Advantages of 6-Pulse VFD with Lineator AUHF vs Active Front End (AFE) Drives
|
|
|
- Hubert Cain
- 9 years ago
- Views:
Transcription
1 White Paper: AUHF-WP001-A1 August 20, 2015 Advantages of 6-Pulse VFD with Lineator AUHF vs Active Front End (AFE) Drives Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2015 Mirus International Inc. 31 Sun Pac Blvd., Brampton, Ontario, Canada L6S 5P6. All Rights Reserved.
2 INTRODUCTION Active Front End (AFE) Drive manufacturers will claim that their technology provides the best solution for treatment of harmonics associated with variable frequency drives (VFDs). They are quick to point out benefits over standard 6-Pulse VFDs equipped with diode bridge rectifiers such as, reduced line current harmonics, improved power factor and inherent regenerative capabilities. But they will hide the fact that current harmonics are much higher when measured above the 50 th and that very serious problems can result from the introduction of these higher frequency harmonics. Also, they will downplay a substantial loss in efficiency due to the increased losses in the input IGBTs. The reality is: 1. AFE s are not the best solution for a low harmonic VFD. 2. A properly designed Wide Spectrum Passive Filter, such as the Lineator AUHF, can outperform AFE especially when harmonics up to the 100 th are taken into consideration. 3. AFE s generate high frequency harmonics which can have more serious consequences than low frequency harmonics. As a passive device, Lineator AUHF cannot introduce high frequency harmonics and will, in fact, help reduce them when they are present. 4. If there is a mixture of 6-Pulse and AFE Drives on the same switchboard, the ripple in voltage from the AFE Drive can raise the DC bus voltage in the 6-Pulse VFDs creating overvoltage conditions. 5. Although an active solution, AFE s still require input passive filters (LCL and EMI/RFI filters) to control switching frequency harmonics and to attenuate ripple in the mains side voltage and current. 6. LCL and EMI/RFI filters are more likely to resonate with the power system at rectifier harmonic frequencies (ie. 5 th, 7 th, 11 th, etc.) than the Lineator AUHF. Also under lightly loaded conditions, the reactive power of the LCL capacitors can cause over-excitation of generators. 7. AFE s generate significant levels of ground leakage current which can cause inadvertent ground fault trips and failure of sensitive equipment. 8. AFE losses are significantly higher and efficiencies much lower than a 6-Pulse VFD with Lineator AUHF. AFE TOPOLOGY VS LINEATOR/6-PULSE VFD Fig. 1a shows a typical AFE drive topology. The problems associated with the operation of AFE rectifiers are related to the converter design characteristics, switching frequency and interaction with the power system. You will note that ahead of the input bridge is a passive LCL filter. The function of this filter is to reduce the switching frequency harmonics introduced by the IGBTs. All AFE manufacturers, however, include LCL filters that are only minimally effective because a more effective filter would be much more expensive and physically larger. In fact, this passive filter would very likely be larger and more expensive than the Lineator AUHF that provides equivalent current harmonic mitigation on a simple 6-Pulse VFD (Fig 1b). Both topologies have an input passive filter but the Lineator/6-Pulse VFD topology is much simpler, more reliable and less expensive. Fig. 1a: AFE Drive topology with LCL filter Fig. 1b: 6-Pulse Drive topology with Lineator AUHF Page 2 of 9
3 AFE INTRODUCES HIGH FREQUENCY HARMONICS In order to reduce input current harmonics, AFE Drives use IGBTs instead of a diode bridge rectifier. Current harmonics can be controlled through the switching action of the IGBTs but in so doing, switching frequency harmonics are introduced. Fig. 2 shows various measurements taken at a Paper Mill equipped with AFE Drives, by the authors of a paper on Practical Problems Associated with the Operation of ASDs Based on Active Front End Converters in Power Distribution Systems [1]. They compare Ph-to-Gnd voltages and input currents while operating the AFE Drives as simple 6-Pulse Rectifiers and in full AFE operation. Both operations show Ph-to-Gnd voltage with high frequency components but during AFE operation these distortions are substantially worse. Input current measurements show much lower levels of low frequency harmonics than in 6-Pulse operation but the high frequency ripple is very obvious in the waveform and the spectrum reflects this ripple with higher bars around the 50 th. With a band of harmonics near the 50 th, the IGBTs on these Drives would be switching at around 2-3 khz. With higher switching frequencies, the harmonic band would move out to higher harmonic orders. In many cases, these are well above the 50 th where almost all power quality analyzers do not measure. Despite AFE Drive manufacturers efforts to ignore them, these higher frequency harmonics do certainly exist and most definitely can wreak havoc with connected equipment. These failures can be very difficult to diagnose even for trained power quality professionals. Operating as a 6-Pulse Rectifier Drive Operating as an Active Front-End Drive Ph-to-Gnd Voltage Waveform Ph-to-Gnd Voltage Spectrum Input Current Waveform Input Current Spectrum Fig. 2: Variable Frequency Drive Voltage and Current Waveforms and Spectrums for an AFE Drive in a Paper Mill [1] Page 3 of 9
4 When AFE Drives are used on marine vessels with weak generator supplies, this problem can become even worse. The American Bureau of Shipping (ABS) has acknowledged this in several locations in Section 13 of its Guidance Notes on Control of Harmonics in Electrical Power Systems, such as: iii) Total harmonic current distortion (Ithd), harmonic current spectrum up to 50 th harmonic (or up to 100 th for equipment with active front ends ) and total magnitude of total harmonic current per unit, per circuit and per installation at rated load, as applicable. [2] Fig. 3 shows frequency spectrums of the voltage at the Bridge Distribution Panel of a catamaran equipped with Main and Propulsion AFE Drives [3]. Measurements were taken over three frequency bands up to 50 th harmonic, 50 th to 10 khz and 10 khz to 50 khz. Although the voltage harmonics were very low in the lower frequency range (VTHD = 1.68%), they were very high in the frequency range above the 50 th (VTHD = 8.14%) with a band around 3450 Hz (69 th harmonic) produced by the AFE Drives operating at a 3.6 khz switching frequency [3]. Most power quality analyzers that only measure up to the 50 th harmonic would not have highlighted these high distortion levels. These higher frequency harmonics will undoubtedly cause problems with connected equipment such as standard AC 6-Pulse VFDs, including those manufactured by the same supplier as the AFE Drives. The following statement is from the Practical Problems paper sited earlier. From the power distribution point of view, the AFE rectifier operates as a current source, and as such injects high frequency current harmonics into the grid. If ASDs that use diode-based rectifiers (standard ASD) are connected to the same ac grid, the high frequency current components are pushed into their dc bus. This is due to the fact that they offer a low impedance path to these high frequency current components (due to the dc link capacitor presence), overloading the respective converter. Moreover, if the standard ASD is operating at light load, its dc bus voltage will tend to increase until the converter shuts down, hopefully by means of the dc link over voltage protection. [1] a) Up to 50 th harmonic (VTHD = 1.68%) b) 50 th harmonic to 10 khz (VTHD = 8.14%) c) 10 khz to 50 khz (VTHD = 0.92%) d) Summary of VTHD at various frequency bands Fig 3: Voltage harmonic spectrum of a Marine Vessel with Main and Auxiliary Propulsion AFE Drives [3] Page 4 of 9
5 The authors of [1] also noted that the high speed IGBT switching action of AFE Drives introduces ground leakage currents (common-mode) that can cause inadvertent operation of ground fault protection equipment. Fig. 4 shows the neutral-to-ground voltage and currents of an AFE Drive running in both 6-Pulse operation and AFE operation. High frequency common-mode noise increases substantially while in AFE operation. Operating as a 6-Pulse Rectifier Drive Operating as an Active Front-End Drive N-to-Gnd Voltage N-to-Gnd Current Fig. 4: Variable Frequency Drive Neutral-to-Ground Voltage and Current for an AFE Drive in a Paper Mill [1] LINEATOR AUHF MATCHES AFE IN REDUCTION OF LOW FREQUENCY HARMONICS (UP TO 50 TH ) WITHOUT INTRODUCING HIGH FREQUENCY HARMONICS Lineator AUHF is a series connected, wide spectrum, passive harmonic filter designed to eliminate harmonics generated by 3-phase, 6-Pulse variable frequency drives. It performs as well as an Active Front End Drive in reducing harmonics in the low frequency range (up to 50 th harmonics) while substantially outperforming AFE in the high frequency range. Lineator will provide some reduction in high frequency harmonics while the AFE Drive actually introduces these more damaging harmonics into the power system as described earlier. The Lineator AUHF consists of a reactor with multiple windings on a common core and a relatively small capacitor bank (Fig. 5). This design exploits the mutual coupling between the windings to improve harmonic mitigation performance, making it far superior to conventional passive filter solutions. To prevent importation of upstream harmonics, the resonant frequency, as seen from the input terminals, is near the 4 th harmonic, comfortably below the predominant harmonics of 3-phase rectifiers. One key advantage of the unique reactor design is that it allows for the use of a significantly smaller capacitor bank (< 15% reactive power as a percent of the full load rating). This reduces voltage boost and reactive power at no load to ensure compatibility with Fig. 5: Lineator AUHF Wide Spectrum Passive Filter Schematic generators. All other passive harmonic filter solutions introduce higher capacitive reactive power at light loads (typically 30% to 40%). Even the LCL filters on AFE Drives have higher capacitive reactance than the Lineator AUHF. The filter is connected in series between the main supply and the drive. Current Total Harmonic Distortion (ITHD) is typically reduced to < 6% (a < 5% ITDD version is available) when applied to a 6-pulse AC PWM drive regardless of whether the drive is equipped with an AC or DC reactor or no reactor at all. Page 5 of 9
6 Lineators can be applied to AC drives with diode or SCR precharge input rectifiers ranging in size from 5HP/4kW to 3500HP/2600kW. They can be applied to single or multiple drives but only drive loads should be connected as the filter is designed specifically for rectifier operation. The filter can usually be retrofitted to existing drives without the requirement for drive modifications, whether for single drive or for multiple drive applications. A model is also available for operation on fully controlled SCR bridges, as used in DC Drives. Figures 6 and 7 provide typical performance results measured in the Mirus Harmonics & Energy Lab on a Lineator AUHF. They show voltage and current waveforms and spectrums at the input to the Lineator measured up to the 500 th harmonic using an ION 7650 Power Quality Analyzer. Current Total Harmonic Distortion (ITHD) is only 5.12% even when all harmonics up to the 500 th are included. Clearly noticeable is that, unlike the AFE Drive, there are extremely low levels of harmonic currents past the 50 th. Voltage Total Harmonic Distortion (VTHD), including all harmonics up to the 500 th, is only 2.54%. This is well below the 5% maximum recommended by IEEE Std 519. Again, the harmonics above the 50 th are virtually non existent, while for the AFE Drive, these were the highest harmonics present. Fig. 6: Input Current Waveform and Spectrum for 200HP, 480V Lineator AUHF Fig. 7: Input Voltage Waveform and Spectrum for 200HP, 480V Lineator AUHF Page 6 of 9
7 LINEATOR AUHF's DESIGN PROTECTS AGAINST POWER SYSTEM RESONANCE As a series connected passive filter, the Lineator s combined inductance and capacitance presents a resonant frequency to the upstream power system. To prevent inadvertent resonance with the power system at a common characteristic harmonic frequency, the input resonant frequency is designed near the 4 th harmonic to be comfortably below the 5 th and other 6-Pulse rectifier harmonics. Fig. 8a and 8b show a simple power system 1-Line and its equivalent diagram. Fig. 8c shows the reactance curves of the Lineator AUHF and the resonance point which occurs where these curves intersect. Since power systems are inherently inductive (unless installed Power Factor Correction capacitors are overcompensating a) Simple Power System 1-Line b) Equivalent Diagram c) Filter Reactance Curves and Resonance Point Fig 8: Lineator AUHF and Power System Resonance d) Shift of Resonance Point due to Inductive Reactance of Power System which should always be avoided), the inductance curve will shift upwards moving the resonant frequency lower and further away from characteristic harmonics (Fig. 8d). The passive LCL and EMI/RFI filters required by AFE Drives, on the otherhand, are always tuned at a frequency above the 5 th harmonic. The added inductive reactance of the power system will then lower the overall resonant frequency. When the resultant frequency matches a predominant harmonic on the power system, resonance will occur with its serious consequences. Therefore, the AFE Drive is much more susceptible to power system resonance than the Lineator AUHF. AFE HAS HIGHER LOSSES RESULTING IN LOWER EFFICIENCY Although the introduction of high frequency harmonics should in itself be enough justification to avoid the use of AFE Drives that do not have sufficient input passive filtering, there are many other reasons why the Lineator AUHF combined with a simple 6-Pulse VFD is a better solution. One significant reason is the higher losses and lower efficiency resulting from the operation of the input IGBT rectifier of the AFE. Tables 1 and 2 show a major electrical manufacturer s technical data for their AFE and 6-Pulse Drives, respectively. Table 3 provides a comparison of electrical losses and efficiency using the power loss statistics of a 75 kw (100 HP) and 400 kw (500 HP) Drive from these tables. With the losses of a Lineator AUHF added to the 6-Pulse VFD, this combination is still 1.7% more efficient than the AFE Drive. It is important to note that the stated AFE losses are for operation at the lowest IGBT switching frequencies. Losses increase with higher switching rates, further widening the efficiency gap. Page 7 of 9
8 Table 1: Technical Data for AFE Drives of a Major Drive Manufacturer [7] Table 2: Technical Data for 6-Pulse VFDs of the same Drive Manufacturer [8][9] VFD Rating VFD Losses AUHF Total Losses Type Efficiency Difference (kw) (kw) Losses (kw) (kw) AFE Drive % 75 6-P with Lineator % 1.7% AFE Drive % P with Lineator % 1.7% Table 3: Efficiency Comparison AFE vs 6-P VFD with Lineator Page 8 of 9
9 This difference in efficiency can result in very substantial savings in energy and operating costs. The following example on a 400kW VFD calculates the annual savings when using the 6-P with Lineator vs an AFE Drive: Assumptions: L = 400 kk VFD load (motor rating) L %aaa = 0.7 Average %Load (assumes 70%) t = 8760 h/yy Operating time (assumes 24/7 operation) E = 0.12 $ kkh Energy cost (assumes $0.12/kWh) G = Efficiency %Gain (1.7% from Table 3) Where: CostSavings/year = L L %aaa t E G = = 5004 $ yy Therefore, by using a Lineator and 6-pulse VFD under the conditions above, an additional cost savings of approximately $5,004 per year can be expected, in comparison to using an AFE Drive. CONCLUSION AND SUMMARY AFE Drive technology is not the best solution for a low harmonic variable frequency drive despite claims by their manufacturers. It is true that they reduce the low frequency harmonics introduced by a VFD, but they do so with very significant negative consequences. These include (i) introduction of high levels of high frequency harmonics, (ii) an input passive LCL filter that performs poorly and can resonate with the power system, (iii) higher levels of common-mode ground leakage current, (iv) much higher losses, (v) increased complexity which reduces reliability and (vi) significantly higher costs. A much better solution is the combination of a Lineator AUHF Wide Spectrum Filter with a simple 6-Pulse VFD. This package meets the most severe requirements for harmonic reduction without the negative consequences of AFE technology. Key advantages are no introduction of high frequency harmonics, compatibility with the power system (including resistance to resonance and low capacitive reactance for generators), higher efficiencies, improved reliability and both lower installed and operating costs. References: [1] Luis Moran, Jose Espinoza, Mauricio Ortiz, Jose Rodriguez, Juan Dixon, Practical Problems Associated with the Operation of ASDs Based on Active Front End Converters in Power Distribution Systems, IEEE Transactions on Industrial Applications, 2004 [2] Guidance Notes on the Control of Harmonics in Electrical Power Systems, American Bureau of Shipping, May 2006 [3] Mariusz Szweda, Tomasz Tarasiuk, An assessment of distortions of supply voltage waveform in All-Electric Ship Power Network Case Study, 9 th International Conference, Electrical Power Quality and Utilization, Barcelona, Oct [4] Janusz Mindykowski, Tomasz Tarasiuk, Mariusz Szweda, Ian C Evans, Electric Power Quality Measurements on an All- Electric Ship with AC Active Front End Propulsion Drives, PRS Technical Report No. 68, Feb [5] Ian C Evans, AFEs: Not the Only Answer for Tackling Harmonics, Letter to the Editor, Drives & Controls magazine, Nov/Dec 2007 [6] Ian C Evans, Using Active Front End Drives Substance or Spin, World Pumps magazine, July 2008 [7] Active Front End SIMOVERT MASTERDRIVES, Siemens Automation & Drives, MK.MC.30MAST WS11013 [8] SINAMICS G120P, SINAMICS DRIVES Answers for industry, Siemens Automation & Drives, A5E B AA [9] SINAMICS G130 Drive Converter Chassis Units, SINAMICS DRIVES Answers for industry, Siemens Automation & Drives, E86060-D4001-A510-C Page 9 of 9
HOW HARMONICS HAVE CONTRIBUTED TO MANY POWER FACTOR MISCONCEPTIONS
White Paper: MIRUS-TP003-A January 15, 2014 HOW HARMONICS HAVE CONTRIBUTED TO MANY POWER FACTOR MISCONCEPTIONS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc.
Meeting Harmonic Limits on Marine Vessels
Meeting Harmonic Limits on Marine Vessels I. C. Evans, A. H. Hoevenaars, P.Eng, Member, IEEE Abstract Recent advances in power electronic drive converters have led to an increased use of this technology
The Facts About Harmonics and Power Factor. Power Quality: Harmonics & Power Factor Correction
The Facts About Harmonics and Power Factor Power Quality: Harmonics & Power Factor Correction 1 Agenda I. Harmonic Basics II. Harmonic Mitigation Methods III. Active Harmonic Filters IV. Applications V.
Variable Frequency Drives - a Comparison of VSI versus LCI Systems
Variable Frequency Drives - a Comparison of VSI versus LCI Systems Introduction TMEIC is a leader in the innovative design and manufacture of large ac variable f requency drive systems. TMEIC has been
Line Reactors and AC Drives
Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences
Interpreting IEEE Std 519 and Meeting its Harmonic Limits in VFD Applications
Interpreting IEEE Std 519 and Meeting its Harmonic Limits in VFD Applications Copyright Material IEEE Paper No. PCIC-2003-15 Tony Hoevenaars, P. Eng. Kurt LeDoux, P.E. Matt Colosino Member IEEE Member,
Product Data Bulletin
Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system
415V DISTRIBUTION FOR GREEN DATA CENTERS
White Paper: HMRP-WP001-A1 October 1, 2010 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2005 Mirus International
415V DISTRIBUTION FOR GREEN DATA CENTERS
White Paper: HMRP-WP001-A5 June 5, 2012 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2012 Mirus International
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS
VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY
VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY Carrier Corporation Syracuse, New York October 2005 TABLE OF CONTENTS INTRODUCTION..........................2
Paralleling Power Sources Which Share a Common Neutral
Paralleling Power Sources Which Share a Common Neutral By: Tony Hoevenaars, P.E., President & CEO, Mirus International, Inc. Mike McGraw, President, NSOEM, Inc. When paralleling power sources that share
Harmonic Distortion and Variable Frequency Drives
Harmonic Distortion and Variable Frequency Drives Definitions Variable Frequency Drives (VFDs); sometimes referred to as variable speed drives. Harmonic Distortion is a measure of the amount of deviation
Specifying a Variable Frequency Drive s
Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable
Properties of electrical signals
DC Voltage Component (Average voltage) Properties of electrical signals v(t) = V DC + v ac (t) V DC is the voltage value displayed on a DC voltmeter Triangular waveform DC component Half-wave rectifier
Chapter 4. LLC Resonant Converter
Chapter 4 LLC Resonant Converter 4.1 Introduction In previous chapters, the trends and technical challenges for front end DC/DC converter were discussed. High power density, high efficiency and high power
Modeling and Analysis of DC Link Bus Capacitor and Inductor Heating Effect on AC Drives (Part I)
00-00-//$0.00 (c) IEEE IEEE Industry Application Society Annual Meeting New Orleans, Louisiana, October -, Modeling and Analysis of DC Link Bus Capacitor and Inductor Heating Effect on AC Drives (Part
UNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS
Page 1 UNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS By Henry Ott Consultants Livingston, NJ 07039 (973) 992-1793 www.hottconsultants.com [email protected] Page 2 THE BASIC
Power Quality Issues, Impacts, and Mitigation for Industrial Customers
Power Quality Issues, Impacts, and Mitigation for Industrial Customers By Kevin Olikara, Power and Energy Management Products Rockwell Automation, Inc. Now, more than ever, electronic equipment and computing
Introduction. Harmonics and IEEE 519 Page 1 of 19
Introduction In an ideal power system, the voltage supplied to customer equipment, and the resulting load current are perfect sine waves. In practice, however, conditions are never ideal, so these waveforms
POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS
A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS By: Robert G. Ellis, P. Eng., Rockwell Automation Medium Voltage Business CONTENTS INTRODUCTION...
SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION
SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION Please read and understand the product instruction manual before installing, servicing or operating Yaskawa products. Technical content
DC-DC Converter Basics
Page 1 of 16 Free Downloads / Design Tips / Java Calculators / App. Notes / Tutorials / Newsletter / Discussion / Components Database / Library / Power Links / Software / Technical Articles / On-Line Textbook
Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies
Soonwook Hong, Ph. D. Michael Zuercher Martinson Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies 1. Introduction PV inverters use semiconductor devices to transform the
Design a Phase Interleaving PFC Buck Boost Converter to Improve the Power Factor
International Journal of Innovation and Scientific Research ISSN 2351-8014 Vol. 11 No. 2 Nov. 2014, pp. 445-449 2014 Innovative Space of Scientific Research Journals http://www.ijisr.issr-journals.org/
UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES
UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES WHITE PAPER: TW0062 36 Newburgh Road Hackettstown, NJ 07840 Feb 2009 Alan Gobbi About the Author Alan Gobbi Alan Gobbi
Rotating Machinery Diagnostics & Instrumentation Solutions for Maintenance That Matters www.mbesi.com
13 Aberdeen Way Elgin, SC 29045 Cell (803) 427-0791 VFD Fundamentals & Troubleshooting 19-Feb-2010 By: Timothy S. Irwin, P.E. Sr. Engineer [email protected] Rotating Machinery Diagnostics & Instrumentation
EET272 Worksheet Week 9
EET272 Worksheet Week 9 answer questions 1-5 in preparation for discussion for the quiz on Monday. Finish the rest of the questions for discussion in class on Wednesday. Question 1 Questions AC s are becoming
98% Efficient Single-Stage AC/DC Converter Topologies
16 POWER CONVERTERS www.teslaco.com 98% Efficient Single-Stage AC/DC Converter Topologies A new Hybrid Switching Method is introduced in this article which for the first time makes possible AC/DC power
7-41 POWER FACTOR CORRECTION
POWER FTOR CORRECTION INTRODUCTION Modern electronic equipment can create noise that will cause problems with other equipment on the same supply system. To reduce system disturbances it is therefore essential
Philosophy of Topology and Components Selection for Cost and Performance in Automotive Converters.
Philosophy of Topology and Components Selection for Cost and Performance in Automotive Converters. Alexander Isurin ( [email protected] ) Alexander Cook ([email protected] ) Vanner inc. USA Abstract- This
The full wave rectifier consists of two diodes and a resister as shown in Figure
The Full-Wave Rectifier The full wave rectifier consists of two diodes and a resister as shown in Figure The transformer has a centre-tapped secondary winding. This secondary winding has a lead attached
FREQUENCY CONTROLLED AC MOTOR DRIVE
FREQUENCY CONTROLLED AC MOTOR DRIVE 1.0 Features of Standard AC Motors The squirrel cage induction motor is the electrical motor motor type most widely used in industry. This leading position results mainly
An Efficient AC/DC Converter with Power Factor Correction
An Efficient AC/DC Converter with Power Factor Correction Suja C Rajappan 1, K. Sarabose 2, Neetha John 3 1,3 PG Scholar, Sri Shakthi Institute of Engineering & Technology, L&T Bypass Road, Coimbatore-62,
Power supply output voltages are dropping with each
DESIGNER S SERIES Second-Stage LC Filter Design First Inductor by Dr. Ray Ridley First Capacitor Power supply output voltages are dropping with each new generation of Integrated Circuits (ICs). Anticipated
HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM
Technical Note No.3 March 2000 HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM This Technical Note discusses harmonic distortion, its causes and adverse effects, what levels are unacceptable and how
High Voltage Power Supplies for Analytical Instrumentation
ABSTRACT High Voltage Power Supplies for Analytical Instrumentation by Cliff Scapellati Power supply requirements for Analytical Instrumentation are as varied as the applications themselves. Power supply
INTRODUCTION TO HARMONIC ASSESSMENT IN POWER SYSTEMS
INTRODUCTION TO HARMONIC ASSESSMENT IN POWER SYSTEMS LIST OF CONTENT 1. INTRODUCTION... 1 2. HARMONIC VOLTAGE ASSESSMENT REQUIREMENT IN THE UK... 2 3. THE ASSESSMENT... 2 3.1. SYSTEM MODELLING...3 3.2.
Power supplies. EE328 Power Electronics Assoc. Prof. Dr. Mutlu BOZTEPE Ege University, Dept. of E&E
Power supplies EE328 Power Electronics Assoc. Prof. Dr. Mutlu BOZTEPE Ege University, Dept. of E&E EE328 POWER ELECTRONICS Outline of lecture Introduction to power supplies Modelling a power transformer
Modelling, Simulation and Performance Analysis of A Variable Frequency Drive in Speed Control Of Induction Motor
International Journal of Engineering Inventions e-issn: 78-7461, p-issn: 319-6491 Volume 3, Issue 5 (December 013) PP: 36-41 Modelling, Simulation and Performance Analysis of A Variable Frequency Drive
Control Development and Modeling for Flexible DC Grids in Modelica
Control Development and Modeling for Flexible DC Grids in Modelica Andreas Olenmark 1 Jens Sloth 2 Anna Johnsson 3 Carl Wilhelmsson 3 Jörgen Svensson 4 1 One Nordic AB, Sweden, [email protected].
LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE
LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE Karl M. Hink, Executive Vice President Originally presented at the Power Quality 99 Conference ABSTRACT Motor protection
AN ULTRA-CHEAP GRID CONNECTED INVERTER FOR SMALL SCALE GRID CONNECTION
AN ULTRA-CHEAP GRID CONNECTED INVERTER FOR SMALL SCALE GRID CONNECTION Pramod Ghimire 1, Dr. Alan R. Wood 2 1 ME Candidate Email: [email protected] 2 Senior Lecturer: Canterbury University
Discover the power of e-learning! The Quick Guide to AC Variable Frequency
The Quick Guide to AC Variable Frequency This ebook is meant as an easy guide to any electrical or electronic engineer or technician, who would like to know how modern ac variable frequency drives work.
DESIGNING MODERN ELECTRICAL SYSTEMS WITH TRANSFORMERS THAT INHERENTLY REDUCE HARMONIC DISTORTION IN A PC-RICH ENVIRONMENT
DESIGNING MODERN ELECTRICAL SYSTEMS WITH TRANSFORMERS THAT INHERENTLY REDUCE HARMONIC DISTORTION IN A PC-RICH ENVIRONMENT by Philip J. A. Ling, P.Eng. Cyril J. Eldridge, B. Sc. POWERSMITHS INTERNATIONAL
Analysis of AC-DC Converter Based on Power Factor and THD
Website: www.ijetae.com (SSN 50-459, SO 900:008 Certified Journal, Volume 3, ssue, February 03) Analysis of AC-DC Converter Based on Power Factor and THD Shiney.S.Varghese, Sincy George Department of Electrical
Neutral Currents in Three Phase Wye Systems
POWER SYSTEMS ENGINEERING DATA PUBLISHED BY SQUARE D, OSHKOSH, WISCONSIN Subject: Neutral Currents in Three Phase Wye Systems by Robert Arthur Square D Company Oshkosh, Wisconsin (414) 46-80 and R. A.
DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS
DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS by Gunnar Asplund, Kjell Eriksson, Hongbo Jiang, Johan Lindberg, Rolf Pålsson, Kjell Svensson ABB Power Systems AB Sweden SUMMARY Voltage Source Converters
Experiment 2 Diode Applications: Rectifiers
ECE 3550 - Practicum Fall 2007 Experiment 2 Diode Applications: Rectifiers Objectives 1. To investigate the characteristics of half-wave and full-wave rectifier circuits. 2. To recognize the usefulness
Planar versus conventional transformer
Planar versus conventional transformer Majid Dadafshar, Principal Engineer Gerard Healy, Field Application Engineer Pulse, a Technitrol Company Power Division Usually the first step on any power supply
Pulse Width Modulated (PWM)
Control Technologies Manual PWM AC Drives Revision 1.0 Pulse Width Modulated (PWM) Figure 1.8 shows a block diagram of the power conversion unit in a PWM drive. In this type of drive, a diode bridge rectifier
WIND TURBINE TECHNOLOGY
Module 2.2-2 WIND TURBINE TECHNOLOGY Electrical System Gerhard J. Gerdes Workshop on Renewable Energies November 14-25, 2005 Nadi, Republic of the Fiji Islands Contents Module 2.2 Types of generator systems
DC/DC power modules basics
DC/DC power modules basics Design Note 024 Ericsson Power Modules General Abstract This design note covers basic considerations for the use of on-board switch mode DC/DC power modules, also commonly known
Pulse Width Modulated (PWM) Drives. AC Drives Using PWM Techniques
Drives AC Drives Using PWM Techniques Power Conversion Unit The block diagram below shows the power conversion unit in Pulse Width Modulated (PWM) drives. In this type of drive, a diode bridge rectifier
PWM Motor Drives and EMC in installations and systems
PWM Motor Drives and EMC in installations and systems Mart Coenen PWM Motor Drives and EMC in installations and systems Intro Problem definition Why What How Problem solutions Application results Conclusions
COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS
COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS Afshin LASHKAR ARA Azad University of Dezfoul - Iran [email protected] Seyed Ali NABAVI NIAKI University of Mazandaran
VICOR WHITE PAPER. The Sine Amplitude Converter Topology Provides Superior Efficiency and Power Density in Intermediate Bus Architecture Applications
The Sine Amplitude Converter Topology Provides Superior Efficiency and Power Density in Intermediate Bus Architecture Applications Maurizio Salato, Applications Engineering, Vicor Corporation Contents
Offshore Platform Powered With New Electrical Motor Drive System
Offshore Platform Powered With New Electrical Motor Drive System Authors: Jan O. Lamell, M.Sc E.E. ABB Automation Technologies Presenters: Thomas Johansson, M.Sc E.E. ABB Automation Technologies Timothy
What Is Regeneration?
What Is Regeneration? Braking / Regeneration Manual Regeneration Overview Revision 1.0 When the rotor of an induction motor turns slower than the speed set by the applied frequency, the motor is transforming
Diode Applications. by Kenneth A. Kuhn Sept. 1, 2008. This note illustrates some common applications of diodes.
by Kenneth A. Kuhn Sept. 1, 2008 This note illustrates some common applications of diodes. Power supply applications A common application for diodes is converting AC to DC. Although half-wave rectification
APPLICATIONS FOR MOTOR CURRENT SIGNATURE ANALYSIS
APPLICATIONS FOR MOTOR CURRENT SIGNATURE ANALYSIS An ALL-TEST Pro White Paper By Howard W Penrose, Ph.D. General Manager ALL-TEST Pro A Division of BJM Corp 123 Spencer Plain Rd Old Saybrook, CT 06475
How To Improve Power Quality
Power Quality Improvement Of Three Phase Four Wire Distribution System Using VSC With A Zig-Zag Transformer Sajith Shaik *, I.Raghavendar ** *(Department of Electrical Engineering, Teegala Krishna Reddy
Power Supplies. 1.0 Power Supply Basics. www.learnabout-electronics.org. Module
Module 1 www.learnabout-electronics.org Power Supplies 1.0 Power Supply Basics What you ll learn in Module 1 Section 1.0 Power Supply Basics. Basic functions of a power supply. Safety aspects of working
Multimeter measurements on variable frequency drives using the new Fluke 289 DMM
Multimeter measurements on variable frequency drives using the new Fluke 289 DMM Application Note Editor s note: For similar instructions using the Fluke 87V DMM, reference Fluke article 12345. In the
Variable Frequency Drives and Energy Savings
Variable Frequency Drives and Energy Savings It s more than just fan and pump applications www.sea.siemens.com by: Stephen Prachyl www.usa.siemens.com/energysavings When discussing energy savings and variable
Parameter Settings for PowerFlex Drives Using Sine Wave Filters, dv/dt Filters, and Adjustable Voltage
Application Technique Parameter Settings for PowerFlex Drives Using Sine Wave Filters, dv/dt Filters, and Adjustable Voltage PowerFlex 750-Series, 700, and 700VC AC Drives Topic Page About This Document
Typical Data Requirements Data Required for Power System Evaluation
Summary 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com [email protected] Harmonic Filter & Power Capacitor Bank Application Studies This document describes NEPSI
Case Studies in On-Line Measurement of PD in Motors Fed by Voltage Source PWM Drives
Case Studies in On-Line Measurement of PD in Motors Fed by Voltage Source PWM Drives G.C. Stone, I. Culbert, H.G. Sedding Qualitrol-Iris Power Mississauga, Ontario, Canada Abstract On-line partial discharge
MICRO HYDRO POWER PLANT WITH INDUCTION GENERATOR SUPPLYING SINGLE PHASE LOADS
MICRO HYDRO POWER PLANT WITH INDUCTION GENERATOR SUPPLYING SINGLE PHASE LOADS C.P. ION 1 C. MARINESCU 1 Abstract: This paper presents a new method to supply single-phase loads using a three-phase induction
DC GROUND FAULT DETECTION PROVIDED FOR UNINTERRUPTIBLE POWER SUPPLIES
DC GROUND FAULT DETECTION PROVIDED FOR UNINTERRUPTIBLE POWER SUPPLIES Edward P. Rafter, P. E. Principal Tier IV Consulting Group Lee s Summit, Missouri 64064 INTRODUCTION There are concerns among owners
APPLICATION NOTE TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION. Abstract.
TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION Abstract This application note describes the four quadrant mode of operation of a linear AC Power
CONTROL OF HARMONICS IN ELECTRICAL POWER SYSTEMS
GUIDANCE NOTES ON CONTROL OF HARMONICS IN ELECTRICAL POWER SYSTEMS MAY 006 American Bureau of Shipping Incorporated by Act of Legislature of the State of New York 186 Copyright 006 American Bureau of Shipping
Data Bulletin Variable Frequency Drives and Short-Circuit Current Ratings
Data Bulletin Variable Frequency Drives and Short-Circuit Current Ratings 8800DB1203 03/2013 Retain for future use. Introduction Short-circuit current s (SCCRs) for variable frequency drives (VFDs) is
The design and performance of Static Var Compensators for particle accelerators
CERN-ACC-2015-0104 [email protected] The design and performance of Static Var Compensators for particle accelerators Karsten Kahle, Francisco R. Blánquez, Charles-Mathieu Genton CERN, Geneva, Switzerland,
Harmonic components: electrical network polluters. LV and MV networks are becoming increasingly polluted by current and voltage harmonics. Harmonics a
Harmonics and transformers Harmonic component filter Harmonic components: electrical network polluters. LV and MV networks are becoming increasingly polluted by current and voltage harmonics. Harmonics
ANADOLU UNIVERSITY DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING
ANADOLU UNIVERSITY DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EEM 102 INTRODUCTION TO ELECTRICAL ENGINEERING EXPERIMENT 9: DIODES AND DC POWER SUPPLY OBJECTIVE: To observe how a diode functions
Bridgeless PFC Implementation Using One Cycle Control Technique
Bridgeless PFC Implementation Using One Cycle Control Technique Bing Lu Center for Power Electronics Systems Virginia Polytechnic Institute and State University 674 Whittemore Hall Blacksburg, VA 24061
Module 11: Conducted Emissions
Module 11: Conducted Emissions 11.1 Overview The term conducted emissions refers to the mechanism that enables electromagnetic energy to be created in an electronic device and coupled to its AC power cord.
Fundamentals of Power Electronics. Robert W. Erickson University of Colorado, Boulder
Robert W. Erickson University of Colorado, Boulder 1 1.1. Introduction to power processing 1.2. Some applications of power electronics 1.3. Elements of power electronics Summary of the course 2 1.1 Introduction
Power System Harmonic Fundamental Considerations: Tips and Tools for Reducing Harmonic Distortion in Electronic Drive Applications
Power System Harmonic Fundamental Considerations: Tips and Tools for Reducing Harmonic Distortion in Electronic Drive Applications October 2011/AT313 by Larry Ray, P.E. Louis Hapeshis, P.E. Make the most
Harmonic Reduction and Load Balancing of Three Phase Four Wire DSTATCOM using Three Leg VSC and a Zig Zag Transformer
IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 05, 2015 ISSN (online): 2321-0613 Harmonic Reduction and Load Balancing of Three Phase Four Wire DSTATCOM using Three Leg
Understanding Variable Speed Drives
Understanding Variable Speed Drives April 1, 1997 Solomon S. Turkel, Solomon S. When applied properly, the variable frequency drive (VFD) is the most effective motor controller in the industry today. Modern
DIODE CIRCUITS LABORATORY. Fig. 8.1a Fig 8.1b
DIODE CIRCUITS LABORATORY A solid state diode consists of a junction of either dissimilar semiconductors (pn junction diode) or a metal and a semiconductor (Schottky barrier diode). Regardless of the type,
A Design of DC/DC Converter of Photovoltaic Generation System for Streetcars
Journal of International Council on Electrical Engineering Vol. 3, No. 2, pp.164~168, 2013 http://dx.doi.org/10.5370/jicee.2013.3.2.164 A Design of DC/DC Converter of Photovoltaic Generation System for
Simulation of Ungrounded Shipboard Power Systems in PSpice
Simulation of Ungrounded Shipboard Power Systems in PSpice Haibo Zhang IEEE Student Member Karen L.Butler IEEE Member Power System Automation Lab Electrical Engineering Department Texas A&M University
WHITE PAPER. DC Motors Explained. DC Motors Explained: White Paper, Title Page
DC Motors Explained: White Paper, Title Page DC Motors Explained By Joe Kimbrell, Product Manager, Drives, Motors & Motion, AutomationDirect DC Motors Explained: White Paper, pg. 2 How many types of DC
The New Radio Receiver Building Handbook
The New Radio Receiver Building Handbook And Related Radio Subjects Vacuum Tube and Transistor Shortwave Radio Receivers by Lyle Russell Williams, BSEE KC5KBG Copyright 2006 by Lyle Russell Williams All
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02
Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka
Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka S S B Udugampala, V Vijayarajah, N T L W Vithanawasam, W M S C Weerasinghe, Supervised by: Eng J Karunanayake, Dr. K T M U Hemapala
HVDC 2000 a new generation of high-voltage DC converter stations
HVDC 2000 a new generation of high-voltage DC converter stations Improved performance and robustness, shorter lead times and faster delivery, plus reduced maintenance needs, were the development goals
Modeling and Simulation of a Novel Switched Reluctance Motor Drive System with Power Factor Improvement
American Journal of Applied Sciences 3 (1): 1649-1654, 2006 ISSN 1546-9239 2006 Science Publications Modeling and Simulation of a Novel Switched Reluctance Motor Drive System with Power Factor Improvement
Equipment: Power Supply, DAI, Transformer (8341), Variable resistance (8311), Variable inductance (8321), Variable capacitance (8331)
Lab 5: Single-phase transformer operations. Objective: to examine the design of single-phase transformers; to study the voltage and current ratios of transformers; to study the voltage regulation of the
Practical Overview of Mine Power System Harmonics
Practical Overview of Mine Harmonics Western Mining Electrical Association Tucson, Arizona November 1999 11/20/2003 10:26:46 PM wmea-harmonic-1.ppt Slide 1 Harmonic Topics What are harmonics? Where do
5. MINIMIZATION OF CONDUCTED EMI. Chapter Five. switch-mode power supply decrease approximately linearly with the increase of the switching
5. MINIMIZATION OF CONDUCTED EMI Chapter Five MINIMIZATION OF CONDUCTED EMI The sizes of the energy storage elements (transformers, inductors, and capacitors) in a switch-mode power supply decrease approximately
Power Quality Standards for Electric Service
Power Quality Standards for Electric Service Effective June 1, 2008 A transition period will exist from June 1 through December 31, 2008 in which installations may be approved and connected as long as
Output Ripple and Noise Measurement Methods for Ericsson Power Modules
Output Ripple and Noise Measurement Methods for Ericsson Power Modules Design Note 022 Ericsson Power Modules Ripple and Noise Abstract There is no industry-wide standard for measuring output ripple and
Renewable Energy Grid Integration
Renewable Energy Grid Integration Jian Sun Professor and Director Grid Integration Issues Cost, Reliability & Efficiency of Grid Interface Grid Congestion, Weak Grids Variability of Renewable Production
Development of Power Supply System with Hybrid Turbocharger for Marine Application
JFE TECHNICAL REPORT No. 19 (Mar. 2014) Development of Power Supply System with Hybrid Turbocharger for Marine Application SUTO Naonori*1 MINAMI Hiroki*2 Abstract: Hybrid turbocharger is a turbocharger
Type SA-1 Generator Differential Relay
ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet 41-348.11C Effective: November 1999 Supersedes I.L. 41-348.11B, Dated August 1986 ( ) Denotes