DS A 07/99 MN MI I/A SERIES MICRONET INTERFACE APPLICATION SPECIFICATION
|
|
|
- Alexina Carpenter
- 10 years ago
- Views:
Transcription
1 DS A 07/99 MN MI WIRING AND COMMISSIONING INFORMATION FOR I/A SERIES MICRONET INTERFACE APPLICATION Order Type: MNN-Ml-100 MicroNet NCP Interface The I/A Series MicroNet Interface (MI) provides network-level supervision functions for a network of MicroNet controllers and displays. An RS232 port on the MI furnishes a single connection to a PC running the MicroNet Tech Tool, the MicroSat Tool or MicroNet View software or a Wide Area Network (WAN) for remote access. The MN MI features password protection. It can supervise up to 61 devices on a LonWorks network or 20 x 95 devices on a NCP network and 95 devices on an ARCNET network. An MI features a built-in real-time clock with battery-backup that can be used for network synchronization. The MI connects a PC running the MicroNet View or MicroNet Tech Tool software or MicroSat Tool to a communications network that is LonWorks FTT-10 Free Topology, NCP or ARCNET. When connected to a modem, the MI can allow modem access from MicroNet View. SPECIFICATION Order Type Description Communications MNN-Ml-100 MicroNet NCP Interface NCP a b a. ARCNET communications protocol available for this model with optional plug-in card, MNA-C. b. LonWorks communications protocol available for this model with optional plug-in card, MNL-C-ENM. An Invensys company
2 DS A /99 INSTALLATION INSPECTION Inspect carton for damage. If damaged, notify carrier immediately. Inspect MI for damage. Return damaged products. REQUIREMENTS (These items not provided) Installer must be an experienced technician Job wiring diagrams Tools: Drill and bits Digital Volt-Ω meter (DVM) Static protection wrist strap EN power transformer supplying a nominal 24Vac (20.4 to 30Vac) with a minimum rating of 10VA, 50/60Hz per MI. Three No. 10 self-starting screws or 35mm DIN rail for mounting Terminators (If MicroNet LONWORKS or ARCNET network is used): One LON-TERM1 terminator required for free topologies Two LON-TERM2 terminators required for bus topologies Two 120Ω terminators required for ARCNET bus topology Null modem cable for RS232 connection to PC, Satchwell part number CBL-002. Cable for RS232 connection to modem, Satchwell part number CBL-003. PRECAUTIONS Warning: Electrical shock hazard! Disconnect power before installing or removing the cover. GENERAL Follow Static precautions when installing this equipment. Use copper conductors that are suitable for 75 C (167 F). Make all connections according to electrical wiring diagram, national and local electrical codes. STATIC PRECAUTIONS Static charges damage electronic components. The microprocessor and associated circuitry are extremely sensitive to static discharge. Use the following precautions when installing, servicing, or operating the system: Work in a static-free area. Discharge static electricity by touching a known, securely grounded object. Use a wrist strap connected to earth ground when handling the MI s printed circuit board. EUROPEAN COMMUNITY DIRECTIVES This equipment meets all requirements of European Community Directives for Low Voltage (72/23/EEC), General Safety (92/59/EEC), and Electromagnetic Compatibility (89/336/EEC). FEDERAL COMMUNICATIONS COMMISSION (FCC) This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. CANADIAN DEPARTMENT OF COMMUNICATIONS (DOC) This digital apparatus does not exceed the Class A limits for radio noise emissions from digital apparatus set out in the radio interference regulations of the Canadian Department of Communications. GENERAL WIRING PRECAUTION When using RS232 communication connections, remove and discard conduit plate. MICRONET NETWORK WIRING PRECAUTIONS Do not mix network wiring with other types of wiring. Communication wire pairs must be dedicated to MicroNet network communications. They cannot be part of an active, bundled telephone trunk. Shielded cable is not required for LonWorks wiring, but is required for NCP and ARCNET wiring. Terminals accept 1.5mm 2 (No.16 to 24 AWG) wire. If the cable is installed in areas of high RFI/EMI, the cable must be in conduit. RS232 COMMUNICATION WIRING PRECAUTIONS Use Null modem cable for RS232 connection to PC, Satchwell part number CBL pin to 25 pin cable for RS232 connection to modem. Do not exceed 15m (50 feet) total length. POWER SUPPLY WIRING PRECAUTIONS This product contains a non-isolated half-wave rectifier power supply and must not be powered by transformers used to power other devices containing non-isolated full-wave rectifier power supplies. Refer to DS , Guidelines for Powering Multiple Full- Wave and Half-Wave Rectifier Devices from a Common Transformer for detailed information. Do not mix power wiring with network, AO, UI or DI wiring. Use EN power transformer supplying a nominal 24Vac (20.4 to 30Vac) with a minimum rating of 10VA at 50/60Hz. The supply to transformer must have a breaker or disconnect. The transformer frame must be grounded. LOCATION Suitable for indoor use only (IP40). When selecting a mounting location make certain the following conditions are met: Do not install where excessive moisture, corrosive fumes, vibration, or explosive vapours are present. Do not install near large contactors, electrical machinery or welding equipment. Allow 150mm (6 inch) clearance from contactors, switches and associated cabling. Locate where ambient temperatures do not exceed 50 C (120 F) or fall below 0 C (32 F) and relative humidity does not exceed 95% or fall below 0%, non-condensing.
3 07/ DS A PANEL OR DIN RAIL MOUNTING 1. Select mounting location. Allow minimum 50mm (2 inch) clearance around MI. 2. Do the following to mount MI on a panel: a. Loosen two screws securing terminal cover and remove cover. b. Press wall mounting bracket clip onto back of controller. c. Lift wall mounting bracket clip. d. Using a self-starting screw, install top screw. MOUNTING METHODS Wall Mounting e. Level controller. f. Using two self-starting screws, install bottom screws. g. Re-install terminal cover. (May be left off until wiring is completed.) 3. Do the following to mount MI on a DIN rail: a. While pulling down on DIN rail locking bracket, snap MI base on a 35mm DIN mounting rail. b. Release DIN rail locking bracket. DIN Rail Mounting
4 DS A /99 WIRING When using RS232 communications connection, remove and discard conduit plate before making other connections. The following electrical connections can be made to MI: MicroNet LonWorks connection to other LonWorks equipped controllers MicroNet NCP connection to other NCP type MicroNet controllers. MicroNet ARCNET connection (MNN-MI-100 with MNA-C fitted) to other ARCNET equipped controllers. 24Vac nominal EN power source and earth ground power connection RS232 communication connection to a personal computer (PC) RS232 communication connection to a modem. COMMUNICATIONS WIRING Review Precautions section before connecting or installing any communications wiring. Communications wiring includes a connection between the MI and a MicroNet controller network. Depending on the specific interface model, one of three network types can be used: FTT LonWorks Networks (MNN-MI-100 with MNL-C-ENM fitted) NCP Networks (MNN-MI-100) ARCNET Networks (MNN-MI-100 with MNA-C fitted). MICRONET NETWORK WIRING Review Precautions section. For complete details on designing and wiring MicroNet networks (including approved cable models) refer to the I/A Series MicroNet System Engineering Guide. MN MI TERMINAL CONNECTIONS
5 07/ DS A LONWORKS NETWORK ATTACHMENT (MNN WITH MNL-C-ENM FITTED) Unshielded cable is recommended. ARCNET NETWORK ATTACHMENT (MNA-MI) 2. Connect two twisted wires of the FTT network cable to terminals 9 and 10 of MI. Polarity makes no difference. MicroNet ARCNET Network MicroNet LonWorks Network 3. Depending on topology chosen for the FTT segment, attach other controllers freely using multiple wiring tees and stars (Free topology), or daisy-chain connect controllers only in a device-todevice fashion (Bus Topology). 4. If shielded cable is used, connect one end only to earth ground by a 470KΩ, 1/4 watt resistor. Keep the shield wire continuous throughout the wiring segment. 5. Attach terminators as required. NCP NETWORK ATTACHMENT (MNN-MI) MicroNet NCP Network Recommended cable is Belden 8762 or equivalent twisted pair overall screened cable. 2. Connect positive wire to terminal 9 and negative wire to terminal Connect ARCNET wiring shield to terminal 6. Keep shield continuous between ARCNET devices and LAN. 4. Using daisy-chain method, connect MI with other MNA equipped devices on network. Do not use wiring tees or stubs. 5. Fit bias links to LK1 and LK2 on ARCNET daughter board. (In controller at approximate mid-network position only). 6. Attach 120Ω terminators to each end of LAN. RS232 COMMUNICATION WIRING TO A PERSONAL COMPUTER (PC) Connector PL3 on MI is not used. 2. Remove and discard conduit plate. 3. Connect 9-pin female RS232 (Siebe part number CBL-002) connector to PL4 on MI. 4. Connect other end of cable to computer. (Do not exceed 15m (50 feet) in length.) Cable CBL-002 For 9-Pin PC COM Port DB9F DB9F Cable CBL-003 For 25-Pin Modem DB25M DB9F Recommended cable is Belden 8762 or equivalent twisted pair overall screened cable. 2. Connect positive wire to terminal 5 and negative wire to terminal Connect NCP wiring shield to terminal 3. Keep shield continuous between all NCP devices on LAN. 4. Using daisy-chain method, connect MI with other NCP devices in a device-to-device fashion. Do not use wiring tees or stubs. Null Modem Cable RS232 COMMUNICATION WIRING TO A MODEM Connector PL3 on MI is not used. 2. Remove and discard conduit plate. 3. Connect 9-pin female RS232 connector to PL4 on MI. 4. Connect other end of cable to modem. (Do not exceed 15m (50 feet) in length.)
6 DS A /99 POWER SUPPLY WIRING This product contains a non-isolated half-wave rectifier power supply and must not be powered by transformers used to power other devices containing non-isolated full-wave rectifier power supplies. Refer to DS , Guidelines for Powering Multiple Full- Wave and Half-Wave Rectifier Devices from a Common Transformer for detailed information. Twisted or untwisted cable can be used for power wiring. POWER WIRING 2. Ensure that the controller 0V terminal is connected to Earth before connecting the power wiring to the controller. 3. Connect power ground wiring to terminal 1 (0V 24G). 4. Connect power 24Vac wiring to terminal 2 (24H). Primary Ground Frame of Transformer to Known Ground 24Vac Secondary EN CHECKOUT MECHANICAL HARDWARE CHECKOUT 1. Verify network wiring between MI and other devices is installed according to job wiring diagram and national and local electrical codes. 2. Verify 24Vac power is provided from an EN power transformer and wiring is installed according to job wiring diagrams and with national and local electrical codes. 3. Verify RS232 communication is wired according to job wiring diagram and with national and local electrical codes. COLD START PROCEDURE Caution: The cold start procedure clears all configuration data from the nonvolatile EEPROM of the MI. A cold start is normally performed only once when MI is first installed. The cold start is performed using DIP switch S1. Status LED location is shown on page 7. To perform a cold start: 1. Energize MI and verify RUN LED flashes at about once per second. 2. Place DIP switch 1 in ON position. 3. Place DIP switch 8 in ON position and then return to OFF position. Verify the following: RUN, MODEM and WINK LEDs light steady for about one second, then: RUN LED flashes at about once per second. 4. Place DIP switch 1 in OFF position. Cold start procedure does not clear assigned node address (LON only). DIP SWITCH S1 LOCATION BATTERY SETUP The unit is shipped with the battery disabled to preserve battery life. To enable battery, do the following: 1. Remove cover. 2. Remove battery. 3. Remove protective strip from battery. 1. Re-install battery. (Make certain polarity is correct.) 2. Make certain battery is fully seated in battery holder. 3. Re-install cover.
7 07/ DS A SETTING THE ADDRESS LONWORKS EQUIPPED MI The LonWorks network address is fixed in firmware as node 62, Subnet 1. The service pin switch is not used. Address other network devices using an online function of MicroNet Tech Tool. See I/A Series MicroNet Tech Tool Engineering Guide for other LON addressing details. ARCNET AND NCP EQUIPPED MI The ARCNET and NCP network address is fixed as Subnet 0 node 1. Bit 8 should then be toggled ON then OFF. In the initial release, when connecting to MicroSat, set Bits 1 to 4 ON, then toggle Bit 8 ON then OFF. The address will then be set to Subnet 0, node 1. STATUS LED INDICATIONS GENERAL OPERATION CHECKOUT There are five LEDs on the MI. Three of the LEDs (Status LEDs) are under processor control. These LEDs are: RUN - Green LED MODEM - Yellow LED WINK - Red LED Two of the LEDs are hard wired to the receive data lines. These two LEDs indicate activity on the communication ports and are: MASTER RX - Yellow LED LAN RX - Yellow LED 1. Turn ON power to MI. 2. Observe LEDs during normal operation RUN LED flashes at about once per second. 3. Compare other LED indications to Status LED Indications. Indicator Context Action Status Corrective Action RUN (green), MODEM (yellow), WINK (red) Power-up Anytime All three Status LEDs steady on for about 1.5 seconds All three Status LEDs blink rapidly Indicates defaults have been loaded. Unit has a problem. Reload defaults. Anytime Blinks at 50% on, 50% off rate heartbeat MI is operating properly, and has good communication. RUN LED Green Blinks at 25% on, 75% off rate. Indicates no or bad communications. Check communications wiring. Off Unit has a problem. Make certain MI power is on. If power is on and LED remains off, replace MI. Off No modems detected. MODEM LED Yellow Anytime Steady on Blinks every 2 seconds Modem is on-line Modem detected and currently idle. Blinks rapidly Indicates initializing or searching for modem. WINK LED Red Anytime Off Blinks rapidly for 10 seconds. Nothing to report. Indicates LonTalk wink function. STATUS LED LOCATION COMMUNICATIONS CHECKOUT LONWORKS EQUIPPED MNN-MI Ensure MI is powered and connected to LonWorks network. 2. If cover is attached, remove cover. 3. Observe yellow Heartbeat LED on LonTalk Daughter Board and do the following: a. If yellow Heartbeat LED is blinking, go to Step 4. b. If yellow Heartbeat LED is off, check power. The LonWorks MI addresses itself when power is turned on. Service LED should be off if MI has addressed itself correctly. 4. Verify red service LED is off. See I/A Series MicroNet Tech Tool Engineering Guide for details on addressing other devices on a LONWORKS network and downloading applications.
8 DS A /99 LOCATION OF LONTALK DAUGHTER BOARDS LEDs 5. Compare other LED indications to Table Re-install cover. LONTALK DAUGHTER BOARD (LDB) LED INDICATION Indicator Context Action Status Corrective Action Blinks at 50% duty-cycle rate MI is operating properly. Heartbeat LED Yellow Anytime Flash Clear Off Blinks at 80% on, 20% off May remain off for extended amount of time during power up and reset. Indicates flash clear jumper is installed. Make certain MI power is on. If power is on and LED remains off, replace MI. Contact factory service representative for procedure to restore MI to normal operating status. See LDB Flash Clear section. Power-up LED blinks several times If a valid application is loaded, indicates successful power-up. Power-up On Indicates that the neuron application is not running. Neuron applications are not field replaceable. Replace the MI. Service LED Red After Flash Clear Procedure Blinks once per second Indicates that the neuron application is loaded, but the neuron s communication parameters are not loaded, are being reloaded, or have been corrupted. Communication parameters cannot be configured by field personnel. If ENM does not automatically reconfigure the neuron after several seconds, replace MI. Power-up Off Indicates that the neuron application is loaded None required
9 07/ DS A LDB FLASH CLEAR Caution: This function clears the Lontalk Daughter Board (LDB) and ENM of all information. Perform this procedure only when instructed by a factory service representative. If the LDB is flash cleared, all devices on the LDBs network must be reinstalled. If a device is not re-installed and still connected, the LDB may assign another device to the same address. 1. Verify all devices connected to MI are in a manually controlled safe state. 2. Turn OFF power to MI. 3. If cover is attached, remove cover. 4. Place jumper in Flash Clear position (jumper pin 2 and 3). FUSE REPLACEMENT A fuse (2A, fast blow) provides overcurrent protection for the MI. Do the following to check and replace fuse: 1. Turn OFF power to MI. 2. Remove cover. 3. Remove fuse. 4. Check continuity across fuse. 5. If fuse is faulty, replace fuse with same type and rating. 6. Re-install cover. 7. Turn ON power to MI FUSE LOCATION 5. Turn ON power to MI. 6. Wait about 15 seconds and verify red Service LED and yellow Heartbeat LED blink rapidly. 7. Turn OFF power to MI. Caution: When restoring Flash Clear jumper to normal operating position, place jumper on Pin 1 only. Placing jumper on Pin 1 and 2 will initiate a factory test operation. 8. Remove jumper from Flash Clear position and place jumper on Pin 1 only (Normal Operation position). 9. Re-install cover. 10. Turn ON power to MI. SERVICE Components within MI can not be field repaired. If there is a problem with a MI, follow the steps below before contacting your local Satchwell Controls office. 1. Make sure MI is connected and communicating to desired devices. 2. If MI is operating, make sure the LonWorks application is loaded by using MicroNet Tech Tool and the NCP and ARCNET applications are loaded using MicroSat Tool. For more information, see I/A Series MicroNet Tech Tool Engineering Guide, and MicroSat Engineering Guide. 3. Record precise hardware setup indicating the following: Version numbers of applications software. MI firmware version number. Information regarding the MicroNet Tech Tool or MicroSat Tool. A complete description of difficulties encountered. BATTERY REPLACEMENT Should there be a power failure, the clock and RAM are protected with a battery-backup. Do the following to check and replace battery: Caution: All clock functions and data stored in RAM will be lost with power turned OFF and battery removed. 1. Turn OFF power to MI. 2. Remove cover. 3. Remove battery. 4. Check battery. 5. If battery is faulty, replace battery with same type and rating. (Siebe part number E17-129, 3.6V AA Non-rechargeable lithium) 6. Re-install cover. 7. Turn ON power to MI. 8. Dispose of battery properly.
10 07/ DS A MOUNTING DIMENSIONS Dimensions in mm Satchwell Control Systems Limited Farnham Road Slough Berkshire SL1 4UH United Kingdom CAUTION This is a 24Vac device. Do not exceed rated Voltage. Local wiring regulations and usual safety precautions apply. 24Vac must be supplied by a transformer conforming to EN Do not exceed the maximum ambient temperature. Interference with parts under sealed covers invalidates guarantee. The design and performance of Satchwell equipment is subject to continual improvement and therefore liable to alteration without notice. Information is given for guidance only and Satchwell do not accept responsibility for the selection or installation of its products unless information is given by the company in writing relating to a specific application. A periodic system and tuning check of the control system is recommended. Please contact your local Satchwell Service Office for details. Telephone +44 (0) Facsimile +44 (0) An Invensys company 1999 Satchwell Control Systems Limited All rights reserved. Unauthorised copying of any part of the contents is prohibitied. Printed in England.
ENCL-MZ800-WAL ENCL-MX800-PAN MNL-800-101. TAC I/A Series MicroNet MN 800 Series Controller Installation Instructions. Application.
ENCL-MZ800-WAL ENCL-MX800-PAN MNL-800-101 TAC I/A Series MicroNet MN 800 Series Controller Installation Instructions Application The TAC I/A Series MicroNet 800 Series Controllers are programmable, interoperable,
MNL-10Rxx Series MNL-15Rxx Series MNL-20Rxx Series
MNL-10Rxx Series MNL-15Rxx Series MNL-20Rxx Series TAC I/A Series MicroNet MN 100, MN 150, and MN 200 Controllers Installation Instructions Application The TAC I/A Series MicroNet MNL-10Rxx, MNL- 15Rxx,
MCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit
Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit SLCLE5504AUX for Use with Wired C-Bus Networks Instruction Bulletin Retain for future use. Square D Clipsal DIN-Rail Four-Channel Auxiliary Input
MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS
MAKING MODERN LIVING POSSIBLE AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS How to Use This Guide Read this Guide completely as you install and start up your new AK-SC 255 controller.
LevelOne IFE-0500 4-Port PoE + 1-Port TP Industrial Fast Ethernet Switch User Manual
LevelOne IFE-0500 4-Port PoE + 1-Port TP Industrial Fast Ethernet Switch User Manual Ver. 1.0.0-0711 1 FCC Warning This Equipment has been tested and found to comply with the limits for a Class-A digital
DS 1.102 DRTE. AIR ROOM TEMPERATURE SENSOR with fan speed control switches
DS 1.102 02/99 AIR ROOM TEMPERATURE SENSOR with fan speed control switches Specification No. 528-X-XXX* The Active Room Temperature sensor incorporating fan speed control switches is designed to give a
INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930
INSTALLATION GUIDE Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930 Card Reader and Controller Model 3.5 with KIM Swipe Reader Table of Contents 1. Features..................................
ELCOMPONENT LTD. User Manual
ELCOMPONENT LTD R-DCU - Remote Data a Collection Unit User Manual al CONTENTS Page 1. GENERAL... 1 2. SPECIFICATION... 4 3. INSTALLATION AND INSTRUCTIONS... 6 4. INSTRUMENT SET-UP AND RESET... 11 All rights
Perle Protocol Transparent Media Converter Modules
Perle Protocol Transparent Media Converter Modules Installation Guide C-4GPT-DSFP CM-4GPT-DSFP Part# 5500335-10 Overview This document contains instructions necessary for the installation and operation
Installation Instructions for FT-10 Network PowerCommand ATS Communication Module (NCM) Kits 541 0812 and 541 0868
Instruction Sheet 10-2004 Installation Instructions for FT-10 Network PowerCommand ATS Communication Module (NCM) Kits 541 0812 and 541 0868 PowerCommand is a registered trademark of Cummins Inc. InPower
BACnet Automation Interface Module (Network Version)
Sense +V Tx Rx LAN LINK Over ARCNET KBaud BACnet Rx BACnet Tx Archive Valid Port S Tx Port S Rx Low Battery Network- Enhanced Access Default MSTP PTP = Download Required on Rnet and Port S IP Address IP
Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION
Modular, Customizable Wire Replacement 128 / 256 Bit AES Encryption Software Selectable RF Transmit Power Software Selectable Over-the-air Data Rate Modbus ASCII /RTU Compatible Wide Operating Temperature
Secure Ethernet Gateway SEG-1 and SEG-M for IEI Access Systems Installation Manual
Secure Ethernet Gateway SEG-1 and SEG-M for IEI Access Systems Installation Manual Section 1: Introduction SECURITY WARNING: New SEG's shipped after April 2008 will have Telnet setup option enabled by
Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596
Installing the Tracer ZN517 Unitary Controller Ordering number: 4950 0496, 4950 0596 Product overview The Tracer ZN517 controller is a field-installed, application-specific controller that provides directdigital
Cisco TelePresence MCU 4500 Series safety and compliance information
Cisco TelePresence MCU 4500 Series safety and compliance information On this page: Safety information symbols Operating guidelines Safety warnings Technical specifications Compliance information WEEE information
HP UPS R1500 Generation 3
HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications
AXIS T81B22 DC 30W Midspan
INSTALLATION GUIDE AXIS T81B22 DC 30W Midspan ENGLISH About this Document This document includes instructions for installing AXIS T81B22 on your network. Previous experience of networking will be beneficial
EMBEDDED ACCESS CONTROL Hardware Installation Guide
EMBEDDED ACCESS CONTROL Hardware Installation Guide Lenel goentry Hardware Installation Guide, product version 1.00. This guide is item number DOC- ENHW-ENU, revision 1.003, April 2009 Copyright 2009 Lenel
MicroTech III Rooftop and Self Contained Unit Controller BACnet Communication Module (MS/TP)
Installation and Maintenance Manual IM 917-1 Group: Controls Part Number: IM 917 Date: October 2009 Supercedes: IM 917 MicroTech III Rooftop and Self Contained Unit Controller BACnet Communication Module
Application Note - Connecting an Electricity Meter to SolarEdge Devices (Europe and APAC)
February 2015 February 2015 Application Note - Connecting an Electricity Meter to SolarEdge Devices (Europe and APAC) This document describes how to connect an electricity meter to a SolarEdge device (inverters,
5-port 10/100Base-TX Industrial Switch (314500) User s Guide
5-port 10/100Base-TX Industrial Switch (314500) User s Guide COPYRIGHT All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by
HMI display Installation Guide
HMI display Installation Guide Product Description Specifications Important Information o Package Contents o Related Documents o Accessories Cautions and Warnings Mounting and Dimensions o BAC-DIS-ENC
Advantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
Perle 10/100 Ethernet Media Converters
Perle 10/100 Ethernet Media Converters Installation Guide S-110-XXXXXX S-110-XXXXXX-XT P/N 5500302-16 (Rev B) Overview This document contains instructions necessary for the installation and operation of
Installation instructions for Series NRX INCOM communications adapter module
4000 NRX RF DRAWOUT SUBTITLE IMAGE (12/15/2010) Effective July 2015 Supersedes October 2010 IL01301033EH04 Installation instructions for Series NRX INCOM communications adapter module Instructions apply
Fire Fighter Phone System Installation Instructions
Fire Fighter Phone System Installation Instructions Introduction This publication describes the installation procedure for the Fire Fighter s Phone on a 4100U or a 4100ES Fire Alarm Control Panel (FACP).
AI120 AIswitch Series 120 Chassis
AI120 AIswitch Series 120 Chassis Guide INSTALLATION GUIDE Westell Technologies Part # 030-300715 Rev. A Copyright 2015 by Westell Technologies. All Rights Reserved. Westell, Kentrox and Optima Management
IP DSLAM IDL-2402. Quick Installation Guide
IP DSLAM IDL-2402 Quick Installation Guide Table of Contents Package Contents... 3 Overview... 4 Setup the IDL series IP DSLAM... 5 Safety Instruction... 5 Hardware Installation... 6 WEB Configuration...
Quick Installation Guide 24-port PoE switch with 2 copper Gigabit ports and 2 Gigabit SFP ports (af Version 15.4W)
Quick Installation Guide 24-port PoE switch with 2 copper Gigabit ports and 2 Gigabit SFP ports (af Version 15.4W) Table of Contents Introduction.. Power Over Ethernet (PoE) & Features.... Unpacking and
Water Leak Detection System
Water Leak Detection System Installation and Operating Manual 505-334-5865 ph 505-334-5867 fax www.rodisystems.com email:[email protected] 936 Highway 516 Aztec, NM 87410-2828 Manual Revisions and Copyright
Infrastructure Management & Monitoring For Business-Critical Continuity. Liebert AC4. User Manual
Infrastructure Management & Monitoring For Business-Critical Continuity Liebert AC4 User Manual TABLE OF CONTENTS 1.0 INTRODUCTION 1.1 Methods of Viewing and Configuring the Liebert AC4..............................
ZC-24DO CANopen I/O Module: 24 Digital Outputs
Z-PC Line EN ZC-24DO CANopen I/O Module: 24 Digital Outputs Installation Manual Contents: - General Specifications - Technical Specifications - Installation Rules - Electrical connections - DIP-switches
BroadBand PowerShield. User Manual
BroadBand PowerShield User Manual 990-0375G 12/2006 Chapter 1 General Information The PowerShield provides a power source for broadband telephony and other DC applications. Safety This Safety Guide contains
Daikin Magnitude TM Chiller Unit Controller BACnet Communication Module (MS/TP, IP, Ethernet)
Installation and Maintenance Manual IM 963-1 Group: Controls Part Number: IM 963 Date: July 2010 Supercedes: IM 963 Daikin Magnitude TM Chiller Unit Controller BACnet Communication Module (MS/TP, IP, Ethernet)
MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP)
Installation and Maintenance Manual IM 852 Group: Controls Part Number: IM 852 Date: June 2007 Supercedes: New MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP)
Telephone- and leased line modem for industrial applications TD-36
Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased
LIEBERT VNSA Installation Sheet
LIEBERT VNSA Installation Sheet Description The Liebert vnsa network switch is designed for connecting multiple Ethernet-ready devices and comes in various models. The unit may have: A Liebert icom display
Operation and Installation Manual
Operation and Installation Manual RCM-10 Remote Control Monitor and RSM-10 Remote Status Monitor for the CNA-100 & CNA-200 Automations Revision 1.1 9/98 WARRANTY INFORMATION The RCM-10 Remote Control
ADSL Modem Installation Guide. Model # 36R515 Part # 030-300108 Rev. D Revision Date 12/2000. ADSL Modem Installation Guide
ADSL Modem Installation Guide Model # 36R515 Part # 030-300108 Rev. D Revision Date 12/2000 ADSL Modem Installation Guide Installation Instructions Westell ADSL Modem 1. Package Inspection and Contents...2
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual
5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual Content Overview... 1 Introduction... 1 Features... 3 Packing List... 4 Safety Precaution... 4 Hardware Description... 5 Front Panel...
DRM75A 230V 20/100A DIN rail single phase two wire energy meter
DRM75A 230V 20/100A DIN rail single phase two wire energy meter 1.1 Safety instruction 1.2 Foreword 1.3 Performance criteria 1.4 Specifications 1.5 Basic errors 1.6 Description 1.7 Dimensions 1.8 Installation
ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL
RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,
IPG/7700 Hardware Manual SYSTECH. Document number 80-001099-7 Revision A
IPG/7700 Hardware Manual SYSTECH C O R P O R A T I O N Document number 80-001099-7 Revision A Created 2010, and Protected Under the U.S. Copyright Act of 1976. Copyright 2010, SYSTECH Corporation All Rights
Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment
Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment FAST SHIPPING AND DELIVERY TENS OF THOUSANDS OF IN-STOCK ITEMS EQUIPMENT DEMOS HUNDREDS OF MANUFACTURERS SUPPORTED
Mobile Data Power Model: MDP-25
Mobile Data Power Model: MDP-25 Topic Section Features... 2 Operational Features Summary... 2 Back-up Battery Power Internal Charger Voltage Spike Protection RF Noise Filtering Warning of Imminent Loss
AXIS 291 1U Video Server Rack Installation Guide
AXIS 291 1U Video Server Rack Installation Guide About This Document This document describes how to install Axis blade video servers in the AXIS 291 1U Video Server Rack. Updated versions of this document
Model 201 Wiegand Touchpad Reader Installation Guide
Model 201 Wiegand Touchpad Reader Installation Guide P/N 460353001C 15AUG11 2011 UTC Fire & Security. All rights reserved. This document may not be copied in whole or in part or otherwise reproduced without
MOUNTING AND OPERATING INSTRUCTIONS
MOUNTING AND OPERATING INSTRUCTIONS CF 51/55 1. Delivery CF 51/55-1 calculator with battery (optionally with mains power supply) - 1 wall mounting bracket - package with material for sealing, screws, wall
How To Power A Power Control On An Ip40 (Ipl) With A Power Supply (Iplug) With An Ip20 Controller (Iphones) With Power Control (Power Control) With No Antenna) With The Ip20 (Power)
MODEL NUMBER: ISC910-1-0-GB-XX ISC911-5-0-GB-XX IXP20 CONTROLLER SPECIFICATIONS Working Environment Plastic Housing... Power ImproX IXP20 Controller INSTALLATION MANUAL Designed to work in an indoor (dry)
FOSTCDR. Industrial Serial to Multimode Fiber Optic Converter PRODUCT INFORMATION B&B ELECTRONICS. Specifications Serial Technology
FOSTCDR pn 8684R1 FOSTCDR-0812ds page 1/5 Industrial Serial to Multimode Fiber Optic Converter Data Rates up to 115.2 kbps 2.5 Mile (4 km) Range 10 to 30 VDC Input Voltage Wide Operating Temperature 2000V
HM-W536 Install Guide
HM-W536 Install Guide 9/13/2013 IMPORTANT SAFETY INSTRUCTIONS Warning - When using electrical devices, basic safety precautions should be followed to reduce the risk of fire, electrical shock or injury.
Electronic Control Devices The European Product Catalogue 2007
FX14 Field Controller (1/4) FX14 Field Controller The FX14 is an equipment field controller in the Facility Explorer range of products. The controller is designed specifically for commercial Heating, Ventilating,
ADM1TE 5/30A DIN rail single phase two wire energy meter
ADMTE 5/30A DIN rail single phase two wire energy meter. Safety instruction.2 Foreword.3 Performance criteria.4 Specifications.5 Basic errors.6 Description.7 Dimensions.8 Installation.9 Operating.0 Troubleshooting.
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points
Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points Features SELV Compliant No Detection Passive Injector Gigabit Compatible Full Protection
SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS
SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
=============================== WARNING
=============================== WARNING EXPLANATION OF GRAPHICAL SYMBOLS This symbol is intended to alert the user to the presence of unprotected dangerous voltage" within the product's enclosure that
Keysight N4877A Clock Data Recovery and Demultiplexer 1:2
Keysight N4877A Clock Data Recovery and Demultiplexer 1:2 Getting Started Getting Started with the Keysight N4877A Clock Data Recovery and Demultiplexer 1:2 You only need a few minutes to get started
Troubleshooting and Diagnostics
Troubleshooting and Diagnostics The troubleshooting and diagnostics guide provides instructions to assist in tracking down the source of many basic controller installation problems. If there is a problem
RMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions
Heat-Tracing Remote Monitoring Module for the NGC Control System Installation Instructions Tools Required 3 mm slotted screwdriver 3/8 hex key (for -4X only) Approvals Nonhazardous locations Type NM LISTED
UniStream CPU-for-Panel
UniStream CPU-for-Panel Installation Guide USC-P-B10 Unitronics UniStream platform comprises control devices that provide robust, flexible solutions for industrial automation. This guide provides basic
Application/Connection Examples
This Quick Start Guide is designed to familiarize the user with the connection and configuration of the DTS-305 DIN rail mounted single / 3 phase power & energy meter with RS-485 or TCP communications.
Unpacking the Product. Rack Installation. Then, use the screws provided with the equipment rack to mount the firewall in the rack.
About This Guide This guide contains step-by-step instructions for setting up the D-Link DFL-260E/860E Firewall. Please note that the model you have purchased may appear slightly different from those shown
8-port 10/100Base-TX +2-port 100Base-FX Switch. User s Guide
8-port 10/100Base-TX +2-port 100Base-FX Switch User s Guide COPYRIGHT All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by
Hardware Installation Guide
Integrated security for an IP-connected world Hardware Installation Guide June 2012 S2 Security Corporation One Speen Street Suite 300 Framingham, MA 01701 S2 Chat Support: www.s2pronto.com/prontosupport
ConneXium Ethernet Switches TCSESU0 F N0 Quick Reference Guide
31007950 7/2009 ConneXium Ethernet Switches TCSESU0 F N0 Quick Reference Guide 7/2009 31007950.02 www.schneider-electric.com NOTICE Read these instructions carefully, and look at the equipment to become
User Manual Revision 1.400 English Converter / Adapter Ethernet to RS232 / RS485 (Order Code: HD67038-2 HD67038-2-M HD67038-25 HD67038-25-M)
Document code: MN67038-2_ENG Revision 1.400 Page 1 of 25 User Manual Revision 1.400 English Converter / Adapter Ethernet to RS232 / RS485 (Order Code: HD67038-2 HD67038-2-M HD67038-25 HD67038-25-M) for
Installation Guide. Wireless N Access Point EAP110/EAP120/EAP220
Installation Guide Wireless N Access Point EAP110/EAP120/EAP220 CONTENTS Network Topology 01 Hardware Overview 02 Hardware Installation 05 1. Installation Requirements... 05 2. Mounting Bracket... 05
BODi rs BD004 Series Bandwidth-on-Demand Internet with Reliability and Survivability. Quick Start Guide NOTES
NOTES BODi rs BD004 Series Bandwidth-on-Demand Internet with Reliability and Survivability Quick Start Guide This is a Class A device and is not intended for use in a residential environment. Important
PCS0100en 02.2008. Persy Control Services B.V. Netherlands
P-Bus Gateway PBGW2.128 Universal gateway between the P-bus protocol and open standard protocols. The variety of available electrical interfaces on the gateway offers a wide range of possibilities for
CAUTION! THE 7I29 USES VOLTAGE AND POWER LEVELS THAT REPRESENT A HAZARD TO LIFE AND LIMB.
7I29 MANUAL Rev 1.5 CAUTION! THE 7I29 USES VOLTAGE AND POWER LEVELS THAT REPRESENT A HAZARD TO LIFE AND LIMB. THE 7I29 IS INTENDED FOR USE BY OEMS THAT WILL INTEGRATE IT INTO A SYSTEM WITH INTERLOCKS AND
SCREENLOGIC INTERFACE WIRELESS CONNECTION KIT
SCREENLOGIC INTERFACE WIRELESS CONNECTION KIT FOR INTELLITOUCH AND EASYTOUCH CONTROL SYSTEMS INSTALLATION GUIDE IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS Technical
Disclaimers. Important Notice
Disclaimers Disclaimers Important Notice Copyright SolarEdge Inc. All rights reserved. No part of this document may be reproduced, stored in a retrieval system, or transmitted, in any form or by any means,
Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811
Instruction Sheet 1-2003 Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit 541 0811 PURPOSE OF KIT A CCM-T is used to monitor and control an automatic transfer switch. The
Rack mounted telephone- and leased line modem for industrial applications
Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as
esata External Storage
esata External Storage Operation Manual DA-ES110 Before reading this manual This operation manual contains basic instruction on installing and using esata External Storage, an IDIS product. Users who are
NGC-30-CR -CRM -CRMS -CTM -CVM
NG-0-R -RM -RMS -TM -VM ontrol and monitoring modules for use with the Raychem NG-0 Installation Instructions Description The NG-0-RM/-RMS and NG-0-TM provide ground-fault and line current sensing, alarming,
TrueAlarm Fire Alarm Systems
TrueAlarm Systems UL, ULC, CSFM Listed; FM Approved* Network Annunciators; es Features Provides a dedicated local area network (LAN) for connection of a TrueSite workstation server to remote clients: es
Duct Humidity Transmitter
SDC-H Duct Humidity Transmitter Features Replaceable sensor element Humidity measurement for air ducts Minimum and maximum value memory 0 0V, 0 0mA or 0V, 4 0mA measuring signals selectable with jumpers
INSTALLATION INSTRUCTIONS
LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.
PRO 5000 CPE 1D Quick Installation Guide
PRO 5000 CPE 1D Quick Installation Guide Introduction This Quick Installation Guide covers the basic installation of the PRO 5000 CPE. For more information, refer to the relevant sections in the Product
AC-115 Compact Networked Single Door Controller. Installation and User Manual
AC-115 Compact Networked Single Controller Installation and User Manual December 2007 Table of Contents Table of Contents 1. Introduction...5 1.1 Key Features... 6 1.2 Technical Specifications... 7 2.
CM400 High Speed Cable Modem User Manual
User Manual July 2015 202-11412-02 350 East Plumeria Drive San Jose, CA 95134 USA Support Thank you for selecting NETGEAR products. After installing your device, locate the serial number on the label of
4-CH Video Server SED-2310Q. Ver. 061031. User s Manual
4-CH Video Server SED-2310Q Ver. 061031 User s Manual 0 0 PRECAUTIONS 1. Read these instructions All the safety and operating instructions should be read before the product is operated. 2. Heed all warnings
Liebert Universal Monitor
Infrastructure Management & Monitoring For Business-Critical Continuity Liebert Universal Monitor User Manual TABLE OF CONTENTS 1.0 INTRODUCTION 1.1 Methods of Viewing and Configuring the Liebert Universal
Perle 10/100/1000 Ethernet Media Converter Module
Perle 10/100/1000 Ethernet Media Converter Module Installation Guide C-1110-XXXXX CM-1110-XXXXX C-1110-SFP CM-1110-SFP Unmanaged Module Managed Module Unmanaged Module Managed Module P/N 5500308-21 Overview
How To Use A Power Supply Unit (Upu)
BRAVER UPS (Uninterruptible Power System) User s Manual Safety CAUTION! This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user replaceable parts.
33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application
33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application Features Compliant with the IEEE802.3at Standard -40 to +60 C Temperature Range Diagnostic LEDs Full Protection
FTW 175 VERIZON Wireless Monitoring System Reference Manual Part Number 7911751VERIZON
FTW 175 VERIZON Wireless Monitoring System Reference Manual Part Number 7911751VERIZON SERIAL NUMBER Flash Technology, 332 Nichol Mill Lane, Franklin, TN 37067 (615) 261-2000 Front Matter Abstract This
Manual. Simrad StructureScan LSS-1 Sonar Module. English
Manual Simrad StructureScan LSS-1 Sonar Module English www.simrad-yachting.com A brand by Navico - Leader in Marine Electronics Disclaimer As Navico is continuously improving this product, we retain the
HP R12000 and R18000 DirectFlow UPS User Guide
HP R12000 and R18000 DirectFlow UPS User Guide Abstract This document includes installation, configuration, and operation information for the HP R12000 and R18000 DirectFlow UPS. This document is for the
MultiVOIP FX FXS-Only SIP Gateways
MultiVOIP FX FXS-Only SIP Gateways MVPFXS-8 MVPFXS-16 MVPFXS-24 Cabling Guide MultiVOIP MVPFXS-8/16/24 Cabling Guide Cabling Guide MultiVOIP FX SIP FXS-Only Gateways Models MVPFXS-8, MVPFXS-16, MVPFXS-24
StorTrends 3400 Hardware Guide for Onsite Support
StorTrends 3400 Hardware Guide for Onsite Support MAN-3400-SS 11/21/2012 Copyright 1985-2012 American Megatrends, Inc. All rights reserved. American Megatrends, Inc. 5555 Oakbrook Parkway, Building 200
alpha DSL WTM HS Instructions for use ADSL modem alpha DSL WTM HS
alpha DSL WTM HS Instructions for use ADSL modem alpha DSL WTM HS Safety precautions Safety precautions The DSL modem alpha DSL WTM HS complies with the European norm EN60950 safety of information technology
is then retained absolutely without interruption.
Page 1 of 11 DC UPS uninterruptible power supplies - DC UPS module 15 A Compact design, only 50 mm wide Absolutely interruption-free buffering of power failures through immediate electronic connection
2013 VTech Printed in China 91-009656-000 US
Rechargeable Power Pack User s Manual 2013 VTech Printed in China 91-009656-000 US INTRODUCTION The Rechargeable Power Pack makes it easier than ever to keep the InnoTab 3 or InnoTab 3S charged and ready
Table of Contents. Creating a VC1000 Network... 3
2 Table of Contents Creating a VC1000 Network... 3 Topology... 3 Unit ddressing... 4 Terminating Resistors... 5 Shielding... 5 Interconnecting the common... 6 ias Resistors... 6 VC1000 Hardware Configuration...
LDG DTS-4/4R Desktop Coaxial Switch / Remote
LDG DTS-4/4R Desktop Coaxial Switch / Remote LDG Electronics 1445 Parran Road, PO Box 48 St. Leonard MD 20685-2903 USA Phone: 410-586-2177 Fax: 410-586-8475 [email protected] www.ldgelectronics.com
FriendlyNet Hub 5-Port or 8-Port Ethernet Hub User s Manual
FriendlyNet Hub 5-Port or 8-Port Ethernet Hub User s Manual Asanté Technologies, Inc. 821 Fox Lane San Jose, CA 95131 Copyright Notice Copyright 1997 by Asanté Technologies, Inc. All rights reserved. No