Harmonic Distortion and Variable Frequency Drives



Similar documents
Product Data Bulletin

The Facts About Harmonics and Power Factor. Power Quality: Harmonics & Power Factor Correction

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS

Specifying a Variable Frequency Drive s

Power System Harmonics

Introduction. Harmonics and IEEE 519 Page 1 of 19

Line Reactors and AC Drives

VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY

Power Quality Issues, Impacts, and Mitigation for Industrial Customers

LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE

Interpreting IEEE Std 519 and Meeting its Harmonic Limits in VFD Applications

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

FREQUENCY CONTROLLED AC MOTOR DRIVE

Application Guide. Power Factor Correction (PFC) Basics

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

UNDERSTANDING POWER FACTOR AND INPUT CURRENT HARMONICS IN SWITCHED MODE POWER SUPPLIES

Power Supplies. 1.0 Power Supply Basics. Module

Phase-Control Alternatives for Single-Phase AC Motors Offer Smart, Low-Cost, Solutions Abstract INTRODUCTION

Pulse Width Modulated (PWM)

Considering the effects of UPS operation with leading power factor loads

Relationship between large subject matter areas

Design a Phase Interleaving PFC Buck Boost Converter to Improve the Power Factor

Properties of electrical signals

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM

The Different Types of UPS Systems

LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES

Advantages of 6-Pulse VFD with Lineator AUHF vs Active Front End (AFE) Drives

Harmonics in your electrical system

HVAC Applications. VFD considerations for HVAC systems...

The Different Types of UPS Systems

Discover the power of e-learning! The Quick Guide to AC Variable Frequency

Electromagnetic Compatibility (EMC) Low-Frequency Standards. Standards on Low-Frequency Emission: IEC

SECTION VARIABLE FREQUENCY DRIVES

Pulse Width Modulated (PWM) Drives. AC Drives Using PWM Techniques

The HVAC SOLUTION DELIVERING POWER...SAVING ENERGY

APPLICATION OF IEEE STD HARMONIC LIMITS

7-41 POWER FACTOR CORRECTION

Rectifier circuits & DC power supplies

Principles of Adjustable Frequency Drives

Additional Benefits of VFDs In addition to energy savings and better process control, VFDs can provide other benefits:

The Different Types of UPS Systems

SmartVFD HVAC and BYPASS

EMC STANDARDS STANDARDS AND STANDARD MAKING BODIES. International. International Electrotechnical Commission (IEC)

Rotating Machinery Diagnostics & Instrumentation Solutions for Maintenance That Matters

Variable Frequency Drives and Energy Savings

Survey of Harmonics Measurements in Electrical Distribution Systems

HVAC DRIVE H300 HVAC Drive for Building Automation

Triplen Harmonics Mitigation 3 Phase Four-Wire Electrical Distribution System Using Wye- Zig-Zag Transformers

Power Quality Standards for Electric Service

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS

PHASE CONVERSION TECHNOLOGY OVERVIEW

VARIABLE FREQUENCY DRIVES Revised 4/30/ Mechanical Systems

DC UPS. RTB.e A. IMB.e/ITB.e kva. E2001.e/E3001.e kva. Input voltage: 110/125/220 Vdc. 115/120/230 Vac, 1-phase (IMB.

HOW HARMONICS HAVE CONTRIBUTED TO MANY POWER FACTOR MISCONCEPTIONS

Paralleling Power Sources Which Share a Common Neutral

DESIGNING MODERN ELECTRICAL SYSTEMS WITH TRANSFORMERS THAT INHERENTLY REDUCE HARMONIC DISTORTION IN A PC-RICH ENVIRONMENT

Session 10: General Overview of Interconnection Standards & Grid Codes for High Penetration PV October 21, 2015 Santiago, Chile

Balun Parameter Definitions & Measurement May 2004

Unidrive M Energy Savings

Power System Harmonic Fundamental Considerations: Tips and Tools for Reducing Harmonic Distortion in Electronic Drive Applications

Series 7400 M (10/20/30/40/60 kva) Maximum Protection For Mission Critical Network Applications. Series 7400 M

Understanding Variable Speed Drives

Three phase circuits

Tamura Closed Loop Hall Effect Current Sensors

Power Analysis of PWM Motor Drives

Power Quality Analysis and Evaluation at Water Pumping Station Supplied by Medium Voltage

WIND TURBINE TECHNOLOGY

Modeling and Analysis of DC Link Bus Capacitor and Inductor Heating Effect on AC Drives (Part I)

Electricity Meter in the age of Photovoltaic

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

APPLICATION NOTE TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION. Abstract.

Power Quality. Uninterruptible Power Supply

Mitigating data center harmonics

Impedance Matching and Matching Networks. Valentin Todorow, December, 2009

How To Improve Power Quality

The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity

Understanding Power Factor, Crest Factor, and Surge Factor. White Paper #17

Speed Control Methods of Various Types of Speed Control Motors. Kazuya SHIRAHATA

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA

DIODE CIRCUITS LABORATORY. Fig. 8.1a Fig 8.1b

Kit Watt Audio Amplifier

EET272 Worksheet Week 9

City of Leesburg, Florida I.T. Data Center APPENDIX A TOSHIBA UPS INFORMATION

FACTS. Solutions to optimise network performance GRID

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT

Constructing a precision SWR meter and antenna analyzer. Mike Brink HNF, Design Technologist.

Power Factor Correction for Power Systems First Semester Report Spring Semester 2007

APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 15kVA and 20kVA Smart-UPS RT 230VAC Uninterruptible Power Supply

32VFD Variable Frequency Drives for Centrifugal Chillers

Practical Overview of Mine Power System Harmonics

Analog & Digital Electronics Course No: PH-218

Table of Contents. The Basics of Electricity 2. Using a Digital Multimeter 4. Testing Voltage 8. Testing Current 10. Testing Resistance 12

Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka

Op Amp Circuit Collection

Neutral Currents in Three Phase Wye Systems

Semiconductor Diode. It has already been discussed in the previous chapter that a pn junction conducts current easily. Principles of Electronics

How To Limit Voltage Unbalance

Transcription:

Harmonic Distortion and Variable Frequency Drives Definitions Variable Frequency Drives (VFDs); sometimes referred to as variable speed drives. Harmonic Distortion is a measure of the amount of deviation from a pure sinusoidal wave form that can be caused by a non-linear load (a VFD is considered a non-linear load because it only draws current from the power line as required). Distorted Waveform = fundamental (60Hz sinusoidal waveform) + multiples of the fundamental frequency, typically the 5th, 7th, 11th, 13th, and 17th, etc. (e.g. 5 x 60Hz = 300Hz, 7 x 60Hz = 420Hz, etc.) Voltage Distortion is the deviation in the supplied voltage from a pure sinusoidal waveform. Current Distortion is the deviation in current drawn by a non-linear load from a purely sinusoidal waveform. Pulse Width Modulation (PWM) is a means by which nearly sinusoidal current can be caused to flow in a motor, at a desired frequency (40, 50, 60Hz for example), by sinusoidally varying the pulse width of a much higher frequency squarewave. Point of Common Coupling (PCC): A connection point in a power system where it is important and desirable to control the level of harmonic content and/or voltage distortion (deviation from a pure sinewave). Total Demand Distortion (TDD) is the ratio between the RMS sum of all the harmonic currents drawn and (divided by) the total fundamental current (at 60Hz in N.A.) at a point of common coupling (over a 15 or 30 minute period). continues on page 3... 1

Unidrive SP Key Features Static and rotational auto tune 8 preset speeds; 8 sets of accel / decel rates Catch spinning motor function Built-in PID Energy savings mode Power metering Network connectivity Easy-to-use, plain text LCD keypad 3 option slots for other communication options and/or for I/O expansion SmartCard for parameter cloning FREE energy saving software and drive setup tools Clean, efficient and reliable motor control with low harmonic distortion. Designed to meet the demand for clean power, Control Techniques offers the latest in both microprocessor and power semiconductor technology to provide the industry with economical, compact and highly flexible active front end drive packages. These packages integrate Control Techniques Unidrive SP Active Front End controller and EMC filtering for high performance with extremely low harmonic distortion. Active Front End Features Integral Active Front End controller and EMC filter 100kA fault rating NEMA 1 enclosure is standard, other enclosure ratings available Optional easy-to-use electronic bypass control Active Front End Benefits Low Harmonic Distortion IEEE519-1992 harmonic compliance at the drive input terminals Won t interfere with sensitive equipment Not sensitive to line imbalances Superior to 12- and 18-pulse solutions Maintains Unity Power Factor Easy Installation Available up to 2,000hp at 460V Single package no need for external filters or transformers UL508A approved 100kA SCCR ratings Flexible Solutions Wide range of I/O and communications option modules including LonWorks Electronic bypass three contactor and soft start option 2

Active Front End Emerson Harmonic Reduction Technologies The first stage of a PWM VFD (the rectifier) creates distortion of the AC line as the rectifier charges a capacitor bank called the DC bus. Current is drawn from the AC line only when the rectified voltage exceeds the voltage level to which the capacitor is charged. Severe harmonic distortion can have several detrimental effects. Over the years, several standards have been adopted to address these potential effects in terms of recommendations for maximum allowable levels of distortion. One such standard cited frequently in North America is IEEE-519. Rectifier DC Bus Inverter THDV Level Sensitive Applications Airports 3% Hospitals Telephone companies THDV Level General Applications 5% Office buildings Schools THDV Level Dedicated Systems 10% Factories Figure 3 Rectified AC DC Bus Figure 1 Typical PWM VFD IEEE-519 Standard ANSI/IEEE Standard 519, IEEE Guide for Harmonic Control and Reactive Compensation of Static Power Converters, was published in 1981. It recommended maximum levels of totalharmonic-voltage-distortion (THDV) at the point that the utility connects to different types of users (point of common coupling, or PCC), shown in Figure 2. Different maximum levels were provided for different types of buildings (see Figure 3). Grid Transformer Cable PCC Cable i h Panel i h ih i h Drive 1 Drive 2 Drive 3 Rectified Voltage Peak DC Bus Figure 4 Current Current only flows when the rectified voltage exceeds the voltage that the capacitor is charged to. Current Flow thus becomes non-linear (not sinusoidal). Voltage distortion created by VFDs can cause flat-topping of power-system voltage waveforms which, in turn, can cause sensitive electronic equipment to malfunction. The area between the two waveforms shown in Figure 5 is the actual level of distortion and is expressed as a percent of the fundamental pure 60Hz waveform. Other Loads Drive n Distortion i h Figure 2 Point of Common Coupling Distortion Figure 5 Flat-topped power-system voltage waveform 3

IEEE-519 Compliance IEEE-519 was revised in 1992 to provide recommendations on maximum allowable levels of harmonic current distortion (see Figure 6). The new standard also defined the maximum recommended contribution of any individual harmonic. The amount of allowable distortion is based on a ratio of the short circuit current available to the distribution system (ISC maximum short circuit current available at point of common coupling), and the maximum load current recognized by the distribution system (I l the maximum load current at the point of common coupling). Basically, a large transformer feeding a building will have more short circuit current available and the ratio becomes larger allowing for a higher level of harmonics. I SC /I I h < 11 11 h < 17 17 h < 23 23 h < 35 35 h < 20 4.0 2.0 1.5 0.6 0.3 20-50 7.0 3.5 2.5 1.0 0.5 50-100 10.0 4.5 4.0 1.5 1.0 100-1000 12.0 5.5 5.0 2.0 1.0 > 1000 15.0 7.0 5.0 2.0 1.0 Figure 6 - IEEE-519 recommended maximum individual current harmonics Also introduced by IEEE-519-1992 is the term Total Demand Distortion (TDD) which provides recommendations for maximum total current distortion (contribution by all individual harmonics) as a percent of the total demand load current during a 15 or 30 minute demand (see Figure 7). Again the TDD is referenced to the ratio of the load current to the short circuit current available. I SC /I I Total Demand Distortion (TDD) < 20 5.0 20-50 8.0 50-100 12.0 100-1000 15.0 > 1000 20.0 Figure 7 - IEEE-519 Total Current Demand Distortion The key issue with current distortion is that it creates voltage distortion. However, current distortion can also create increased audible noise as well as additional heating of distribution transformers and the cables providing power to the equipment generating the harmonics. IEEE Standard 519-1992 states, Within an industrial plant, the PCC is the point between the nonlinear load and other loads. This statement has been widely misunderstood and misused. Some consulting engineers have interpreted this to mean that the current distortion is to be measured at the VFD input-power connections, a total misunderstanding of the purpose behind this standard and use of it. The drive itself is the only component in the entire electrical system that will see the level of distortion (measured at the drive input terminals). Main taining some level of current distortion at the input of the drive will not guarantee any level anywhere else in the building. This misapplication of the standard has led to use of costly and energy-consuming reactors, passive filters, multi-pulse drives and active filters that are in many cases unnecessary. Because these devices can increase the initial cost of the drives by as much as 500%, it is important to understand the intent and purpose of this standard and use it accordingly. A variety of information is required to determine whether or not any form of harmonic mitigation is necessary to comply with a recommended level of distortion as defined by IEEE-519: The transformer feeding the building must be defined (KVA and % impedance). The larger the transformer, the stiffer the power line resulting in lower levels of harmonic distortion. The total number of drives and their cumulative horsepower must be defined. A few small drives on a very large transformer will have very little effect. The amount of non-linear load (drives) versus the building s linear load will, to a large degree, determine the total amount of current distortion thus determining if the drives are a big or small percentage of the load on the transformer. Using this information, an estimate of the current and voltage distortion can be made. More accurate calculations can be made if additional information is available such as existing harmonic distortion levels and wire lengths/sizes between the drives and the PCC. As a rule of thumb, unless the drives constitute more than 30% of the load on the main distribution transformer from which they receive power, there is little need to be concerned about harmonics and standard 6-pulse drives should be sufficient. In most commercial buildings, the fan and pump drives being used are not more than 30% of the total load. If any doubt remains, however, a harmonic analysis of a given installation should be performed. 4

Harmonic Mitigation Techniques for AC Drives If harmonics are higher than desired after performing an analysis, there are a number of ways to mitigate the harmonic distortion. Harmonics are caused by the first stage of a VFD (the rectifier). The distortion of input current feeding this rectifier on a standard (6-pulse) VFD ranges between 70-100%. Reactors AC line reactors (see Figure 8) and DC link chokes (reactors) will make the current drawn from the power line more sinusoidal (see Figure 9). With an AC line reactor or DC link choke, the distortion of the input current will typically be 30-40% compared to the 70-100% of a drive with no reactor. Reactors will increase the initial cost of the drive 10-20% and are included as standard in many drives 5 horsepower and larger. AC line reactor As a general rule, the total AC reactance should not exceed 5%. This is sufficient to meet the harmonic levels required by international standard IEC-61000-3-12 for a balanced 3 phase rectifier with Rsce (the ratio of the drive-rated current-tosupply fault level at the point of common coupling with other supply users) greater than or equal to 120 (i.e. primarily a 5th harmonic not exceeding 40% and a THD not exceeding 48%). DC Link Chokes DC link chokes can be used individually (typically on the positive DC bus) or in pairs with one each on the positive and negative bus. When two DC reactors are used on the bus, the inductance is additive. Equivalent impedances can be achieved using either one larger reactor on the positive or negative bus or two smaller reactors on both the positive and negative bus. DC inductors Figure 8 Figure 10 Ideal No Reactor With Reactor Figure 9 Blue- standard 6 pulse, Red-6 pulse with AC reactor or DC link choke, Green pure sinusoidal current flow AC line reactors have the dual benefit of convenience and providing additional attenuation of AC power supply disturbances such as surges or poor phase balance. They do however cause a reduction in DC link voltage so they can create voltage drop issues. An oversized AC line reactor with a low line voltage can create enough of a voltage drop that not enough output voltage can be created to provide full motor torque and horsepower. A key advantage of DC link inductors is the minimal drop in DC voltage with increasing load. For reactance values on the order of 4%, the benefit for harmonics is similar to that of the AC reactor but with slightly greater benefit for the lower order harmonics such as the 5th. However, the benefit is subject to diminishing returns since the harmonics can never be reduced below the levels for an infinite inductance (e.g. 20% for the 5th harmonic) and in practice, the 5th harmonic is unlikely to be reduced cost-effectively to below 30%. The disadvantage of DC inductors is that the rectifier becomes more susceptible to the effects of supply surges and poor balance and must therefore be equipped with adequate surge suppression. To avoid undue sensitivity to supply unbalance, it is important to choose inductor values such that the inherent resonant frequencies with the DC capacitors do not coincide with the characteristic frequencies of an unbalanced supply. 5

Used alone, DC inductors do not reduce the high-order harmonics significantly and may even increase them. For this reason it may be desirable to use standard AC reactors. The use of Emerson Control Techniques VFDs with AC line reactors and DC link chokes varies based on the drive s horsepower and voltage ratings. Drives smaller than 5 horsepower have neither AC line reactors or DC link chokes since their harmonic impact is normally negligible. The equivalent impedance of the reactors used on larger drives will vary as well based on horsepower and voltage with an average of approximately 5%. Midsize drives (greater than 5 horsepower and smaller than 100 horsepower) will use DC link chokes (either one on the positive leg or one on both the positive and negative leg). Larger drives (100 horsepower and larger) will use AC line reactors. Multi-Pulse Drives (12 and 18-Pulse) An additional method of mitigating harmonics is the use of 12-pulse drives (see Figure 11) and 18-pulse drives (see Figure 12). These drives contain multiple rectifiers as well as an expensive transformer with one primary and multiple secondary. These configurations act to cancel some of the lower level, higher amplitude harmonic currents. +20 0-20 INVERTER STANDARD AC DRIVE Figure 12 18-pulse rectifier Includes transformer (1 primary, 3 secondaries) and 3 input bridges and balancing reactors Refer to Figure 13. Current distortion at the input terminals is approximately 10% for 12-pulse drives; 5% for 18-pulse drives. 12-pulse input current INVERTER 18-pulse input current Figure 11 12-pulse rectifier includes transformer (1 primary, 2 secondaries) and 2 input bridges and balancing reactors Figure 13 These technologies have several drawbacks: Initial cost of a 12-pulse drive is approximately 400% higher than a standard 6-pulse drive (500% higher for 18-pulse drive) Input power lines must be very well balanced (1% or better); even a slight imbalance of 3% will negate nearly all of the harmonics mitigation. Physical size extra bridges and custom transformers increase size requirements Higher operating losses create lower efficiencies 6

Passive Filters Refer to Figure 14. Passive filters comprised of a tuned configuration of capacitors, inductors and in some cases resistors, are sometimes used to eliminate specific harmonics (typically the 5th, 7th, etc.). Depending on the level of mitigation, use of passive filters increases the total cost of the installed drives by 200-500%. These filters are slightly more tolerant of line imbalances but also have losses associated with using them. Active filter reduces the source current distortion to less than 5% THID. Current sensing C/T Active Harmonic Filter Non-linear loads draw distorted current Active filter supplies only the distortion current demanded by non-linear loads. Figure 15 active filter L L Line inverter (rectifier) Motor inverter Inductor-capacitor-inductor (LCL) filter Figure 16 - Active Front End Figure 14 passive filter Active Harmonic Filter and Active Front End Newer technologies are the active harmonic filter (AHF) and the active front end (AFE) VFD. A single AHF can filter the harmonics of several VFDs or an entire facility. The AHF is in parallel with the other loads and only handles the corrective harmonics required to offset those generated by the nonlinear loads. The current distortion at the input of the filter will be less than 4% and these filters are relatively unaffected by line imbalances. The AFE is really a combination of two inverters. One inverter powers the motor and the other actively draws power from the line. The AFE handles both the fundamental current and the harmonic currents created by the load. Both techniques act like active audible noise reduction techniques. If a 5th harmonic is detected, a harmonic of equal and opposite amplitude is generated that effectively eliminates the 5th harmonic. These techniques, while still costing as much as an 18-pulse drive, have the most promise to become lower in cost. Summary When choosing VFDs, it is important to properly compare and analyze drive manufacturers products including a complete harmonic analysis based on individual drive sizes and quantities being used and the system to which they are connected. While one manufacturer s products may have better performance at a given frame size, the aggregate performance of all the sizes and quantities of drives being used on any individual project may indicate another manufacturer s products are the better choice. The easy-to-use Unidrive SP keypad can be customized to display parameters using your terminology, and any of five foreign languages. 50hp Unidrive SP AFE system 7

Driving Technology................................................... www.controltechniques.com Drive and Application Centers International Distribution Centers AMERICAS Toll-free: 1 800-893-2321 info.cta@emerson.com Headquarters / Minneapolis Drive Center Tel: 1 952 995 8000 Fax: 1 952 995 8020 Calgary Drive Center Tel: 1 403 253 8738 Fax: 1 403 255 4323 Charlotte Application Center Tel: 1 800 893 2321 Cleveland Drive Center Tel: 1 216 901 2400 Fax: 1 216 901 2401 Detroit Application Center Tel: 1 248 882 2652 Grand Island Support & Service Center Tel: 1 716 774 1193 Fax: 1 716 774 8327 After Hours: 1 716 556 1639 Portland Drive Center Tel: 1 503 266 2094 Fax: 1 503 266 1152 Providence Application Center Tel: 1 401 392 4256 Fax: 1 401 392 4250 Salt Lake City Application Center Tel: 1 801 566 5521 Fax: 1 801 566 5673 Toronto Application Center Tel: 1 905 948 3402 Fax: 1 905 948 3418 LATIN AMERICA Miami Application Center Tel: 1 954 846 5082 Fax: 1 954 494 4027 São Paulo Application Center Tel: 55 11 3618 6661 Fax: 55 11 3618 6611 For a listing of Control Techniques global facilities, please visit: www.controltechniques.com HVACR Support in the Americas The Control Techniques Center of Engineering Excellence for HVACR is located in Eden Prairie, Minnesota. This facility manufactures HVACR systems and provides its customers with pre- and post-sales drive support. Control Techniques Americas Headquarters 7078 Shady Oak Road Eden Prairie, MN 55344 Telephone: 1-800-893-2321 or (952) 995-8000 www.hvacr-drives.com P/N WHP-HARMONIC-110418 Control Techniques 2012. The information contained in this brochure is for guidance only and does not form part of any contract. The accuracy cannot be guaranteed as Control Techniques has an ongoing process of development and reserves the right to change the specification of its products without notice. Printed in the USA.