Integrated Flywheel Based Uninterruptible Power Supply (UPS) System for Broadcast Applications

Similar documents
Power Quality. Uninterruptible Power Supply

IT S TIME TO EXPECT MORE FROM AN ENERGY STORAGE SOLUTION

Relationship between large subject matter areas

Understanding the Alternator

Liebert GXT MT+ CX UPS, 1000VA VA Intelligent, Reliable UPS Protection. AC Power for Business-Critical Continuity

Power Quality. Voltage Sag Ride-through Mitigation in Sequence by Increasing Cost

E&I MAINTENANCE ENTRY TEST ENABLING OBJECTIVES. DESCRIBE hazards and precautions taken to avoid injury in the workplace.

Technical Comparison of On-line vs. Line-interactive UPS designs

Power surges can also be generated by equipment in your facility such as:

A COMPARISON OF TYPICAL UNINTERRUPTIBLE POWER SUPPLY (UPS) DESIGNS IN TODAY S MARKETS

POWER QUALITY IN YOUR HOME

UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES

Diode Applications. by Kenneth A. Kuhn Sept. 1, This note illustrates some common applications of diodes.

NO-BREAK KS 7e. Concentrated Energy kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Principles of Adjustable Frequency Drives

Selecting a UPS Topology for your Data Center. by Dr. Daniel Becker, Ph.D., Methode Active Energy Solutions

Rectifier filter stage post filtering sense

CONSTRUCTING A VARIABLE POWER SUPPLY UNIT

Constructing a precision SWR meter and antenna analyzer. Mike Brink HNF, Design Technologist.

Designed for uptime. Defining data center availability via a tier classification system

Tough Decision: On-Line or Line-Interactive UPS?

Guidelines for ATS selection: How to choose the right transfer solution for your power application.

The beginning of the end of the incumbent UPS

Asia Pacific Regional Power Quality Seminar March 2005, Marriot Putrajaya, Malaysia. Voltage Source Converter based Power Quality Solutions

LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500

EssPro Energy Storage Grid Substation The power to control energy

Specifying a Variable Frequency Drive s

HT 30/35CD transmitters

SmartPro 230V 3kVA 2.25kW Line-Interactive UPS, Extended Run, SNMP, Webcard, Tower, USB, DB9 Serial

Power Quality For The Digital Age INVERTING SOLAR POWER A N E N V IRONME N TA L P OT E N T I A L S W HI T E PA PER

Coordination of Telecommunications Surge Protective Devices in Countries with Unstable AC Power

KINETIC ENERGY RECOVERY SYSTEM BY MEANS OF FLYWHEEL ENERGY STORAGE

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

Eco-mode: Benefits and Risks of Energy-saving Modes of UPS Operation

Power Quality Issues, Impacts, and Mitigation for Industrial Customers

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

Isolated-Parallel UPS Configuration

SCALE ENERGY STORAGE SYSTEMS

Programmable Single-/Dual-/Triple- Tone Gong SAE 800

Modular architecture for high power UPS systems. A White Paper from the experts in Business-Critical Continuity

Which UPS is right for the job?

SECTION STANDBY GENERATOR TESTING AND COMMISSIONING

Data center energy efficiency and power quality: an alternative approach with solid state transformer

Once you know the volume of air and the static pressure of the system to be cooled, you can determine the fan specifications for your product.

Impact of Leading Power Factor on Data Center Generator Systems

Properties of electrical signals

UPS Topologies & Architectures. Don Lemmon Tubbesing Solutions (214) don@tubbesing.com

Video Camera Installation Guide

Fundamentals of Inverter Fed Motors

Cahier technique no. 196

AND8008/D. Solid State Control Solutions for Three Phase 1 HP Motor APPLICATION NOTE

The Different Types of UPS Systems

Liebert GXT3 Reliable On-Line UPS Protection In A Compact 2U Package 700VA -3000VA

Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications

WINDING RESISTANCE TESTING

Galleon 6-10K Online UPS. Voltronic Power Technology Corporation

DISTRIBUTED REDUNDANCY:

SmartPro 120V 500VA 300W Line-Interactive UPS, SNMP, Webcard, 1U Rack/Tower, USB, DB9 Serial

Model Owner s Manual. Español - P. 19 Français - P. 39

Common Power Problems & Power Protection Solutions

Hybrid Power Considerations for Today s Telecommunications

Lab 8: DC generators: shunt, series, and compounded.

GE Consumer & Industrial Power Protection. Digital Energy LP Series UPS. Uninterruptible Power Supply 3-30 kva. GE imagination at work

Smart Pro Rack/Tower UPS Intelligent, line interactive network power management system

EET272 Worksheet Week 9

ECEN 1400, Introduction to Analog and Digital Electronics

Product Guide AC Voltage Control Devices. Guide Guide. Popular Variable Transformers and AC Power Supplies.

Understanding Power Factor, Crest Factor, and Surge Factor. White Paper #17

Speed Control Methods of Various Types of Speed Control Motors. Kazuya SHIRAHATA

LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

Why and How we Use Capacity Control

Fundamentals of Power

AC Kinetics Variable Frequency Drive Comparative Transient Inertial Testing. This document was prepared by Advanced Energy.

CHAPTER 2B: DIODE AND APPLICATIONS. D.Wilcher

GAMATRONIC ELECTRONIC INDUSTRIES LTD.

Chen. Vibration Motor. Application note

Inductance. Motors. Generators

Maximizing UPS Availability

The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity

Study Guide for the Electronics Technician Pre-Employment Examination

WIND TURBINE TECHNOLOGY

Ameritron ATP-102 Tuning Pulser II

TV hearing aid BL-8008A BL-8008B. Manual

PV (photovoltaic) Basics There are generally two types of PV systems. The first and easiest (though the least flexible) is a grid tie system where

Enterprise Remote Monitoring

HVDC 2000 a new generation of high-voltage DC converter stations

DC Motor control Reversing

SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION

The Different Types of UPS Systems

PowerGem Pro Uninterruptible Power Supply

Theoretical review. Contents

Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS

Application Information Fully Integrated Hall Effect Motor Driver for Brushless DC Vibration Motor Applications

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION

PHASE CONVERSION TECHNOLOGY OVERVIEW

Evaluating the Opportunity for DC Power in the Data Center

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

Transcription:

Integrated Flywheel Based Uninterruptible Power Supply (UPS) System for Broadcast Applications White Paper 110 2128 W. Braker Lane, BK12 Austin, Texas 78758-4028 www.activepower.com

Objective This paper will review television transmitters, their sensitivity to certain power disturbances and the application of integrated flywheel UPS systems on the front end to provide appropriate protection to broadcasting equipment. 2

Severe Step Load of TV Transmitters Television transmitters are highly sensitive to voltage variations for a number of reasons. For example, incoming electric power disturbances can easily take a transmitter off the air, resulting in stranded viewers and potential loss in commercial revenue. Power outages can also cause some transmitters to undergo a hard shutdown, which can damage transmitter components due to the sudden loss in cooling or other control malfunctions. Figure 1: Broadcast Antenna Fortunately, UPS systems can provide power conditioning and voltage regulation to ensure constant quality power to transmitters and the necessary ride-through power to a standby generator for protection from extended outages. An integrated flywheel based UPS system like that of the CleanSource UPS system from Active Power is proven to protect broadcast companies from costly downtime and to guard transmitters from possible damage due to utility events. The architecture of the flywheel system handles overloads and step loads better than conventional double conversion UPS systems with batteries, in part because it is designed to efficiently manage a crowbar event a protective shutdown process that is built into many transmitters. 3

Flywheel Technology Active Power produces the integrated UPS and DC power system with flywheel technology that serves as an alternative to chemical batteries. The flywheel energy storage system stores kinetic energy by spinning a compact rotor in a low-friction environment. When short-term backup power is required due to fluctuations in utility power or power is lost, the rotor s kinetic energy is converted to electricity. Figure 2: Flywheel Assembly CleanSource integrates the function of a motor, flywheel rotor and generator into a single system. The motor, which uses electric current from the utility grid to provide energy to rotate the flywheel, spins at a constant speed to maintain a store of kinetic energy. The generator converts the kinetic energy of the flywheel into electricity as required. Refer to white paper #108 Operation and Performance of a Flywheel-Based UPS System for further information. The flywheel rotor is supported by Active Power s magnetic bearing technology. This technology unloads a majority of the flywheel s weight from the field-replaceable mechanical bearing cartridge. A vacuum pump evacuates the chamber, reducing the drag on the spinning flywheel. The flywheel s speed decreases as power is transferred to the load. Regulated current is supplied to the field coils to maintain constant voltage output throughout the discharge. The flywheel based system provide ride-through power for a majority of power disturbances, such as voltage sags and surges and bridges the gap between a power outage and the time required to switch to generator power. 4

Figure 3: CleanSource UPS 300 Series What is a Crowbar Event? A crowbar event is the automatic shutdown method used in a high power transmitter as a safety circuit to protect the transmitter amplifier tube or the inductive output tube (IOT) in the event of an arc-over inside the IOT. The function of the crowbar is to remove the high voltage from the amplifier as quickly as possible, typically within a few microseconds of the detected problem. The crowbar circuit shorts out the high voltage DC power supply to the IOT for a brief period of time, often in the range of several milliseconds. This function is typically performed with a device called a thyratron, which is a gas-filled tube that is similar in construction to a vacuum tube. The thyratron is connected directly across the high voltage DC supply. It is a very fast, high-voltage switch, comparable to a silicon-controlled rectifier, but with much higher voltage ratings and speed. When a problem is detected in the amplifier, the crowbar acts quickly; otherwise, the IOT would be destroyed, resulting in significant capital expense. The crowbar action produces a current of several thousand amps on the AC input of the high voltage supply and on the output of the UPS supplying the transmitter. The event is equivalent to a short circuit applied directly to the output of the UPS system, which can draw up to 20 times rated current. Assuming the input power supply to the transmitter can supply the large current that is demanded, the action of the crowbar does no harm to the transmitting equipment and after a few seconds the high voltage supply returns to normal. In the event of an overload from a crowbar event, the flywheel based UPS system switches to bypass in order to help supply the desired current from the lowest impedance source and does so without disturbing the operation of other transmitters on the same circuit. 5

Putting the Flywheel UPS System to the Crowbar Test A television network with a potential audience of more than 15 million viewers has several flywheel UPS systems deployed at different transmitter sites throughout the southeastern United States. At a site near Tampa, Fla., crowbar testing was performed on the output of one of its flywheel UPS systems. This transmission site has a primary 60 kw analog transmitter with a backup 30 kw transmitter that shares the output of the UPS system with a new 65 kw digital transmitter equipped with a crowbar circuit. The UPS system was tested several times in order to view the response of the system during a crowbar event of the digital transmitter. The current delivered by the UPS system during the crowbar test peaked at 3,000 to 4,000 amps, which varied due to the position of the voltage sine wave when the crowbar fired. In one of the crowbar tests, the UPS system only discharged for a short period and did not have to go to bypass. In five of the six crowbar tests, the UPS system went to bypass via the static bypass switch and displayed a warning message due to the severe step load. The UPS system then returned to normal on-line operation within a few seconds. The UPS system is configured so that if the same warning message occurs more than once per hour, the UPS system will remain in bypass mode and will require an operator to reset it. An external contact signal from a delay relay may also be used to automatically return the UPS to on-line operation if multiple crowbar events are expected within one hour. The other transmitter at the network s site, which was connected to the output of the UPS system, stayed on the air without a glitch during all of the crowbar tests. This is partly because the UPS static bypass switch allows transfer to the bypass source without affecting downstream equipment; otherwise, the critical loads could be subject to power disturbances during the event. CONCLUSION The crowbar test at the transmitter site indicates the flywheel based UPS system performed exceptionally well under extreme conditions and delivers stable, uninterrupted power to sensitive loads even during severe transient conditions. 6 TM 2008 Active Power, Inc. All rights reserved. WP-119