1336 PLUS FAULT DESCRIPTIONS

Similar documents
NX Series Inverters. HVAC Pocket Programming Guide

SECTION VARIABLE FREQUENCY DRIVES

Display Group Parameters

SJ200 Series Inverter Quick Reference Guide

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

A1000 Cheat Sheet (Open Loop Vector)

ACS800. Firmware Manual ACS800 Standard Control Program 7.x

Installation and Start-up Guide. RS485 and RS232 Adapter for product type ACS 140

GPD 506/P5 Start-up Procedure and Checklist

Kelly KBS-L Brushless Motor Controller User s Manual

32VFD Variable Frequency Drives for Centrifugal Chillers

ACS800. Firmware Manual ACS800 Standard Control Program 7.x

Variable Frequency Drive For use with Block Machines

Configuring Allen-Brandly ControlLogix PLC with Moxa MGate 5105-MB-EIP. 1 Application Description Objective Goals...

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options

Permissible ambient temperature Operation Storage, transport

Kinetix 6000 Troubleshooting

MEMOBUS/Modbus Communications

Troubleshooting and Diagnostics

REGAL-BELOIT. Installation and Operation Manual. Variable Speed AC Motor Drives. Micro and PowerWash Series

Troubleshooting and Diagnostics

with Electronic Assistant

Fan Coil EC Motor Control

FlexPak 3000 Digital DC Drive Software Reference Manual Version 4.3

MAKING MODERN LIVING POSSIBLE. UniLynx Indoor User Manual. ULX 1800i ULX 3000i ULX 3600i ULX 5400i SOLAR INVERTERS

ABB general machinery drives. User s manual ACS355 drives

Pulse Width Modulated (PWM) Drives. AC Drives Using PWM Techniques

CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit

CAUTION! THE 7I29 USES VOLTAGE AND POWER LEVELS THAT REPRESENT A HAZARD TO LIFE AND LIMB.

Technical Data PLUS II Adjustable Frequency AC Drive

VEHICLE SPEED CONTROL SYSTEM

SAFETY INSTRUCTIONS WARNING

Variable Speed AC Motor Drives SM-Basic Installation and Operation Manual

ABB HVAC Drives ACH400 Vertical Electronic Bypass to ACH550 E-Bypass, 208V, 480V (R1... R4 Frame Size Drives)

TAKEDO -3VF V20 INSTRUCTION MANUAL REL. DATE T.M. Check and Approval

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

Pulse Width Modulated (PWM)

1 Application Description Objective Goals... 3

Sigma Control PC INSIDE. 97 psi 187 F R on load

IQAN MDM Operation Manual

LIFT CONTROL SYSTEMS CATALOGUE 2007

Data sheet GIOD.1 Input/output module with CAN bus. ERP no.: Data sheet GIOD.1 V_3.0

MOVFR ELECTRICAL ADJUSTMENTS. G.A.L. MFG. CORP. NEW YORK CITY U.S.A.

Meritor WABCO Pneumatic Antilock Braking System (ABS) 42.22

Allen-Bradley/Rockwell

SYSTEM 45. C R H Electronics Design

Programming Logic controllers

Number 1 in efficiency

2.1 FOR Series 15i Servo Alarm TROUBLESHOOTING 2.ALARM NUMBERS AND BRIEF DESCRIPTIONS. Alarm No. SVM PSM Description Remarks

Vario Tractors - Fault Codes. Faults. all Vario tractors Tractor / General system. EDC / EMR bus fault. Fault in ECU Programming errors in ECU.

Analog Servo Drive 25A8

Fixed - Over/Under voltage limits, ( ) U N respectivity Link selectable - 5 min or 10 min delay. Fixed limits

LG Air Conditioning - Universal Split Fault Codes Sheet. Universal Split Systems

Non-Isolated Analog Voltage/Current Output module IC695ALG704 provides four configurable voltage or current output channels. Isolated +24 VDC Power

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Operating Manual for the Electronic Built-in Interval Timer. Micro II (Countdown Timer)

Adaptive Cruise Control System Overview

11. PROTECTIVE CIRCUITS, LED INDICATORS and FAULT CONDITIONS... 15

A.3 ALARMS (SERIAL SPINDLE)

Brushless DC Motor Controller Product Specification Assembly 025F0129

Line Reactors and AC Drives

ABB machinery drives. User s manual ACS355 drives

Transmission electronic controls outline. Inputs- processing- outputs

Automatic start of a generator

Installation and User Guide

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

ABB PSPS Erich Steinmann; Generator control-2013

Service Manual Trucks

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Electronic Power Control

OPERATING MANUAL. Table of contents. 2 Phase Stepping Motor Driver 2M542. Rev. A. Introduction page 2. Specifications page 2 Timing chart page 3

DF Frequency Inverter

Specifying a Variable Frequency Drive s

VX 2400 Dimmer User's Manual

Installation & Operation Manual Dial-A-Flow Adjustable Frequency Drives

SAFETY INSTRUCTIONS WARNING

USER MANUAL ESP. Enhanced Steering Performance. R-Net

VLT 6000 HVAC. Contents

FREJA 300 Relay Testing System

Multimeter measurements on variable frequency drives using the new Fluke 289 DMM

Install the DeviceNet Module using the following procedure:

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01

Back-UPS 650 VA 120 V with AVR (BX650CI-LM)


Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

TABLE OF CONTENTS. Fig. 1 EV Pictorial Wiring Diagram 5. Section 2 Inverter Option Modules 6

Disturbance Recoder SPCR 8C27. Product Guide

Kurz Instruments Inc. Document AV Document Title: MFTB Event Code Definitions. MFT B-Series Event Codes

OWNER S MANUAL 2.5/3.0 ACS PANEL (ADVANCED CONTROL SYSTEM) 7725 Lougheed Highway Burnaby, BC V5A 4V8 Canada

ABS Flash Code (Blink Code) Instructions

Air conditioning, electrical testing

IGBT Protection in AC or BLDC Motor Drives by Toshio Takahashi

CONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING

NOTE: It is the responsibility of the installation organization to have only technically qualified personnel performing the installation.

SYSTEM 4C. C R H Electronics Design

User Manual for CH-PFC76810

3753 en /b VE/B - VE/RG Va V riable speed drives

THE INPUT/OUTPUT SYSTEM. Key Points

Siemens Standard Drives. Application Handbook

Transcription:

1336 PLUS FAULT DESCRIPTIONS Objectives Fault Descriptions BULLETIN 1336 PLUS FAULT DESCRIPTIONS GUIDE provides information to guide the user in troubleshooting the 1336 PLUS. Included is a listing and description of the various drive faults (with possible solutions, when applicable). Fault Display The LCD display is used to indicate a fault by showing a brief text statement relating to the fault (see figure below). The fault will be displayed until a drive reset is initiated. Refer to Table A for a listing and description of the various faults. Table B provides a listing of faults by number. Clearing a Fault When a fault occurs, the cause must be corrected before the fault can be cleared. After corrective action has been taken, simply cycling drive power will clear the fault. Issuing a valid Stop command will also clear a fault if the [Flt Clear Mode] parameter is set to "Disabled." In addition, a reset command can be issued anytime from a serial device (if connected). Contact Description During normal operating conditions (no faults present, drive running) the CR3 fault contacts at TB2-13 & 14 are closed, and the contacts at TB2-14 & 15 are open. When a fault occurs, the state of these contacts will change.

Auxiliary Fault The auxiliary input interlock is If Control Interface option is 02 open. installed, check connections at TB3. If option is not installed, check Main Control Board jumpers at J4 (J7 on 7.5-30 HP drives), pins 3 & 4 and 17 & 18. BGND 10ms Over Microprocessor loop fault. Occurs Replace Main Control Board. 51 if the 10ms background task has not been run in 15 ms. Diag C Lim Flt The drive output current has Check programming of [Cur Lim 36 exceeded the hardware current Trip En] parameter. Check for limit and the [Cur Lim Trip En] excess load, improper DC boost parameter was enabled. Meant to setting, DC brake volts set too high diagnose applications where hardware or other causes of excess current. current is being encountered. EE Init Read This fault occurs on power up: In order to clear the fault the default 53 - If the serial EEprom cannot be read parameters should be reset and the power successfully to restore the drive to the drive should be cycled. If it is the parameters or drive type, the problem cannot be cleared - If the checksums on the EEprom without changing the driver board. are not valid or - If the drive type stored in the EEprom is invalid. Note: This fault cannot be cleared. The condition must be corrected and power cycled. This signals a bad EEprom or a noise problem while writing to the EEprom. EE Init Value This fault signifies that one of the drive parameters If it is the drive type, then the problem 54 stored in the EEprom was out of range on power up cannot be cleared without changing the or the drive type was invalid. The parameter number driver board. In order to clear the fault the can be found in parameter 207, Fault Data. default parameters should be reset and power to the driver should be cycled. Note: This fault cannot be cleared. The condition must be corrected and the power cycled. This signals a bad EEprom or a noise problem while writing to the EEprom. EE prom Fault This fault will display when there is a problem Check all wire and cable 32 programming the serial EEprom on the Main connections to the Main Control Board. Replace Main Control Board. Fgnd 10ms Over Microprocessor loop fault. Occurs if a 10ms Replace Main Control Board. 52 interrupt is pending before the current interrupt is complete.

Ground Short Fault A current path to earth ground has Check the motor and external 13 been detected at one or more of the wiring to the drive output terminals drive output terminals. This is a hardware for a grounded condition. fault condition. The trip levels are solely determined by hardware components. (100 amps instantaneous) Ground Warning Low level ground fault present. When the Check the motor and external 57 parameter is enabled the drive will fault with wiring to the drive output terminals a small amount of ground current detected. for a grounded condition. Trip level is 2 amps for 30-50 msec. Hertz Err Fault This fault indicates that there is not 1. Check [Minimum Freq] and 29 a valid operating frequency. It can [Maximum Freq] parameters. be caused by any of the following: 2. Check [Skip Freq 1], [Skip Freq 2], 1.[Maximum Freq] is less than [Skip Freq 3] and [Skip Freq [Minimum Freq]. Band] parameters. 2. Skip frequencies and skip 3. Check for broken wires, loose bandwidth eliminate all operating connections or transducer loss at frequencies. 4-20mA input, TB2. 3. 4-20mA input signal speed reference has been lost and [4-20mA Loss Sel] is set for "Stop-Fault." Hertz Sel Fault A frequency select parameter has Reprogram [Freq Select 1 ] and/or 30 been programmed with an out of [Freq Select 2] with a correct value. range value. If problem persists, replace Main Control Board or complete drive. Loop Overrn Flt An overrun of the 2.5ms control Check all connections to the Power 23 loop has occurred. Board. Replace the board or complete drive as required. Max Retries Fault Drive unsuccessfully attempted to Check fault buffer for fault code 33 reset a fault and resume running requiring reset. Correct the cause for the programmed number of of the fault and manually clear by [Reset/Run Tries]. pressing the local Stop key or cycling the TB3 Stop input. Motor Mode Flt A fault has been detected originating from Check parameter programming. Check 24 the Control Board. This fault will occur if all connections to the Control Board. the value in the motor Mode parameter gets Replace the board or complete drive as written to an invalid value. required. Motor Stall Fault Current remained over 150% for If the motor is drawing excessive 06 more than 4 seconds. current (over 150%), the motor load is excessive and will not allow the drive to accelerate to set speed. A longer accel time or a reduced load may be required.

Neg Slope Fault Drive software detected a portion Check drive programming. 35 of the volts/hertz curve with a 1. [Maximum Voltage] parameter negative slope. must be greater than [Base Voltage]. 2. [Base Voltage] parameter must be greater than [Start Boost]. 3. If the [DC Boost Select] parameter is set to "Custom," [Base Voltage] must be greater than [Break Voltage] and [Break Voltage] must be greater than [Start Boost]. Open Pot Fault An external pot is connected and Check the external potentiometer 09 the ground lead of the pot is circuit at TB2, terminals 1, 2 and 3 disconnected creating a potential for an open circuit. drive overspeed hazard. The analog voltage level of the pot exceeds 3.9V DC. Operator Error Fault PWM frequency is set too high. 11 Frequency calculations receive an invalid number. A SCANbus TM device requests a Read or Write of a data type not supported. Overcurrent Flt Overcurrent is detected in Check for a short circuit at the 12 overcurrent hardware trip circuit. drive output or excessive load conditions at the motor. Overload Fault Internal electronic overload trip. An excessive motor load exists. It 07 must be reduced such that drive output current does not exceed the % of current set by the [Overload Current] parameter. Overtemp Fault Heat sink temperature exceeds a Check for blocked or dirty heat sink 08 predefined value of 90 C (195 F). fins. Check that the ambient temperature has not exceeded 40 C (104 F). Overvolt Fault DC bus voltage exceeded maximum Monitor the AC line for high line 05 value. voltage or transient conditions. Bus overvoltage can also be caused by motor regeneration. Extend the decel time or install dynamic brake option.

Phase U Fault A phase to ground fault has been Check the wiring between the drive 38 detected between the drive and and motor. Check motor for grounded motor in this phase. phase. The fault is checked during the power stage diagnostics (Which is after the start button is pushed, but before the accel is started) During the power stage diagnostics the drive goes out and switches on/off the IGBT s in a certain pattern and measures for excessive current. Phase V Fault A phase to ground fault has been Check the wiring between the drive 39 detected between the drive and and motor. Check motor for grounded motor in this phase. phase. The fault is checked during the power stage diagnostics (Which is after the start button is pushed, but before the accel is started) During the power stage diagnostics the drive goes out and switches on/off the IGBT s in a certain pattern and measures for excessive current. Phase W Fault A phase to ground fault has been Check the wiring between the drive 40 detected between the drive and and motor. Check motor for grounded motor in this phase. phase. The fault is checked during the power stage diagnostics (Which is after the start button is pushed, but before the accel is started) During the power stage diagnostics the drive goes out and switches on/off the IGBT s in a certain pattern and measures for excessive current. P Jump Err Flt An attempt has been made to Verify that both P Jump and Slip 37 enable both P Jump and Slip Compensation are not both Compensation. enabled. Pole Calc Fault A fault will occur if: Check parameter programming. Motor 50 1. motor rmp > 120 *motor_hertz/motor_poles or poles is calculated using Parameter 178, 2. motor rpm < 180 *motor _hertz/motor _poles or motor hertz, and Parameter 177, motor 3. motor poles < 2 or rpm. 4. motor poles > 32 Power Loss Fault DC bus voltage remained below Monitor the incoming AC line for 03 85% of nominal for longer than low voltage or line power 0.500ms. [Line Loss Fault] interruption. parameter is enabled. Power Mode Fault The internal power mode variable Check parameter programming. 26 received an incorrect value. Check all connections to the Control Board. Replace the board or complete drive as required.

Power Test Flt The internal power mode variable Check parameter programming. 46 received an incorrect value. Check all connections to the Power Board. Replace the board or complete drive as required. Precharge Fault Occurs if precharge device is open Check the precharge circuit for. 19 20ms after the end of a line loss possible IGBT failure or damage. condition or if the bus charging Replace drive. alarm remains on for 20 seconds. Precharge Open Precharge device malfunction. Check the precharge circuit. 56 Replace drive. Reprogram Fault An attempt was made to program a Reprogram parameter after drive is 48 parameter while the drive was stopped and fault is reset. running. ROM or RAM Flt Internal power-up ROM or RAM Check Language Module. Replace 68 tests have failed. Control Board or complete drive as required. Run Boost Fault An attempt has been made to set Verify that parameter has been 34 the [Run Boost] parameter to a programmed correctly. value greater than the [Start Boost] parameter. Serial Fault An active SCANbus TM adapter is Check for break in communications 10 disconnected while it possesses line. control of a local bus function. Temp Sense Open Heat sink thermistor is open Check thermistor and connections. 55 or malfunctioning. Undervolt Fault DC Bus voltage fell below the Monitor the incoming AC line for 04 minimum value (388V DC at 460V low voltage or line power AC input). [Line Loss Fault] interruption. parameter is enabled. UV Short Fault Excessive current has been Check the motor and external 41 detected between these two drive wiring to the drive output terminals output terminals. This fault is checked for a shorted condition. during the power stage diagnostics (Which is after the start button is pushed, but before the accel is started). During the power stage diagnostics the drive goes out and switches on/off the IGTB s in a certain pattern and measures for excessive current.

UW Short Fault Excessive current has been Check the motor and external 42 detected between these two drive wiring to the drive output terminals output terminals. This fault is checked for a shorted condition. during the power stage diagnostics (Which is after the start button is pushed, but before the accel is started). During the power stage diagnostics the drive goes out and switches on/off the IGTB s in a certain pattern and measures for excessive current. VW Short Fault Excessive current has been Check the motor and external 43 detected between these two drive wiring to the drive output terminals output terminals. This fault is checked for a shorted condition. during the power stage diagnostics (Which is after the start button is pushed, but before the accel is started). During the power stage diagnostics the drive goes out and switches on/off the IGTB s in a certain pattern and measures for excessive current. Xsistr Desat Flt One or more of the output 47 transistors has gone into desaturation.

Fault # Display Name Fault Description 02 Auxiliary Fault Auxiliary Input 03 Power Loss Fault Power Loss 04 Undervolt Fault Undervoltage 05 Overvolt Fault Overvoltage 06 Motor Stall Fault Motor Stall 07 Overload Fault Overload 08 Overtemp Fault Overtemperature 09 Open Pot Fault Open Potentiometer 10 Serial Fault Serial Communications 11 Op Error Fault Operation Error 12 Overcurrent Flt Overcurrent 13 Ground Fault Ground Fault 19 Precharge Fault Precharge 23 Loop Overrn Flt Loop Overrun 24 Motor Mode Flt Motor Mode Fault 26 Power Mode Fault Power Mode 29 Hertz Err Fault Hertz Error 30 Hertz Sel Fault Hertz Set 32 EEprom Fault EEprom 33 Max Retries Fault Maximum Retries 34 Run Boost Fault Run Boost 35 Neg Slope Fault Negative Slope 36 Diag C Lim Flt Diagnostic Current Limit 37 P Jump Err Flt P Jump Error 38 Phase U Fault Phase U Open 39 Phase V Fault Phase V Open 40 Phase W Fault Phase W Open 41 UV Short Fault UV Short 42 UW Short Fault UW Short 43 VW Short Fault VW Short 46 Power Test Flt Power Fault 47 Xsistr Desat Flt Transistor Desaturation 48 Reprogram Fault Reprogram Fault 50 Pole Calc Fault Motor Poles Fault 51 BGND 10ms Over Microprocessor Loop Fault 52 FGND 10ms Over Microprocessor Loop Fault 53 EE Init Read EEprom Fault 54 EE Init Value EEprom Fault 55 Temp Sense Open Thermistor Open Fault 56 Precharge Open Precharge Circuit Fault 57 Ground Warning Ground Fault Warning 68 ROM or RAM Flt ROM or RAM Internal Memory Fault