devices IQ Analyzer 6400/6600 Series Technical Data Supersedes TD.17.02A.T.E pages 1-8 dated May 2000 Description Page General Description............................................. 2 Applications....................................................
TROUBLESHOOTING PRELIMINARY
TROUBLESHOOTING PRELIMINARY To troubleshoot, one must first have a working knowledge of the individual parts and their relation to one another. Must have adequate hand tools Must have basic instrumentation:
Typical Data Requirements Data Required for Power System Evaluation
Summary 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com [email protected] Harmonic Filter & Power Capacitor Bank Application Studies This document describes NEPSI
AN-641 APPLICATION NOTE
APPLICATION NOTE One Technology Way P.O. Box 96 Norwood, MA 262-96 Tel: 78/329-47 Fax: 78/326-873 www.analog.com A 3-Phase Power Meter Based on the ADE7752 By Stephen English and Rachel Kaplan INTRODUCTION
THREE PHASE CIRCUITS
THREE PHASE CIRCUITS A. PREPARATION 1. Three Phase Voltages and Systems 2. The Determination of Phase Sequence 3. Blondel's Theorem and Its Consequences 4. References B. EXPERIMENT 1. Equipment List 2.
Equipment: Power Supply, DAI, Wound rotor induction motor (8231), Electrodynamometer (8960), timing belt.
Lab 13: Wound rotor induction motor. Objective: to examine the construction of a 3-phase wound rotor induction motor; to understand exciting current, synchronous speed and slip in this motor; to determine
CURRENT TRANSFORMERS INSTALLATION GUIDE
CURRENT TRANSFORMERS INSTALLATION GUIDE Information contained within this document is subject to change without notice and does not represent a commitment on the part of PRI Ltd or its agents. E&OE. Copyright
Considering the effects of UPS operation with leading power factor loads
Considering the effects of UPS operation with leading power factor loads Over the past five years, a new generation of data processing and communications equipment has become prevalent in modern data centers
Creating a Usable Power Supply from a Solar Panel
Creating a Usable Power Supply from a Solar Panel An exploration in DC- DC converters By Kathleen Ellis Advised by Dr. Derin Sherman Department of Physics, Cornell College November 21, 2012 Introduction
ECEN 1400, Introduction to Analog and Digital Electronics
ECEN 1400, Introduction to Analog and Digital Electronics Lab 4: Power supply 1 INTRODUCTION This lab will span two lab periods. In this lab, you will create the power supply that transforms the AC wall
PHASE CONVERSION TECHNOLOGY OVERVIEW
Dr. Larry Meiners, Ph.D. PHASE CONVERSION TECHNOLOGY OVERVIEW Introduction A wide variety of commercial and industrial electrical equipment requires three-phase power. Electric utilities do not install
HOW HARMONICS HAVE CONTRIBUTED TO MANY POWER FACTOR MISCONCEPTIONS
White Paper: MIRUS-TP003-A January 15, 2014 HOW HARMONICS HAVE CONTRIBUTED TO MANY POWER FACTOR MISCONCEPTIONS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc.
How To Choose A Transformer
Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV
FUNDAMENTALS OF ENGINEERING (FE) EXAMINATION REVIEW
FE: Electric Circuits C.A. Gross EE1-1 FUNDAMENTALS OF ENGINEERING (FE) EXAMINATION REIEW ELECTRICAL ENGINEERING Charles A. Gross, Professor Emeritus Electrical and Comp Engineering Auburn University Broun
How To Balance Three Phase Power In A Balanced System
Three-Phase Circuits Three-Phase Circuit Three-Phase Circuits What is a Three-Phase Circuit? Balance Three-Phase oltages Balance Three-Phase Connection Power in a Balanced System Unbalanced Three-Phase
Power Supplies. 1.0 Power Supply Basics. www.learnabout-electronics.org. Module
Module 1 www.learnabout-electronics.org Power Supplies 1.0 Power Supply Basics What you ll learn in Module 1 Section 1.0 Power Supply Basics. Basic functions of a power supply. Safety aspects of working
Power factor correction. An introduction to technology and techniques
Power factor correction An introduction to technology and techniques 2 Contents Understanding power factor 03 Power factor correction 05 Implementing power factor correction techniques 06 Glossary 07 Further
Product Data Bulletin
Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system
Kit 106. 50 Watt Audio Amplifier
Kit 106 50 Watt Audio Amplifier T his kit is based on an amazing IC amplifier module from ST Electronics, the TDA7294 It is intended for use as a high quality audio class AB amplifier in hi-fi applications
INSTRUCTION MANUAL IPM 3600 3 Phase Power Analyser EN FR IT DE ES
INSTRUCTION MANUAL IPM 3600 3 Phase Power Analyser EN FR IT DE ES CONTENTS / EN CONTENTS Title Page I. SAFETY INFORMATION...1 II. INTRODUCTION...3 III. SPECIFICATIONS...4 3-1 Environmental Conditions...4
UNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS
Page 1 UNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS By Henry Ott Consultants Livingston, NJ 07039 (973) 992-1793 www.hottconsultants.com [email protected] Page 2 THE BASIC
Fig.1 block of PFC using PIC. Index Terms:-power factor, PIC, Hardware
Power Factor Correction Using PIC Microcontroller Pranjali Sonje, Pursuing MTech, Bharati Vidyapeeth University college of Engineering, Pune Anagha Soman, Assistant Professor, Bharati Vidyapeeth University
AC generator theory. Resources and methods for learning about these subjects (list a few here, in preparation for your research):
AC generator theory This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,
COOL-01, Cooling Fan Operation and Troubleshooting
COOL-01, Cooling Fan Operation and Troubleshooting Table of Contents Introduction Early 944s With Air Conditioning Cooling Fan Operation On Early 944s With Air Conditioning Testing Fan Relay One Early
Line Reactors and AC Drives
Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences
HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM
Technical Note No.3 March 2000 HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM This Technical Note discusses harmonic distortion, its causes and adverse effects, what levels are unacceptable and how
max 6f / computer max
POWER FACTOR REGULATORS computer max max 6f / computer max max 12f Instructions Manual ( M98234601-03-10A ) - 1 - Index 1 INTRODUCTION AND SAFETY RECOMMENDATIONS... 3 1.1 DELIVERY SPOT CHECK... 3 1.2 STARTING
The full wave rectifier consists of two diodes and a resister as shown in Figure
The Full-Wave Rectifier The full wave rectifier consists of two diodes and a resister as shown in Figure The transformer has a centre-tapped secondary winding. This secondary winding has a lead attached
Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26
Management Systems 10 Electrical Safety Audit 14 PPE 20 Arc Mitigation 22 Hazard Assessment 26 Assessing The Hazards Of High and Low Voltage Single-Phase Arc-Flash By Albert Marroquin One common question
Chapter 4 AC to AC Converters ( AC Controllers and Frequency Converters )
Chapter 4 AC to AC Converters ( AC Controllers and Frequency Converters ) Classification of AC to AC converters Same frequency variable magnitude AC power AC controllers AC power Frequency converters (Cycloconverters)
= (0.400 A) (4.80 V) = 1.92 W = (0.400 A) (7.20 V) = 2.88 W
Physics 2220 Module 06 Homework 0. What are the magnitude and direction of the current in the 8 Ω resister in the figure? Assume the current is moving clockwise. Then use Kirchhoff's second rule: 3.00
Current Transformers
Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 Current Transformers Current transformers (CT's) provide
The Charging System. Section 5. Charging System. Charging System. The charging system has two essential functions:
The Charging System Charging System The charging system has two essential functions: Generate electrical power to run the vehicle s electrical systems Generate current to recharge the vehicle s battery
Motor Efficiency and Power Factor ME 416/516
Motor Efficiency and Power Factor Motivation More than half of all electric energy generated goes to power electric motors. Electric motor converts electric power into shaft power. In thermodynamics terms,
MULTIPLE CHOICE. Choose the one alternative that best completes the statement or answers the question.
MULTIPLE CHOICE. Choose the one alternative that best completes the statement or answers the question. 1) If the voltage at a point in space is zero, then the electric field must be A) zero. B) positive.
Transistor Amplifiers
Physics 3330 Experiment #7 Fall 1999 Transistor Amplifiers Purpose The aim of this experiment is to develop a bipolar transistor amplifier with a voltage gain of minus 25. The amplifier must accept input
Power Factor in Electrical Energy Management
PDHonline Course E144 (4 PDH) Power Factor in Electrical Energy Management Instructor: A. Bhatia, B.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone & Fax: 703-988-0088
However, industrial applications may utilize a relay, which short-circuits the ICL path after the inrush sequence.
Application note for Inrush Current Limiters (ICL) Turning on electrical devices generally cause high inrush currents which can damage electronic components and cause interruption of the line voltage if
Measuring Electric Phenomena: the Ammeter and Voltmeter
Measuring Electric Phenomena: the Ammeter and Voltmeter 1 Objectives 1. To understand the use and operation of the Ammeter and Voltmeter in a simple direct current circuit, and 2. To verify Ohm s Law for
Introduction to Paralleling of LTC Transformers by the Circulating Current Method
TAPCHANGER CONTROLS Application Note #11 Introduction to Paralleling of LTC Transformers by the Circulating Current Method 1.0 ABSTRACT This Application Note discusses the elements of paralleling load
PRODUCTIVITY THROUGH INNOVATION 600 CONTROL DIRECT DRIVE TECHNICAL/OPERATION MANUAL
Rev. D PRODUCTIVITY THROUGH INNOVATION 600 CONTROL DIRECT DRIVE TECHNICAL/OPERATION MANUAL 10 BORIGHT AVENUE, KENILWORTH NEW JERSEY 07033 TELEPHONE: 800-524-0273 FAX: 908-686-9317 TABLE OF CONTENTS Page