1 HVAC Applications VFD considerations for HVAC systems... 1

2 COMMON TERMINOLOGY VFD (VARIABLE FREQUENCY DRIVES) AFC (ADJUSTABLE FREQ. CONTOLLER) ASD (ADJUSTABLE SPEED DRIVES) VSD (VARIABLE SPEED DRIVES) FREQ. DRIVE INVERTER DRIVE Inverter Duty Motors =?? = New motors meet NEMA MG 1, Part 31 = peak voltage of 1600 volts and a minimal rise time of 0.1 microseconds 2

3 Typical Large HVAC System Cooling Tower Fans Secondary Hot/Chilled Water Pumps Systems don t necessarily have all components. Supply Fan Condenser Water Pump Primary Hot/Chilled Water Pumps Return Fan 3

4 Good Retrofit Candidates Large energy cost saving possibility Large motors Poor present efficiency Flows manually throttled back Malfunctioning mechanical flow modulation Inefficient control methods High energy costs Easy retrofit 4

5 Why Flow Control? HVAC systems are designed for worst case situations. Most of the time they have excess capacity. Controlling flow Saves energy Improves occupant comfort 5

6 Methods of Flow Control Air flow Inlet guide vanes Outlet dampers Variable pitch in motion fan Adjustable speed Fluid flow Throttling valve (two-way) Bypass valve (three-way) Adjustable speed 6

7 Why Adjustable Speed? Energy savings Secondary pumping example 7

8 Energy Requirements Important Curves Pressure Setpoint Pressure F low Pump Curve Operating Point Control Curve System Curve P P 8

9 Energy Requirements Pressure Power a Flow x Pressure Flow 9

10 Energy Requirements Pressure Flow Desired Flow 10

11 Energy Requirements Two-Way Valve (Throttling) Power Pressure Flow 11

12 Energy Requirements Three-Way Valve (Bypass) Pressure Flow Power Balancing Valve 12

13 Energy Requirements Adjustable Speed Pressure Power Flow 13

14 Why Adjustable Speed? Energy savings System control Reduced maintenance Sound control 14

15 Why Adjustable Frequency Drives? High efficiency Easy retrofit Replace the existing motor starter Flexible mounting Simple control Minimum maintenance 15

16 Typical Large HVAC System Heat Rejection Section Cooling Tower Fans Chiller Condenser Water Pump 16

17 Cooling Tower & Fluid Cooler Fan Cooling Tower Fan 17

18 Cooling Tower Fan Fan Motors 18

19 Cooling Tower Fan Notes Traditional Control Methods None Poor efficiency Staging cells in multi-cell towers Poor efficiency High mechanical stress Dual-speed motors Moderate efficiency High mechanical stress 19

20 Cooling Tower Fan Notes, continued Traditional Control Methods, continued Variable pitch in motion fans Good efficiency, when functioning High maintenance, often don t function Other Concerns Wasting highly treated water Audible noise 20

21 Condenser Water Pump Cooling Tower Fan Condenser Water Pump 21

22 Condenser Water Pump Cooling Tower Pump Pump Motors 22

23 Condenser Water Pump Cooling Tower From Cooling Tower Strainer Differential Pressure Switch (Flow Proof) Motor To Chiller Pump Motors 23

24 Condenser Water Pump Notes Traditional Control Methods No active control It is important to maintain design flow for Proper cooling tower operation Proper chiller operation However the pump is often over-sized to compensate for pipe scaling later on Manually close a valve to reduce flow If the valve is closed a lot, a drive can save significant energy 24

25 Condenser Water Pump Cooling Tower Fan Chiller Condenser Water Pump 25

26 Heat Rejection Section Chiller Chillers 26

27 Chiller Notes While the chiller has a large motor, Inaccurate control can cause major problems Some chillers require constant torque Less energy savings Be sure you know its design and operation before considering retrofitting a chiller with a drive 27

28 Rooftop Units 28

29 Rooftop Units Notes Rooftop units generally don t have cooling towers and condenser water pumps They are often direct exchange (DX) heat with the outside air It can be economical to retrofit drives in the DX section 29

30 Typical Large HVAC System Chiller Secondary Hot/Chilled Water Pumps Boiler Primary Hot/Chilled Water Pumps 30

31 CHW, HW (Water Source Heat Pump Circulating & Booster) Primary Pumps Boilers or Chillers Primary Hot/Chilled Water Pump 31

32 Primary Pumps From Chillers Primary Pumps 32

33 Primary Pumps Air Separator From Chillers To Chillers Secondary Pumps Primary Pumps 33

34 Primary Pump Notes Traditional Control Methods No active control The pump is often oversized Flow is reduced by Trimming the pump s impeller Closing a pressure reducing valve When a valve significantly reduces flow, a drive can provide large energy savings 34

35 Primary Pump Notes Although some modern chillers can accept some amount of flow variation, be careful about attempting to actively control flow through either part of the chiller 35

36 Secondary Pumps Automatic valves at each coil control the flow of water to the coil. Boilers or Chillers Secondary Hot/Chilled Water Pump Primary Hot/Chilled Water Pump Variable flow in the secondary loop. Constant or Variable flow in the primary loop. 36

37 Secondary Pump Valve Motor Secondary Pump 37

38 Secondary Pump Secondary Pumps Valves Motors 38

39 Secondary Pump Notes Traditional Control Methods Valves control flow through each coil Two-way throttling valve Three-way bypass valve For proper operation, drive systems require two-way valves Therefore, retrofitting systems with threeway valves is more expensive 39

40 Secondary Pump Notes Tertiary pump systems are much like secondary pump systems Because the size of the motors is generally quite small, energy savings may also be small 40

41 Single Pump Loop Boilers or Chillers 3-Way Valve Total flow is constant. Variable flow through the coils. Constant or Variable flow through the boiler/chiller. Hot/Chilled Water Pumps 41

42 Single Pump Loop Notes Pumping systems that do not have separate primary and secondary loops present unique problems It will take significant work to convert it to a primary/secondary system Vary the flow through a chiller based manufacturers specifications Approach such systems with caution 42

43 Typical Large HVAC System Air Supply Section Supply Fan Return Fan 43

44 Air Supply Section Supply Fan Supply Fan 44

45 Air Supply Section Supply Fan 45

46 Air Supply Section Supply Fan Fans Drive Belt Motor Sheaves 46

47 Supply Fan Notes Traditional Control Methods Constant air volume systems have no direct method of reducing air flow The flow of water through the coils determines the temperature of the conditioned space Variable air volume systems use VAV boxes to restrict or redirect air when less flow is needed 47

48 Supply Fan Notes Methods of reducing fan capacity Outlet dampers Low efficiency Require maintenance Inlet guide vanes Moderate efficiency Require maintenance Variable pitch in motion fans Better efficiency Very high maintenance/costs Often multiple dampers per fan One per fan 48

49 Supply Fan Notes Old methods of reducing fan capacity Variable speed belt drives Low efficiency High maintenance Eddy current drives Low efficiency at low speeds High maintenance 49

50 Supply and Return Fans Supply Fan Return Fan 50

51 Air Supply Section Return Fan Fan Belt Drive Disconnect Switch Motor 51

52 Return Fan Notes Notes Traditional Control Methods Not controlled Controlled like the supply fan The method of providing the control signal depends on the control system A fixed amount less than supply flow A fixed difference between building and outdoor air pressure 52

53 Return Fan Notes Notes The main purpose of the return fan is to keep from over-pressurizing the building Not all systems require return fans 53

54 Examples of Some Air Supply Systems A wide variety of systems are used to control air flow Some are easy to retrofit with drives Others require more work to retrofit with drives The following are a few examples 54

55 VAV System with Fan Capacity Control The sensors and control signals for drives are already present. 55

56 Open Loop VAV System The sensors and control signals for drives are already present. 56

57 VAV System with Perimeter Terminal Reheat Static Pressure Sensor The sensors and control signals for drives are already present. 57

58 Dual Duct VAV System One drive for each fan. The sensors and controls are already in place. 58

59 VAV System with Bypass Boxes Add Static Pressure Sensor Close bypass part of VAV boxes. Add static pressure sensor to control fan. 59

60 Dual Duct System Terminal units designed for constant air flow make fan speed control less attractive. 60

61 Multi-Zone System Constant volume, multi-zone system. Requires adding VAV boxes and pressure sensors. 61

62 Terminal Reheat System Constant volume, multi-zone system. Requires adding VAV boxes and pressure sensors. 62

63 Induction Reheat System The induction units require high air velocity to function properly. 63

64 CAV Fan & Clean Room Supply Fan Air Filter Conditioned Space Pressure Sensor Supply Fan Drive

65 Garage and Tunnel Fan Vent. Fan Smoke Sensor CO Sensor Vent. Fan Drive

66 Fume Hood Fan Fan Damper Positioning Motor & Limit Switch Fume Hood Fan Drive

67 Outside Air Damper Smoke Extraction Supply Fan Conditioned Space Close this damper Return Air Damper Return Fan Reverse this fan Smoke Sensor Relief Air Damper Supply Fan Drive

68 Stairwell Pressurization Fan Pressure Sensor Fan Drive

69 Exhaust Fan Fan Pressure Sensor Fan Drive

70 Application Interfacing Operator s controls Plain language for Operation Fault display Programming Manual speed control Remote mounting Application MACROs Hand/Off/Auto control Auto OFF HAND

71 Single Motor Bypass Circuit Breaker, Bypass & Output contactors and fuses to service the drive while running Points to consider Can the system run at full speed? Drive fusing Safety interlocks Automatic bypass Run permissive circuit

72 Application Interfacing Operator s controls Bypass Single motor Multiple motor

73 PI and PID Controller (Closed Loop / Set Point) Compares the desired process variable with the set point value Proportional to the error Integral function adds errors over time Derivative function considers the rate of change of error (only for fast response systems) PID Speed Control Reference Set Point Feedback Sensor Controlled System

74 Other Considerations Environment Enclosure type NEMA 1 NEMA 12 Circulating dust Dripping non-corrosive liquid NEMA 3R Outdoor

75 Other Considerations Environment 1-50 HP: NEMA 1 & 12, & 3R Outdoors = -15 to 50ºC (5 to 122ºF) No De-rate 60 HP HP: NEMA 1 & to 40 C (5 to 104 F) Not exceed 10% 122 F

76 Harmonics What? Non-linear loads draw non-sinusoidal current from a sinusoidal line (current doesn t look like voltage): Non-incandescent lighting Computer Equipment UPS (Uninterruptible Power Supplies) Telecommunications equipment Copy machines Variable Frequency Drives Electronic/Controls for Facility Elec. Equip. / Systems, Security, HVAC / Mech. equipment Any load with a solid state AC to DC power converter 76

77 Harmonics Why worry? Harmonic Voltage Distortion Increased heating in motors and other electromagnetic equipment Noisy operation of electromagnetic equipment Malfunctioning of sensitive electronics Nuisance tripping of electronic circuit breakers Overheating of PF correction capacitors Tripping of PF protection equipment Equipment downtime Premature component failures Failed motors and capacitors 77

78 Harmonics Why worry? Harmonic Current Distortion Added heating in transformers and cables, reduces available capacity May stimulate a resonance condition Excessive voltage Shutdown / damage to electronic equipment May cause telephone or electronic interference Failed transformers, equipment Not in Compliance with CODES, STANDARDS, REGULATIONS, IEEE, GOOD DESIGN PRACTICE 78

79 Include: Reactors (Chokes) Least expensive when specified to be included with base drive package 5% impedance AC line reactors -or- DC link reactors Both types provide similar harmonic benefits Also Suppress voltage transients that can cause equipment damage Harmonic Distortion Calculations = only VFD contribution 79

80 RFI / EMI RFI = RADIO FREQ. INTERFERENCE conducted through the air EMI = ELECTROMAGNETIC INTERFERENCE conduct through AC power line EFFECTS SIMILAR TO HARMONIC DISTORTION! 80

81 RFI / EMI Hardware RFI / EMI FILTERS: WILL BE INCLUDED IN ALL VFD SIZES ACH 550: Meets EMC PRODUCT STANDARD EN FOR THE FIRST Environment restricted level BENEFIT: VFD will not interfere with other electronic equipment Other electronic equipment will not interfere with VFD 81

82 Serial Communications BAS / DDC Company Alignment BACnet ALC (Automated Logic Corp.) Andover Controls Novar American Auto-Matrix Alerton Trane Delta Controls Teletrol Tridium JCI (Johnson Controls, Inc.) Honeywell KMC LonWorks Honeywell Invensys Distech Novar TAC (formally CSI) JCI Trane Staefa Circon ModBus RTU ASI Controls KMC Reliable Controls 82

The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY

The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY PowerGate - Cost effective solutions for F 1 Horsepower Rating 001 1-40 HP (208V) 075 1-75 HP (480V) Input Voltage 2V 208-240V 4V 380-480V Disconnect

More information

HVAC Processes. Lecture 7

HVAC Processes. Lecture 7 HVAC Processes Lecture 7 Targets of Lecture General understanding about HVAC systems: Typical HVAC processes Air handling units, fan coil units, exhaust fans Typical plumbing systems Transfer pumps, sump

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 09 93 (November 2015) ----------------------------- Preparing Activity: USACE Superseding UFGS-23 09 23 (May 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

Variable Speed Drives

Variable Speed Drives Variable Speed Drives for HVAC Applications 1-75HP 208-240VAC 1.5-500HP 380-480VAC Air-Modulator cuts air-handler energy costs up to 60% Air-Modulator allows energy-efficient operation during off-peak

More information

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM AIR HANDLING UNITS... 1 CHILLERS... 2 COOLING TOWERS... 2 CLOSED LOOP COOLERS... 2 MISCELLANEOUS SUPPLY FANS...

More information

CONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING

CONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING PART 1-GENERAL 1.01 DESCRIPTION A. This specification is to cover a complete Variable Frequency motor Drive (VFD) consisting of a pulse width modulated (PWM) inverter designed for use on a standard NEMA

More information

Commissioning - Construction Documents (Page 1 of 6)

Commissioning - Construction Documents (Page 1 of 6) Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem

More information

Drives and motors. A guide to using variable-speed drives and motors in retail environments

Drives and motors. A guide to using variable-speed drives and motors in retail environments Drives and motors A guide to using variable-speed drives and motors in retail environments Improving energy efficiency and lowering the carbon footprint Retailers across the UK take their corporate responsibility

More information

Drives and motors. A guide to using variable-speed drives and motors in data centres

Drives and motors. A guide to using variable-speed drives and motors in data centres Drives motors A guide to using variable-speed drives motors in data centres The power behind the data Private public businesses, from banks to supermarkets, to telecommunications companies internet providers

More information

Unidrive M Energy Savings

Unidrive M Energy Savings Unidrive M Energy Savings Why is this important? Some Data: Money, Lots of Money >13.5m electric motors 1Hp or greater installed in US industrial process operations. Industry spends >$33b annually on electricity

More information

Yorkland Controls Ltd. Environmental Solutions www.yorkland.net Email: yorkland@yorkland.net TORONTO + MISSISSAUGA + LONDON (T) 416.661.

Yorkland Controls Ltd. Environmental Solutions www.yorkland.net Email: yorkland@yorkland.net TORONTO + MISSISSAUGA + LONDON (T) 416.661. TORONTO + MISSISSAUGA + LONDON Application Guide Variable Frequency Drives in Retrofit or New Applications Table of Contents REV2005.10 APPLICATION DESCRIPTION 1. Energy Savings with Variable Frequency

More information

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Example Retrocommissioning Measure: Opening Throttled Discharge Valves Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large

More information

VARIABLE FREQUENCY DRIVES Revised 4/30/2015 23 81 07-1 Mechanical Systems

VARIABLE FREQUENCY DRIVES Revised 4/30/2015 23 81 07-1 Mechanical Systems SECTION 23 81 07 - VARIABLE FREQUENCY DRIVES PART 1 - GENERAL 1.1 SUMMARY A. This section includes all variable frequency drives. All standard and optional features shall be included within the VFD panel

More information

Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)

Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC) Drives and motors A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC) The power behind the data Private and public businesses, from banks to

More information

VLT 6000 HVAC Series Contents

VLT 6000 HVAC Series Contents Contents Introduction to HVAC 4 Software version 4 Safety regulations 5 Warning against unintended start 5 Introduction to the Design Guide 7 Available literature 8 Fire mode 11 Star/delta starter or soft-starter

More information

Commercial & Municipal Retrofit 2015 VFD Rebate

Commercial & Municipal Retrofit 2015 VFD Rebate 2015 VFD Rebate Section A: MEMBER INFORMATION Member Name Electric Account Number Rate Number Facility Address City State Zip Code Service Location Identification Email Mailing Address (if different from

More information

32VFD Variable Frequency Drives for Centrifugal Chillers

32VFD Variable Frequency Drives for Centrifugal Chillers 32VFD 32VFD Variable Frequency Drives for Centrifugal Chillers ENERGY-SAVING CONTROL FOR CENTRIFUGAL CHILLERS Reduce energy consumption in your existing centrifugal chiller Your chiller was specified to

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

Heating, Ventilation and Air Conditioning Rebate Catalog Saving energy for a brighter future

Heating, Ventilation and Air Conditioning Rebate Catalog Saving energy for a brighter future Pacific Gas and Electric Company Energy-Efficiency s for Your Business Heating, Ventilation and Air Conditioning Catalog Saving energy for a brighter future Customers may be eligible to participate in

More information

Impact of Control System Technologies on Industrial Energy Savings

Impact of Control System Technologies on Industrial Energy Savings Impact of Control System Technologies on Industrial Energy Savings Priyam Parikh Industrial Assessment Center Texas A&M University Bryan P. Rasmussen Industrial Assessment Center Texas A&M University http://farolconsulting.com/?page_id=110

More information

Specifying a Variable Frequency Drive s

Specifying a Variable Frequency Drive s Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable

More information

Additional Benefits of VFDs In addition to energy savings and better process control, VFDs can provide other benefits:

Additional Benefits of VFDs In addition to energy savings and better process control, VFDs can provide other benefits: Variable Frequency Drives (or VFDs) are becoming almost standard part of aquatics equipment room packages. Most VFDs are fairly simple to install and operate however, they are quite complex with respect

More information

AIR COOLED CHILLER CHILLED WATER PUMP CONTROL: The chilled water pump with the lowest runtime will automatically start when the outside air temperature rises above the system enable setpoint. When the

More information

for Plans Examiners and Building Inspectors

for Plans Examiners and Building Inspectors Building Technologies Program HVAC Controls Guide for Plans Examiners and Building Inspectors September 2011 Authors: Eric Makela, PNNL James Russell, PECI Sarah Fujita, PECI Cindy Strecker, PECI Prepared

More information

Centrifugal Fans and Pumps are sized to meet the maximum

Centrifugal Fans and Pumps are sized to meet the maximum Fans and Pumps are sized to meet the maximum flow rate required by the system. System conditions frequently require reducing the flow rate. Throttling and bypass devices dampers and valves are installed

More information

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB

More information

Product Data Bulletin

Product Data Bulletin Product Data Bulletin Adjustable Frequency Drives and HVAC Systems An Application Guide September, 1994 Raleigh, NC, U.S.A. INTRODUCTION All buildings pose the same problem: how to heat or cool the air

More information

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... ..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com

More information

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same

More information

Introduction to Building Automation Systems (BAS)

Introduction to Building Automation Systems (BAS) Introduction to Building Automation Systems (BAS) Ryan R. Hoger, LEED AP 708.670.6383 ryan.hoger@tecmungo.com Building Automation Systems Centralized controls Change scheduling for multiple HVAC units

More information

Variable Air Volume - VAV

Variable Air Volume - VAV Mode Enable Sensor Options Variable Air Volume - VAV The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during occupied operation. The following options are available:

More information

Fundamentals of HVAC Control Systems

Fundamentals of HVAC Control Systems ASHRAE Hong Kong Chapter Technical Workshop Fundamentals of HVAC Control Systems 18, 19, 25, 26 April 2007 2007 ASHRAE Hong Kong Chapter Slide 1 Chapter 5 Control Diagrams and Sequences 2007 ASHRAE Hong

More information

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options

BT300 HVAC Drives Conventional Bypass (C-Bypass) Options BT300 HVAC Drives Conventional Bypass (C-Bypass) Options Description The BT300 Conventional Bypass is a companion package for the family of BT300 HVAC Drives. For information on the family of BT300 HVAC

More information

Line Reactors and AC Drives

Line Reactors and AC Drives Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences

More information

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01

UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01 GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per

More information

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,

More information

Topvex SX/C, Topvex TX/C. Air Handling Unit

Topvex SX/C, Topvex TX/C. Air Handling Unit Air Handling Unit Document in original language 131677-EN_GB 23-12-2015 A001 Contents 1 Declaration of Conformity... 1 2 Warnings... 2 3 Product information... 2 3.1 General... 2 3.2 Technical data...

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

Energy Design Resources Commissioning Plan Outline Template

Energy Design Resources Commissioning Plan Outline Template IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC is not rendering advice concerning any commission project or practices. This document is neither approved nor intended

More information

SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing

More information

3/29/2012 INTRODUCTION HVAC BASICS

3/29/2012 INTRODUCTION HVAC BASICS INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.

More information

HVAC DRIVE H300 HVAC Drive for Building Automation

HVAC DRIVE H300 HVAC Drive for Building Automation HVAC DRIVE H300 HVAC Drive for Building Automation 1.0 hp - 450 hp (0.75 kw - 336 kw) 208 V - 230 V 400 V 575 V EMERSON Leading the world in climate technologies CONSIDER IT SOLVED. Emerson s promise to

More information

1 Temperature Derating Guide

1 Temperature Derating Guide VLT HVAC Drive FC 02 Application Note Temperature Derating Guide Temperature Derating Guide.. Abstract This paper provides detailed data regarding the operation of the VLT HVAC Drive FC02 at varying ambient

More information

EnVisioneering. www.danfossdrives.com

EnVisioneering. www.danfossdrives.com EnVisioneering As a world leader in components and solutions, Danfoss meets our customers challenges through EnVisioneering. This approach expresses our views on engineering innovation, energy efficiency,

More information

DIABLO VALLEY COLLEGE CATALOG 2015-2016

DIABLO VALLEY COLLEGE CATALOG 2015-2016 HEATING, VENTILATION, AIR CONDITIONING, REFRIGERATION - HVACR Tish Young, Dean Physical Sciences and Engineering Division Physical Sciences Building, Room 263 Possible career opportunities Upon successful

More information

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT Presentation Synopsis Heating, Ventilating and Air Conditioning Building Condition Assessment Vancouver, B.C. Prepared for: EPIC Prepared by: Douglas Spratt, P.Eng Douglas Spratt & Associates Ltd. www.dspratt-associates.com

More information

Printing and Publishing Energy Savings Guide

Printing and Publishing Energy Savings Guide Printing and Publishing Energy Savings Guide Oregon printing and publishing plants face challenges of rising operating costs, environmental and other regulations, outdated equipment and customer demand

More information

Conversion From Constant Flow System To Variable Flow

Conversion From Constant Flow System To Variable Flow White Paper Conversion From Constant Flow System To Variable Flow By: Tony Egan 94.21-4/29/2010 www.armstrongintegrated.com S.A. Armstrong Limited 2010 S.A. Armstrong Limited 23 Bertrand Avenue Toronto,

More information

Sample - Existing Building Commissioning Plan

Sample - Existing Building Commissioning Plan Sample - Existing Building Commissioning Plan Version: Draft for Review Final Approved: Owner Site Address: Primary Site Contact Name and Telephone Number: Date Building Description The site consists of

More information

3466 Building Energy Management Training Systems

3466 Building Energy Management Training Systems 3466 Building Energy Management Training Systems LabVolt Series Datasheet Festo Didactic en 120 V - 60 Hz 06/2015 Table of Contents General Description 3 Courseware 3 Topic Coverage 4 List of Available

More information

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany Life Cycle Costing Analysis of Water-cooled Chillers Chillventa Nuremburg, Germany Spring 2012 Description Life Cycle Cost Analysis is a method of determining and comparing the total costs of investment

More information

1.2 Refrigerant Equipment. General

1.2 Refrigerant Equipment. General Part 1 General 1.1 Summary.1 Unless otherwise indicated, follow the standards below when specifying heating, ventilation and air conditioning (HVAC) work. These standards are not intended to restrict or

More information

Failure code manual. content

Failure code manual. content Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一

More information

Introducing Bihun Commercial Services, Inc.

Introducing Bihun Commercial Services, Inc. Introducing Bihun Commercial Services, Inc. HVAC Maintenance Building Automation Systems Control System: Repairs & Installation Experience and Innovation in HVAC Solutions Bihun Commercial Services brings

More information

SmartVFD HVAC and BYPASS

SmartVFD HVAC and BYPASS SmartVFD HVAC and BYPASS The Smart Choice for Energy Savings. Saving Energy the Smart Way Buildings consume more than 70 percent of the electricity produced in North America and roughly half of that is

More information

The Facts About Harmonics and Power Factor. Power Quality: Harmonics & Power Factor Correction

The Facts About Harmonics and Power Factor. Power Quality: Harmonics & Power Factor Correction The Facts About Harmonics and Power Factor Power Quality: Harmonics & Power Factor Correction 1 Agenda I. Harmonic Basics II. Harmonic Mitigation Methods III. Active Harmonic Filters IV. Applications V.

More information

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION Please read and understand the product instruction manual before installing, servicing or operating Yaskawa products. Technical content

More information

HEATING, VENTILATION & AIR CONDITIONING

HEATING, VENTILATION & AIR CONDITIONING HEATING, VENTILATION & AIR CONDITIONING as part of the Energy Efficiency Information Grants Program Heating and cooling can account for approximately 23 % of energy use in pubs and hotels 1. Reducing heating

More information

Building Controls MORE than a Time Clock. Building Automation is a Tool for the building to use to manage their environment

Building Controls MORE than a Time Clock. Building Automation is a Tool for the building to use to manage their environment Building Controls MORE than a Time Clock Building Automation is a Tool for the building to use to manage their environment Speaker Ken Richardson President of Island Controls Started in the Controls Business

More information

NX Series Inverters. HVAC Pocket Programming Guide

NX Series Inverters. HVAC Pocket Programming Guide NX Series Inverters HVAC Pocket Programming Guide HVAC Pocket Programming Guide HVAC Pocket Programming Guide / Contents This guide provides a single reference document for the user of NXL HVAC (product

More information

Fault codes DM1. Industrial engines DC09, DC13, DC16. Marine engines DI09, DI13, DI16 INSTALLATION MANUAL. 03:10 Issue 5.0 en-gb 1

Fault codes DM1. Industrial engines DC09, DC13, DC16. Marine engines DI09, DI13, DI16 INSTALLATION MANUAL. 03:10 Issue 5.0 en-gb 1 Fault codes DM1 Industrial engines DC09, DC13, DC16 Marine engines DI09, DI13, DI16 03:10 Issue 5.0 en-gb 1 DM1...3 Abbreviations...3 Fault type identifier...3...4 03:10 Issue 5.0 en-gb 2 DM1 DM1 Fault

More information

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building. MSV: Square Footage: 24,844 No. of Floors: 1 Year Built: 1963 Type of Use: Lounge and dining area open all night for snacks Steam Water-cooled condenser, 50-Ton York unit with a 6 cylinder-reciprocating

More information

AABC Specifications for Testing and Balancing HVAC Systems

AABC Specifications for Testing and Balancing HVAC Systems AABC Specifications for Testing and Balancing HVAC Systems The Associated Air Balance Council (AABC) Total System Balancing Specifications for HVAC Testing, Balancing and Performance Verification TOTAL

More information

14. Troubleshooting Guide

14. Troubleshooting Guide 14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include

More information

Condensing Boiler Efficiency

Condensing Boiler Efficiency Condensing Boiler Efficiency Date: July 17, 2012 PRES E NT ED BY DO N L E O NA RDI LE O N A RD I I NC. HV AC T RAI N I N G & C ON SU LT IN G Concepts 1 The current state of evolution in boiler design 2

More information

Harmonic Distortion and Variable Frequency Drives

Harmonic Distortion and Variable Frequency Drives Harmonic Distortion and Variable Frequency Drives Definitions Variable Frequency Drives (VFDs); sometimes referred to as variable speed drives. Harmonic Distortion is a measure of the amount of deviation

More information

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES

SECTION 26 29 23 VARIABLE FREQUENCY DRIVES SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02

More information

ENHANCED LABORATORY HVAC SYSTEM

ENHANCED LABORATORY HVAC SYSTEM ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of

More information

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer engineers volume 36 2 newsletter providing insights for today s hvac system designer energy-saving strategies for Water-Source Heat Pump Systems from the editor... Water-source heat pump (WSHP) systems

More information

CGC s Hybrid System Loop Control

CGC s Hybrid System Loop Control verview The CGC Group Hybrid Heat Pump System does NT operate with the same fluid loop temperatures as a conventional reversing Water Source Heat Pump system. The CGC system differs from a WSHP system

More information

vacon hvac ac drives

vacon hvac ac drives vacon hvac ac drives comfort & control in building automation 1 the smarter way to reduce co 2 emissions Heating, ventilation and air-conditioning (HVAC) is all about efficiency. Room temperatures need

More information

B.C. Buildings Corporation. Mandatory Preventive Maintenance Standard. To Meet Section 4.78 of the WCB OH & S Regulation

B.C. Buildings Corporation. Mandatory Preventive Maintenance Standard. To Meet Section 4.78 of the WCB OH & S Regulation B.C. Buildings Corporation Mandatory Preventive To Meet Section 4.78 of the WCB OH & S Regulation Prepared by: BCBC WCB-IAQ Steering Committee Mandatory Preventive TABLE OF CONTENTS Page no. INTRODUCTION...1

More information

G120P variable speed drive boost efficiency, cut costs

G120P variable speed drive boost efficiency, cut costs G120P variable speed drive boost efficiency, cut costs Intelligent, versatile controlling for fans and pumps in HVAC plants. Easy to use and easy on the environment. www.siemens.com/g120p How do you spell

More information

Using Time-of-Day Scheduling To Save Energy

Using Time-of-Day Scheduling To Save Energy The following article was published in ASHRAE Journal, May 29. Copyright 29 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes only.

More information

Low voltage AC drives. ABB drives for HVAC Committed to your comfort zone

Low voltage AC drives. ABB drives for HVAC Committed to your comfort zone Low voltage AC drives ABB drives for HVAC Committed to your comfort zone Peace of mind as standard Keeps you out of trouble EMC fi lters for building sector, class C2 (1 st environment). Meets mandatory

More information

ASTACEA4 Inspect complex/central air conditioning systems

ASTACEA4 Inspect complex/central air conditioning systems Overview This Unit covers the competences required to inspect complex/central air conditioning systems as defined by the CIBSE TM 44 Figure 1.1: Summary of system types and their component parts. The air

More information

A. The Commissioning Authority (CxA) has been contracted or will be contracted directly with the Owner for this project.

A. The Commissioning Authority (CxA) has been contracted or will be contracted directly with the Owner for this project. DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION 23 08 02 PART 1 GENERAL 1.01 AUTHORITY (CxA) A. The Commissioning Authority (CxA) has been contracted or will be contracted directly

More information

HVAC and Lighting Control Products for Open Building Automation Systems

HVAC and Lighting Control Products for Open Building Automation Systems HVAC and Lighting Control Products for Open Building Automation Systems Distech Controls offers an extensive line of feature-rich and cost effective controllers for building automation, covering HVAC

More information

CONTROL STRATEGIES FOR HVAC SYSTEMS

CONTROL STRATEGIES FOR HVAC SYSTEMS CONROL SRAEGIES FOR HVAC SYSEMS ZBIGNIEW POPIOLEK Department of Heating, Ventilation and Dust Removal echnology Silesian University of echnology, Poland 1 Definition of control: to apply a regulating influence

More information

Product Data Bulletin

Product Data Bulletin Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system

More information

Relationship between large subject matter areas

Relationship between large subject matter areas H02M APPARATUS FOR CONVERSION BETWEEN AC AND AC, BETWEEN AC AND DC, OR BETWEEN DC AND DC, AND FOR USE WITH MAINS OR SIMILAR POWER SUPPLY SYSTEMS; CONVERSION OF DC OR AC INPUT POWER INTO SURGE OUTPUT POWER;

More information

How To Clean Up A Reactor Water Cleanup

How To Clean Up A Reactor Water Cleanup General Electric Systems Technology Manual Chapter 2.8 Reactor Water Cleanup System TABLE OF CONTENTS 2.8 REACTOR CLEANUP SYSTEM... 1 2.8.1 Introduction... 2 2.8.2 System Description... 2 2.8.3 Component

More information

Power Quality. Voltage Sag Ride-through Mitigation in Sequence by Increasing Cost

Power Quality. Voltage Sag Ride-through Mitigation in Sequence by Increasing Cost Power Quality Voltage Sag Ride-through Mitigation in Sequence by Increasing Cost A voltage sag is defined as a decrease in voltage magnitude below 90% of nominal, but not a complete interruption. The typical

More information

Variable Frequency Drives and Energy Savings

Variable Frequency Drives and Energy Savings Variable Frequency Drives and Energy Savings It s more than just fan and pump applications www.sea.siemens.com by: Stephen Prachyl www.usa.siemens.com/energysavings When discussing energy savings and variable

More information

NXL Series Inverters. HVAC Inverters made simple

NXL Series Inverters. HVAC Inverters made simple NXL Series Inverters HVAC Inverters made simple Honeywell s Voice Of the Customer process unveils a range of requirements expressed by specifiers and installers, that are ideally covered by the NXL inverter

More information

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION Air Conditioning Central Heating & Cooling BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION INSTALLATION AND SERVICE MANUAL 2 PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: PHONE NUMBER: INSTALLATION

More information

ULTRA-EFFICIENT HVAC DESIGN AND CONTROL

ULTRA-EFFICIENT HVAC DESIGN AND CONTROL CASE STUDY ULTRA-EFFICIENT HVAC DESIGN AND CONTROL MAJOR HEATING, VENTILATING AND AIR- CONDITIONING REPLACEMENT AT THE COUNTY OF SAN DIEGO CRIME LAB December 30, 2005 8520 Tech Way, Suite 110 San Diego,

More information

Ener.co & Viridian Energy & Env. Using Data Loggers to Improve Chilled Water Plant Efficiency. Randy Mead, C.E.M, CMVP

Ener.co & Viridian Energy & Env. Using Data Loggers to Improve Chilled Water Plant Efficiency. Randy Mead, C.E.M, CMVP Ener.co & Viridian Energy & Env. Using Data Loggers to Improve Chilled Water Plant Efficiency Randy Mead, C.E.M, CMVP Introduction Chilled water plant efficiency refers to the total electrical energy it

More information

HVAC Preventative Maintenance Basics. Presented by Mike Crawley

HVAC Preventative Maintenance Basics. Presented by Mike Crawley HVAC Preventative Maintenance Basics Presented by Mike Crawley Air Handlers/Package Units: Coils have to be clean! The main purpose of any coil is to absorb or reject heat If coils are dirty; air flow

More information

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units

LG Air Conditioning Multi F(DX) Fault Codes Sheet. Multi Split Units Multi Split Units If there is a fault on any LG Multi unit, an Error mark is indicated on the display window of the indoor unit, wired-remote controller, and LED s of outdoor unit control board. A two

More information

Data Center. Ultra-Efficient chilled water system optimization. White paper. File No: 9.236 Date: december 03, 2015 Supersedes: new Date: new

Data Center. Ultra-Efficient chilled water system optimization. White paper. File No: 9.236 Date: december 03, 2015 Supersedes: new Date: new Data Center Ultra-Efficient chilled water system optimization White paper File No: 9.236 Date: december 03, 2015 Supersedes: new Date: new Data Center - Ultra-Efficient white paper 3 abstract The primary

More information

Drives and motors. A guide to using variable-speed drives and motors in car parks

Drives and motors. A guide to using variable-speed drives and motors in car parks Drives and motors A guide to using variable-speed drives and motors in car parks Helping car parks meet the energy and CO 2 reduction challenge In the UK, as population density increases and space becomes

More information

Discover the power of e-learning! The Quick Guide to AC Variable Frequency

Discover the power of e-learning! The Quick Guide to AC Variable Frequency The Quick Guide to AC Variable Frequency This ebook is meant as an easy guide to any electrical or electronic engineer or technician, who would like to know how modern ac variable frequency drives work.

More information

Model: DC-A2IO Advanced HVAC Controller

Model: DC-A2IO Advanced HVAC Controller Model: DC-A2IO Advanced HVAC Controller Job Name: Schedule Reference: Date: DC-A2IO Advanced HVAC Controller Package PAC-IF01 M-Net Adapter AL2-14MR-D α2 Simple Application Controller Accessories AL2-2DA

More information

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm. Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water