Logix5000 Control Systems: Connect POINT I/O Modules over an EtherNet/IP Network

Similar documents
CompactLogix 5370 L1 Controllers

CompactLogix 5370 L3 Controllers

MicroLogix 1100 Embedded Web Server

Stratix 5700 Network Address Translation. Quick Start

SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade

Logix5000 Controllers Security

Logix5000 Controllers Nonvolatile Memory Card

User Manual. DeviceNet Network Configuration

Safety Function: Door Monitoring

CompactLogix Power Supplies Specifications

Universal Serial Bus (USB) to DH-485 Interface Converter

1769 CompactLogix Packaged Controllers

Reference Manual. Pressure/Temperature Compensated Flow (P_PTComp) Version 3.1

Micro800 Programmable Controllers. Bulletin 2080 Selection Guide

Stratix 5700 Switch Configuration

Logix5000 Controllers Nonvolatile Memory Card

Logix5000 Controllers Import/Export Project Components

Logix5000 Controllers Function Block Diagram

Logix5000 Controllers Import/Export Project Components Programming Manual. Programming Manual

ControlNet Standard and High-flex Coax Cable

Hard Disk Drive (HDD)

Application Technique. Safety Function: Door Monitoring

USB-to-Data Highway Plus Cable

Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP. 1 Application Description Objective Goals...

ControlLogix Remote I/O Communication Module

PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit

EtherNet/IP Modules in Logix5000 Control Systems

DriveTools SP v5.04 Software Patch

Logix5000 Controllers Security

GuardLogix Controller Systems

EtherNet/IP Web Server Module

PowerFlex 20-HIM-A3/-A5/-C3S/-C5S Series C HIM Firmware 6.001

PowerFlex 700H and 700S AC Drives Frame 11 Main Fan Capacitor Replacement Kit

Industrial Tower Uninterruptible Power Supply Specifications Bulletin Numbers 1609-P

Application Technique. Safety Function: Magnetic Door Switch Monitoring

Application Guide. ArmorStart DLR Reference Architecture

Logix5000 Controllers

MicroLogix 1400 Embedded Web Server

Bimetallic Overload Relay Specifications

Time Recorder Extension Module for the Dynamix 2500 Data Collector

EtherNet/IP Network Configuration

Integrated Motion on the EtherNet/IP Network: Configuration and Startup

User Manual. ControlNet Network Configuration

Installation Instructions. Before Installation. Read these installation instructions carefully before commissioning the pressure transmitter.

Fiber Optic Cable Installation

Molded Case Circuit Breaker Specifications Bulletin Number 140U-D

Micro800 Programmable Controllers: Getting Started with CIP Client Messaging

Legacy PanelView to PanelView Plus 6 Catalog Number Conversions

User Manual. PowerFlex 525 Embedded EtherNet/IP Adapter

FLEX I/O High-Density Analog Modules

EtherNet/IP Adapter. 22-COMM-E FRN 1.xxx. User Manual

User Manual. PowerFlex 25-COMM-E2P Dual-Port EtherNet/IP Adapter

Building a groov HMI for Allen-Bradley Logix Systems. About groov. Building a groov HMI for Allen-Bradley Logix. A-B Systems and groov

Product Compatibility and Download Center

1756 ControlLogix Chassis Specifications

Accessing EtherNet/IP Network Variables in a WAGO with a ControlLogix PLC Application note

Application Technique. EtherNet/IP Socket Interface

2011, The McGraw-Hill Companies, Inc. Chapter 5

Drive Software Wizards v2.4

Drive Software Wizards Version 3.4

Programming Manual Catalog Numbers 1756 ControlLogix, 1769 CompactLogix, 1789 SoftLogix, 1794 FlexLogix, PowerFlex 700S with DriveLogix

Module 1 Overview ControlLogix5000

1 Application Description Objective Goals... 3

In this section we tell you how to set the fault mode selection plug, key your I/O chassis, install your module and make your wiring connections.

FactoryTalk ViewPoint Quick Start Guide

Introduction to LogixPro - Lab

POINT I/O EtherNet/IP Adapter Module. Catalog Number 1734-AENT User Manual

Safe Torque Off Option (Series B) for PowerFlex 40P and PowerFlex 70 Enhanced Control AC Drives

Allen-Bradley Stratix 5700 Network Address Translation (NAT)

Installation Guide. FactoryTalk Batch Material Manager Installation Guide

Allen-Bradley/Rockwell

QUICK START GUIDE. SG2 Client - Programming Software SG2 Series Programmable Logic Relay

Allen-Bradley/Rockwell

FLEX I/O Isolated Analog Modules

SIMATIC S Getting Started for First Time Users. Order No.: 6ZB5310-0NC02-0BA0 04/2007 A5E

Allen-Bradley/Rockwell

Guard I/O EtherNet/IP Safety Modules

1769-SDN DeviceNet Scanner Module. Catalog Numbers 1769-SDN User Manual

Allen-Bradley. ControlLogix Gateway System (Cat. No series) User Manual

How To Set Up A Cep7 Second Generation Ethernet/Ip Module

L5354 ControlNet Communications Interface

Chapter. Getting Started. In This Chapter...

Ultra3000 Digital Servo Drives

Hands-On Lab Workbook. Introduction to EtherNet/IP

CPU PN/DP: Configuring an ET. 200S as PROFINET IO device SIMATIC. PROFINET CPU PN/DP: Configuring an ET 200S as PROFINET IO device

1732E EtherNet/IP ArmorBlock Supporting Sequence of Events. Catalog Number 1732E-IB16M12SOEDR User Manual

Parameter Settings for PowerFlex Drives Using Sine Wave Filters, dv/dt Filters, and Adjustable Voltage

ControlNet PLC-5 Hot Backup System

FLEX I/O EtherNet/IP Adapter Module

NI InsightCM Server Version 1.0

How To Install A Power Supply (Uplast) With A Battery Pack

Application/Connection Examples

Cloning Utility for Rockwell Automation Industrial Computers

HP UPS R1500 Generation 3

1 Application Description System Topology Hardware and Software Requirements... 3

Technical Note. Setting ACS drive IP address automatically with Rockwell BOOTP/DHCP Server. Contents

Using the WAGO PROFINET Coupler as Remote I/O with a Siemens S7 PLC

HP ProLiant DL380 G6 Carrier-Grade Server Read Before Install

PowerFlex Dynamic Braking Resistor Calculator

AC 800M. EtherNet/IP DeviceNet Linking Device LD 800DN. Power and productivity for a better world TM SP1134

Transcription:

Quick Start Logix5000 Control Systems: Connect POINT I/O Modules over an EtherNet/IP Network Catalog Numbers Logix5000 Controllers, 1734 POINT I/O Modules

Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations. WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present. BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures. IMPORTANT Identifies information that is critical for successful application and understanding of the product. Allen-Bradley, CompactLogix, FLEX I/O, Logix5000, POINT I/O, Rockwell Software, Rockwell Automation, RSLogix 5000, and TechConnect are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.

Table of Contents Preface About This Publication............................................ 5 Before Using This Publication...................................... 5 Other Logix5000 Control System Quick Starts...................... 8 POINT I/O Modules in Device-level Ring or Linear Topology....... 8 Before You Begin.................................................. 8 Where to Start.................................................... 9 How Hardware is Connected..................................... 10 Required Software................................................ 10 Parts List........................................................ 11 Additional Resources............................................. 11 Prepare the Distributed POINT I/O Module Hardware Add the POINT I/O Ethernet Adapter and Digital Output Module to an RSLogix 5000 Project Chapter 1 Before You Begin................................................. 13 What You Need.................................................. 14 Follow These Steps............................................... 15 Mount and Connect the 1734-AENT Ethernet Adapter............ 16 Mount the 1734-OB4E Digital Output Module.................... 17 Mount and Wire the 1794-PS3 Power Supply...................... 18 Wire the 1734-AENT Ethernet Adapter to the Power Supply....... 19 Additional Resources............................................. 19 Chapter 2 Before You Begin................................................. 21 What You Need.................................................. 22 Follow These Steps............................................... 22 Configure the POINT I/O Adapter and Output Module............ 23 Add Ladder Logic to Test the 1734-OB4E Module s Lights.......... 26 Download the Project to Your Logix5000 Controller............... 29 Test the 1734-OB4E Output Module s Light....................... 30 Additional Resources............................................. 30 Index.................................................................. 31 Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012 3

Table of Contents 4 Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012

Preface About This Publication This quick start provides examples and procedures for including POINT I/O modules in a Logix5000 control system over an EtherNet/IP network. The programming examples are not complex, and offer easy solutions to verify that devices are functioning and communicating properly. IMPORTANT This publication describes example tasks you complete when using POINT I/O modules on an EtherNet/IP network. The tasks described are not the only tasks you can complete with the POINT I/O modules on an EtherNet/IP network. Before Using This Publication You can only complete the tasks described in this publication after first completing some prerequisite tasks with a Logix5000 controller. For example, before you can add POINT I/O modules to an RSLogix 5000 project, as described in page 21, you must first create the project. Table 1 describes the tasks you must complete before using this publication. IMPORTANT The example graphics shown in Table 1 - Required Tasks To Complete Before Using this Quick Start on page 6 are for CompactLogix 5370 L3 controllers. Depending on the Logix5000 controller you are using, the specific steps to complete the tasks described in the table might vary. Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012 5

1 (Front) 2 (Rear) Preface For more information on how to complete the prerequisite tasks with specific Logix5000 controllers, see the Integrated Architecture : Logix5000 Control Systems Quick Starts Quick Reference, publication IASIMP-QR024. Table 1 - Required Tasks To Complete Before Using this Quick Start Task Prepare the Logix5000 control system hardware Description Assembling the control system and connecting to necessary communication networks. Some components, for example, a desired Logix5000 controller, system power supply or switch for applications operating on an EtherNet/IP network, are required. Other components, for example, a network communication module, are optional. IMPORTANT: These graphics show the assembly of an example Logix5000 controller. Prepare the computer This task does not include installation of specific hardware components, for example, POINT I/O modules, used over the networks included in your application. Installing necessary software, for example, RSLogix 5000 software, on your computer. 6 Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012

Preface Table 1 - Required Tasks To Complete Before Using this Quick Start Task Configure the networks Description Complete required tasks associated with the networks used in your application, such as assigning an IP address to the controller or a communication module in your Logix5000 control system. Create an RSLogix 5000 project Project used with your Logix5000 controller that includes all desired control system components and necessary programming, for example, adding ladder logic to test tasks associated with individual system components. Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012 7

Preface Other Logix5000 Control System Quick Starts This quick start describes how to add one device on one network in a Logix5000 control system. Typically, though, a Logix5000 control system includes more than one device on one network. For example, if a Logix5000 control system operates on an EtherNet/IP network, in addition to a controller, power supply, and communication modules, the system might use remote I/O modules, drives, or HMI terminals. Other quick starts describe how to use different devices on different networks in Logix5000 control systems. For more information, see the Integrated Architecture: Logix5000 Control Systems Quick Starts Quick Reference, publication IASIMP-QR024. POINT I/O Modules in Device-level Ring or Linear Topology This publication describes how to use POINT I/O modules in an application using a EtherNet/IP network star topology configuration. It does not describe how to use the I/O modules in a device-level ring (DLR) nor linear topology via a 1734-AENTR adapter module. For information on how to use POINT I/O modules in a DLR or linear topology, see the EtherNet/IP Embedded Switch Technology Application Guide, publication ENET-AP005. Before You Begin The beginning of each chapter contains the following information. You should read these sections before beginning work in each chapter: Before You Begin - This section lists the tasks you must complete before starting the chapter. What You Need - This section lists the tools that are required to complete the tasks in the chapter. Follow These Steps - This section illustrates the steps in the current chapter. 8 Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012

Preface Where to Start Prerequisite Tasks Described in Before Using This Publication on page 5. 1. Prepare the Logix5000 control system hardware. 2. Prepare the computer. 3. Configure the networks. 4. Create an RSLogix 5000 project. Logix5000 Controller Prepare the Distributed POINT I/O Module Hardware page 13 Add the POINT I/O Ethernet Adapter and Digital Output Module to an RSLogix 5000 Project page 21 Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012 9

8 7 6 5 4 3 2 1 0 0 2 1734-AENTR POINT I O Module Status Network Activity Network Status Point Bus Link 1 Status Activity/ Status System Power Field Power Link 2 Activity/ Status Preface How Hardware is Connected This quick start demonstrates the following possible control system. Logix5000 Controller with Ethernet Connection Computer Stratix 6000 Managed Switch IP ADDRESS POINT I/O Modules Required Software To complete examples in this quick start, you need the software described in this table. Software Version Required for This Task RSLogix 5000 20.00.00 or later (1) BOOTP/DHCP utility Version automatically installed with RSLogix 5000 software and varies according to that software s version. Create or change RSLogix 5000 projects to use POINT I/O modules. Set or change the IP address for 1734-AENT POINT I/O Ethernet adapter. (1) RSLogix 5000 software, version 20.00.00 or later is required for use of this quick start because the example Logix5000 controller, and associated tasks, described herein are completed in a CompactLogix 5370 L3 control system. CompactLogix 5370 control systems require RSLogix 5000 software, version 20.00.00 or later. If you connect a 1734 POINT I/O module over an EtherNet/IP network in a Logix5000 control system that uses a different controller, the minimum version may differ. 10 Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012

Preface Parts List To complete the tasks described in this publication, you need the parts listed in this table. Quantity Cat. No. Description 1 1734-AENT POINT I/O Ethernet adapter 1 1734-OB4E POINT I/O protected output module 1 1734-TB or 1734-TBS Wiring base with removable IEC screw terminals (1734-TB) Wiring base with removable IEC spring terminals (1734-TBS) 1 1794-PS3 FLEX I/O 85 264V AC to 24V DC 3 A power supply 1 1585J-M8PBJM-2 RJ45-to-RJ45 patchcord Ethernet cables For a list of parts required to complete the prerequisite tasks listed in Table 1 - Required Tasks To Complete Before Using this Quick Start on page 6, see the documentation describing those tasks. Additional Resources Use the additional resources listed in this table for more information when using POINT I/O modules over an EtherNet/IP network in a Logix5000 controller project. Table 2 - Additional Resources Resource POINT I/O Ethernet Adapter Installation Instructions, publication 1734-IN590 POINT I/O and ArmorPOINT I/O 2 Port EtherNet/IP Adapters User Manual, publication 1734-UM014 POINT I/O Protected Output Module, publication 1734-IN056 POINT I/O Wiring Base Assembly Installation Instructions, publication 1734-IN013 Description Describes how to install the 1734-AENT POINT I/O Ethernet adapter and contains technical specifications. Describes how to install, configure, and troubleshoot your 1734-AENT POINT I/O EtherNet/IP adapter. Describes how to install the 1734-OB4E module. Describes how to install the POINT I/O wiring base. Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012 11

Preface Table 2 - Additional Resources Resource FLEX I/O DC Power Supply Installation Instructions, publication 1794-IN069 Logix5000 Controllers Common Procedures Programming Manual, publication 1756-PM001 Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Product Certifications website, http://www.ab.com Description Describes how to install the 1794-PS and 1794-PS13 power supplies. Provides details about adding and configuring modules, establishing communication, and writing ladder logic. Provides general guidelines for installing a Rockwell Automation industrial system. Provides declarations of conformity, certificates, and other certification details. You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative. 12 Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012

Chapter 1 Prepare the Distributed POINT I/O Module Hardware In this chapter, you learn how to complete the following tasks: Install the 1734-AENT Ethernet adapter Install the 1734-OB4E digital output module Install a 1794-PS3 FLEX I/O power supply Connect power to the 1734-AENT Ethernet adapter Before You Begin You must complete these tasks before using this chapter: The tasks described in Before Using This Publication on page 5, including: Prepare the Logix5000 control system hardware Prepare the computer Configure the networks - The tasks described in this chapter require an EtherNet/IP network. Create an RSLogix 5000 project The example RSLogix 5000 project used in this chapter uses a CompactLogix 5370 L3 controller. Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012 13

Chapter 1 Prepare the Distributed POINT I/O Module Hardware What You Need The following table lists the products that you need to complete the tasks described in this chapter. Quantity Cat. No. Description 1 1734-AENT POINT I/O Ethernet adapter 1 1734-OB4E POINT I/O protected output module 1 1734-TB or 1734-TBS Wiring base with removable IEC screw terminals (1734-TB) Wiring base with removable IEC spring terminals (1734-TBS) 1 1794-PS3 FLEX I/O 85 264V AC to 24V DC 3 A power supply 14 Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012

8 6 4 2 7 5 3 1 System Power Field Power Module Status Network Activity Status Network Status PointBus Status 1734-AENT Output Prepare the Distributed POINT I/O Module Hardware Chapter 1 Follow These Steps Mount and Connect the 1734-AENT Ethernet Adapter page 16 Mount the 1734-OB4E Digital Output Module page 17 Mount and Wire the 1794-PS3 Power Supply page 18 0 0 2 24VDC Source Wire the 1734-AENT Ethernet Adapter to the Power Supply page 19 1734 OB4E Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012 15

Chapter 1 Prepare the Distributed POINT I/O Module Hardware Mount and Connect the 1734-AENT Ethernet Adapter 1. Position the adapter vertically in front of the DIN rail and press firmly onto the DIN rail until the adapter locks into place. 2. To set the module s IP address to a valid number, set the module s thumbwheel switches to a number between 001 and 254. Thumbwheel Switches 0 0 2 Module Status Network Activity Status Network Status PointBus Status 1734-AENT System Power Field Numbers outside that range are invalid. If the switches are set to a valid number at powerup, the module automatically uses that number for its IP address. IMPORTANT In addition to the thumbwheel switches, there are other methods to assign an IP address to the POINT I/O adapter, such as using the BOOTP/DHCP utility. For more information on how to set the IP address, see POINT I/O Ethernet Adapter Installation Instructions, publication 1734-IN590. 3. Plug a 1585J-M4TBJM-1, Ethernet cable (straight-through) into a port on the Stratix 6000 switch. 4. Plug the other end of the Ethernet cable into the Ethernet port on the 1734-AENT POINT I/O Ethernet adapter. 8 7 6 5 4 3 2 1 5. Remove the safety end cap. 16 Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012

Prepare the Distributed POINT I/O Module Hardware Chapter 1 Mount the 1734-OB4E Digital Output Module 1. Install the removable terminal base (RTB) on the mounting base. Make sure the handle is in the down position. 2. Using a small screwdriver, rotate the keyswitch on the mounting base to match the position on the keyswitch on the I/O module. Handle This example shows the keyswitch in position 1. Mounting Base Removable Terminal Block 3. Press the 1734-OB4E module into the wiring base. Module 4. Snap the handle up to lock the RTB on the module. 5. Connect the wiring base assembly, including mounting base, module, and RTB, to the POINT I/O Ethernet adapter via the slots on the right side of the adapter. 6. Slide the wiring base assembly along the right side of the network adapter and press it onto the DIN rail. Tongue-and-groove Slots Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012 17

Chapter 1 Prepare the Distributed POINT I/O Module Hardware Mount and Wire the 1794-PS3 Power Supply Use a 1794 FLEX I/O power supply to power the distributed POINT I/O modules. This publication uses the 1794-PS3 power supply. 1794-PS3 Power Supply WARNING: Verify that all incoming power is turned off before wiring power. 1. Hook the upper-lip of the DIN rail latch onto the DIN rail. 2. Press the module onto the DIN rail next to the POINT I/O Ethernet adapter. 3. Connect the 120/240V AC power L1, L2/N and Ground wires to your AC power source. Power 24V DC POWER SUPPLY 1794-PS3 GR L2/N L1 COM 24V 18 Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012

Prepare the Distributed POINT I/O Module Hardware Chapter 1 Wire the 1734-AENT Ethernet Adapter to the Power Supply 1. Connect the 12/24V DC common and 12/24V DC power wires from the power supply to the adapter. 0 0 2 Module Status Network Activity Status Network Status PointBus Status 24VDC Source Output 1734-AENT 2. Turn on incoming power. System Power Field Power 1734 OB4E Common Power Additional Resources For a list of additional resources that might assist you when preparing the distributed POINT I/O module hardware, see page 5. Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012 19

Chapter 1 Prepare the Distributed POINT I/O Module Hardware Notes: 20 Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012

Chapter 2 Add the POINT I/O Ethernet Adapter and Digital Output Module to an RSLogix 5000 Project In this chapter, you complete the following tasks: Add the 1734-AENT Ethernet adapter to the RSLogix 5000 project Add the 1734-OB4E digital output module to the RSLogix 5000 project Use ladder logic to test the 1734-OB4E digital output module s lights Before You Begin You must complete these tasks before using this chapter: The tasks described in Before Using This Publication on page 5, including: Prepare the Logix5000 control system hardware Prepare the computer Configure the networks Create an RSLogix 5000 project The example RSLogix 5000 project used in this chapter uses a CompactLogix 5370 L3 controller. These tasks described in Chapter 1, Prepare the Distributed POINT I/O Module Hardware on page 13: Mount and Connect the 1734-AENT Ethernet Adapter Mount the 1734-OB4E Digital Output Module Mount and Wire the 1794-PS3 Power Supply Wire the 1734-AENT Ethernet Adapter to the Power Supply Verify that the 1734-AENT POINT I/O Ethernet adapter s thumbwheel switches are set to a valid IP address, as described on page 16. Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012 21

Chapter 2 Add the POINT I/O Ethernet Adapter and Digital Output Module to an RSLogix 5000 Project What You Need You need RSLogix 5000 software to complete the tasks in this chapter. Follow These Steps Configure the POINT I/O Adapter and Output Module page 23 Add Ladder Logic to Test the 1734-OB4E Module s Lights page 26 Download the Project to Your Logix5000 Controller page 29 Test the 1734-OB4E Output Module s Light page 30 22 Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012

Add the POINT I/O Ethernet Adapter and Digital Output Module to an RSLogix 5000 Project Chapter 2 Configure the POINT I/O Adapter and Output Module 1. Open your RSLogix 5000 project and verify that it is Offline with the controller. 2. Right-click Ethernet in the I/O Configuration folder and choose New Module. 3. Select the 1734-AENT Ethernet adapter and click Create. 4. Type the name for the adapter. 5. Type the adapter s IP address. 6. Click Change. Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012 23

Chapter 2 Add the POINT I/O Ethernet Adapter and Digital Output Module to an RSLogix 5000 Project 7. Make these changes on the Module Definition dialog box. a. Select the Series. b. Select the Revision. c. Select the Chassis Size. Chassis size equals the number of POINT I/O modules + 1 for the adapter. In this example, the Chassis Size is 2 to account for the 1734-AENT Ethernet adapter and the 1734-OB4E digital output module. d. Select Disable Keying. e. Click OK. RSLogix 5000 software warns you about the effect of module definition changes. f. Click OK. 8. When the New Module dialog box reappears, click OK. The adapter is added to the I/O configuration. 24 Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012

Add the POINT I/O Ethernet Adapter and Digital Output Module to an RSLogix 5000 Project Chapter 2 9. Right-click the 1734-AENT Ethernet adapter and choose New Module. 10. Select the 1734-OB4E digital output module and click Create. 11. Configure the following parameters: Name Slot (Slot number is the position of the module to the right of the adapter.) Electronic Keying 12. Click OK. The 1734-OB4E digital output module is added to the I/O configuration. 13. Save the project. Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012 25

Chapter 2 Add the POINT I/O Ethernet Adapter and Digital Output Module to an RSLogix 5000 Project Add Ladder Logic to Test the 1734-OB4E Module s Lights 1. In RSLogix 5000 software s controller organizer, expand Tasks >MainTask>MainProgram. 2. Double-click MainRoutine. A blank routine opens. 3. Add a new rung to the routine. 4. From the Element Toolbar, drag and drop an Examine On element and an Output Energize element onto the rung. 5. Double-click the? in the Examine On element. 6. Type PB for push button. 7. Press Enter. 26 Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012

Add the POINT I/O Ethernet Adapter and Digital Output Module to an RSLogix 5000 Project Chapter 2 8. Right-click PB and choose New PB. 9. When the New Tag dialog box appears, click Create and Close to use the default values. 10. Double-click the? in the Output Energize element. 11. Name the Output Energize element OB4E_Light. IMPORTANT Do not use spaces in the tag name. Use underscores ( ) instead. Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012 27

Chapter 2 Add the POINT I/O Ethernet Adapter and Digital Output Module to an RSLogix 5000 Project 12. Right-click the OB4E_Light tag and choose New OB4E_Light. OB4E_Light is an alias tag for the I/O point tag name. With an alias tag, you can assign a simple name to a physical I/O point address. 13. From the Type pull-down menu, choose Alias. 14. From the Alias For pull-down menu, browse to the 1734-OB4E digital output module and choose any bit. This example uses my_aent:1:o.data[0]. 15. Click Create and Close. This graphic shows the rung created with these steps. 28 Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012

Add the POINT I/O Ethernet Adapter and Digital Output Module to an RSLogix 5000 Project Chapter 2 Download the Project to Your Logix5000 Controller 1. Save your changes. 2. Move the controller s switch to Program. RUN REM PROG 3. Click the Controller Status icon and choose Download. 4. Click Download. Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012 29

Chapter 2 Add the POINT I/O Ethernet Adapter and Digital Output Module to an RSLogix 5000 Project Test the 1734-OB4E Output Module s Light 1. Move the controller s mode switch to the RUN position. 2. If not open, open the project s Main Routine to find the ladder logic written earlier in this chapter. 3. Select the PB and press Ctrl+T. This toggles the state from 0 to 1 (off to on). 4. Verify that the light on the distributed digital output module turns on. 5. Press Ctrl+T to toggle the state back to 0 (off ). 6. Choose Go Offline. Additional Resources For a list of additional resources that might assist you when preparing the PowerFlex 40 drive hardware, see page 11. 30 Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012

Index B BOOTP/DHCP utility 10 C connections hardware 10 conventions 11 D DLR topology 8 E Ethernet adapter assign IP address 16, 23 connect 16 H hardware connect Ethernet adapter 16 connect I/O modules 17 connect power supply 18 install removable terminal base 17 preparation 13-19 removable terminal base keyswitch 17 I I/O modules add to RSLogix 5000 project 21-25 connect 17 test light 30 IP address assign to Ethernet adapter 16, 23 K keyswitch on removable terminal base 17 L ladder logic alias for tag 28 elements 26 routine 26 use to test I/O module s lights 26-28 linear topology 8 Logix5000 controllers prerequisite tasks 5-7 quick starts 8 N network topologies DLR 8 linear 8 P parts required to complete tasks 11 power supply connect 18 prerequisite tasks 5-7 Q quick starts for devices in Logix5000 control systems 8 R removable terminal base install 17 removable terminal base keyswitch 17 requirements hardware preparation 13-19 parts 11 prerequisite tasks 5-7 software 10 RSLogix 5000 software add element to routine 26 add I/O modules to project 21-25 add routine to project 26 alias for tag 28 ladder logic 26-28 requirements 10 test I/O module s light 30 S software BOOTP/DHCP utility 10 RSLogix 5000 10 T tasks prerequisite tasks 5-7 Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012 31

Index Notes: 32 Rockwell Automation Publication IASIMP-QS027A-EN-P - February 2012

Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/. Installation Assistance If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact Customer Support for initial help in getting your product up and running. United States or Canada 1.440.646.3434 Outside United States or Canada Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell Automation representative. New Product Satisfaction Return Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures. United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process. Outside United States Please contact your local Rockwell Automation representative for the return procedure. Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/. Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400 www.rockwel lautomation.com Power, Control and Information Solutions Headquarters Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444 Europe/Middle East/Africa: Rockwell Automation NV, Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640 Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846 Publication IASIMP-QS027A-EN-P - February 2012 Copyright 2012 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.