Designing a Grocery Store Refrigeration System from Scratch. Presented by Nick Shockley, PE

Similar documents
Heat Recovery In Retail Refrigeration

Skills Canada National Competition Instructions and Competition Details 38 Refrigeration and Air Conditioning / Post - Secondary May 27-30,

Cold Room & Refrigeration System (Casserole Assembly) No of units: 1

ADVANCES IN SUPERMARKET REFRIGERATION SYSTEMS

DIABLO VALLEY COLLEGE CATALOG

THE CASE FOR A REFRIGERATION PREVENTATIVE MAINTENACE PROGRAM

EFFECTS OF INDOOR RELATIVE HUMIDITY ON REFRIGERATED DISPLAY CASE PERFORMANCE

Scroll compressors for Low GWP Heat Pumps using R290 natural refrigerant. Pierre Ginies, Next Heat Pump Generation 2015

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Refrigeration and Air Conditioning Mechanic On-the-Job Training Guide

CPX/HT Series. REFRIGERATED AND HIGH TEMPERATURE DRYER 12 to 2400 CFM. High-performance products. Designed for you!

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

National Grid Small Business Energy Efficiency Program Overview. Central New York Energy Expo March 30, 2010

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

AIR-COOLED CONDENSERS Technical Guide

Air Conditioning 101. STN Presentation AC101

Energy Savings Potential for Commercial Refrigeration Equipment. Final Report Prepared by Arthur D. Little, Inc.

How To Understand Evaporator

Why and How we Use Capacity Control

Refrigeration Basics 101. By: Eric Nelson

Refrigeration Installation 101

Test Code: 8297 / Version 1

Statement of Work. 3.0 Details of Service Pre Start-up Cooling Start-up Service. Installation Service. Table of Contents. 1.0 Executive Summary

Direct Fresh Air Free Cooling of Data Centres

Refrigerant Choices for Commercial Refrigeration. Finding the Right Balance

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

Tim Sisson - Trane HVAC OVERVIEW

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

ENERGY RETROFIT PROGRAM

ULTRA-EFFICIENT HVAC DESIGN AND CONTROL

FAST FACTS. Henderson Engineers, Inc. (HEI) is a multidisciplinary engineering firm headquartered in the Kansas City

Natural geothermal energy.

CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS

FROST PREDICTION ON EVAPORATOR COILS OF SUPERMARKET DISPLAY CABINETS USING ARTIFICIAL NEURAL NETWORKS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

Xcel Business Customers: Program and Rebate Summary

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101

High Pressure Ammonia Systems New Opportunities

How To Design A Refrigeration System

MAC-120HE-01 Air-Cooled Chiller

Commercial Hot Water. Make a difference...

BPI Air Conditioning & Heat Pump Professional Training Sample Slides ( ) Agenda

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

Ammonia Detection System Codes and Design Specifications

In the compression-refrigeration loop (air conditioning), which is likely to be warmer? 1. Condenser coil 2. Evaporator coil

Regency TAFE, SA. An evaluation of the effects of PermaFrost treatment on a Fujitsu Heat Pump. July Prepared by

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now

LH and GH/GL Series UNIT COOLERS. Technical Bulletin: LHGH_001_ Products that provide lasting solutions.

System Trouble Shooting Fault Location REFRIGERATION AND AIR CONDITIONING. Fitters notes

ENERGY AUDITS AND RETRO- COMMISSIONING Local Law 87

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

Thermal Coupling Of Cooling and Heating Systems

TRAINING, EXAMINATION AND CERTIFICATION

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

ADDENDUM NO. 1 TO THE BIDDING DOCUMENTS. HVAC SERVICE AND MAINTENANCE Saint Clair County MidAmerica Saint Louis Airport.

Glossary of Heating, Ventilation and Air Conditioning Terms

Development of Air-to-Water Heat Pump for Home Air conditioning/hot Water Supply Combination System with Chilled/Hot Water in European Markets

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling

Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

Octopus for a sustainable future

Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015

Todd M. Rossi, Ph.D. President

Commercial CO2 Refrigeration Systems. Guide for Subcritical and Transcritical CO2 Applications

Commercial Gas Heat Pump - VRF

Denver International Airport Total Facility Optimization. Josh Foerschler Aurom Mahobian

LG Electronics AE Company, Commercial Air Conditioning

GREEN DATA CENTER DESIGN

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29

Sustainable Strategies for Rehabilitation Projects: 9th Street Office Building Adaptive Reuse Case Study

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Certified HVAC Audit Report Key Takeaways and Implications. Created for: Pets On the Go 445 Logging Road, Building 3 Yardley, PA-19034

Mechanical Insulation. Hospitals and Schools

HIGH PERFORMANCE CHILLED WATER SYSTEMS. EarthWise HVAC. EarthWise HVAC High Performance CHW Plants

Daikin Altherma hybrid heat pump. The natural combination

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers

HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:

Ammonia Detection System Codes and Design Specifications. Brian EuDaly, P.E. Calibration Technologies, Inc.

Low Profile Unit Cooler

Repair, Retrofit, or Replace Choices for Servicing R-22 Equipment

Energy Efficient Data Centre at Imperial College. M. Okan Kibaroglu IT Production Services Manager Imperial College London.

Midea Commercial Air Conditioner Malfunction Handbook

State of the Art Energy Efficient Data Centre Air Conditioning

POLICY BULLETIN Tecumseh Compressor Company Compressor Group

High School Graduation years 2013, 2014, Unit/Standard Number

Introduction To VRF: System Overview, Applications, & Savings Opportunities

Troubleshooting HVAC/R systems using refrigerant superheat and subcooling

How To Clean Water From An Ammonia Refrigeration System

Boilers and cogeneration/trigeneration. Abhi Sawant Business Development Manager Simons Green Energy

Chapter 3.4: HVAC & Refrigeration System

Enclosed Football Stadium Design History and Lessons Learned

In Row Cooling Options for High Density IT Applications

How to choose a heat pump and use it wisely

Transcription:

Designing a Grocery Store Refrigeration System from Scratch Presented by Nick Shockley, PE

Founded 1970 Locations Kansas City Bentonville Dallas Houston Las Vegas New York Metro Philadelphia Metro Phoenix Tampa Services Mechanical Electrical Plumbing Acoustics Architectural Lighting Audio/Visual Code Consulting Commissioning Fire Protection Refrigeration Security Sustainable Design Technology Licensed in Size 50 States District of Columbia Canada Puerto Rico US Virgin Islands British Columbia More than 450 employees More than 150 PEs More than 100 LEED APs Licensed in all 50 states

Grocery Experience

The Cost Equation: What Drives Cost? The Cost Equation: What Drives Cost?

Floor space requirements Tax & utility incentives Maintenance cost Life expectancy Life-Cycle Cost Retail Sales First Cost Energy Cost Refrigerant regulations

Floor space requirements Tax & utility incentives Maintenance cost Life expectancy Life-Cycle Cost Retail Sales First Cost Energy Cost Refrigerant regulations

Maintenance Cost I have a limited service base. Please design a simple system! Dedicated/home run circuits No subcooling Single suction groups Single stage comps, evenly sized

Maintenance Cost Circuited System 24,000 linear ft. copper pipe 14,500 lbs. copper pipe 4,500 lbs. R404A

Maintenance Cost Circuited System Pros 1. Control valves in one location 2. Single stage compressors 3. Can handle large range of capacity 4. Service friendly Cons 1. Centralized location leads to longer piping and electrical runs 2. Large refrigerant charge

Floor space requirements Tax & utility incentives Maintenance cost Life expectancy Life-Cycle Cost Retail Sales First Cost Energy Cost Refrigerant regulations

First Cost Copper pricing is through the roof! How can we reduce it? Loop piping Subcooling

First Cost Loop Piping with Mechanical Subcooling Pros 1. Smaller pipe diameters 2. Less refrigerant 3. Fewer brazed joints (leaks) 4. More energy efficient 5. Lower installed cost Cons 1. Control valves (LLSVs, EPRs) located at fixtures 2. Less service friendly 3. Subcooler setup and control

First Cost Piping Comparison Piping Savings calculated for San Antonio bin hours on a typical grocery store load (290 MBH LT, 770 MBH MT);404A, Subcooled to 50 degrees for both low and medium temp

First Cost Subcooling 10% Reduction in Installed Compressor Horsepower 5% Reduction in Condenser THR Compressor HP Savings calculated for San Antonio bin hours on a typical grocery store load (290 MBH LT, 770 MBH MT);404A, Subcooled to 50 degrees

First Cost I want the best price for my systems. System selection and bid Competitive bid Performance spec/allow OEMs to leverage their buying power

Floor space requirements Tax & utility incentives Maintenance cost Life expectancy Life-Cycle Cost Retail Sales First Cost Energy Cost Refrigerant regulations

Refrigerant Regulations What refrigerant should I be using? How can we reduce our exposure? The R-22 phase-out A large portion of existing stores are R-22 R-22 is currently at $15/lb and increasing The Carbon Tax threat Natural refrigerant system options

Refrigerant Regulations Alternate Refrigerants other considerations

Refrigerant Regulations Secondary Coolant Schematic Direct Expansion System CONDENSER Secondary Coolant CONDENSER COMP. DIRECT EXPANSION LOOP RECEIVER COMP. PRIMARY REFRIGERANT LOOP CHILLER RECEIVER EVAPORATOR PUMP SECONDARY COOLANT LOOP HEAT EXCHANGER

Refrigerant Regulations System Comparison Traditional + Proven technology, reliable + Central system, Serviceable + Equipment 1 st cost Secondary + Significant decrease in refrigerant volumes + Less case maintenance + Leak potential isolated to machine room + Improved temperature control + Case controls System controls Long pipe runs Quantity of joints/welds Large volume of refrigerant Valve adjustments Parasitic heat gains Energy Service Tech base First cost

Refrigerant Regulation Why Secondary?

Refrigerant Regulation Why Secondary?

Floor space requirements Tax & utility incentives Maintenance cost Life expectancy Life-Cycle Cost Retail Sales First Cost Energy Cost Refrigerant regulations

Energy Cost I want an energy efficient system. Medium Temperature doors Subcooling VFDs condensers and floating head pressure control Variable capacity control compressors Heat reclaim Suction Float

Annual Energy Use Intensity (EUI) 180 160 140 120 100 80 Green Bay, WI Kansas City Jacksonville, FL 60 40 20 0 Office Strip Retail Big Box Retail Grocery Grocery is second only to Fast Food!

Grocery Store Energy Use * Energy use and cost data taken from New Construction Benchmark Data Files for Commercial Buildings - http://www.eere.energy.gov/buildings/highperformance/new_const.html

Energy Costs How many residential refrigerators without doors are on the market?

Energy Cost Medium Temperature Door Comparison Adding doors reduces compressor horsepower by 83% and energy usage by 75%!

Cost in Dollar per Year Energy Cost Subcooling Compressor Energy Savings around 10% per year Energy Cost Per Year $80,000 Not Subcooled, $79,121 $75,000 $70,000 Subcooled, $73,487 $65,000 $60,000 $55,000 $50,000 Compressor Energy Savings calculated for San Antonio bin hours on a typical grocery store load (290 MBH LT, 770 MBH MT);404A, $0.08 kwh, Subcooled to 50 degrees

Energy Cost Condenser VFDs EVAP RACK RACK CONDENSER FAN CONDENSER COND POWER VFD SCT LOAD NRE CAPACITY THR AMBIENT Bin Hours TD SPEED POWER # OF FANS W/ CYCLING SAVINGS (F) MBH MBH % OF LOAD MBH F F (VFD) VFD (KW) (CYCLING) (KW) (KW) 107.5 159.39 164.15 103.0% 360.5 97.5 24 10 92% 9.36 6 11.50 2.14 102.5 156.82 158.43 101.0% 327.8 92.5 167 10 84% 7.04 5 9.58 2.54 97.5 154.24 157.66 102.2% 320.8 87.5 279 10 82% 6.60 5 9.58 2.99 92.5 151.67 160.91 106.1% 313.3 82.5 631 10 80% 6.15 5 9.58 3.44 87.5 149.09 160.99 108.0% 305.8 77.5 766 10 78% 5.71 5 9.58 3.87 82.5 146.52 149.28 101.9% 267.8 72.5 759 10 69% 3.84 5 9.58 5.74 77.5 143.94 146.76 102.0% 261.7 67.5 628 10 67% 3.58 4 7.67 4.08 72.5 141.37 141.82 100.3% 244.1 62.5 780 10 63% 2.91 4 7.67 4.76 70 140.08 145.60 103.9% 248.0 57.5 540 12.5 51% 1.56 4 7.67 6.11 70 140.08 145.60 103.9% 248.0 52.5 529 17.5 36% 0.57 3 5.75 5.18 70 140.08 145.60 103.9% 248.0 47.5 605 22.5 28% 0.27 2 3.83 3.57 70 140.08 145.60 103.9% 248.0 42.5 503 27.5 23% 0.15 2 3.83 3.69 70 140.08 145.60 103.9% 248.0 37.5 761 32.5 20% 0.09 2 3.83 3.74 70 140.08 145.60 103.9% 248.0 32.5 593 37.5 17% 0.06 1 1.92 1.86 70 140.08 145.60 103.9% 248.0 27.5 513 42.5 15% 0.04 1 1.92 1.88 70 140.08 145.60 103.9% 248.0 22.5 263 47.5 13% 0.03 1 1.92 1.89 70 140.08 145.60 103.9% 248.0 17.5 224 52.5 12% 0.02 1 1.92 1.90 70 140.08 145.60 103.9% 248.0 12.5 130 57.5 11% 0.02 1 1.92 1.90 70 140.08 145.60 103.9% 248.0 7.5 47 62.5 10% 0.01 1 1.92 1.90 70 140.08 145.60 103.9% 248.0 2.5 18 67.5 9% 0.01 1 1.92 1.91

Energy Cost Compressor variable capacity control EVAP RACK RACK CONDENSER FAN CONDENSER COMPRESSOR SCT LOAD NRE CAPACITY THR AMBIENT Bin Hours TD SPEED POWER # OF FANS VFD SAVINGS (F) MBH MBH % OF LOAD MBH F F (VFD) VFD (KW) (CYCLING) (KW/YEAR) 107.5 159.39 159.39 100.0% 342.6 97.5 24 10 88% 8.04 6 2.87 102.5 156.82 156.82 100.0% 324.5 92.5 167 10 83% 6.83 5 0.40 97.5 154.24 154.24 100.0% 304.9 87.5 279 10 78% 5.66 5 2.73 92.5 151.67 151.67 100.0% 291.9 82.5 631 10 75% 4.97 5 2.69 87.5 149.09 149.09 100.0% 278.4 77.5 766 10 71% 4.31 5 3.40 82.5 146.52 146.52 100.0% 266.3 72.5 759 10 68% 3.77 5-0.16 77.5 143.94 143.94 100.0% 256.7 67.5 628 10 66% 3.38 4 0.49 72.5 141.37 141.37 100.0% 243.4 62.5 780 10 62% 2.88 4 0.07 70 140.08 140.08 100.0% 238.5 57.5 540 12.5 49% 1.39 4 0.87 70 140.08 140.08 100.0% 238.5 52.5 529 17.5 35% 0.51 3 0.87 70 140.08 140.08 100.0% 238.5 47.5 605 22.5 27% 0.24 2 0.87 70 140.08 140.08 100.0% 238.5 42.5 503 27.5 22% 0.13 2 0.87 70 140.08 140.08 100.0% 238.5 37.5 761 32.5 19% 0.08 2 0.87 70 140.08 140.08 100.0% 238.5 32.5 593 37.5 16% 0.05 1 0.87 70 140.08 140.08 100.0% 238.5 27.5 513 42.5 14% 0.04 1 0.87 70 140.08 140.08 100.0% 238.5 22.5 263 47.5 13% 0.03 1 0.87 70 140.08 140.08 100.0% 238.5 17.5 224 52.5 12% 0.02 1 0.87 70 140.08 140.08 100.0% 238.5 12.5 130 57.5 11% 0.01 1 0.87 70 140.08 140.08 100.0% 238.5 7.5 47 62.5 10% 0.01 1 0.87 70 140.08 140.08 100.0% 238.5 2.5 18 67.5 9% 0.01 1 0.87 Using variable capacity compressor control to exactly match the load not only results in compressor energy savings but also reduces the THR and results in further condenser energy savings

KWH / YEAR Energy Cost Compressor and Condenser KWH 1200000 1000000 VFD Condenser Condenser 72, 425 Fan Cycling 236, 262 VFD Condenser 65, 283 800000 600000 400000 Fixed Speed Compressors 894, 446 Fixed Speed Compressors 894, 446 Variable Capacity Compressors 856, 980 200000 0

Cost in $ per Year Energy Cost Compressor and Condenser KWH ($) $100,000 $90,000 Condenser Fan Cycling $18, 901 VFD Condenser $5, 794 VFD Condenser $5, 223 $80,000 $70,000 $60,000 $50,000 $40,000 $30,000 Fixed Speed Compressors $71, 556 Fixed Speed Compressors $71, 556 Variable Capacity Compressors $68, 558 $20,000 $10,000 $0 Compressor + Condenser $/Year Total Annual Cost Fixed Speed Compressors $71,556 Condenser Fan Cycling $18,901 $90,457 Fixed Speed Compressors $71,556 VFD Condenser $5,794 $77,350 Variable Capacity Compressors $68,558 VFD Condenser $5,223 $73,781

Heat Reclaim Domestic hot water desuperheating yields 15-20% of THR Full condensing for ventilation air preheat can yield up to 100% of THR in cold ambient conditions EVAP RACK RACK SCT LOAD NRE CAPACITY THR AMBIENT Heating Load Bin Hours Heating Load Offset by Reclaim Heating Load Offset by Reclaim % of THR Available (F) MBH MBH % OF LOAD MBH F MBH MBH MBTU/YEAR 107.5 159.39 159.39 100.0% 342.6 97.5 0 24 0 0 0% 102.5 156.82 156.82 100.0% 324.5 92.5 0 167 0 0 0% 97.5 154.24 154.24 100.0% 304.9 87.5 0 279 0 0 0% 92.5 151.67 151.67 100.0% 291.9 82.5 0 631 0 0 0% 87.5 149.09 149.09 100.0% 278.4 77.5 0 766 0 0 0% 82.5 146.52 146.52 100.0% 266.3 72.5 0 759 0 0 0% 77.5 143.94 143.94 100.0% 256.7 67.5 3 628 2.7 1696 1% 72.5 141.37 141.37 100.0% 243.4 62.5 30 780 29.7 23166 12% 70 140.08 140.08 100.0% 238.5 57.5 57 540 56.7 30618 24% 70 140.08 140.08 100.0% 238.5 52.5 84 529 83.7 44277 35% 70 140.08 140.08 100.0% 238.5 47.5 111 605 110.7 66974 46% 70 140.08 140.08 100.0% 238.5 42.5 138 503 137.7 69263 58% 70 140.08 140.08 100.0% 238.5 37.5 165 761 164.7 125337 69% 70 140.08 140.08 100.0% 238.5 32.5 192 593 191.7 113678 80% 70 140.08 140.08 100.0% 238.5 27.5 219 513 218.7 112193 92% 70 140.08 140.08 100.0% 238.5 22.5 246 263 238.5 62732 100% 70 140.08 140.08 100.0% 238.5 17.5 273 224 238.5 53430 100% 70 140.08 140.08 100.0% 238.5 12.5 300 130 238.5 31008 100% 70 140.08 140.08 100.0% 238.5 7.5 327 47 238.5 11211 100% 70 140.08 140.08 100.0% 238.5 2.5 354 18 238.5 4293 100% 749876 $ 7,499

Floor space requirements Tax & utility incentives Maintenance cost Life expectancy Life-Cycle Cost Retail Sales First Cost Energy Cost Refrigerant regulations

Commissioning Commission and Measure On average, the operating costs of a commissioned building range from 8% to 20% below that of a non-commissioned building. Source: US General Services Administration

Commissioning Benefits

Commissioning Refrigeration Commissioning Overview Preliminary (in-office) work Walking the systems (visual and audible inspections) Testing the systems Reporting the results Post-GO performance logs

Commissioning Controls and Programming Reviews Preliminary controls reviews can avert performance issues in the field. Preliminary controls reviews will ensure the optimum parameters are loaded into the system before arrival on site. Performance testing is recommended after system startup but prior to the cases being loaded with product

Commissioning Refrigeration Commissioning Why is the load profile important? Example: the original defrost schedule for this store had 85% of the load defrosting simultaneously (all three dairy cooler circuits)

Commissioning Refrigeration Commissioning Why is the load profile important? Load profile reveals system instabilities or performance issues. This store had problems with oil management, cases going into alarm three times a day and excessive compressor cycling. cycles.

Commissioning Case Temperature Balance DF 50 48 46 44 42 40 38 36 34 D10 MD SEAFD Defrosts D10 MD SEAFD - CASE TEMP 1 cut-in = 32F target = 30F cut-out = 28F 32 30 28 26 05/04 05/05 05/06 05/07 Cases that are too cold lead to excessive solenoid cycling and load instability On D10 MD SEAFD - REFRIG SOLENOID Off 0

Commissioning Case Temperature Balance DF D10 MD SEAFD 50 48 46 44 42 40 38 36 34 32 30 28 05/19 05/20 05/21 Control valves tuned to stabilize temperature and reduce solenoid cycling On Off 0

Commissioning Case Temperature Balance DF 55 50 45 D05 DELI PROMO Three cases in the lineup 40 35 cut-in = 30F target = 28F cut-out = 26F 30 25 20 05/04 05/05 05/06 05/0 On Off About 5 F spread between warmest and coldest case Coldest case drags down the average temperature, leading to excessive solenoid cycling 0

Commissioning Case Temperature Balance DF RX-300 5: RACK MTD 60 50 40 30 20 10 0 05/11 05/12 05/13 On Off 0

Commissioning Suction Temperature Logs Oil and/or liquid returns to the rack in slugs after defrost DF 60 40.04 DF RX-400 5: RACK MTD MTD COMP GROUP - SAT SUCT TEMP 1.13 D1 S. TMP - OUTPUT 50 40 30 20 10 04/21 04/22 08:31 Mon 04/20 D04 MEAT CLR - REFRIG SOLENOID On Off

Commissioning Rack Control Parameters Floating Suction range of 15 21 psig enabled February 3rd. Average suction pressure increased from 17 psig to approximately 19 psig

Commissioning Condenser Control Parameters Condensing Pressure set point changed from 200 psig to 165 psig on February 3rd.

Commissioning Impact of Programming Changes Before programming review -19 F SST = 17 PSIG R404A 89 F SDT = 200 PSIG R404A

Commissioning Impact of Programming Changes After programming changes EER increased from 7.8 to 10.2-16 F SST = 19 PSIG R404A 76 F SDT = 165 PSIG R404A

Questions and Answers Thank You!