Generator Loading, Harmonics Monitoring and Mitigating Analysis in a Water Treatment Plant



Similar documents
Product Data Bulletin

Power System Harmonic Fundamental Considerations: Tips and Tools for Reducing Harmonic Distortion in Electronic Drive Applications

Line Reactors and AC Drives

The Facts About Harmonics and Power Factor. Power Quality: Harmonics & Power Factor Correction

Power System Harmonics

VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY

Introduction. Harmonics and IEEE 519 Page 1 of 19

LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE

Harmonics in your electrical system

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

EXTENDING THE LIFE OF POWER FACTOR CAPACITORS

DESIGNING MODERN ELECTRICAL SYSTEMS WITH TRANSFORMERS THAT INHERENTLY REDUCE HARMONIC DISTORTION IN A PC-RICH ENVIRONMENT

Interpreting IEEE Std 519 and Meeting its Harmonic Limits in VFD Applications

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION

EET272 Worksheet Week 9

Harmonic Distortion and Variable Frequency Drives

Power Quality Issues, Impacts, and Mitigation for Industrial Customers

UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES

Advantages of 6-Pulse VFD with Lineator AUHF vs Active Front End (AFE) Drives

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

Modeling and Analysis of DC Link Bus Capacitor and Inductor Heating Effect on AC Drives (Part I)

Considering the effects of UPS operation with leading power factor loads

APPLICATION OF IEEE STD HARMONIC LIMITS

Standards of Power Quality with reference to the Code of Practice for Energy Efficiency of Electrical Installations

Harmonic components: electrical network polluters. LV and MV networks are becoming increasingly polluted by current and voltage harmonics. Harmonics a

Typical Data Requirements Data Required for Power System Evaluation

FREQUENCY CONTROLLED AC MOTOR DRIVE

Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka

Triplen Harmonics Mitigation 3 Phase Four-Wire Electrical Distribution System Using Wye- Zig-Zag Transformers

Specifying a Variable Frequency Drive s

Circuits with inductors and alternating currents. Chapter 20 #45, 46, 47, 49

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

Three phase circuits

Fundamentals of Power Electronics. Robert W. Erickson University of Colorado, Boulder

Power Quality Standards for Electric Service

APPLICATION OF IEEE STD HARMONIC LIMITS

Survey of Harmonics Measurements in Electrical Distribution System of a Technical Institution

Modified Cascaded Five Level Multilevel Inverter Using Hybrid Pulse Width Modulation

Neutral Currents in Three Phase Wye Systems

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Diode Applications. by Kenneth A. Kuhn Sept. 1, This note illustrates some common applications of diodes.

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS

Power Quality. Voltage Sag Ride-through Mitigation in Sequence by Increasing Cost

Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

Power supply output voltages are dropping with each

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS

Paralleling Power Sources Which Share a Common Neutral

98% Efficient Single-Stage AC/DC Converter Topologies

INTRODUCTION TO HARMONIC ASSESSMENT IN POWER SYSTEMS

Understanding Variable Speed Drives

Simulation and Analysis of PWM Inverter Fed Induction Motor Drive

High Voltage Power Supplies for Analytical Instrumentation

Design a Phase Interleaving PFC Buck Boost Converter to Improve the Power Factor

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

A Low Cost Power Quality and Energy Savings Laboratory for Undergraduate Education and Research

How To Understand And Understand The Theory Of Electricity

Relationship between large subject matter areas

How To Wire A Three Phase, Single Phase, Wye Transformer

Power Quality Analysis and Evaluation at Water Pumping Station Supplied by Medium Voltage

Modelling, Simulation and Performance Analysis of A Variable Frequency Drive in Speed Control Of Induction Motor

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

VOLTAGE REGULATOR AND PARALLEL OPERATION

BSNL TTA Question Paper-Instruments and Measurement Specialization 2007

LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

Analysis of AC-DC Converter Based on Power Factor and THD

Pierre Archambault, PEng. VP Engineering Power Survey International Inc. 16 September 2009

Survey of Harmonics Measurements in Electrical Distribution Systems

Module Title: Electrotechnology for Mech L7

Conducted EMI filter design for SMPS

Current and Temperature Ratings

415V DISTRIBUTION FOR GREEN DATA CENTERS

Power Supplies. 1.0 Power Supply Basics. Module

POWER FACTOR CORRECTION

PWM Motor Drives and EMC in installations and systems

Analysis of Space Vector Pulse Width Modulation VSI Induction Motor on various conditions

DATA CENTER POWER SYSTEM HARMONICS: AN OVERVIEW OF EFFECTS ON DATA CENTER EFFICIENCY AND RELIABILITY

System Standard For the Installation of New Loads

Voltage Unbalance and Motors

Practical Overview of Mine Power System Harmonics

Electromagnetic Compatibility (EMC) Low-Frequency Standards. Standards on Low-Frequency Emission: IEC

ECONOMIC AND ELECTRICAL BENEFITS OF HARMONIC REDUCTION METHODS IN COMMERCIAL FACILITIES

Data Bulletin Variable Frequency Drives and Short-Circuit Current Ratings

Iron Powder Cores for Switchmode Power Supply Inductors. by: Jim Cox

Design and Simulation of Soft Switched Converter Fed DC Servo Drive

Basics of Electricity

7-41 POWER FACTOR CORRECTION

Chapter 11. Inductors ISU EE. C.Y. Lee

Control Development and Modeling for Flexible DC Grids in Modelica

415V DISTRIBUTION FOR GREEN DATA CENTERS

EMC STANDARDS STANDARDS AND STANDARD MAKING BODIES. International. International Electrotechnical Commission (IEC)

The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY

Short Circuit Current Calculations

The following table shows approximate percentage wise the

PHASE CONVERSION TECHNOLOGY OVERVIEW

HVAC Applications. VFD considerations for HVAC systems...

Current Ripple Factor of a Buck Converter

any electrical system depends upon knowledge, preventive maintenance and subsequently the test equipment used to monitor that system.

Evaluating AC Current Sensor Options for Power Delivery Systems

Transcription:

Generator Loading, Harmonics Monitoring and Mitigating Analysis in a Water Treatment Plant Eddie Jones, PE; Larry Ray, PE; Tim Shuter, PE; Square D Engineering Services Abstract Water treatment plants are often equipped with variable-frequency drives, ozone generators, and other loads that produce harmonic distortion. These facilities are also equipped, in many cases, with emergency standby generators required to operate critical electrical loads during extended electric utility outages. One such facility, a reverseosmosis desalination plant located on the United States coast, was concerned about the ability of its 938-kVA standby generator to operate reliably in the presence of harmonic distortion injected by large VFD s serving pump motors. Subsequent harmonic measurements compared distortion levels on both utility and generator sources, and engineering analysis offered harmonic mitigating techniques indicated by the measured harmonic levels. Electric System Utility source 2 kva 6% Z T1 VFD1 MF1 Open transition transfer switch 2 A 3-section QED Switchboard T2 T3 R1 R2 Onsite Genset 76 kw synch 938 kva Standby rated VFD2 VFD3 VFDTP1 VFDTP2 MF2 MF3 Circuit Monitor Key: T1-3: 27 kva dry-type isolation transformers; 46/46-V, 5.3% Z at 17 C R1, R2: Line reactors, 3% Z at 6 hp VFD1-3: 25-hp 6-pulse PWM VFDTP1, VFDTP2: 6-hp, 6-pulse PWM MF1-3: Drive output (motor) filters HPP1-3: 25-hp vertical suction water pumps TP1, TP2: 6-hp pumps HPP1 HPP2 HPP3 TP1 TP2 Summary of Results Load measurements indicated that the onsite standby generator was loaded to about 53% of its rated capacity under the load conditions that existed at the time. Load levels peaked at 43 kw and 431 kva during the test. Key power system parameters, including voltage regulation and unbalance, and current unbalance, were within acceptable limits during the test on both electric utility and generator sources. Harmonic distortion levels measured during the test did not cause noticeable operating problems for any of the plant equipment. Harmonic voltage distortion at the 48-V bus peaked at about 6.3% at highest load on the electric utility, and about 1.5% at highest load on the generator. Square D Engineering Services 1

Recommendations While harmonic distortion levels did not cause noticeable operating problems for the facility loads, harmonic reduction techniques should be considered in order to maximize equipment life and system reliability. IEEE Standard 519-1992 harmonic limits are being exceeded when operating on the standby generator. Bypassing one of the existing isolation transformers serving a 25-hp drive may achieve some beneficial effects due to increased harmonic cancellation of 5 th and 7 th current components, but this measure should be considered temporary. The better solution is to replace one delta/wye isolation transformer with a delta/zig-zag transformer to improve cancellation while maintaining attenuation effects. The best solution is to install an active harmonic filter at the service entrance. Onsite power monitoring should be installed to track performance of desalination facility in harmonic distortion, voltage quality, disturbances, and costs. Monitoring Results Summary Testing was performed at the line (source) side of the Square D QED switchboard serving the desalination facility. Testing was performed with a PowerLogic CM4T Portable Circuit Monitor, capable of measuring over 2 power system parameters. Harmonic distortion measurements were taken at a sampling rate of 512 points per cycle, to provide accuracy to the 25 th harmonic. Average During Load Test 7 Three 25 hp, two 6 hp 6 Three 25 hp, one 6 hp Three 25 hp, two 6 hp Three 25 hp, one 6 hp Average 3 Phase RMS 5 4 3 2 Three 25 hp VFD Two 25 hp VFD One 25 hp VFD Lighting and HVAC Three 25 hp VFD Two 25 hp VFD One 25 hp VFD 1 Lighting Only; Transfer to Generator 13:3 14: 14:3 15: 15:3 Average RMS current during the test shows the effects of various machines operating. unbalance was acceptable during the test, about 2% without the drives operating (lighting and HVAC only), and less than 5% with drives operating. Square D Engineering Services 2

RMS During Load Test 495 Three 25 hp, two 6 hp Three 25 hp, two 6 hp 49 VOLTAGE (PHASE TO PHASE) 485 48 Lighting and HVAC Lighting Only; Transfer to Generator 475 47 13:3 14: 14:3 15: 15:3 levels were slightly lower on the generator source, but both utility and generator sources were able to maintain acceptable steady state voltage (1% to 13% of 48 V) for the entire duration of the testing. unbalance was likewise within acceptable limits, less than 1%. Real and Total Power Demand During Load Test 5 45 Three 25 hp, two 6 hp Three 25 hp, two 6 hp Real (kw) & Total (kva) Demand 4 35 3 25 2 15 1 Lighting and HVAC Total Power, kva Real Power, kw 5 Lighting Only; Transfer to Generator 13:3 14: 14:3 15: 15:3 Real and total power demand trends on one-minute intervals during the test. Note that the 938-kVA-rated generator is about 5% loaded during peak operation. Square D Engineering Services 3

Power Factor During Load Test 1.9.8 Lighting and HVAC Three 25 hp, two 6 hp Three 25 hp, two 6 hp.7 Power Factor (Lagging).6.5.4 Lighting Only; Transfer to Generator.3.2.1 13:3 14: 14:3 15: 15:3 Power factor during the load test. Note that power factor is lowest during times of lightest load and is high when all drives are operating. This makes it difficult to utilize conventional harmonic filters to reduce harmonics on this circuit due to their inherent power factor improvement characteristics. Harmonic Distortion During Load Test 2 18 THD or TDD, % 16 14 12 1 8 6 4 Lighting and HVAC Three 25 hp, one 6 hp Three 25 hp VFD Distortion Distortion Three 25 hp, two 6 hp Three 25 hp VFD Lighting Only; Transfer to Generator Three 25 hp, one 6 hp Three 25 hp, two 6 hp 2 13:3 14: 14:3 15: 15:3 Harmonic distortion levels during testing. distortion peaked at about 6.5% on the utility source and about 1% on the generator source. Note that current distortion drops when 6 hp drives are operated with 25 hp drives. This is due to the cancellation effects of the combination of delta-wye transformers and line reactors. Total Demand Distortion (TDD) is based on IL of 9 A, or 8% of the generator rating of 1129 A. Square D Engineering Services 4

Harmonic Analysis Summary Square D performed harmonic simulations to estimate the reduction in harmonic current that could be achieved by the following modifications. Note that the Existing Harmonic Cancellation section shows that some harmonic cancellation is already being achieved when 25-hp and 6-hp drives are operated at the same time. The other techniques that were considered include: Bypass one existing delta-wye isolation transformer serving a 25-hp drive to increase cancellation of 5 th and 7 th harmonics (short-term measure); Replace one existing delta-wye isolation transformer serving a 25-hp drive with a delta/zig-zag-wound transformer to increase cancellation of 5 th and 7 th currents, and to maintain the beneficial effects of harmonic attenuation; Install a passive harmonic filter at the 48-V main to remove harmonics injected by the drives. Install an active harmonic filter at the 48-V main. Existing Harmonic Cancellation Harmonic Shows Effects of Cancellation 6 Amperes, RMS 5 4 3 2 Despite increase in total rms current when all drives are operating......5th and 7th harmonic currents show effects of cancellation from mix of delta-wye transformers (25 hp drives) and line reactors (6 hp drives) Base Case Worst Case All Drives 1 Total 5th 7th 11th 13th Harmonic Note that existing system of delta-wye transformers and line reactors serving the facility s drives benefits from some cancellation of 5 th and 7 th harmonic currents. The system required about 27% and 16% less current at 5 th and 7 th harmonics, respectively, despite a 19% increase in total rms current. Worst Case occurs when only the 25-hp drives are operating. Square D Engineering Services 5

Harmonic Reduction/Mitigation Analysis Replace One Isolation Transformer Bypassing one of the existing three isolation transformers serving a 25-hp drive seems to have a beneficial effect on the amount of harmonic current distortion at the facility. As shown in the following summary, cancellation effects can be improved to further reduce 5 th and 7 th harmonic currents by bypassing one transformer and allowing its 5 th and 7 th harmonic currents to be unchanged. Once these currents are added to the other one or two 25-hp drive currents, additional cancellation occurs. This technique, however, should be considered only for temporary improvement until more effective means are installed. Harmonic: <11 11-17 17-23 Measured Worst Case 1.6% 3.4% 1.5% All Drives 7.9% 3.4% 1.5% Simulated w/o isol xfmr 6.5% 2.% 1.1% Total Demand Distortion, I TDD, based on I L =9 A (8% of generator rating of 1129 A) A better technique is to replace one isolation transformer instead of bypassing it with a harmonic mitigating transformer of similar impedance. This modification would provide both cancellation effects (harmonic currents are not phase-shifted through delta/zig-zag-wound transformers) and attenuation effects. At this point, however, the simple computer model breaks down, perhaps due to a resonance between the drive capacitance and the line reactor that may or may not be real. The model predicts a further reduction in 5 th and 11 th currents to about 5.8%, but shows an increase in 11 th and 13 th currents over the w/o isol xfmr case that cannot be fully explained. Other Techniques Two other options were considered. The first option that was considered but is not recommended is the addition of a 5 th harmonic filter at the 48-V main. This option is not practical because passive harmonic filters of this type also increase fundamental power factor. Since power factor at the facility is already high (94%) at full load, the system cannot tolerate much parasitic capacitance without putting the facility into a leading power factor. The best option that should be considered if further harmonic current reduction is desired is an active filter. Active filters measure the amount of harmonic current required by the load and inject current 18 out of phase with that current. This technique reduces the harmonic distortion levels considerably and is often used where stringent harmonic limits are applied. How Much Harmonic Distortion Is Too Much? IEEE Guidelines Drives and other facility loads operated without disruption during the May 7 testing, so why consider harmonic reduction? Since the adverse effects of harmonics may be manifested over an extended time period, it is difficult to determine the economic attractiveness of reducing harmonic distortion. The Institute of Electrical and Electronics Engineers developed the Recommended Practices and Requirements for Harmonic Control in Electric Power Systems, IEEE Standard 519-1992, to offer guidelines on this question. While this standard was developed primarily as a recommended practice for electric utilities and their customers, not as an equipment or facility standard, it can be used to develop some guidelines. Square D Engineering Services 6

Harmonic: <11 11-17 17-23 IEEE "Limit" 4.% 2.% 1.5% Measured Worst Case 11% 3.4% 1.5% All Drives 7.9% 3.4% 1.5% Simulated w/o isol xfmr 6.5% 2.% 1.1% IEEE 519-1992 is often used as a guide for assessing existing harmonic current levels inside a facility even though that is not its primary purpose. This table shows the harmonic limits from Table 1-3 of the Standard typically imposed on power generation equipment. Note that these limits were exceeded during the onsite measurements. As before, Measured and Simulated I TDD figures on based on 8% of the generator full-load amperage. Square D Engineering Services 7

and Waveforms Baseline No Drives Operating 4 3 2 1-1 -2-3 -4. 2.5 5. 7.5 1. 12.5 15. 2 15 1 5-5 -1-15 Phase A. 2.5 5. 7.5 1. 12.5 15. 4 3 2 1-1 -2-3 -4. 2.5 5. 7.5 1. 12.5 15. 15 1 5-5 -1-15 Phase A. 2.5 5. 7.5 1. 12.5 15. Worst Case Three 25-hp Drives Operating at 83% of Rated Load 4 3 2 1-1 -2-3 -4. 2.5 5. 7.5 1. 12.5 15. 4 3 2 1-1 -2-3 -4. 2.5 5. 7.5 1. 12.5 15. 75 5 25-25 -5-75 75 5 25 - -25-5 -75 Phase A. 2.5 5. 7.5 1. 12.5 15. Phase A. 2.5 5. 7.5 1. 12.5 15. Square D Engineering Services 8

All Drives Operating (Three 25 hp, Two 6 hp) 4 3 2 1-1 -2-3 -4. 2.5 5. 7.5 1. 12.5 15. 4 3 2 1-1 -2-3 -4. 2.5 5. 7.5 1. 12.5 15. 75 5 25-25 -5-75 1 75 5 25-25 -5-75 Phase A. 2.5 5. 7.5 1. 12.5 15. Phase A. 2.5 5. 7.5 1. 12.5 15. Square D Engineering Services 9

Harmonic Distortion Fundamentals Introduction Electronic or non-linear loads, such as variable frequency and dc motor drives, computers, and automation equipment, draw current from the power system that is not sinusoidal. The resulting non-linear current may be expressed as a series of sinusoidal waves with frequencies equal to integer multiples of the 6 Hz system frequency. The individual high-frequency waves are referred to as harmonics the 3 rd harmonic is equal to 3 times the system frequency (i.e., 18 Hz), the 5 th harmonic has a frequency of 5 x 6 Hz = 3 Hz, etc. Harmonic currents are undesirable because they are an additional source of thermal stress on various types of electric equipment, reducing the current-carrying capability of conductors and transformers. Harmonic currents also interact with line impedance, causing the system voltage to become distorted. When equipment such as capacitors or motors are served with a distorted system voltage, significant harmonic currents may flow, effectively reducing the lifetime of such equipment. When power factor correction capacitors are installed in a facility that contains harmonic-producing loads, the plant electrical system should be evaluated to ensure that no resonant conditions are created that could cause excessive harmonic voltage or current levels within the facility. Parallel resonance occurs when the installed capacitance interacts with the existing power system to create a high impedance at some resonant frequency greater than the 6 Hz system frequency. As a result, harmonic currents near the resonant frequency are amplified, in turn producing harmonic voltage levels higher than would normally be expected. Cancellation Effects Harmonic cancellation is an effective means of reducing harmonic distortion, especially among three-phase drives. Cancellation works best when pairs of drives of similar size are operating at similar loading on the same bus. Cancellation is achieved by serving one of the drives from a delta-wye transformer, and the other by a delta-delta transformer or simple line reactor. Some cancellation can also be achieved by using a combination of delta-wye transformer and no inductive device, as has been modeled for Dare County. Cancellation is achieved because 5 th and 7 th harmonic frequency current components are phase-shifted by 3 in a delta-wye transformer. When these phase-shifted currents are combined with the unchanged currents passing through line reactors or delta-delta transformers, significant cancellation can occur. 48 Volt Bus ASD ASD Harmonic cancellation can be achieved on similar size adjustable-speed drives (ASD) operating at similar load levels. Source: IEEE Standard 519a, Draft Application Guide. Attenuation Effects Harmonic distortion can be reduced by adding impedance, usually in the form of an isolation transformer or line reactor, between the harmonic load and its source. Inductive impedance serves to limit the amount of higher Square D Engineering Services 1

frequency currents that the harmonic load can inject into the system. Of course, there is a limit to the amount of impedance that can be inserted into the system without affecting performance and operation of the harmonic load. Input Distortion as a Function of Choke Inductor Size 8.% 7.% Input Distortion (%) 6.% 5.% 4.% 3.% 2.% 1.%.% % 1% 2% 3% 4% 5% Choke Inductor (% on Drive Base) Reduction in harmonic currents can also be achieved by attenuation. This chart shows the typical drop in current distortion for line reactors (inductors) of various impedances. Harmonic Mitigating Transformers Harmonic Mitigating Transformers, or HMT s, use phase shifting, electromagnetic flux, and source impedance to help reduce the effects of harmonics in electrical distribution systems. These devices provide the beneficial effects of harmonic cancellation and harmonic attenuation, as described above, in order to improve reliability of power systems serving variable-frequency drives. These transformers can be supplied with either delta/wye windings that provide 3 phase shift for 5 th and 7 th harmonics, or delta/zig-zag windings that do not provide phase shifting. System Modeling A computer simulation of the power system was performed using the SKM Hi_Wave computer program. The model of the system, complied from data collected by the Power Logic monitoring along with information gained from inspection of equipment at the site, depicts the major loads and sources. Information about the utility system was derived based on load measurements taken during the onsite visit. Square D Engineering Services 11