Advanced FBC: Changes to the Wind Load Provisions of the 2010 Florida Building Code and ASCE 7-10



Similar documents
2010 Florida Building Code Wind Standard

Informational Bulletin

The Florida Building Code

Wind Load Design Criteria 3.0

determining wind and snow loads for solar panels America s Authority on Solar

Wind-Resistive Design of Wood Buildings

Florida Building Code, 5th Edition (2014) June 30 th, 2015

CITIZENS PROPERTY INSURANCE CORPORATION. STREET ADDRESS: Gulf Blvd, Maderia Beach, FL Six story masonry residence

Appendix B Florida Building Code Building Section Public Shelter Design Criteria

Insurance Mitigation Factors for Homeowners Purchasing Garage Doors In Florida

Status of Building Codes in New Jersey and New York: The Future of Resilience in a Post-Sandy Environment

The Florida Building Code

Solar America Board for Codes and Standards

ANSI/SPRI Wind Design Standard Practice for Roofing Assemblies

Load Design Charts. R-CONTROL SIPs STRUCTURAL INSULATED PANELS. CONTROL, NOT COMPROMISE.

Windows, skylights, vents, and glazed portions of doors are critical components of a building s

providing documentation that validates the year of construction. Acceptable documents include

Wind Speed Maps for the Caribbean for Application with the Wind Load Provisions of ASCE 7

Wind Mitigation Inspection

Vestibule Case Study. Vestibule Requirement Intent [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, , ]

Property Policyholder Risk Improvement Report and Hurricane Survey

Wind Mitigation Discount Plan

(800) (562) A Subsidiary of the International Code Council *Revised April 2014

INTERNATIONAL BUILDING CODE STRUCTURAL

Advanced Wind Mitigation Methodologies Pt. 2 Online Retrofit Course. Section 1: Introduction

Quick RefeRence Guide comparison of Select nfip and Building code Requirements for Special flood Hazard Areas

FLORIDA PRODUCT APPROVAL

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: CONCRETE ROOF TILES REPORT HOLDER:

FLORIDA BUILDING CODE RESIDENTIAL

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: CONCRETE ROOF TILES REPORT HOLDER: BORAL ROOFING

DEPARTMENT OF ACCOUNTING AND GENERAL SERVICES. Adoption of Chapter Hawaii Administrative Rules SUMMARY

CF-Mesa, CF-Light Mesa, CF-Flute, CF-Metl-Plank, CF-Striated, CF-Santa Fe, CF-Architectural Flat, CF...

APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET

Tornado Risks and Hazards in the Southeastern United States


Protecting YOUR NEW HOME FROM Wind Damage

Report on. Wind Resistance of Signs supported by. Glass Fiber Reinforced Concrete (GFRC) Pillars

SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION

During storm events, a roof is expected to perform many functions from preventing water intrusion

Computer Program for the Analysis of Loads On Buildings. Using the ASCE 7-93 Standard. Stephen E. Browning. Master of Engineering.

Building Permit Application Packet. BUILDING CODES Adopted by La Plata County For Enforcement In The Unincorporated Areas Of La Plata County

Specifying Windows. Performance Standards

Proposed 9 th Edition of the Massachusetts Building Code (780 CMR) Summary of Key Changes to the Residential Volume 12/3/15 (Rev 1/13/16)

HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES

Commercial Residential Model Reviews

Dollars & Sense of Compliance!

Structural Damage Due to Floods

MAJOR 2015 MN RESIDENTIAL CODE CHANGES Effective Date: January 24 th, 2015

Florida Building Code Cost and Loss Reduction Benefit Comparison Study

TechPractices: Home Front Homes:

Comparison of the Structural Provisions in the International Existing Building Code 2012 versus the Rhode Island State Rehabilitation Code

The replacement or modification of existing windows shall comply with the following requirements:

Basic Assessment and Characterization of Damage

Loads and Seismic Design National Building Code Wind and Snow Importance Factors

Conservatory Roof Structural Information Guide

DEPARTMENT OF ACCOUNTING AND GENERAL SERVICES. Adoption of Chapter Hawaii Administrative Rules SUMMARY

ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC

PROJECT SUMMARY. Scope of work details: (If phased construction, please see plan submittal guidelines.)

2Floodplain Management Regulations, Building Codes, and Standards

RESIDENTIAL ROOF PERMITTING A REFRESHER WORKSHOP September 11, 2014

Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013

Approval Standard for Class 1 Exterior Wall Systems

REQUIREMENTS FOR SUBMITTING PLANS FOR NEW CONSTRUCTION

Protecting Roofing Systems Against Windstorm Damage

EN :2005. Wind actions

Hurricane Damage. How Wind Forces Affect Homes

THE DOW CHEMICAL COMPANY Issued: August 1, LARKIN CENTER 1605 JOSEPH DRIVE MIDLAND MICHIGAN (989)

CERTIFICATE OF COMPLIANCE Prescriptive Residential Re-roof Project Name:

Certification: Building Plans Examiner. Exam ID: B3

M E M O R A N D U M. To: Partnership for Safer Buildings Date: 21 March 2003

Florida Building Code Advanced Training: Residential Roofing Shingles

2014 FLORIDA BUILDING CODE

PLEASE RETURN DENIAL COMMENTS WHEN RESUBMITTING PLANS*

CITY OF FLORIDA CITY Building and Zoning Department 404 West Palm Drive Florida City, FL ROOFING PERMIT APPLICATION

CITIZENS PROPERTY INSURANCE CORPORATION BUILDING TYPE II AND III MITIGATION VERIFICATION AFFIDAVIT

Impact-Resistant Windows and Sliding Glass Doors

Prof. Dr. Zahid A. Siddiqi, UET, Lahore WIND LOAD

Catastrophe Bond Risk Modelling

Wind vs. Water and Unique Monroe County Mitigating Factors for Wind Damage

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

2008 Florida Residential Wind Loss Mitigation Study

BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS

HRAC Update: Asphalt Shingle Research. Principal Investigator: Forrest J. Masters, Ph.D., P.E. (FL)

STRUCTURAL DESIGN CHAPTER 16

Testing Water Penetration Resistance of Window Systems Exposed to Realistic Dynamic Air Pressures

Transcription:

Advanced FBC: Changes to the Wind Load Provisions of the 2010 Florida Building Code and ASCE 7-10 presented by T. Eric Stafford T. Eric Stafford & Associates, LLC This material is protected and the property of T. Eric Stafford & Associates, LLC and cannot be reproduced or used without the express written permission of T. Eric Stafford & Associates, LLC. 1 ASCE 7-10 Available May 2010 Most comprehensive update to wind load provisions since ASCE 7-98 Referenced in the 2012 IBC and the 2012 IRC Referenced in the 2010 Florida Building Codes (Primary references in the Building and Residential Codes) 2 1

2010 Florida Building Codes Glitch Amendments to be incorporated in First Printing of Codes Codes available December 2011 Effective Date March 15, 2012 3 ASCE 7-10 4 2

ASCE 7-10 Wind Provisions Topics Discussed Reorganization New wind speed maps Exposure Categories Wind-borne Debris Rooftop Structures 2010 Florida Building Code, Building 2010 Florida Building Code, Residential 5 ASCE 7-10 Reorganization ASCE 7-05: Chapter 6 contains all wind provisions ASCE 7-10: 6 new Chapters (Chapters 26-31) Step by step design procedure provided at the beginning of each method Intent is to clarify the applicability of the wind provisions 6 3

ASCE 7-10 Reorganization Chapter 26 General Requirements Scoping Definitions Wind speed map Exposure Gust factor Topographic factor 7 ASCE 7-10 Reorganization Chapter 27 MWFRS Directional Procedure Buildings of all heights method New simplified method for buildings with h 160 ft 8 4

ASCE 7-10 Reorganization Chapter 28 MWFRS Envelope Procedure Low-rise buildings method Simplified method for simple diaphragm buildings 9 ASCE 7-10 Reorganization Chapter 29 MWFRS Other Structures and Appurtenances Signs Rooftop structures Other structures 10 5

ASCE 7-10 Reorganization Chapter 30 Components and Cladding Analytical method for h 60 ft Simplified method for h 60 ft Analytical method for h > 60 ft Simplified method for h 160 ft Analytical method for free roofs Building appurtenances 11 ASCE 7-10 Reorganization Chapter 31 Wind Tunnel Procedure 12 6

ASCE 7-10 Reorganization Each chapter further subdivided into Parts for example Chapter 27 Part 1 Chapter 27 Part 2 13 ASCE 7-10 Reorganization How to find provisions in ASCE 7-10 using ASCE 7-05 as the basis. Significant Changes to Wind Load Provisions contains a crosswalk table. 14 7

Excerpt 15 ASCE 7-10 Reorganization Each method/part also is provided with a tabular step-by-step design procedure 16 8

17 18 9

ASCE 7-10 Reorganization Procedures for determining wind loads have not changed Presentation of wind load design procedures have changed 19 20 10

ASCE 7-10 Basic Wind Speeds Basic wind speeds didn t changed at all from ASCE 7-98 through ASCE 7-05 3-sec gust wind speeds introduced in ASCE 7-95 to replace fastest-mile wind speeds Minor adjustments between ASCE 7-95 and ASCE 7-98 21 ASCE 7-10 Basic Wind Speeds 3 new maps Risk Category II (700 year return period) Risk category III and IV (1700 year return period) Risk Category I (300 year return period) Strength design-based or Ultimate wind speeds Risk Category replaces the term Occupancy Category 22 11

ASCE 7-10 Basic Wind Speeds In most of the non-hurricane US mainland, the mapped values are exactly a 50 year mean recurrence interval In hurricane regions, the mapped values vary from 50 to 100 years along the hurricane coastline Wind speeds along the hurricane coastline have been adjusted upward so that when incorporated with the wind LF, produce a wind load having a consistent hazard level with the interior US (700 MRI) 23 Risk Category II 24 12

Risk Category II 25 Risk Category III and IV 26 13

Risk Category III and IV 27 Risk Category I 28 14

Risk Category I 29 ASCE 7-10 Basic Wind Speeds Implications Net wind loads are decreasing New data suggests ASCE 7-05 wind speeds are conservative 30 15

ASCE 7-10 Wind Speeds Why lower wind speeds? New model produces more intense hurricanes making landfall than the old model but results in lower wind speeds Lower winds associated with the new model for the Holland B parameter. Holland B controls the wind-pressure relationship Paper describing the statistical model for B published in the Journal of Applied Meteorology in 2008. 31 Additional Data in New Model 32 16

Comparison of (V 700 / 1.6) to ASCE 7-05 Wind Speeds 33 34 17

35 Design Pressure Comparisons City V ASCE 7-05/2007 FBC V ASCE 7-10 (est.) Percent Difference in Comparable Design Pressures Exp B Inland Exp D 2,3 Coastal Pensacola 140 155-27% -12% Tampa 123 145-17% 0% Orlando 110 135-10% NA Miami-Dade 1 146 175-14% 1 +3% Broward 1 140 170-12% 1 +6% Tallahassee 110 118-31% NA Gainesville 100 125-7% NA Jacksonville 120 125-35% -22% 36 18

ASCE 7-10 Basic Wind Speeds Strength Design Load Factor = 1.0 Allowable Stress Design multiply W x 0.6 Use of different maps for different Risk Categories negates the need for Importance Factors I deleted from wind chapters 37 ASCE 7-10 Basic Wind Speeds 38 19

ASCE 7-10 Exposure Categories Determination of Exposure Categories is a two step process Evaluate Surface Roughness Type Determine Exposure Category based on type and amount of surface roughness Wind direction and sectors Exposure of building to be determined for the two upwind sectors extending 45 degrees either side of selected wind direction. 39 ASCE 7-10 Exposure Categories 40 20

ASCE 7-10 Exposure Categories Surface Roughness Directions 41 ASCE 7-10 Surface Roughness B 42 21

ASCE 7-10 Surface Roughness C and D Older research and modeling suggested roughness increased with increase in wind speed Hence ASCE 7-98, -02, and -05 classified water surfaces in hurricane-prone regions as Exposure C 43 ASCE 7-10 Surface Roughness C and D New research suggests otherwise Roughness of ocean does not continue to increase with increasing wind speed. 44 22

45 ASCE 7-10 Surface Roughness C and D Sea surface drag coefficient reaches a maximum at wind speeds of 60-80 mph Some evidence that sea surface drag coefficient actually decreases at higher wind speeds reflecting a frothing or smoothing Use of Surface Roughness D now required for all water surfaces in Hurricane Prone Regions 46 23

ASCE 7-10 Surface Roughness C and D 47 ASCE 7-10 Surface Roughness C and D 48 24

ASCE 7-10 Exposure Categories 49 ASCE 7-10 Exposure Categories 50 25

51 ASCE 7-10 Enclosure Classification Protection of Glazed Openings Wind-borne debris region triggered by wind speed New wind speeds necessitate recalibration of the trigger. 52 26

ASCE 7-10 Protection of Glazed Openings Definitions revised for correlation with ASTM E 1996 53 ASCE 7-10 Protection of Glazed Openings Wind-borne Debris Regions 54 27

ASCE 7-10 Protection of Glazed Openings 55 ASCE 7-10 Protection of Glazed Openings Cont. 56 28

ASCE 7-10 Protection of Glazed Openings Risk Category II and Risk Category III Buildings, excluding health care facilities use Risk Category II Map wind speeds Risk Category III health care facilities and Risk Category IV Buildings use Risk Category III and IV Map wind speeds 57 58 29

59 60 30

61 ASCE 7-10 Protection of Glazed Openings 62 31

ASCE 7-10 Protection of Glazed Openings 63 ASCE 7-10 Protection of Glazed Openings 64 32

ASCE 7-10 Chapter 29 Rooftop Equipment 65 ASCE 7-10 Chapter 29 Rooftop Equipment 66 33

ASCE 7-10 Chapter 29 Rooftop Equipment 67 ASCE 7-10 Chapter 29 Rooftop Equipment 68 34

ASCE 7-10 Chapter 29 Rooftop Equipment 69 ASCE 7-10 Chapter 30 Components and Cladding Old analytical method for h 60 ft Old simplified method (Method 1) for h 60 ft 70 35

ASCE 7-10 Chapter 30 Components and Cladding Old analytical method for h > 60 ft New simplified method for h 160 ft 71 ASCE 7-10 Chapter 30 Components and Cladding 72 36

ASCE 7-10 Chapter 30 Simplified h 160 ft T. Eric Stafford & Associates, LLC 73 ASCE 7-10 Chapter 30 Simplified h 160 ft 74 37

75 Partial table 76 38

EAF 77 Reduction Factors 78 39

2010 Florida Building Codes 79 2010 Florida Building Codes Available December 2011 Effective Date: March 15, 2012 Glitch Amendments included in first printing No yellow or blue replacement pages 80 40

2010 Florida Building Codes Scope. The provisions of this chapter shall govern the structural design of buildings, structures and portions thereof regulated by this code. Exception: Buildings and structures located within the high-velocity hurricane zone shall comply with the provisions of Section 1615 through 1626, and, as applicable in flood hazard areas, Section 1612. 81 2010 Florida Building Code, Building 1609.1.1 Determination of wind loads. Wind loads on every building or structure shall be determined in accordance with Chapters 26 through 30 of ASCE 7 or the provisions of the alternate all heights method in Section 1609.6. Wind shall be assumed to come from any horizontal direction and wind pressures shall be assumed to act normal to the surface considered. 82 41

2010 Florida Building Code, Building Exceptions: ICC 600 AF&PA WFCM AISI 230 TIA 222 Screen enclosures comply with Section 2002.4 83 2010 Florida Building Code, Building Note: Clarification to ASCE 7. Arrows shown on Figure 6-10 of ASCE 7 indicate that the pressure coefficients apply specifically to Direction of MWFRS being designed. This means that the longitudinal pressure coefficients are not applicable to trusses that span in the transverse direction and therefore uplift reactions for trusses that span in the transverse direction would be determined by the pressure coefficients associated with those shown for the transverse direction. 84 42

85 86 43

87 2010 Florida Building Code, Building High Velocity Hurricane Zones Section 1620.2 Miami-Dade County Risk Category I: 165 mph Risk Category II: 175 mph Risk Category III and IV: 186 mph Broward County Risk Category I: 156 mph Risk Category II: 170 mph Risk Category III and IV: 180 mph 88 44

2010 Florida Building Code, Building Risk Categories replace Occupancy Categories Risk Category I Occupancy Category I Risk Category II Occupancy Category II Risk Category III Occupancy Category III Risk Category IV Occupancy Category IV Table 1604.5 89 2010 Florida Building Code, Building Risk Category I Low hazard to human life in the event of failure Ag facilities Temporary facilities Minor storage facilities Screen enclosures 90 45

2010 Florida Building Code, Building Risk Category II All buildings and structures except those listed in Risk Categories I, III and IV One- and two-family dwellings Retail Office 91 2010 Florida Building Code, Building Risk Category III Substantial hazard to human life in the event of failure Public assembly with occupant load greater than 300 I-3 Certain educational facilities Occupant load greater than 5000 92 46

2010 Florida Building Code, Building Risk Category IV Essential facilities I-2 with surgery or emergency treatment Fire, rescue, ambulance, police stations Shelters Toxic materials Aviation control towers Critical national defense functions 93 2010 Florida Building Code, Building Key issues with new wind speed maps: Strength Design Load Factor = 1.0 Allowable Stress Design multiply W x 0.6 Use of different maps for different Risk Categories negates the need for Importance Factors I deleted from wind chapters 94 47

2010 Florida Building Code, Building Strength Design Load Combinations 1.4(D+F) 1.2(D + F + T) + 1.6(L + H) + 0.5(L r or R) 1.2D+ 1.6(L r or R) + (f 1 L or.5w) 1.2D + 1.0W+ f1l + 0.5(L r or R) 1.2D+ f 1 L 0.9D + 1.0W + 1.6H 0.9D + 1.6H 95 2010 Florida Building Code, Building Allowable Stress Design Load Combinations D + F D + H + F + L + T D + H + F + (L r or R) D + H + F + 0.75(L + T) + 0.75(L r or R) D + H + F + 0.6W D + H + F +.45W + 0.75L + 0.75(L r or R) 0.6D + 0.6W + H 0.6D + H 96 48

2010 Florida Building Code, Building Section 1609.1.1 (cont.). The wind speeds in Figure 1609A, 1609B and 1609C shall be converted to nominal wind speeds, V asd, in accordance with Section 1609.3.1 when the provisions of the standards referenced in Exceptions 1 through 5 and 7 are used unless the wind provisions in the standards are based on Ultimate Wind Speeds as specified in Figures 1609A, 1609B, or 1609C or Chapter 26 of ASCE 7. 97 2010 Florida Building Code, Building Wind Speed, V ult. Ultimate design wind speeds. Wind Speed, V asd. Nominal design wind speeds. 98 49

2010 Florida Building Code, Building Section 1609.3.1 Converting from V ult to V asd V asd = V ult 0.6 Where: V asd = allowable stress design wind speed applicable to methods specified in Exceptions 1 through 5 of Section 1609.1.1 V ult = strength design wind speeds determined from Figures 1609A, 1609B, or 1609C. 99 2010 Florida Building Code, Building Wind Speeds Testing to allowable or nominal loads Where testing for wind load resistance is based on allowable or nominal wind loads, the design wind loads determined in accordance with ASCE 7 or Section 1609 of the Florida Building Code, Building are permitted to be multiplied by 0.6 for the purposes of the wind load resistance testing. Applicable to ASTM E 330 for doors AAMA/WDMA 101 standards for glass windows and doors 100 50

2010 Florida Building Code, Building Wind Speeds AAMA/WDMA 101 NAFS assign Performance Grades based on allowable stress design 101 2010 Florida Building Code, Building Wind Speeds 1715.5.1. Exterior windows and doors. The design pressures for window and door assemblies shall be calculated in accordance with component and cladding wind loads in Section 1609. The design pressures, as determined from ASCE 7, are permitted to be multiplied by 0.6. 102 51

2010 Florida Building Code, Building Wind Speeds 1609.3 Basic wind speed. The ultimate design wind speed V ult, in miles per hour, for the development of the wind loads shall be determined by Figures 1609A, 1609B and 1609C. The ultimate design wind speed V ult for use in the design of Risk Category II buildings and structures shall be obtained from Figure 1609A. The ultimate design wind speed V ult for use in the design of Risk Category III and IV buildings and structures shall be obtained from Figure 1609B. The ultimate design wind speed V ult for use in the design of Risk Category I buildings and structures shall be obtained from Figure 1609C. The exact location of wind speed lines shall be established by local ordinance using recognized physical landmarks such as major roads, canals, rivers and lake shores wherever possible. 103 2010 Florida Building Code, Building Wind Speeds Wind speed maps for each county developed by University of Florida for local jurisdictions to use as a guide for determining exact location of wind speed lines Also see ATC Windspeed By Location www.atcouncil.org/windspeed/ 104 52

2010 Florida Building Code, Building Section 1609.2 Wind-borne Debris Regions 1. 1 mile of coastal mean high water line where V ult is 130 mph or greater 2. Areas where V ult is 140 mph or greater 105 2010 Florida Building Code, Building Wind-borne Debris Regions Risk Category II and Risk Category III Buildings, excluding health care facilities based on Figure 1609A (Risk Category II map) Risk Category III health care facilities and Risk Category IV Buildings based on Figure 1609B (Risk Category III and IV map) 106 53

107 WBDR Risk Category II Buildings and Risk Category III excluding healthcare facilities 108 54

WBDR Risk Category IV Buildings and Risk Category III healthcare facilities 109 2010 Florida Building Code, Building Protection of Openings Section 1609.1.2 Glazed openings required to be protected from wind-borne debris through impact resistance or protection with impact-resistant covering meeting ASTM E 1886 and ASTM E 1996 SSTD 12 ANSI/DASMA 115 TAS 201, 202, and 203 110 55

2010 Florida Building Code, Building Protection of Openings Exceptions to Opening Protections Wood Structural Panels still permitted for 1 and 2 story buildings Limited to Groups R-3 and R-4 Anchorage required to be permanently installed on the building Attachments designed per ASCE 7 or in accordance with Table 1609.1.2 for h 45 ft and V asd 140 mph 111 Protection of Openings - WBDR 112 56

2010 Florida Building Code, Building Protection of Openings 113 2010 Florida Building Code, Building Protection of Openings ASTM E 1996 Wind Zones modified for correlation with ASCE 7-10 wind speeds Cyclic Pressure Loading table modified for correlation with ASCE 7-10 wind speeds 114 57

2010 Florida Building Code, Building Protection of Openings ASTM E 1996 Wind Zones Section 6.2.2 of ASTM E 1996 shall be modified as follows: 6.2.2.1 Wind Zone 1-130 mph basic wind speed < 140 mph, and Hawaii. 6.2.2.2 Wind Zone 2-140 mph basic wind speed < 150 mph at greater than 1.6 km (one mile) from the coastline. The coastline shall be measured from the mean high water mark. 6.2.2.3 Wind Zone 3-150 mph (58 m/s) basic wind speed 160 mph (63 m/s), or 140 mph (54 m/s) basic wind speed 160 mph (63 m/s) and within 1.6 km (one mile) of the coastline. The coastline shall be measured from the mean high water mark. 6.2.2.4 Wind Zone 4 - basic wind speed >160 mph (63 m/s). 115 2010 Florida Building Code, Building Protection of Openings ASTM E 1996 Cyclic Loading (Table 1626 HVHZ) Air Pressure Cycles 0.2 to 0.5 P pos 1 0.0 to 0.6 P pos 0.5 to 0.8 P pos 0.3 to 1.0 P pos 0.3 to 1.0 P neg 2 0.5 to 0.8 P neg 0.0 to 0.6 P neg Notes: P pos = 0.6 x positive ultimate design load in accordance with ASCE 7. P neg = 0.6 x negative ultimate design load in accordance with ASCE 7. 0.2 to 0.5 P neg 116 58

2010 Florida Building Code, Building Exposure Categories Surface Roughness and Exposure Categories mostly consistent with ASCE 7 FBC Surface Roughness also considers: Open patches in Surface Roughness B Short term Surface Roughness Changes 117 2010 Florida Building Code, Building Exposure Categories Surface Roughness C excerpt (Section 1609.4.2) Open Patches: This surface roughness shall also apply to any building located within surface roughness B- type terrain where the building is within 100 feet horizontally in any direction of open areas of surface roughness C or D-type terrain that extends more than 600 feet (182.9 m) and width greater than 150 ft. in the upwind direction. 118 59

119 2010 Florida Building Code, Building Exposure Categories Surface Roughness C excerpt (Section 1609.4.2) Short term changes: Short-term (less than two year) changes in the pre-existing terrain exposure, for the purposes of development, shall not be considered surface roughness C. Where development buildout will occur within three years and the resultant condition will meet the definition of surface roughness B, surface roughness B shall be regulating for the purpose of permitting. 120 60

C 121 2010 Florida Building Code, Building Exposure Categories High Velocity Hurricane Zones Miami-Dade and Broward Counties All buildings considered to be Exposure C unless Exposure D applies 122 61

2010 Florida Building Code, Building Wind Speed Conversions, V asd Table 1507.2.7.1 Classification of Asphalt Shingles Classification of Asphalt Shingles Maximum Basic Wind V asd ASTM D 7158 ASTM D 3161 Speed From Figures 1609A, B or C 110 85 D, G or H A, D or F 116 90 D, G or H A, D or F 129 100 G or H A, D or F 142 110 G or H F 155 120 G or H F 168 130 H F 181 140 H F 194 150 H F 123 2010 Florida Building Code, Building Rooftop Equipment 1609.8 (1620.6 HVHZ) The lateral force on rooftop structures and equipment with A f less than(0.1bh) located on buildings of all heights shall be determined from Equation 29.5-1 in which the value of GC f is 3.1. GC f shall be permitted to be reduced linearly from 3.1 to 1.1 as the value of A f is increased from (0.1Bh) to (Bh). The value of G from Section 26.9 shall not be used. Additionally, a simultaneous uplift force shall be applied, given by Equation 29.5-1 in which GC f = 1.5 and A f is replaced by the horizontal projected area, A r, of the rooftop structure or equipment. For the uplift force GC f shall be permitted to be reduced linearly from 1.5 to 1.0 as the value of A r is increased from (0.1BL) to (BL). 124 62

2010 Florida Building Code, Building Alternate All-heights Procedure Section 1609.6 Not really a simplification Based on ASCE 7-05 All-heights method Mostly reorganization of the controlling variables for simple diaphragm building Modified in the 2010 FBCB to work with ASCE 7-10 Still have to use ASCE 7 More complicated than ASCE 7 125 2010 Florida Building Code, Building Alternate All-heights Procedure Limitations H 75 ft, with height to least width ratio of 4 or less, or frequency greater than or equal to 1 hz Not sensitive to dynamic effects Not subject to channeling or buffeting in wake of upwind obstructions Simple diaphragm building Open buildings, certain roof types, signs, and rooftop equipment have to comply with ASCE 7 126 63

2010 Florida Building Code, Building Alternate All-heights Procedure Basic Equation P net = q s K z C net K zt q s = 0.00256V 2 C net = K d [(G)(C p )-(GC pi )] q s given in Table 1609.6.2(1) C net given in Table 1609.6.2(2) K z and K zt given in ASCE 7 Have to consider torsional load case from ASCE 7 127 128 64

129 2010 Florida Building Code, Residential Wind Provisions Wind speed maps and designations same as FBCB Protection of Openings and Windborne Debris Regions similar to FBCB Exposure Categories same as FBCB 130 65

131 2010 Florida Building Code, Residential Wind Provisions Section R301.2.1.2 Protection of openings (3) Ventilation openings in an exterior wall into an attic space in buildings located in windborne debris regions shall have opening protection from windborne debris. Such opening protection into an attic space shall meet the requirements AMCA 540 or shall be protected by an impact resistant cover complying with an approved impact-resistance standard or the large missile test of ASTM E 1996. 132 66

2010 Florida Building Code, Residential Wind Speeds Testing to allowable or nominal loads Where testing for wind load resistance is based on allowable or nominal wind loads, the design wind loads determined in accordance with ASCE 7 or Section 1609 of the Florida Building Code, Building are permitted to be multiplied by 0.6 for the purposes of the wind load resistance testing. Applicable to ASTM E 330 for doors AAMA/WDMA 101 standards for glass windows and doors 133 The End T. Eric Stafford, P.E. testafford@charter.net 205/987-9034 134 67