OCC Fiber Optic Field Testing Guidelines Excerpt from Optical Cable Corporation s INSTALLATION GUIDE

Similar documents
FIBER OPTIC SYSTEM TEST PROCEDURES

Measuring of optical output and attenuation

Optical Fiber Data Center Field Testing. ANSI/BICSI Data Center Design and Implementation Best Practices

Removing the Mystery from OTDR Measurements. Keith Foord Product Manager Greenlee Communications

Accurately Testing fibre Optic Cables

Four Ways To Test Installed Fiber Optic Cables And How The Results Will Differ With Each Method

Cabling & Test Considerations for 10 Gigabit Ethernet LAN

Fiber Optic Specifications

Module 13 : Measurements on Fiber Optic Systems

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE FOR TRAFFIC SIGNAL INTERCONNECT JANUARY 19, 2007

Technical Bulletin. Guidelines For Testing And Troubleshooting Fiber Optic Installations

home site map help ECMS Project: Standard / Federal Oversight Advertised

SECTION TESTING OF FIBER OPTIC CABLES

Optical Fibres. Introduction. Safety precautions. For your safety. For the safety of the apparatus

Explanation of Reflection Features in Optical Fiber as Sometimes Observed in OTDR Measurement Traces

Polymer Coated Fiber Cable (PCF)

Field Measurements of Deployed Fiber

The following terms are defined within the context of the fiber optic industry

White Paper: 10GbE Fiber A Practical Understanding and Functional Approach

APPLICATION NOTE POLARIZATION MEASUREMENTS

Guidelines. LANscape Solutions Recommended Fiber Optic Test Guidelines. Table of Contents. 1. Introduction. 2. Why Test? 1. Introduction...

SINGLEMODE OR MULTIMODE FIBER OPTIC PATCHCORDS

Best Practices for Ensuring Fiber Optic System Performance. David Zambrano

Fibre optic testing best practices

USE OF FIBRE OPTICS INTERNATIONAL STANDARDS FOR CALIBRATION LABORATORY ACCREDITATION INTERNATIONAL ELECTROTECHNICAL COMMISSION

ETA International FIBER OPTICS INSTALLER CERTIFICATION SUPPLEMENTAL STUDY PACKAGE (For U.S. Military Personnel) EXAM FEE - $150.00

Splicing and Fiber Assembly Compatibility for Non-Zero Dispersion-Shifted Fiber and Standard Single-Mode Fiber

The Conversion Technology Experts. Fiber Optics Basics

SECTION 680 FIBER OPTIC CABLE DESCRIPTION

Structured Connectivity Solutions Field Testing Guidelines for Fiber-Optic Cabling Systems

MTS/T-BERD Platforms Very Long Range (VLR) OTDR Module

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION STRUCTURE CABLING TESTING

Testing and troubleshooting enterprise fiber-optic cabling. Presenter: Neftali Usabal Fluke Networks - LATAM

CamSplice Assembly Manual

What testing is required for PREMISES Fiber Optic Cabling and the standards used

Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables. Steve Swanson May 5, 2009

The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects

Fiber-to-the-Home/FTTH

Optical Fibers Fiber Optic Cables Indoor/Outdoor

Insertion Losses of Fiber Optical Connectors

7.4 3M No Polish Connector

Fiber Optic Terminus End Face Quality Standards

BOTDR Measurement Techniques and Brillouin Backscatter Characteristics of Corning Single-Mode Optical Fibers

M310 Data Center OTDR

Graphical User Interface Capabilities of MATLAB in Centralized Failure Detection System (CFDS)

12 Fibre MTP Jumper, MTP (non-pinned) to MTP (pinned)

Attaching the PA-A1-ATM Interface Cables

DIRECTIONAL FIBER OPTIC POWER MONITORS (TAPS/PHOTODIODES)

M310 Enterprise OTDR. Designed for Enterprise Network Testing, Troubleshooting and Documentation. or (800) , (603)

palmotdr Series Handheld OTDR

FTB-720 LAN/WAN Access OTDR OPTIMIZED FOR MULTIMODE AND SINGLEMODE ACCESS NETWORK TESTING

Attenuation: Bending Loss

Fiber Optic Cable Installation

Fiber Optics: Fiber Basics

POLARIZATION EXTINCTION RATIO METER

FTB-720 LAN/WAN Access OTDR OPTIMIZED FOR MULTIMODE AND SINGLEMODE ACCESS NETWORK TESTING

CORNING CABLE SYSTEMS GENERIC SPECIFICATION FOR TIGHT BUFFER OPTICAL FIBER CABLES FOR INTER- AND INTRABUILDING APPLICATIONS.

Testing Fiber Optic Cables. Rudy De Winter C.N. Rood

Properties and Potential Applications of a Bend Optimised Singlemode Optical Fibre

Industry solutions: Broad cast

What are Fibre Optics?

Items Supplied. Frequency. Designation Description / Delivery Unit Order Number

Cable Preparation and Pulling Procedure Best Practices for Fiber Optic Indoor Tight-Buffered Cable

Indoor/Outdoor Tight-Buffered Cable Lowers Installation Costs, Reduces Time, and Increases Reliability

Patch Cords for Data Center Applications

Compatibility of Bend Optimized Multimode Fibers White Paper. Issued September 2009

INTRODUCTION FIGURE 1 1. Cosmic Rays. Gamma Rays. X-Rays. Ultraviolet Violet Blue Green Yellow Orange Red Infrared. Ultraviolet.

Fiber Characterization Service

Special Specification 6033 Computerized Transportation Management System

BICSInews. plus. Show Issue. september/october 2012 volume 33, number 5. + Migration to High-Speed Ethernet

Fiber Optics: Fiber Preparation and Fiber Connectors

Fiber Optic Connections in the Sea

Procedure for Cutting and Respooling Fiber Optic Cable

Plastic Optical Fiber for In-Home communication systems

SPLICE LOSS IN NON-ZERO DISPERSION-SHIFTED FIBERS

Optocore Guideline for Fiber Optical Cabling in Permanent Installations

Plug - Type (Male/Female) Attenuators CAA series Singlemode

Why Expanded Beam types are essential in military and other harsh environment applications

and LP 11 are illustrated at right.

OFS AllWave Zero Water Peak (ZWP) single-mode

Simulation of Gaussian Pulses Propagation Through Single Mode Optical Fiber Using MATLAB . MATLAB

Overcoming OM3 Performance Challenges

By D.A. Bo Conrad. What is the proper way to store fiber optic spools of cable?

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

200-Micron Single-Mode Fiber Enables New Cable Designs Copyright 2014 OFS FITEL, LLC

Installation Effects Upon Alien Crosstalk and Equal Level Far End Crosstalk

How To Read A Fiber Optic Sensor

MICRO-COAX Space Grade Cable Assembly Integration Manual

HIGH POWER FIBER OPTIC PATCHCORDS

Dispersion in Optical Fibers

GLOBAL COLLEGE OF ENGINEERING &TECHNOLOGY: YSR DIST. Unit VII Fiber Optics Engineering Physics

The Importance of minembc Laser Bandwidth Measured Multimode Fiber for High Performance Premises Networks White Paper

Cable Network Transparency Fiber Optic Monitoring

Fiber Optic Selector Guide for Analog & Digital Data Links, Contact Closures & Multiplexers

Different Types of Dispersions in an Optical Fiber

TEST & INSPECTION. Featured Data Center Products. OTDRs Certification Test Kits Inspection Cleaning

Patch Cord Quality, Reliability and Performance. The Impact of Industry Specifications and Physical Parameters on Patch Cord Performance

99 Washington Street Melrose, MA Phone Toll Free Visit us at

Termination Procedure. FCUPC One Piece Connector

Transcription:

Fiber Optic Field Testing Guidelines Excerpt from Optical Corporation s INSTALLATION GUIDE

Field Testing Field testing fiber optic cables can be done with different types of equipment. Most test procedures for this equipment have been standardized by national standards bodies such as TIA (Telecommunications Industry Association) and EIA (Electronic Industries Alliance). The most commonly used pieces of equipment are the power meter and source and the OTDR (Optical Time Domain Reflectometer). s The power meter is used in conjunction with a source (operating at wavelengths of 850 nm & 1300 nm for multimode fibers or at 1310 nm & 1550 nm for singlemode fibers) to measure the light loss in a fiber optic cable. The unit of measure is milliwatt (mw) or decibel (). In the measurement of light loss in an optical fiber or cable, a decibel is the ratio, in logarithmic form, of the power levels at the input and output ends of the cable. The test source for a loss measurement should be similar to the actual sources that will be used in the network system that is under test. The source should be the same type, wavelength, and modal distribution as the network transmitters. Mulitmode Fiber Modal Effects In order to test multimode fiber optic cables accurately with a power meter and source, the modal distribution must be conditioned. The most commonly used mode filter during field testing is the mandrel wrap, which removes higher order modes effectively by stressing the fiber. TIA/EIA-455-50B Light Launch Conditions for Long-Length Graded- Index Optical Fiber Spectral Attenuation Measurements requires different mandrel sizes based upon the fiber core size. Fiber Core Size Mode Filter Mandrel Diameter 50µm 25 mm 62.5µm 20 mm 100µm 25 mm wrap diameter should be reduced by the overall cable diameter. For example, to test a 3 mm cable would require a 22 mm mandrel for a 50µm multimode fiber (25 mm - 3 mm = 22mm). For larger cable diameters, be careful not to exceed the minimum bending radius limits when using the mandrel wrap. Stripping or removing the buffered or coated fibers from a cable is the preferred approach. Singlemode Fiber Modal Effects Singlemode fiber supports one mode of transmission. Problems with mode distribution are not a factor. However, it does take a short distance for sinlgemode fiber to actually become singlemode. Short singlemode fibers may have multiple modes. A 4 to 6 inch diameter loop of fiber may be used to strip out these multiple modes. Testing There are two methods that can be used to measure loss with power meters in fiber optic cables: Single reference testing and double reference testing. Both methods are described in TIA/EIA-455-171 Attenuation by Substitution Measurement for Short Length Multimode Graded-Index and Single- Mode Optical Fiber Assemblies. Single Testing Single reference testing is done by mating the fiber optic cable that needs to be tested to a reference launch cable, which is connected to a source, and measuring the power out the far end of the fiber optic cable with a power meter. In order to get an accurate measurement of the fiber optic cable, the loss of the reference cable has to be zeroed out (0 ) or subtracted from the total loss. This is done by connecting the reference cable to the source and to the meter. Depending on the equipment, this loss of the reference cable can either be zeroed out (0 ) on the power meter or the loss may have to be written down and then subtracted from the loss of the fiber optic cable when it is tested. See Figures 1-1 and 1-2. 5 turns around the mandrel is required. The mandrel should be smooth and round. For fiber that has been jacketed, the mandrel Fiber Optic Field Testing Guidelines Excerpt from Optical Corporation s Installation Guide Page 2 of 6

Figure 1-1: Referencing (Zeroing) the Launch for Single Testing Test Figure 2-1: Referencing (Zeroing) the Launch s for Double Testing Test Figure 1-2: Single Testing However, since only one launch cable is used, the loss measured for the fiber optic cable also includes the loss of the connector mated to the launch cable and the fiber optic cable. Optical Corporation does not recommend this method of loss testing with power meters. Double Testing Double testing is done by attaching the fiber optic cable that needs to be tested between two reference cables, one attached to the source and one to the power meter. In order to get an accurate measurement of the fiber optic cable, the loss of the two reference cable has to be zeroed out (0 ) or subtracted from the total loss. This is done by connecting the two reference cables together, with one attached to the source and one attached to the meter. Depending on the equipment, this loss of the reference cables can either be zeroed out (0 ) on the power meter or the loss may have to be written down and then subtracted from the loss of the fiber optic cable when it is tested. See Figures 2-1 and 2-2. Figure 2-2: Double Testing Precautions When testing with power meters, it is necessary to adhere to certain steps prior to and during testing. All connectors being used should be cleaned prior to use. If several tests are being done, it may be necessary to periodically clean the connectors. The quality of the launch cable will affect the measurements. When turning on the power meter and source for use, ample time should be given to allow the power meter and light source to warm up and stabilize. s on the ends of the reference cables that have poor end-faces (cracked, chipped, etc) should not be used. These damaged connectors could possibly damage the end face of the connectors on the test cable when mating and un-mating is done. Optical Time Domain Reflectometer The optical time domain reflectometer (OTDR) is used to visually represent an optical fiber s attenuation characteristics along its length. The OTDR plots these Fiber Optic Field Testing Guidelines Excerpt from Optical Corporation s Installation Guide Page 3 of 6

characteristics with the distance as the X- axis and the attenuation as the Y-axis. The OTDR uses backscattering to visually display these characteristics. When testing with an OTDR, short pulses of light are sent down the fiber from the OTDR. The reflected light measured by the OTDR is backscattering. By knowing the fiber s index of refraction, the OTDR can accurately compute the length of a fiber and locate events along the fiber, such as splices, connector interfaces, bad bends, etc. The OTDR also measures the received optical power of the reflected light and plots an optical fiber s attenuationby-distance display. The graphical displays produced by the OTDR are an advantage over the power meters. The graphs can be stored for documentation and used for troubleshooting later. Another advantage for the OTDR is that only one end of the cable that is being tested is needed to make a measurement. OTDR Test Set Up If the cable to be tested is not connectorized, the cable should be stripped to expose approximately 6 inches or more of fiber. The fiber should be cleaned and cleaved. This also includes removing all primary coatings down to the cladding diameter of the fiber. A quality launch reel of the same fiber type being tested should be connected to the OTDR with a length of approximately 1. This launch reel is necessary in order to measure past the dead zone in the OTDR. See Figures 3-1 and 3-2. Dead zones in the OTDR result from the very short period of time after the OTDR launches a light pulse into the fiber during which the OTDR cannot see the reflected light from the fiber. These dead zones occur at the beginning of the OTDR plots and can be up to 1 in length. In the dead zone, the OTDR cannot determine events in the fiber. Therefore, it is necessary to have the launch reel. One end of the launch reel should be connectorized with a connector that mates to the OTDR output and the other end of the launch reel should be prepped for the type of connection needed on the fiber being tested (connector if testing to connectorized cable or bare fiber adaptor if testing to bare fiber). See Figure 3-2. Dead Zone Figure 3-1: Dead Zone in OTDR Plot The OTDR should be turned on and ample time should be given to allow the OTDR source to warm up and stabilize. Enter in the OTDR parameters for the test such as the wavelength, index of refraction, pulse length, etc. Be sure that no source is connected at the opposite end of the fiber being tested. If there is, disconnect the source at the opposite end. This could possibly damage the OTDR. Once the previous items have been completed, connect the launch reel to the fiber being tested (either by connector adaptor or bare fiber adaptor). Start the OTDR test and allow the OTDR average the measurements long enough to provide a smooth trace. Launch Reel OTDR Figure 3-2: OTDR Test Set Up OTDR Events As mentioned earlier, the OTDR plots the length of the fiber on the X-axis and the loss () on the Y-Axis. The sloped line plotted on the OTDR represents the fiber. The slope of the line represents the attenuation of the fiber over its length. Also, the beginning of the plot is the called dead zone. See Figure 3-1. This is the non-linear region of the trace where OTDR Test Fiber Fiber Optic Field Testing Guidelines Excerpt from Optical Corporation s Installation Guide Page 4 of 6

events cannot be seen. Past the dead zone, the linear portion of the plot and accurate loss readings of the fiber under test can be seen. Following are plots with various events that may occur and explanations of those events (Figures 4-1 through 4-5). Broken Fiber End of Fiber Figure 4-1: OTDR Plot with and The plot in Figure 4-1 represents an OTDR plot that contains a launch reel connected to fiber that contains a splice in it. The launch reel contains the dead zone and has a connector at the end of the launch reel. Where two connectors are mated together, the OTDR plot reveals a slight reflection (or spike) in the plot. The Y-axis difference from where the reflection begins and ends is the connector loss (two connectors mated together). The plot in Figure 4-1 also reveals a splice in the fiber. A splice is displayed on the plot as a sharp drop. The Y-axis difference in where the drop begins and ends is the splice loss. The plot in Figure 4-1 also shows the end of the fiber. This is seen as a sharp reflection (or spike) caused by the OTDR pulse reflected when hitting air. If there is no reflection at the end of the plot, then there is a possibly that the fiber is broke somewhere in the cable and the end of the plot is not the end of the cable. See Figure 4-2. Figure 4-2: OTDR Plot with Broken Fiber s can also be seen as a sharp rise (splice gainer). See Figure 4-3. This scenario is typically caused by a difference in mode field diameters between two fibers at the splice. For example, a splice gainer may occur when a splice is measured from light passing from a 62.5 µm fiber into a 50 µm fiber. In order to obtain a true splice loss, TIA/EIA-455-61A Measurement of Fiber or Attenuation with an OTDR requires that a bi-directional average be taken to obtain the most accurate loss for a splice. End of Fiber Figure 4-3: OTDR Plot with and Gainer Other TIA/EIA documents that can be referenced when using an OTDR are TIA/EIA-455-59A Measurement of Fiber Point Discontinuities Using an OTDR and TIA/EIA-455-60A Measurement of Fiber or Length Using an OTDR. OTDR ghosts are typically seen on OTDR plots when testing short cables with highly reflective connectors. See Figure 4-4. These are caused by reflected light from a connector reflecting back and forth. Ghosts can be deceptive. The reflective event will appear to be connector loss. However, the reflective event will not show any loss (0 Fiber Optic Field Testing Guidelines Excerpt from Optical Corporation s Installation Guide Page 5 of 6

change on the Y-axis). Ghosts can be eliminated by reducing the reflections by using index matching fluid on the reflective connector or sometimes by thoroughly cleaning the connector. of the cable and a step near the end of cable. End of Fiber Ghost Step Step Figure 4-4: OTDR Plot with a Ghost Figure 4-5: OTDR Plot with Steps Point discontinuities can show up as steps on an OTDR plot. These steps can be caused by bends in the cable that exceed the minimum bending radius, the cable being crushed, etc. The plot in Figure 4-5 represents a cable with a step in the middle Fiber Optic Field Testing Guidelines Excerpt from Optical Corporation s Installation Guide Page 6 of 6