1 Price $.00 IMS ALARM 3 PORT EXPANSION BOX OPERATING INSTRUTIONS READ THOROUGHLY BEFORE INSTALLING EQUIPMENT fm

2 TABLE OF ONTENTS GENERAL SPEIFIATIONS... 3 INTRODUTION... 4 RS232 ONNETION... 4 OMPATIBILITY... 4 SETUP... WIRING... 6 NTR SWITH SETTINGS... 7 S... 7

3 IMS ALARM 3 PORT RS 48 GENERAL SPEIFIATIONS Supply: 11 Vac Load: 2.0 VA Enclosure: Type 1 Relay Output: DPDT contacts; Amps 20 VA IMS Version requirements: Version 2.0 or later (Windows version) P Serial Port RS232 3

4 INTRODUTION The BinMaster IMS Alarm/ 3 Port expansion box provides 3 different RS 48 Ports and three SPDT relay outputs for system alarm conditions. There are 3 system alarm conditions, LOW, HIGH, and ERROR. The LOW level alarm relay will activate when any of the SmartBobs has triggered a Low level alarm in the IMS program. The HIGH level alarm relay will activate when any of the SmartBobs has triggered a High level alarm in the IMS program. The ERROR alarm relay will activate whenever there is a system error in the IMS program. A system error could be either a SmartBob not responding to a measurement command, or a Bob that has not retracted completely. The BinMaster IMS Alarm/3 Port expansion box has a nine pin RS232 port and three RS 48 ports. The RS232 port is connected to a serial communications port on the P running the IMS software. The three ports are labeled Port A, Port B, and Port. Each of these ports can communicate with up to 30 Smart Bobs. RS232 ONNETION The IMS Alarm/3 Port expansion box has a female 9 pin D connector for connection to the serial port on the P that is running the IMS program. The IMS program will need to be set up for the om port that the IMS Alarm/ 3 Port expansion box is connected to. OMPATIBILITY The IMS Alarm/3 Port expansion box requires the BinMaster IMS software for Windows version 2.0 or later to utilize all of the features. The 3 Port expansion feature also functions with the BinMaster ActiveX ontrol, however the Alarm relays are not supported by the ActiveX ontrol.

5 SETUP To utilize the 3 Ports in the IMS software program, you will need to set the Port Settings options to "Expanded". This is done by slecting the Setup tab on the menu bar and selecting Options. This will bring up the SmartBob IMS Options window. Select the Port Settings tab. Select the appropriate interface and check the Expanded box. This will activate additional tabs for up to 90 bins. The SmartBobs connected to each port must be individually addressed from 1 through 30 by their address DIP switches. The IMS program will have 90 addresses when running in Expanded Port Setting. The SmartBobs that are addressed 1 through 30 in the IMS program will connect to Port A. The SmartBobs that are addressed 31 through 60 in the IMS program will connect to Port B. The SmartBob that is addressed 31 in the IMS program will be communicating with the SmartBob that is connected to Port B and has its address DIP switches set to address 1. The SmartBobs that are addressed 61 through 90 in the IMS program will connect to Port. The SmartBob that is addressed 61 in the IMS program will be communicating with the SmartBob that is connected to Port and has its address DIP switches set to address 1.

6 > J1 1 4 GRD 2 F1 K1 K2 K3 D4 U9 U6 U U8 R7 R6 R8 R9 R11 R12 R13 R14 R1 R32 R10 U11 R3 R31 D D6 D7 D8 D9 R34 R33 R26 R22 R28 R29 R30 U1 R T1 R38 U3 MAX232 R U R4 DB1 4 R17 U 6 R3 3 D2 D3 R1 U2 L1 L2 U10 R2 X J3 WIRING There are three ports on the IMS Alarm/3 Port adapter box. The ports are labeled A, B, and. Each port has a 3 terminal pluggable connector. The cable will have its (), (), and shield wires connected to their appropriate terminal. Be sure that the polarity of the connection is correct! The wiring must be wired in a daisy chain wiring scheme. All wiring must start at an terminal and terminate at an terminal. There can be no spliced or taps in the line. The ports on the IMS Alarm/3 Port adapter box provides the biasing for their daisy chain wiring. No other biasing of the line is required. SmartBob Interconnect Wiring Diagram SBRX Remote #1 SBRX Remote #2 16VA 16VA Shield 16VA 16VA Shield ON ON 1 POWER TRANSFORMER OFF NTR 3 OFF NTR 120VA 16VA 2 4!!! IMPORTANT!!! Do not Ground Secondary of Transformer! 1.) The power transformer should be located near the SBRX Remote units so as to keep the voltage drop to a minimum. LOW Level Alarm Relay HIGH Level Alarm Relay System ERROR Relay 11VA Power ord N N N LOW HIGH ERROR 30 R18 R19 RTS RTS RTS A B 1 R20 A A DATA A R36 DATA DATA B R37 R2 R21 16 R24 R23 LM2902 R16 TD NTR_ NTR_B NTR_A RD OFF ON OFF ON OFF ON PORT PORT B PORT A Shd Shd Shd DB9 TB1 TB2 TB3 Shield Port A Port B Port RS232 to omputer running the IMS program 2.) Recommended wire size for connecting the transformer to remotes is 14 AWG minimum or as required by local electrical codes. 3.) Use shielded twisted pair data cable when connecting the remotes and interface. onnect all shields together and connect shields to terminal block as shown. Do not connect shields to earth ground. 4.) Additional units are connected in daisy chain manner as units 1 and 2 illustrated..) NTR (Network Termination) is in the "ON" position only on the last unit in the network. NTR SWITH SETTINGS Each port has an NTR switch located on the printed circuit board that is used to properly terminate the line. If the port is on the end of the daisy chain wiring scheme for the line then the NTR switch should be in the ON position. If the port is somewhere in the middle of the daisy chain wiring, then the NTR switch should be in the OFF position. In each SmartBob there is also an NTR switch, it should be set in the same manner. On the daisy chain wiring scheme, the NTR switch at each end on the daisy chain should be in the ON position. All of the rest of the NTR switches should be in the OFF position. There should always be two and only two NTR switches in the ON position.

7 The IMS Alarm/3 Port adapter box has three SPDT alarm relays. There is a Low Level Alarm relay, a High Level Alarm relay, and a System Error Alarm relay. The Low Level Alarm relay will pull in if the IMS program detects a Low Level alarm condition on any of the vessels that have their Low Level alarm active. The High Level Alarm relay will pull in if the IMS program detects a High Level alarm condition on any of the vessels that have their High Level alarm active. The Error Alarm relay will pull in if the IMS program detects a System Error when trying to take a measurement. A system error could be either a SmartBob not responding to a measurement command, or a Bob that has not retracted completely. In an alarm condition the relays make connection between the terminal and the terminal. In a normal state there is a connection between the and the N terminals. 12 R7 LOW LEVEL HIGH LEVEL SYSTEM ERROR 11 Vac POWER ORD N N N LOW HIGH ERROR J1 F1 K1 K2 U9 K3 D4 R18 D R19 1 D6 R20 RTS RTS RTS A B U1 2 T1 U6 U10 13 U7 X U8 R10 DATA DATA DATA A B D7 D8 D9 R22 R2 R36 R37 R2 R38 U3 R21 16 R24 R23 R9 R12 R13 R14 R1 9 R8 R6 R11 U11 LM2902 R32 8 NTR_ NTR_B NTR_A R30 MAX232 7 OFF ON PORT A OFF ON PORT B OFF ON PORT Shd Shd Shd R3 R31 R34 R33 R26 R28 R29 R27 DB9 TB1 TB2 TB3 PORT A PORT B PORT A A 1 DB1 4 R U 3 6 U4 R3 R4 R16 R J3 RS232 ONNETOR R1 D2 TD D3 RD GRD U2 L1 L2

Data Bulletin. Communications Wiring for POWERLINK G3 Systems Class 1210 ABOUT THIS BULLETIN APPLICATION INTRODUCTION.

Data Bulletin. Communications Wiring for POWERLINK G3 Systems Class 1210 ABOUT THIS BULLETIN APPLICATION INTRODUCTION. Data Bulletin 1210DB0002R3/05 03/2005 LaVergne, TN, USA Communications Wiring for POWERLINK G3 Systems Class 1210 Retain for future use. ABOUT THIS BULLETIN This data bulletin describes the proper wiring

More information

Application/Connection Examples

Application/Connection Examples This Quick Start Guide is designed to familiarize the user with the connection and configuration of the DTS-305 DIN rail mounted single / 3 phase power & energy meter with RS-485 or TCP communications.

More information

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems EN Security System CM705B CM705B - Universal Expander Module The CM705B universal expander provides a cost effective way

More information

Programming and Using the Courier V.Everything Modem for Remote Operation of DDF6000

Programming and Using the Courier V.Everything Modem for Remote Operation of DDF6000 Programming and Using the Courier V.Everything Modem for Remote Operation of DDF6000 1.0 Introduction A Technical Application Note from Doppler System July 5, 1999 Version 3.x of the DDF6000, running version

More information

Bluetooth HC-06 with serial port module Easy guide

Bluetooth HC-06 with serial port module Easy guide 1 Bluetooth HC-06 with serial port module Easy guide This manual consists of 3 parts: PART 1. Overview of Bluetooth HC-06 module with serial port. PART 2. Installing Bluetooth HC-06 module with Bolt 18F2550

More information

Cable Guide. Click on the subject to view the information. Digi Cables Building Cables General Cable Information

Cable Guide. Click on the subject to view the information. Digi Cables Building Cables General Cable Information Cable Guide Click on the subject to view the information. Digi Cables Building Cables General Cable Information Digi Cables Click on the subject to view the information. Digi Connector Options Digi Connector

More information

Rack mounted telephone- and leased line modem for industrial applications

Rack mounted telephone- and leased line modem for industrial applications Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as

More information

RS232C < - > RS485 CONVERTER S MANUAL. Model: LD15U. Phone: 91-79-4002 4896 / 97 / 98 (M) 0-98253-50221 www.interfaceproducts.info

RS232C < - > RS485 CONVERTER S MANUAL. Model: LD15U. Phone: 91-79-4002 4896 / 97 / 98 (M) 0-98253-50221 www.interfaceproducts.info RS232C < - > RS485 CONVERTER S MANUAL Model: LD15U INTRODUCTION Milestone s model LD-15U is a RS232 to RS 485 converter is designed for highspeed data transmission between computer system and or peripherals

More information

Telephone- and leased line modem for industrial applications TD-36

Telephone- and leased line modem for industrial applications TD-36 Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased

More information

ALARMS-xx. Remote Alarm Unit Setup Guide 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 RESET ALL

ALARMS-xx. Remote Alarm Unit Setup Guide 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 RESET ALL Remote Alarm Unit Setup Guide 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 RESET ALL User s Guide Version 1.0 07/01/2009 Michael Stevens & Partners Ltd. has made

More information

MechoNet TM Network Interface (MNI) Specification Submittal

MechoNet TM Network Interface (MNI) Specification Submittal MechoNet TM Network Interface (MNI) Specification Submittal Models MechoNet Network Interface: MNI RJ (RJ45 Motor Ports): Stock No.: IMNI 0001 TP AS (US version) Stock No.: IMNI 0004 TP AS (UK version)

More information

E2 Controller Wiring Practices. 026-1903 Rev 4 19-APR-2010

E2 Controller Wiring Practices. 026-1903 Rev 4 19-APR-2010 E2 Controller Wiring Practices 026-1903 Rev 4 19-APR-2010 3240 Town Point Drive NW Suite 100 Kennesaw, GA 30144 Phone: 770-425-2724 Fax: 770-425-9319 ALL RIGHTS RESERVED The information contained in this

More information

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS MAKING MODERN LIVING POSSIBLE AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS How to Use This Guide Read this Guide completely as you install and start up your new AK-SC 255 controller.

More information

DGM1D Controller + Contact less Smartcard Reader

DGM1D Controller + Contact less Smartcard Reader Edition 01/00 G0301FR010 DGM1D ontroller ontact less Smartcard ersion.0 WIRING DIAGRAM AND INSTRUTIONS DGM1 ontroller The DGM1 is a 1-door control unit. Unlimited number of cardholders. The DGM1 controller

More information

SmartVFD Frame 4 Wiring Diagrams and Dimensional Drawings

SmartVFD Frame 4 Wiring Diagrams and Dimensional Drawings Smart Frame Wiring Diagrams and Dimensional Drawings Smart Frame Size 60 Vac:.5-7.5 HP 08/0 Vac: 0.75- HP SPECIFICATION DATA CONTENTS Smart Frame Wiring Diagrams... Frame, Fused Disconnect Wiring Diagrams...

More information

Controller Automation, Model II+

Controller Automation, Model II+ Controller Automation Page 2 of 2 Automation with the RADAK II+ power controller II+ I/O Points: Inputs 5 Programmable Digital inputs 2 Dedicated digital inputs (Channel select and External SCR control

More information

Cable Specifications. T3 Trunk Cabling APPENDIX

Cable Specifications. T3 Trunk Cabling APPENDIX APPENDIX B This appendix contains details on the MGX 8230 cabling. It includes the following sections: T3 Trunk Cabling Frame Relay Cabling DC Power Cabling AC Power Cabling Control and Clock Cabling External

More information

Software Operations Manual

Software Operations Manual Software Operations Manual Version 5.0 BinMaster 7201 North 98th Street Lincoln, NE 68507 Phone: 402-434-9102 / Fax: 402-434-9133 info@binmaster.com - www.binmaster.com System Requirements PC with 1GHz

More information

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL CONTENTS GENERAL INFORMATION...3 INSTALLATION...3 FIELD WIRING...4 PROGRAMMING...4 Circuit Monitor Options...5 Power Frequency...5 Alarm Silence

More information

ACS-CRM CONTROL AND MONITORING MODULES FOR USE WITH THE RAYCHEM ACS-30 SYSTEM INSTALLATION INSTRUCTIONS

ACS-CRM CONTROL AND MONITORING MODULES FOR USE WITH THE RAYCHEM ACS-30 SYSTEM INSTALLATION INSTRUCTIONS AS-RM ONTROL AND MONITORING MODULES FOR USE WITH THE RAYHEM AS-0 SYSTEM INSTALLATION INSTRUTIONS APPROVALS/ERTIFIATIONS Hazardous Locations lass I, Div., Groups A,B,,D Ex n II T5 lass I, Zone, AEx n II

More information

MDM192 MULTI-DROPS DIGITAL MODEM FOR PRIVATE LINE. USER GUIDE Document reference : 9010709-03

MDM192 MULTI-DROPS DIGITAL MODEM FOR PRIVATE LINE. USER GUIDE Document reference : 9010709-03 MDM192 MULTI-DROPS DIGITAL MODEM FOR PRIVATE LINE USER GUIDE Document reference : 9010709-03 If you have questions about the MDM192 or desire assistance, contact ETIC TELECOMMUNICATIONS at the following

More information

Multipoint Scanning Alarm System

Multipoint Scanning Alarm System Multipoint Scanning Alarm System Many gas detection applications require multiple sensing locations to provide adequate area protection for plant personnel. Signals from a variety of field measurement

More information

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 INSTALLATION GUIDE Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 Card Reader and Controller Model 3.5 with KIM Swipe Reader Table of Contents 1. Features..................................

More information

SMS Alarm Messenger. Setup Software Guide. SMSPro_Setup. Revision 090210 [Version 2.2]

SMS Alarm Messenger. Setup Software Guide. SMSPro_Setup. Revision 090210 [Version 2.2] SMS Alarm Messenger SMSPro_Setup Revision 090210 [Version 2.2] ~ 1 ~ Contents 1. How to setup SMS Alarm Messenger?... 3 2. Install the SMSPro_Setup software... 5 3. Connection Type... 6 4. Connection Port

More information

Copyrights 2010 Victron Energy B.V. All Rights Reserved

Copyrights 2010 Victron Energy B.V. All Rights Reserved Manual EN 1 Copyrights 2010 Victron Energy B.V. All Rights Reserved This publication or parts thereof may not be reproduced in any form, by any method, for any purpose. For conditions of use and permission

More information

EQUIPMENT SPECIFICATIONS

EQUIPMENT SPECIFICATIONS EQUIPMENT SPECIFICATIONS IC-1600 Intelligent Controller The IC-1600 Intelligent Controller is a fully intelligent panel that has a complete database on board. It operates in conjunction with the Access

More information

Contact Center CC-165 INSTALLATION & USER'S GUIDE

Contact Center CC-165 INSTALLATION & USER'S GUIDE Contact Center CC-165 INSTALLATION & USER'S GUIDE Table of Contents Introduction... 2 Specifications... 2 J4 Host Communications... 2 J5 and J12 (upper board)... 3 J6, J13, and 14 Input Connections...

More information

Sentry. Remote Power Manager. Installation and Setup Manual

Sentry. Remote Power Manager. Installation and Setup Manual Sentry Remote Power Manager Installation and Setup Manual Copyright 2001 by Server Technology, Inc. All rights reserved. Second Edition, January 2001. Sentry, Intelligent Power Module, and Power Tower

More information

WinLIN Setup and Operation:

WinLIN Setup and Operation: Frequently Asked Questions about the 07551-Series Masterflex L/S Computer-Compatible drives and about the Masterflex WinLIN Linkable Instrument Control Software (07551-70) WinLIN Setup and Operation: Will

More information

FOSTCDR. Industrial Serial to Multimode Fiber Optic Converter PRODUCT INFORMATION B&B ELECTRONICS. Specifications Serial Technology

FOSTCDR. Industrial Serial to Multimode Fiber Optic Converter PRODUCT INFORMATION B&B ELECTRONICS. Specifications Serial Technology FOSTCDR pn 8684R1 FOSTCDR-0812ds page 1/5 Industrial Serial to Multimode Fiber Optic Converter Data Rates up to 115.2 kbps 2.5 Mile (4 km) Range 10 to 30 VDC Input Voltage Wide Operating Temperature 2000V

More information

NGC-30-CR -CRM -CRMS -CTM -CVM

NGC-30-CR -CRM -CRMS -CTM -CVM NG-0-R -RM -RMS -TM -VM ontrol and monitoring modules for use with the Raychem NG-0 Installation Instructions Description The NG-0-RM/-RMS and NG-0-TM provide ground-fault and line current sensing, alarming,

More information

Connector and Cable Specifications

Connector and Cable Specifications APPENDIX B This appendix provides the following cabling and pinout information for the Cisco IAD1101 integrated access device: Console Port Signals and Pinouts Ethernet Connector Pinouts Analog Subscriber

More information

Installation manual. Version 1.1. www.videx-security.com

Installation manual. Version 1.1. www.videx-security.com Installation manual Version 1.1 www.videx-security.com 2 Table of Contents MANUAL INTRODUCTION... 4 SYSTEM INTRODUCTION... 4 SYSTEM COMPONENTS... 5 CONTROLS... 6 3.5A 13.8Vdc PSU... 6 CONTROL PCB... 6

More information

SolarEdge. RS485 Expansion Kit Installation Guide. Version 1.0

SolarEdge. RS485 Expansion Kit Installation Guide. Version 1.0 SolarEdge RS485 Expansion Kit Installation Guide Version 1.0 Disclaimers Disclaimers Important Notice Copyright SolarEdge Inc. All rights reserved. No part of this document may be reproduced, stored in

More information

BACnet Wiring Guidelines. For Price Controls MANUAL INSTALLATION

BACnet Wiring Guidelines. For Price Controls MANUAL INSTALLATION MANUAL INSTALLATION BACnet Wiring Guidelines For Price Controls Revision #: 01 Issue Date: 01/22/14 2014 Price Industries Limited. All rights reserved. TABLE OF CONTENTS Product Overview Overview...1 Power

More information

Ethernet. Customer Provided Equipment Configuring the Ethernet port.

Ethernet. Customer Provided Equipment Configuring the Ethernet port. Installing the RDSP-3000A-NIST Master Clock. Ethernet Connect the RJ-45 connector to a TCP/IP network. Equipment The following equipment comes with the clock system: RDSP-3000A-NIST Master Clock Module.

More information

is then retained absolutely without interruption.

is then retained absolutely without interruption. Page 1 of 11 DC UPS uninterruptible power supplies - DC UPS module 15 A Compact design, only 50 mm wide Absolutely interruption-free buffering of power failures through immediate electronic connection

More information

12 Series - Time switches 16 A. Features 12.01 12.11 12.31

12 Series - Time switches 16 A. Features 12.01 12.11 12.31 Mechanical time switches - daily time setting Type 12.01-1 Pole 16 A CO (SPDT) Type 12.11-1 Pole 16 A O (SPST-O) 17.6 mm width Type 12.31-0000 - 1 Pole 16 A CO (SPDT) Type 12.31-0007 - 1 Pole 16 A CO (SPDT)

More information

Operations and Programming Manual. ERC/EC-1000 Environmental Control. Supermarket Refrigeration

Operations and Programming Manual. ERC/EC-1000 Environmental Control. Supermarket Refrigeration Supermarket Refrigeration Operations and Programming Manual ERC/EC-1000 Environmental Control REFRIGERATION AND AIR CONDITIONING Literature No. RS.8B.J1.22 Code No. 084R9900 Release: Version 5.30/7.30

More information

Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit

Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit SLCLE5504AUX for Use with Wired C-Bus Networks Instruction Bulletin Retain for future use. Square D Clipsal DIN-Rail Four-Channel Auxiliary Input

More information

Application Note - Connecting an Electricity Meter to SolarEdge Devices (Europe and APAC)

Application Note - Connecting an Electricity Meter to SolarEdge Devices (Europe and APAC) February 2015 February 2015 Application Note - Connecting an Electricity Meter to SolarEdge Devices (Europe and APAC) This document describes how to connect an electricity meter to a SolarEdge device (inverters,

More information

TrueAlarm Fire Alarm Systems

TrueAlarm Fire Alarm Systems TrueAlarm Systems UL, ULC, CSFM Listed; FM Approved* Network Annunciators; es Features Provides a dedicated local area network (LAN) for connection of a TrueSite workstation server to remote clients: es

More information

IMMS-CCC. IMMS-CCC Hardwire Central Interface. Installation Instructions

IMMS-CCC. IMMS-CCC Hardwire Central Interface. Installation Instructions IMMS-CCC IMMS-CCC Hardwire Central Interface Installation Instructions TABLE OF CONTENTS... Choose a Location... 1 Connections... 2 Operations... 3 Software Configuration... 4 Troubleshooting... 5 Loopback

More information

Application & Quick-Start Guide

Application & Quick-Start Guide Model: CRMWIC Web Intelligent Controller 1 This document will illustrate various ways to connect and use a CRM-WIC as well as programming examples. When connecting CRM-WIC, the installer has several interface

More information

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment

More information

Short Range Wireless Switch System Handheld 8 Installation and Operations Guide

Short Range Wireless Switch System Handheld 8 Installation and Operations Guide Phone: (866) 701-1146 Fax: (425) 216-7558 www.remotecontroltech.com Short Range Wireless Switch System Handheld 8 Installation and Operations Guide Introduction... 2 Before Installation... 2 Receiver Installation...

More information

TECHNICAL BULLETIN. Wiring Diagrams. TPI Wiring. TB1010-04 Rev. March 4, 2013 Page 1 of 5. Switch Settings 3 PHASE POWER SUPPLY 3 PHASE POWER SUPPLY

TECHNICAL BULLETIN. Wiring Diagrams. TPI Wiring. TB1010-04 Rev. March 4, 2013 Page 1 of 5. Switch Settings 3 PHASE POWER SUPPLY 3 PHASE POWER SUPPLY Page 1 of 5 Wiring and Programming of the TPI (Turbine Pump Interface) with an FEPetro SCIII (3-Phase Smart Controller) Overview The STP-SCIII 3-Phase Smart Controller can be controlled by the INCON TPI

More information

Current Loop Application Note 1495

Current Loop Application Note 1495 Current Loop Application Note Document No. CLAN1495 International Headquarter B&B Electronics Mfg. Co. Inc. 707 Dayton Road -- P.O. Box 1040 -- Ottawa, IL 61350 USA Phone (815) 433-5100 -- General Fax

More information

Power Supply and Cabling Options. SmartTrak 100/101/140

Power Supply and Cabling Options. SmartTrak 100/101/140 Power Supply and Cabling Options SmartTrak 00/0/40 2 Power Supply and Cabling Options SmartTrak 00/0/40 Table of Contents Power Supplies... Communication Cables... Accessory Options... Appendix A Communication

More information

HSG Engineering Tech Bulletin

HSG Engineering Tech Bulletin Specifications subject to change OCT 2013; Rev. 1.3 HSG Engineering Tech Bulletin Recommended RS-485 Wiring for NetAXS-4/NetAXS-123 Loops Overview This document provides the recommended RS-485 wiring for

More information

8 Channel Status Input Panel model SIP-8

8 Channel Status Input Panel model SIP-8 Description The Sine Systems model SIP-8 Status Input Panel is to be used with the RFC-1/B Remote Facilities Controller. It consists of a long PC board mounted on a 1.75 inch (1U) rack panel. The SIP-8

More information

CREATING YOUR OWN RF SWITCHING SYSTEM

CREATING YOUR OWN RF SWITCHING SYSTEM AN2008-08-YOM rev. 2.0 By Sara Nazemzadeh April, 20 Application Note REATING YOUR OWN RF SWITHING SYSTEM Abstract The purpose of this Application Note is to introduce an alternative way of meeting switching

More information

Driver Pant 8 and antenna switcher Ant 8. User manual

Driver Pant 8 and antenna switcher Ant 8. User manual Driver Pant 8 and antenna switcher Ant 8 User manual Table of contents Table of contents... 2 Introduction... 3 Shipping Contents... 3 Technical Data... 3 Control Panel... 4 Rear panel... 5 Controller

More information

NC-12 Modbus Application

NC-12 Modbus Application NC-12 Modbus Application NC-12 1 Table of Contents 1 Table of Contents... 2 2 Glossary... 3 SCADA...3 3 NC-12 Modbus in general... 3 4 Entire system... 4 4.1 PFC to PC connection alternatives...4 4.1.1

More information

How to set up EARTH FAULT ALARM On Fronius inverters

How to set up EARTH FAULT ALARM On Fronius inverters How to set up EARTH FAULT ALARM On Fronius inverters According to AS/NZS 5033:2014 (c) Fronius Australia Pty. Ltd, 01/2015 1/6 EARTH FAULT ALARM FOR FRONIUS INVERTERS The installation of earth fault alarms

More information

Innovative Electronics for a Changing World INDEX

Innovative Electronics for a Changing World INDEX Innovative Electronics for a Changing World INDEX 1. SYSTEM DESCRIPTION 2. BOARD CONNECTIONS terminals and indicators 3. CONNECTION DIAGRAM 4. START UP GUIDE and passwords 5. HOME PAGE 6. STATUS PAGE 7.

More information

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE for solar energy management LEATEC Delivering Solutions for Energy Management SOLAR ENERGY DATA CENTER BUILDING 4 to8 String Monitoring with 0.% Accuracy

More information

Life Alarm Fire Alarm Controls

Life Alarm Fire Alarm Controls FIRE SUPERVISORY SUPV SILENCED SILENCE AC POWER RESET UL, ULC Listed FM Approved MEA Approved* Life Alarm Fire Alarm Controls Fire Alarm Controls 4005 Series Fire Alarm Control Panels Eight through Thirty-Six

More information

MIC-BP4 Bi-Phase Converter Card For the MIC400 series camera

MIC-BP4 Bi-Phase Converter Card For the MIC400 series camera MIC-BP4 Bi-Phase Converter Card for the MIC400 PTZ Camera Series Bosch Security Systems EN Installation and Operation Manual BP4 Bi-phase card Installation and Operation Manual AAAEN 2 MIC-BP4 Bi-Phase

More information

EDI Distributor Control Interface Wiring and Setup Instructions

EDI Distributor Control Interface Wiring and Setup Instructions Universal I/O EDI Distributor Control Interface Wiring and Setup Instructions EDI UNIVERSAL I/O INTERFACE MODULE The only interface needed for EDI-V5 controls Network compatible with all older EDI controls

More information

Fire Fighter Phone System Installation Instructions

Fire Fighter Phone System Installation Instructions Fire Fighter Phone System Installation Instructions Introduction This publication describes the installation procedure for the Fire Fighter s Phone on a 4100U or a 4100ES Fire Alarm Control Panel (FACP).

More information

RMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions

RMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions Heat-Tracing Remote Monitoring Module for the NGC Control System Installation Instructions Tools Required 3 mm slotted screwdriver 3/8 hex key (for -4X only) Approvals Nonhazardous locations Type NM LISTED

More information

EMBEDDED ACCESS CONTROL Hardware Installation Guide

EMBEDDED ACCESS CONTROL Hardware Installation Guide EMBEDDED ACCESS CONTROL Hardware Installation Guide Lenel goentry Hardware Installation Guide, product version 1.00. This guide is item number DOC- ENHW-ENU, revision 1.003, April 2009 Copyright 2009 Lenel

More information

Different Ways of Connecting to. 3DLevelScanner II. A.P.M Automation Solutions LTD. www.apm-solutions.com Version 3.0

Different Ways of Connecting to. 3DLevelScanner II. A.P.M Automation Solutions LTD. www.apm-solutions.com Version 3.0 3DLevelScanner II Different Ways of Connecting to 3DLevelScanner II A.P.M Automation Solutions LTD. www.apm-solutions.com Version 3.0 2 Different Ways of Connecting to 3DLevelScanner II Version 3.0 Table

More information

Computer Control of Satellite Antennas

Computer Control of Satellite Antennas Computer Control of Satellite Antennas This paper discusses the use of the serial interface available on Research Concepts, Inc. (RCI) satellite antenna controllers. The serial communications interface

More information

AC-115 Compact Networked Single Door Controller. Installation and User Manual

AC-115 Compact Networked Single Door Controller. Installation and User Manual AC-115 Compact Networked Single Controller Installation and User Manual December 2007 Table of Contents Table of Contents 1. Introduction...5 1.1 Key Features... 6 1.2 Technical Specifications... 7 2.

More information

PXL-250: Network Wiring

PXL-250: Network Wiring This document provides the network wiring requirements for a PXL-250 access control network. Network Requirements The PXL-250 uses a half-duplex, RS-485 communication bus. Per the RS-485 specification,

More information

General Information. Installation Wiring Practices for Vickers Electronic Products

General Information. Installation Wiring Practices for Vickers Electronic Products Vickers eneral Information Installation Wiring Practices for Vickers Electronic Products Revised 12/97 268 Installation Requirements Introduction Vickers Electronic Products are designed to be used in

More information

Quick Installation. A Series of Intelligent Bar Code Reader with NeuroFuzzy Decoding. Quick Installation

Quick Installation. A Series of Intelligent Bar Code Reader with NeuroFuzzy Decoding. Quick Installation Quick Installation A Series of Intelligent Bar Code Reader with NeuroFuzzy Decoding This chapter intends to get your new FuzzyScan scanner working with your existing system within minutes. General instructions

More information

Installation instructions for Series NRX INCOM communications adapter module

Installation instructions for Series NRX INCOM communications adapter module 4000 NRX RF DRAWOUT SUBTITLE IMAGE (12/15/2010) Effective July 2015 Supersedes October 2010 IL01301033EH04 Installation instructions for Series NRX INCOM communications adapter module Instructions apply

More information

IP DSLAM IDL-2402. Quick Installation Guide

IP DSLAM IDL-2402. Quick Installation Guide IP DSLAM IDL-2402 Quick Installation Guide Table of Contents Package Contents... 3 Overview... 4 Setup the IDL series IP DSLAM... 5 Safety Instruction... 5 Hardware Installation... 6 WEB Configuration...

More information

MicroTech Remote Monitoring and Control Panel

MicroTech Remote Monitoring and Control Panel Installation & Maintenance Data IM 444-1 Group: Controls Part Number: 573384Y Date: February 1998 MicroTech Remote Monitoring and Control Panel Applied Rooftop and Self-contained Air Conditioning Systems

More information

NOTE: It is the responsibility of the installation organization to have only technically qualified personnel performing the installation.

NOTE: It is the responsibility of the installation organization to have only technically qualified personnel performing the installation. This quick start guide provides, basic installation information, drawings, first time power-on instructions, and short descriptions of key terms and concepts for installing the EntraGuard Platinum Telephone

More information

Water Leak Detection System

Water Leak Detection System Water Leak Detection System Installation and Operating Manual 505-334-5865 ph 505-334-5867 fax www.rodisystems.com email:info@rodisystems.com 936 Highway 516 Aztec, NM 87410-2828 Manual Revisions and Copyright

More information

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short

More information

Solar monitoring gateway quick start guide

Solar monitoring gateway quick start guide Instructional Leaflet I70002E LGATE101-1B LGATE101-1A LGATE101-5B LGATE101-5A Contents Description Page General................................. 2 Information collection sheet............... 2 Quick reference

More information

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION Modular, Customizable Wire Replacement 128 / 256 Bit AES Encryption Software Selectable RF Transmit Power Software Selectable Over-the-air Data Rate Modbus ASCII /RTU Compatible Wide Operating Temperature

More information

HomeSeer Technologies. HomeSeer Technologies LLC 35 Constitution Dr, Suite C Bedford NH, 03110 www.homeseer.com

HomeSeer Technologies. HomeSeer Technologies LLC 35 Constitution Dr, Suite C Bedford NH, 03110 www.homeseer.com HomeSeer Technologies HomeSeer Z-Troller Z-Wave Computer Interface Installation guide HomeSeer Technologies LLC 35 Constitution Dr, Suite C Bedford NH, 03110 www.homeseer.com Description Thank for your

More information

LTM-1338B. Plus Communications Manual

LTM-1338B. Plus Communications Manual LTM-1338B Plus Communications Manual 2000. Best Power, Necedah, Wisconsin All rights reserved. Best Power The System Setup option from the Main Menu on the front panel is passwordprotected. The default

More information

Connectors and Cables

Connectors and Cables APPENDIX B This appendix describes the connectors, cables, and adapters that you use to connect the switch to other devices. Connector Specifications 10/100 Ports The 10/100 Ethernet ports use standard

More information

DASDEC Interfacing to DM Engineering MSRA/MSRE Series Switchers

DASDEC Interfacing to DM Engineering MSRA/MSRE Series Switchers Introduction DASDEC Interfacing to DM Engineering MSRA/MSRE Series Switchers The DASDEC-II EAS/CAP Encoder/Decoders include a single analog balanced-stereo audio switch for inserting an EAS/CAP audio message

More information

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,

More information

BACnet Automation Interface Module (Network Version)

BACnet Automation Interface Module (Network Version) Sense +V Tx Rx LAN LINK Over ARCNET KBaud BACnet Rx BACnet Tx Archive Valid Port S Tx Port S Rx Low Battery Network- Enhanced Access Default MSTP PTP = Download Required on Rnet and Port S IP Address IP

More information

APPENDIX A PIN-OUT OF RJ12 / RJ45 CONNECTORS. RJ12 connectors

APPENDIX A PIN-OUT OF RJ12 / RJ45 CONNECTORS. RJ12 connectors APPENDIX APPENDIX A PIN-OUT OF RJ12 / RJ45 CONNECTORS RJ12 connectors Pin # 1 Signal Name Not Used 2 +TR Description + Data Line 3 +R Remote OFF Required or Remote OFF control 4 -TR 5 Not Used 6 RTN -

More information

LDG DTS-4/4R Desktop Coaxial Switch / Remote

LDG DTS-4/4R Desktop Coaxial Switch / Remote LDG DTS-4/4R Desktop Coaxial Switch / Remote LDG Electronics 1445 Parran Road, PO Box 48 St. Leonard MD 20685-2903 USA Phone: 410-586-2177 Fax: 410-586-8475 ldg@ldgelectronics.com www.ldgelectronics.com

More information

Modular I/O System Analog and Digital Interface Modules

Modular I/O System Analog and Digital Interface Modules OPERATING INSTRUCTIONS Modular I/O System Analog and Digital Interface Modules Installation Operation Maintenance Document Information Document ID Title: Operating Instructions Modular I/O System Part

More information

SenseLink TM. End-Point Controller. Addendum

SenseLink TM. End-Point Controller. Addendum SenseLink TM End-Point Controller Addendum MKS Instruments, Inc. Control & Information Technology Products Group 3350 Scott Blvd Bldg 4 Santa Clara, CA 95054 Main: 408.235.7620 Fax: 408.235.7625 SenseLink

More information

Paragon Explorer Lite Communication Software

Paragon Explorer Lite Communication Software CU-111 APRIL 11, 2013 Paragon Explorer Lite Communication Software For Fireye Paragon Scanners using Windows XP DESCRIPTION Paragon Explorer Lite, is the basic PC based configuration tool for Paragon model

More information

SMART SENSOR COLLECTION

SMART SENSOR COLLECTION TEMPERATURE SENSOR This sensor measures temperature in degrees Celsius or Fahrenheit. It works with all SensorHawk base units (SensorHawk-2, SensorHawk-8 and SensorHawk8/20) as well as the SecurityHawk-8

More information

SECTION 13850 DETECTION AND ALARM

SECTION 13850 DETECTION AND ALARM SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring

More information

How To Set Up A 366101 Modem (Marc) Model 366101 (Marc) Model 2 (Marr) Model 1 (Marm) Model 4 (Mariar) Model 8 (Marp) Model 6 (Mar

How To Set Up A 366101 Modem (Marc) Model 366101 (Marc) Model 2 (Marr) Model 1 (Marm) Model 4 (Mariar) Model 8 (Marp) Model 6 (Mar DIN Rail Mounted Leased Line Modem Users Manual 366-101 Rev. 2 Copyright 2008 Miille Applied Research Co., Inc. Houston, Texas This page is left blank intentionally Page i TABLE OF CONTENTS LIST OF FIGURES...

More information

An Ethernet Cable Discharge Event (CDE) Test and Measurement System

An Ethernet Cable Discharge Event (CDE) Test and Measurement System An Ethernet Cable Discharge Event (CDE) Test and Measurement System Wei Huang, Jerry Tichenor ESDEMC Technology LLC Rolla, MO, USA whuang@esdemc.com Abstract A Cable Discharge Event (CDE) is an electrostatic

More information

5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual

5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual 5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual Content Overview... 1 Introduction... 1 Features... 3 Packing List... 4 Safety Precaution... 4 Hardware Description... 5 Front Panel...

More information

No Phone Line II-48 System

No Phone Line II-48 System Used in conjunction with an EntraGuard Telephone Entry System, the -48 provides No Phone Line communication and door or gate control through existing building telephone lines without the need to purchase

More information

FlexPoint T1/E1 Copper to Fiber Line Driver

FlexPoint T1/E1 Copper to Fiber Line Driver BLACK BOX NETWORK SERVICES MT660A-MM MT661A-SM MT660A-MM-E MT661A-SM-E FlexPoint T1/E1 Copper to Fiber Line Driver CUSTOMER Order toll-free in the U.S.: Call 877-877-BBOX SUPPORT (outside U.S. call 724-746-5500)

More information

Digital I/O: OUTPUT: Basic, Count, Count+, Smart+

Digital I/O: OUTPUT: Basic, Count, Count+, Smart+ Digital I/O: OUTPUT: Basic, Count, Count+, Smart+ The digital I/O option port in the 4-Series provides us with 4 optically isolated inputs and 4 optically isolated outputs. All power is supplied externally.

More information

EVAL-UFDC-1/UFDC-1M-16

EVAL-UFDC-1/UFDC-1M-16 Evaluation Board for Universal Frequency-to- Digital Converters UFDC-1 and UFDC-1M-16 EVAL-UFDC-1/UFDC-1M-16 FEATURES Full-Featured Evaluation Board for the Universal Frequency-to-Digital Converters UFDC-1

More information

Application Note 83 Fundamentals of RS 232 Serial Communications

Application Note 83 Fundamentals of RS 232 Serial Communications Application Note 83 Fundamentals of Serial Communications Due to it s relative simplicity and low hardware overhead (as compared to parallel interfacing), serial communications is used extensively within

More information

Communication Setup Application Note

Communication Setup Application Note Communication Setup Application Note This Application Note describes how to install and set up communication between the inverter and the SolarEdge Monitoring Server. This document contains the following

More information

PowerCommand iwatch 100 Remote Network Monitoring

PowerCommand iwatch 100 Remote Network Monitoring PowerCommand iwatch 100 Remote Network Monitoring Description The PowerCommand iwatch provides a convenient means for remotely monitoring generator sets and transfer switches. The Microsoft Internet Explorer

More information