Instruction Bulletin. POWERLINK RS232 to 485 Converter. for use with POWERLINK G3 Systems INTRODUCTION SAFETY PRECAUTIONS CLASS A FCC STATEMENT

Similar documents
Data Bulletin. Communications Wiring for POWERLINK G3 Systems Class 1210 ABOUT THIS BULLETIN APPLICATION INTRODUCTION.

Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit

Square D Clipsal C-Bus Network Analyzer

Square D Clipsal Two-Channel DIN-Rail DALI Gateway

Wiser Panel Meter, Model Number WISERCTPM200 Installer s Guide

Comm5 Wiring Installation

PowerLogic Sub Meter Display (SMD and SMDOPN)

MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP)

FN2001-A1 Network module (SAFEDLINK) Mounting Installation

8-Port 10/100M N-Way Mini Switch

BACnet Automation Interface Module (Network Version)

SCREENLOGIC INTERFACE WIRELESS CONNECTION KIT

Application Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters

HDMI Switch USER MANUAL VS481A

8-Port HDMI Switch USER MANUAL VS0801H

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

ScreenLogic Wireless Connection Kit. Installation Guide. pool/spa control system

=============================== WARNING

FIBER OPTIC APPLICATION IN A PROFIBUS NETWORK

Planning BACnet networks

HDMI over Cat5 Video Extender with RS232 and IR Control

NOTE: It is the responsibility of the installation organization to have only technically qualified personnel performing the installation.

Fire Fighter Phone System Installation Instructions

Bluetooth HC-06 with serial port module Easy guide

XPort Universal Demo Board User Guide

When any of the following symbols appear, read the associated information carefully. Symbol Meaning Description

Paragon Explorer Lite Communication Software

Daikin Magnitude TM Chiller Unit Controller BACnet Communication Module (MS/TP, IP, Ethernet)

E2 Controller Wiring Practices Rev 4 19-APR-2010

HSG Engineering Tech Bulletin

HDMI Matrix Switch USER MANUAL VM0404H

4100U/4100ES to TFX Fire Fighter Phone System Installation Instructions

User Manual IC-485AI

PS/2 KVM Console Extender User Manual (GCE250)

EMBEDDED ACCESS CONTROL Hardware Installation Guide

OPT SERIAL TO FIBER OPTIC CONVERTER

WxGoos-1 Climate Monitor Installation Instructions Page 1. Connections. Setting an IP Address

FOSTCDR. Industrial Serial to Multimode Fiber Optic Converter PRODUCT INFORMATION B&B ELECTRONICS. Specifications Serial Technology

IMS ALARM 3 PORT RS485 EXPANSION BOX

USB/VGA Cat 5 UTP Console Extender

ADACSNET USB Control Module

User manual Compact Web PLC WP240 series IEC-line

4 Port VGA Video Audio Switch with RS232 control

Table of Contents. Creating a VC1000 Network... 3

RS485 & RS422 Basics

BLACK BOX. T1/E1 Link Extenders OCTOBER 2007 MT195A-T1 MT196A-E1

Computer Control of Satellite Antennas

DSX Master Communications

Installation instructions for Series NRX INCOM communications adapter module

BACnet Wiring Guidelines. For Price Controls MANUAL INSTALLATION

Instructions for Connecting PETROSMART EZ Control Systems To Wayne Electronic Dispensers With/Without CAT CREDIT CARD MODULES

About the HotWire Slot Standalone Shelf

Communication Setup Application Note

Manual Serial PCI Cards

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet

TCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL

Programming and Using the Courier V.Everything Modem for Remote Operation of DDF6000

Power Over Ethernet Adapters POE101

Communicate and view data from meters with one simple device

CONSOLE REMOTE I /O AC 9V

USB-RS232 Converter USB-RS422/485 Converter. User's Manual

PXL-250: Network Wiring

MechoNet TM Network Interface (MNI) Specification Submittal

FCC COMPLIANCE STATEMENT

xpico Wi-Fi Embedded Device Server Evaluation Kit Quick Start Guide

INSTALLATION INSTRUCTIONS

Secure Ethernet Gateway SEG-1 and SEG-M for IEI Access Systems Installation Manual

Telebyte 209 Short Haul Modem

Power supply unit Model: PAC-SC50KUA

Square D Powerlink G3 Lighting Control Systems

Pan Dacom. Nets work together. SPEED-DSL 2.3 Ethernet connection over 2-wires up to 2.3 Mbit/s ( A, A) Manual

LevelOne IFE Port PoE + 1-Port TP Industrial Fast Ethernet Switch User Manual

SATA and SAS Hard Drive Backplane

INSTALLATION GUIDE ConnectLine TV Adapter Getting started

SPEED-DSL 2.3 Ethernet connection over 2-wires up to 2.3 Mbit/s. Manual

Using installed Fieldbus Wiring to carry Ethernet Communications

LocoNet, the Digitrax Difference

MicroTech III Rooftop and Self Contained Unit Controller BACnet Communication Module (MS/TP)

HMI display Installation Guide

T7560A,B,C Digital Wall Module

MDM192 MULTI-DROPS DIGITAL MODEM FOR PRIVATE LINE. USER GUIDE Document reference :

MCR1900 Media Converter 19-Slot Chassis

Configuration Instructions

100 - SERIES NETWORK SWITCHES QUICK START GUIDE

System Wiring Design Guide

Options for ABB drives, converters and inverters. User s manual FDPI-02 diagnostics and panel interface

DS A 07/99 MN MI I/A SERIES MICRONET INTERFACE APPLICATION SPECIFICATION

USER MANUAL VS92A / VS94A / VS98A

Speed-DSL 9.2 Ethernet connection over 8-wires up to 9.2 Mbit/s. Manual * * * *

BPM Series. Metered Rack Mount PDUs. Quick Start Guide. Models Covered:

IEEE 802.3af 4-Port Power over Ethernet Injector Hub POE-400. User s Manual

USB to IDE or SATA Adapter

9,'(2 #6(3$5$725 8VHU V#0DQXDO

LT Charging Cart for Laptops

Video Splitter VS-104 / VS-108 User's Manual

Technical Manual. For use with Caller ID signaling types: Belcore 202, British Telecom, & ETSI

EDI Distributor Control Interface Wiring and Setup Instructions

Grounding and Shield Termination. Application Note 51204

WPR400 Wireless Portable Reader

Universal Serial Bus (USB) to DH-485 Interface Converter

Transcription:

Instruction Bulletin 63249-420-317A1 01/2009 POWERLINK RS232 to 485 Converter for use with POWERLINK G3 Systems INTRODUCTION SAFETY PRECAUTIONS The POWERLINK G3 Controllers are used to control the operation of a POWERLINK G3 lighting and control system. The controller uses remotely operated circuit breakers to control up to 168 remotely operated branch circuits. Control signals originate externally from dry-contact inputs, from the internal time scheduler, or from commands received via the communications network. Typical control devices include low voltage pushbutton wall switches, occupancy sensors, photocell controllers, and security and building management systems. This section contains important safety precautions that must be followed before attempting to install or maintain electrical equipment. Carefully read and follow the safety precautions below. HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E. This equipment must be installed and serviced by qualified electrical personnel. Turn off all electrical power supplying this equipment before working on or inside the equipment. Always use a properly rated voltage sensing device to confirm that power is off. Replace all devices, doors, and covers before turning on power to this equipment. Failure to follow these instructions will result in death or serious injury. CLASS A FCC STATEMENT This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designated to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his own expense. 2009 Schneider Electric. All Rights Reserved.

POWERLINK RS232 to 485 Converter 63249-420-317A1 Instruction Bulletin 01/2009 AUTOMATION NETWORK COMMUNICATIONS All POWERLINK G3 controllers feature an automation network for communication. Two serial communication ports are available on all controllers: RS-232, and RS-485. The NF2000, NF3000, and NF3000C controllers have a third communication port for Ethernet. Refer to the "Ports on the Controller" figure. The RS-232 and RS-485 ports are connected internally to the same controller serial communication port. Therefore, only one master device can be connected through one of the ports to the controller. For example, you cannot simultaneously connect a computer to the RS-485 port and a computer to the RS-232 serial port. Attempting to do so may result in improper operation. The Ethernet port, on applicable controllers, is also located internally. It is used to permanently connect multiple NF2000, NF3000, or NF3000C controllers to an existing ethernet LAN or a dedicated lighting control LAN. An internal RS-232 communication port also is available externally. The NFFPCG3 front panel serial cable is required to temporarily connect the controller to a computer. Refer to the Controller Front Panel Serial Cable instruction bulletin 63249-405-01 for the serial cable installation procedures. Figure 1: Ports on the Controller KEY: A. RS-232 Port (requires serial cable NFFPCG3 for temporary PC connection) B. Ethernet Port (for NF2000, NF3000, and NF3000c Controllers only) C. Serial Port 2 2009 Schneider Electric. All Rights Reserved.

63249-420-317A1 POWERLINK RS232 to 485 Converter 01/2009 Instruction Bulletin RS-485 Communications Multiple controllers can be networked together by wiring the system using the RS-485 port on the controllers. The "RS-485 Automation Level Communications Wiring" figure illustrates a typical configuration where three master panels are shown (each controlling its own independent subnet.) A maximum of 247 controllers can be connected together. Use a line repeater for each group of 32 controllers. The maximum cable distances at various baud rates are listed in the "Maximum Communication Cable Distance" table. Figure 2: RS-485 Automation Level Communications Wiring KEY: A. Personal Computer or Modem B. RS-232 to RS-485 Converter C. Power Supply D. RS-232 Port E. RS-485 Daisy Chain, 2-Wire, Twisted Pair Belden 9841 or equivalent F. Master Panel G. Slave Panel Table 1: Maximum Communication Cable Distances Baud Rate Maximum Distances 1-8 Controllers 9-16 Controllers 17-32 Controllers *76,800 4,000 ft (1,219 m) 4,000 ft (1,219 m) 3,000 ft (914 m) 38,400 4,000 ft (1,219 m) 4,000 ft (1,219 m) 3,000 ft (914 m) 19,200 5,000 ft (1,524 m) 4,000 ft (1,219 m) 4,000 ft (1,219 m) 9,600 5,000 ft (1,524 m) 5,000 ft (1,524 m) 4,000 ft (1,219 m) 4,800 5,000 ft (1,524 m) 5,000 ft (1,524 m) 4,000 ft (1,219 m) 2,400 5,000 ft (1,524 m) 5,000 ft (1,524 m) 4,000 ft (1,219 m) 1,200 5,000 ft (1,524 m) 5,000 ft (1,524 m) 4,000 ft (1,219 m) *NOTE: BACnet MS/TP only 2009 Schneider Electric. All Rights Reserved. 3

POWERLINK RS232 to 485 Converter 63249-420-317A1 Instruction Bulletin 01/2009 RS-485 Controller Connections Using a RS-232/485 Converter Figure 3: 2-Wire, RS-485 Connection Using a Converter Kit KEY: A. RS-232 Female DB-9 B. Serial Cable C. RS-232 Female DB-9 D. RS-485 Converter Comms Terminal E. Ground shield in one place only. F. Jumper ON, ECHO OFF G. Power Supply H. Black/White Stripe I. Controller 5-pin Comms Terminal in Master Panel (1) J. RS-485 Daisy Chain, 2-Wire, Twisted Pair, Belden 9841 or equivalent K. Controller 5-pin Comms Terminal in Master Panel (n) L. To Next Controller Master Panel Connection from the network to a personal computer, modem, or a building management system with the appropriate interface drivers often requires the use of a converter that will convert the RS-485 signal to an RS-232 signal. When the automation network is connected to the serial port (comms port) on the computer, the POWERLINK Controller Software (PCS-101) can be used. A female DB9 to female DB9 cable is required for the connection from the computer serial port to the converter. Square D offers a standard RS-232/485 converter kit that includes the converter, power supply, and serial cable (Square D catalog number 6382RS485G3KIT). Connection of this kit to the automation network is shown in the "2-Wire, RS-485 Connection Using a Converter Kit" figure. The communication wires are daisy-chained from one controller RS-485 port to the next in the following manner: positive to positive (+ to +), negative to negative ( to ), and shield to shield. Other types of third-party converters are available, depending on the application needs. When using a third-party converter, make sure it has biasing configurable by the user. 4 2009 Schneider Electric. All Rights Reserved.

63249-420-317A1 POWERLINK RS232 to 485 Converter 01/2009 Instruction Bulletin Automation Communications Wiring Specifications The National Electric Code (NEC) classifies automation communications wiring as a Class 2 circuit. Conductors may range in size from 24 to 18 AWG and consist of a single set of twisted pair conductors with a shield (Belden 9841 or equal). Maximum wiring distance should not exceed 5000 ft (1524 m) at 19,200 baud for eight controllers. See the "Maximum Communication Cable Distances" table for the maximum communication cable distances at various baud rates. 2009 Schneider Electric. All Rights Reserved. 5

POWERLINK RS232 to 485 Converter 63249-420-317A1 Instruction Bulletin 01/2009 Shielding and Grounding The automation network shield should be grounded in one place only, typically at the RS-232/485 converter as shown in the "Alternate Controller Communications Wiring Detail for 3-Wire, RS-485 Systems" figure. The controller circuitry and associated Class 2 wiring is electrically isolated from all system voltages and earth ground. Maintaining the integrity of this isolation is important for proper operation and performance. The controller s input terminals and auxiliary power source are part of the Class 2 circuitry. External devices connected to the controller must meet the isolation requirements and other Class 2 wiring standards. Do not connect the controller to external voltage sources or earth ground. The RS-485 network communications circuit is also part of the Class 2 circuitry. In most applications, the shield of each communications cable will be interconnected at the center terminal of the communications connector. This connection ensures networked controllers are tied together to a common reference potential. The shield must be grounded at only one point in the system. Grounding the shield at multiple points will create a ground loop that may disrupt communications or cause damage to the controller circuitry. 6 2009 Schneider Electric. All Rights Reserved.

63249-420-317A1 POWERLINK RS232 to 485 Converter 01/2009 Instruction Bulletin Alternate RS-485 Wiring An alternate RS-485 wiring scheme that uses a third reference wire is preferred in certain applications: When you cannot avoid connecting the Class 2 input circuitry to earth ground. When an external device s isolation from ground is minimal. When the controller is installed on a network with non-isolated devices. This 3-wire method uses a separate reference wire, or pair of wires, to interconnect the center terminal of all communications connectors. Refer to the "Alternate Controller Communications Wiring Detail for 3-Wire, RS-485 Systems" figure. The shield should remain isolated from the controller and should not be connected to this point. Instead, interconnect the shields using a wire nut. Connect the shield to ground at only one point. Figure 4: Alternate Controller Communications Wiring Detail for 3-Wire, RS-485 Systems KEY: A. RS-485 Converter Terminal B. Black/White Stripe C. Power Supply D. Ground shield in one place only E. Controller Comms Terminal in Master Panel 1 F. RS-485 Daisy Chain, 3-Wire, Twisted Pair, Belden 8723 or equivalent G. Controller Comms Terminal in Master Panel 2 H. Controller Comms Terminal in Master Panel (n) I. To next Controller 2009 Schneider Electric. All Rights Reserved. 7

POWERLINK RS232 to 485 Converter Instruction Bulletin Support and Service Contact the Square D Customer Information Center for technical support by phone at 1-888-Square D (1-888-778-2733) or e-mail at lightingcontrol.support@us.schneider-electric.com. Contact your local Square D service representative for repairs or service to your network. You may also find helpful information on our web site at www.squaredlightingcontrol.com. Schneider Electric, USA 320 Tech Park Drive La Vergne, TN, 37086 1-888-SquareD (1-888-778-2733) www.squaredlightingcontrol.com Square D,, Clipsal, C-Bus, Saturn and Neo are trademarks or registered trademarks of Schneider Electric and/or its affiliates in the United States and/or other countries. Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. 2009 Schneider Electric. All Rights Reserved. 63249-420-317A1 01/2009