Property Policyholder Risk Improvement Report and Hurricane Survey

Size: px
Start display at page:

Download "Property Policyholder Risk Improvement Report and Hurricane Survey"

Transcription

1 Risk Engineering Property Policyholder Risk Improvement Report and Hurricane Survey Zurich Services Corporation Risk Engineering 1400 American Lane Schaumburg, IL Fax: Client: Location: Texas Woman's University Texas Woman's University 6700 Fannin Houston, T Date: 3/30/2011 and 4/01/2011 Policy Period: 8/31/2010-8/31/2011 Completed By: Account Coordinator: Juan Sauceda Gary Wood Important Notice: Only you can make your workplace safe. Those duties are not delegated and Zurich Services Corporation accepts no delegation of those duties. Zurich Services Corporation will assist you by providing the specific services for which you have contracted. However, it makes no warranties in conjunction with those services, and it undertakes no obligations other than as set out in the contract. Page 1 of 13

2 Participants William J. Bussman Texas Woman's University Institute of Health Sciences Juan Sauceda Risk Engineering Zurich Distribution William J. Bussman Texas Woman's University Institute of Health Sciences Robert Tuggle Texas Woman's University Institute of Health Sciences Greg Hoes Vice-President Crump Insurance Services, Inc. Debra Collins Underwriter Zurich Gary Wood Portfolio Engineer Zurich Page 2 of 13

3 Location: Contact: Serviced By: Texas Woman's University 6700 Fannin Houston, T Mr. William J. Bussman Manager Facilities Operations Houston Juan Sauceda Senior Property Consultant Serviced Date: 3/30/2011 and 4/01/2011 Purpose of Visit This visit was made as a property insurance survey to this Texas Woman's University high-rise office building. In addition, a hurricane survey was performed. Activities and Observations The risk is a high-rise building. It was built as a medical school curriculum branch extension to the main Texas Woman's University in Denton, T. It is own and operated by Texas Woman's University. The curriculum includes the studies of Nursing, Occupational Therapy, Physical Therapy, and Nutritional Sciences. Better than 60% of the student body is postgraduates. During this visit, there was a discussion of loss prevention programs. In general, the programs are satisfactory. A tour of the building was made as well as a visual inspection of the roof. All water-based fire protection equipment was visually inspected. Several deficiencies were observed during the tour of the building, and action for correction is covered by recommendations on this report. Management indicated positive action for correction of most of the recommendations. The building is in general good condition. The high-rise building is provided sprinkler protection. A fire detection alarm system is provided as well. The building is located in the Houston Medical Center area. Items of Interest Impairment Notification: Prior to removing any fire protection equipment from service, Zurich Services Corporation should be notified via fax at , through (Online Resources) or at [email protected]. Notify the local fire department of the impairment. Do not leave the equipment impaired overnight. If this is unavoidable, then shut down all hazardous processes and operations and establish a fire watch. When the impaired equipment is returned to service, the fire department and Zurich Services Corporation should be notified. Hot Work: Utilize the Zurich Hot Work Permit System whenever burning, cutting, or welding operations are performed outside designated hot work areas. It is especially important to ensure contractors follow safe hot work practices. Closely supervise hot work performed by outside contractors. Page 3 of 13

4 Management of Change: Submit all future changes in process, construction, and protection, which could affect the current level of loss prevention and control, to Zurich Services Corporation prior to the start of work for review and comment. This service aids local management by providing an engineering review of all construction projects involving the design, installation, and modification of any protection system or critical building structural features. Forward all plans, calculations, and component specification sheets for any new construction or renovation projects involving facility or special hazard protection to Zurich Services Corporation for review and comment. Hurricanes cause significant property damage when they compromise the integrity of building roof and wall systems that normally form a protective envelope around the building. This protective envelope can be compromised by high wind. Once compromised, water entry into the building can lead to extensive damage. The hurricane survey conducted during this visit provides an initial assessment of wind and water exposures to your property. This assessment was limited to visual observations and on-site discussions. The results are summarized in the table below. Hurricane Assessment Summary Assessment Element Recommendation Recommendation Developed Number Yes No N/A Roof Wind Cladding Exposures Glazing Drains Flood Exposure Surface Water Water Runoff Exposures Storm Surge Wave Action Recommendation and provide guidance to achieve a Superior wind grading for this location. Contact your Zurich account team to discuss the benefits of pursing a Superior Wind grading. Next Visit The Zurich account team will determine the next visit to this location. Test Results Fire Pump Test Data Pump # Date Flow (Gpm) Net (Psi) Satisfactory (Y/N) 1 02/11/ gpm 212 psi Y 1000 gpm 195 psi Y 1500 gpm 169 psi Y Page 4 of 13

5 Recommendations Priority 2 Priority 2 Recommendations are intended to correct serious / significant exposures to the assets of the corporation, are potential regulatory code violations or exposures which could cause a moderate outage of production capability but which are not of an imminent nature. These exposures require prompt response from the facility management in order to provide an adequate level of protection of property and production capabilities. These recommendations also incorporate your organizations management controls regarding loss prevention and human element. If management controls are absent or not enforced the probability of having an uncontrolled exposure is much higher Water Supply: Pressure Reducing Devices Scheduled for Completion Approved pressure-reducing valves should be provided on each sprinkler system where water pressures in excess of 175 psi are experienced. The fire pump's capacity pressure rating is oversized and water pressures in excess of 175 psi during Churn (no water flow) are experienced. This is per NFPA 25, Maintenance, and Testing of Water-Based Fire Protection Equipment. An alternative would be to have the pump's impeller reworked by the pump' manufacture where capacity pressure would assure of no pressures over 175 psi. Comments: Mr. Bussman will work with the sprinkler contractor to resolve this issue. If pressurereducing devices are needed, they will be installed Human Element: Infrared Inspections Open An infrared inspection program should be established. An infrared inspection of electrical switch panels, circuit breakers, and building equipment motors is needed. This should be done on an annual basis. The inspections should be done by a qualified and license company. Any deficiencies noted should be corrected. Comments: There is no infrared inspection program. The inspections are needed to detect possible hot spots (high temperature due to loose connections) on electrical that could result in mechanical equipment failure. Mr. Bussman indicated that this would be reviewed Exposure: Fire Cabinet Scheduled for Completion The 55-gallon drum of Phenol Solutions stored in Room # 6315 on the sixth floor should be placed in an approved fire cabinet. The one container of combustible liquid is maintained by the Anatomy Department. In addition, additional spill skids should be provided for the containers of waste stored in the Anatomy Class room. Comments: Phenol Solutions is a combustible liquid with a FP of 172 F. It should be stored in an appropriate approved fire cabinet. Mr. Bussman indicated that approved fire cabinet is to be purchased as well as spill skids. Page 5 of 13

6 Drum containing Phenol Solutions Human Element: Housekeeping Scheduled for Completion Remove all combustibles of cardboard boxes, plastics, etc., in the electrical room label as RM # 5328 located on the fifth floor. Mechanical and electrical rooms should not be use for storage rooms. Comments: Mr. Bussman indicated that all combustibles are to be removed. Electrical room. Page 6 of 13

7 CAT Exposure: Wind - Superior Wind Open To achieve a Superior wind rating for this location, the following actions are needed: a. Verify and/or improve the roof system and glazing for the Main Building to meet the wind design requirements of the American Society of Civil Engineers standard ASCE 7-05 "Minimum Design Loads for Buildings and Other Structures". Wind load calculations should be based upon appropriate parameters including: When applying ASCE 7, the following parameters should be used: Basic design wind speed (V) = 110 mph (nominal 3 second gust). Importance Factor (I) = Exposure = "C". Other factors or coefficients (Topographical, Directional, etc.) based upon facility conditions. b. Conduct a nondestructive negative pressure wind uplift test for the built up, adhered substrate roof cover for the Main Building. A qualified roofing consultant in accordance with ASTM E 907 "Test Method for Field Testing Uplift Resistance of Roofing Systems Employing Steel Deck, Rigid Insulation, and Bituminous Built-Up Roofing" should conduct the test. Testing should be based upon achieving a minimum Safety Factor of 1.5. If testing indicates inadequate uplift resistance, mechanically fasten the entire roof system to improve the building roof to meet the wind design requirements of the American Society of Civil Engineers standard ASCE 7-05 "Minimum Design Loads for Buildings and Other Structures". Comments: The primary concerns with meeting the Zurich Superior Wind guidelines are verifying and/or improving the current roof cover design, and cladding to meet the above criteria. This is per NFPA CAT Exposure: Wind - Glazing - Provide Impact Resistance Open Provide wind-borne debris protection for the glazing systems for the Main Building. Protection options may include: a. Provide missile resistant glazing systems that are approved and tested in accordance per ASTM 1886 and ASTM Glazing systems should possess the following ratings and properties: Missile Resistance: Provide glazing systems that are tested and approved in accordance with ASTM 1886 and ASTM Large missile impact resistant glazing should be provided within 30 ft. of grade. Small missile impact resistant glazing should be installed within 30 to 60 ft. above grade or within 30 ft. above any aggregate covered roofs located within 1,500 ft. Page 7 of 13

8 OR b. Provide hurricane shutters or other type of impact resistant covering that are Miami-Dade County Approved for large missile impact resistance. Shutters should be provided for all glazing within 60 ft. of grade and within 30 ft. above any aggregate covered roofs located within 1,500 ft. If a manual shutter system is selected, verify that the needed personnel will be available to implement the system once a hurricane warning is issued. Shutters should be pre-fitted and stored on-site. At least once each year, personnel should practice the complete installation of all shutters. The Hurricane Emergency Action Plan should be revised to include these actions. Comments: The building is located in an area susceptible to wind-borne debris from surrounding buildings. Mr. Bussman was not certain if the glazing is compatible to Miami-Dade County approved type impact resistive rated glazing CAT Exposure: Wind - Rooftop Equipment Improve Securement (Small Equipment) Scheduled for Completion Improve the securement for the air conditioning condenser units (two) located on the roof. The a/c units should be permanently secured to the roof or a wall structure. In addition, anchoring should meet the basic wind speed of 110 mph per the wind design requirements of the American Society of Civil Engineers standard ASCE 7-05 "Minimum Design Loads for Buildings and Other Structures". For further guidance, go to or Comments: Mr. Bussman indicated that plans are to properly anchor the two units against wind damage. A/c unit needs to be anchored. Page 8 of 13

9 Summary of Construction The site consists of one high-rise building. The specifics for the building are as follows: Main Bldg.: Total floor area: Approximately 211,000 sq. ft. Year Built: Built in 2006 Maximum number of floors: 10 Primary structural elements: Exterior wall construction: Roof deck assemblies: Roof cover assemblies: Glazing/door protection: Glazing percentage/ area: Glazing door protection: Fire Resistive Steel/Glazing Reinforced concrete Modified Bitumen Safety, double pane glass All building wall sides at 300 % or better coverage Unprotected There are no shutters. Summary of Hurricane Procedures Hurricane procedures for this facility are extensive and comprehensive with fully documented steps for pre-, during and post hurricane activities. Pre-hurricane procedures consist of tracking the storm front, removing any yard storage, clean up any roof debris, and other related items. Post procedures are typical. Page 9 of 13

10 Photographs Elevation view of building. Another elevation view glazing surfaces. Page 10 of 13

11 Typical glazing frame and glazing pane. View of typical roof surface primary and secondary drains. Page 11 of 13

12 Another view of roof surface. Bottom view of roof deck. Page 12 of 13

13 View of hollow shell floor. Closing Remarks We appreciate the assistance provided to our service representative during this visit. The recommendations attached offer solutions to problems that could result in serious loss to your facility. Please provide an response to these recommendations to Gary Wood, Account Coordinator, Zurich Services Corporation Feedback for Priority 2 recommendations is requested within days. Page 13 of 13

The Florida Building Code

The Florida Building Code Setting New Standards for Safety The Florida Building Code Florida Building Commission Florida Department of Community Affairs The Florida Building Code System The Florida Building Commission Florida Building

More information

Appendix B. 2010 Florida Building Code Building Section 423.25 Public Shelter Design Criteria

Appendix B. 2010 Florida Building Code Building Section 423.25 Public Shelter Design Criteria Appendix B 2010 Florida Building Code Building Section 423.25 Public Shelter Design Criteria 423.25 Public shelter design criteria. 423.25.1 New facilities. New educational facilities for school boards

More information

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result

More information

Protecting Roofing Systems Against Windstorm Damage

Protecting Roofing Systems Against Windstorm Damage Protecting Roofing Systems Against Windstorm Damage This brochure is made available for informational purposes only in support of the insurance relationship between FM Global and its clients. This information

More information

In accordance with NFPA 30, these containers are not to store Class I flammable liquids.

In accordance with NFPA 30, these containers are not to store Class I flammable liquids. In accordance with NFPA 30, these containers are not to store Class I flammable liquids. Zurich recommends storing these containers in dedicated liquid storage rooms, detached buildings, or in listed dispensing

More information

Suffolk County Department of Health Services. Division of Environmental Quality

Suffolk County Department of Health Services. Division of Environmental Quality Suffolk County Department of Health Services Division of Environmental Quality Guidelines For the Construction of Storage Areas for Portable Containers ~~~~ Clare B. Bradley, M.D., M.P.H. Suffolk County

More information

contractors, etc. and establish relationships with lease and rental companies.

contractors, etc. and establish relationships with lease and rental companies. The following may serve as a checklist when preparing for a Tropical Storm or Hurricane. Although Tornadoes usually provide little advance warning, locations subject to Tornadoes may apply much of the

More information

Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY

Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY Insulation for Above the Deck WALL SPECIALTY PRODUCT DESCRIPTION Rmax Re-Cover Board-3 is an energy-efficient thermal insulation board composed of a closed-cell polyisocyanurate (polyiso) foam core bonded

More information

Building Code Clarifications - 7. Fire Resistance

Building Code Clarifications - 7. Fire Resistance Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,

More information

Wind Mitigation Discount Plan

Wind Mitigation Discount Plan Wind Mitigation Discount Plan Louisiana Hurricane Loss Mitigation Survey Form Inspector Instructions The purpose of these instructions is to provide guidance to certified inspectors on how to properly

More information

General Fire Code Requirements Within Commercial Tenant Spaces

General Fire Code Requirements Within Commercial Tenant Spaces FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding

More information

OREGON FIRE CODE Interpretations and Technical Advisories

OREGON FIRE CODE Interpretations and Technical Advisories OREGON FIRE CODE Interpretations and Technical Advisories A collaborative service by local and state fire professionals, along with our stakeholders and customers, to provide consistent and concise application

More information

Insurance Mitigation Factors for Homeowners Purchasing Garage Doors In Florida

Insurance Mitigation Factors for Homeowners Purchasing Garage Doors In Florida Insurance Mitigation Factors for Homeowners Purchasing Garage In Florida The following questions and answers are intended to clarify the effect on insurance premiums for Florida homeowners when a new or

More information

Wind Mitigation Inspection

Wind Mitigation Inspection [email protected] Tampa Bay Area: SW & Central Florida: (813) 368-6407 (239) 896-3986 Wind Mitigation Inspection VonHaase, Dale 4585 Bowen Bayou Road Sanibel, FL 33957 5/6/2013 Note to Policyholder:

More information

Fire Alarm System Plans Review Checklist Property location Date of Review

Fire Alarm System Plans Review Checklist Property location Date of Review Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include

More information

PROJECT SUMMARY. Scope of work details: (If phased construction, please see plan submittal guidelines.)

PROJECT SUMMARY. Scope of work details: (If phased construction, please see plan submittal guidelines.) APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL FIRE RESTORATION PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) (Reproduce the following data on the building plans sheet 1 or 2) Name of

More information

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to

More information

Development Services City of Lawrence, KS

Development Services City of Lawrence, KS Development Services City of Lawrence, KS Building Planning Table R301.2 (1) Climatic & Geographic Design Criteria Building Planning The design criteria for wind speed increased from 90 MPH to 115 MPH.

More information

CITIZENS PROPERTY INSURANCE CORPORATION. STREET ADDRESS: 14300 Gulf Blvd, Maderia Beach, FL 33708 6 Six story masonry residence

CITIZENS PROPERTY INSURANCE CORPORATION. STREET ADDRESS: 14300 Gulf Blvd, Maderia Beach, FL 33708 6 Six story masonry residence CITIZENS PROPERTY INSURANCE CORPORATION BUILDING TYPE II AND III MITIGATION VERIFICATION AFFIDAVIT This affidavit must be completed to capture mitigation features applicable to a Type II (4 to 6 story)

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

The Florida Building Code

The Florida Building Code The Florida Building Code Florida s Response to Hurricane Risk Rick Dixon Florida Building Commission Florida Building Commission Architect Structural Engineer Mechanical Engineer Fire Protection Engineer

More information

Water Damage During Construction

Water Damage During Construction Allianz Global Corporate & Specialty Americas Water Damage During Construction May 2012 A Contractor s Loss Prevention Guide Water damage losses are a major cause of loss during construction and represent

More information

UNIVERSITY OF TOLEDO

UNIVERSITY OF TOLEDO UNIVERSITY OF TOLEDO SUBJECT: INTERIM LIFE SAFETY MEASURES AND INFECTION Procedure No: LS-08-008 CONTROL PROCEDURE STATEMENT Interim life safety and infection control measures will be implemented to protect

More information

c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.

c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use. Walmart Standards for Suppliers Section 7. Health and Safety 7. Health and Safety Suppliers must provide workers with a safe and healthy work environment. Suppliers must take proactive measures to prevent

More information

Informational Bulletin

Informational Bulletin Informational Bulletin March 2007 Bulletin #31 *Replaces Informational Bulletin #8 Updated Impact Requirements for Building Components This Bulletin presents a general overview of the current impact requirements

More information

Fire Pump Plan Review March 2010

Fire Pump Plan Review March 2010 Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:

More information

Commercial Residential Model Reviews

Commercial Residential Model Reviews Commercial Residential Model Reviews Prepared by the Professional Team for The Florida Commission on Hurricane Loss Projection Methodology May 2002 I. Background and Items for Consideration In May, 2000,

More information

Hurricane Checklist. It is in the best interest to ensure that our employees are safe and that our properties are secure prior to a hurricane event.

Hurricane Checklist. It is in the best interest to ensure that our employees are safe and that our properties are secure prior to a hurricane event. Hurricane Checklist Although most hurricane warnings refer to the time a hurricane will make landfall, the impact from a hurricane can begin to be felt several hours prior to landfall. Landfall is defined

More information

Text Box 1 Important Actions, Questions and Constraints to Consider on Standards and Vulnerability

Text Box 1 Important Actions, Questions and Constraints to Consider on Standards and Vulnerability 259 Text Box 1 Important Actions, Questions and Constraints to Consider on Standards and Vulnerability Actions Reach agreement on standards through public review and consensus Balance objectives for standards

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION 17650 SECURITY SYSTEMS PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES A. Inspections and observations by the Owner do not relieve the A/E of contract responsibilities. B. Chain of command 1. The DPS Project Manager is

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS

FLAMMABLE AND COMBUSTIBLE LIQUIDS GAP.8.1.0 A Publication of Global Asset Protection Services LLC FLAMMABLE AND COMBUSTIBLE LIQUIDS INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection

More information

Water Damage on Construction Sites. A guide to loss prevention

Water Damage on Construction Sites. A guide to loss prevention Water Damage on Construction Sites A guide to loss prevention Water damage is the second most frequent cause of loss during building projects and represents a large percentage of Construction All Risk

More information

SECTION 3 ONM & J STRUCTURAL ANALYSIS

SECTION 3 ONM & J STRUCTURAL ANALYSIS Historic Boynton Beach High School Existing Building Assessment City of Boynton Beach February 10, 2011 SECTION 3 ONM & J STRUCTURAL ANALYSIS STRUCTURAL ENGINEERS SPECIAL INSPECTORS STRUCTURAL CONDITION

More information

foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.

foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs. Skylight Installation Instructions This document provides instruction and guidelines for installation of both curb mount (CM) and self flashing (SF) unit skylights on flat, pitched (> or equal to 3/12

More information

Risk Management Report

Risk Management Report Risk Management Report Main Street, White Plains, NY 060 Member: Joan Smith Policy No.: 45678 Agency: ABC Insurance Brokers, Inc. Date of Visit: January, 0 Prepared By: Tim Arone Summary of Scheduled Changes

More information

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for

More information

Hurricane-prone wind guide. Risk management handbook for properties in hurricane-prone regions

Hurricane-prone wind guide. Risk management handbook for properties in hurricane-prone regions Hurricane-prone wind guide Risk management handbook for properties in hurricane-prone regions Managing property risk in hurricane-prone regions When it comes to hurricanes, do you have more questions than

More information

BUILDING SAFETY UNIT

BUILDING SAFETY UNIT POLICY Page 1 of 5 SUBMITTAL REQUIREMENTS FOR ONE AND TWO FAMILY DWELLINGS, ADDITIONS AND RENOVATIONS All submittals shall be site specific and designed to the provisions of the 2012 International Residential

More information

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-

More information

Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com

Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Portland Area PO Box 665 West Linn, OR 97068 Ph: (503) 650-6957 Salem Area 5434 River Rd. N; #192 Keizer, OR 97303 Ph: (503) 362-5809

More information

A cure for water damage in real estate

A cure for water damage in real estate A cure for water damage in real estate Presented for BC Non-Profit Housing Association by Jeff Shearman, Zurich Services Corporation 2010 Zurich Canada Focused on our customer Reduce overall risk by reducing:

More information

SACRAMENTO VALLEY FIRE MARSHALS ASSOCIATION

SACRAMENTO VALLEY FIRE MARSHALS ASSOCIATION SACRAMENTO VALLEY FIRE MARSHALS ASSOCIATION Sacramento Valley Fire Marshals Association Standards Article No: 10 Section: CFC 1003.1 Standard No: 13 Title: Centrifugal Fire Pumps Date: April 24, 2002 Revised:

More information

Residential Sheltering: In-Residence and Stand-Alone Shelters

Residential Sheltering: In-Residence and Stand-Alone Shelters Residential Sheltering: In-Residence and Stand-Alone Shelters Intended Audience and Purpose The purpose of this Tornado Recovery Advisory (RA) is to alert homeowners, renters, and apartment building owners

More information

HOT WORK PERMIT PROGRAM TRAINING. John Braun

HOT WORK PERMIT PROGRAM TRAINING. John Braun HOT WORK PERMIT PROGRAM TRAINING John Braun 1.0 INTRODUCTION 1.2 Purpose The Hot Work Permit Program has been developed for University employees that work on or around hot work activities. This program

More information

Protecting YOUR NEW HOME FROM Wind Damage

Protecting YOUR NEW HOME FROM Wind Damage Protecting YOUR NEW HOME FROM Wind Damage Blueprint for Safety... A Blueprint for Life When severe weather threatens, protecting life and property automatically becomes top priority for millions of Florida

More information

Automatic Fire Sprinkler Submittal Requirements

Automatic Fire Sprinkler Submittal Requirements Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance

More information

Four Point Inspection

Four Point Inspection [email protected] Tampa Bay Area: Southwest Florida: (813) 368-6407 (239) 896-3986 Four Point Inspection Izzo, Frank & Jacqueline 3214 Williamsburg Street Sarasota, FL 34231 9/26/2013 Note to Policyholder:

More information

HOT WORK PERMIT PROCEDURES

HOT WORK PERMIT PROCEDURES COLUMBIA UNIVERSITY ENVIRONMENTAL HEALTH & SAFETY HOT WORK PERMIT PROCEDURES COLUMBIA UNIVERSITY MEDICAL CENTER February 2010 1 TABLE OF CONTENTS A. PURPOSE 3 B. SCOPE 3 C. POLICIES AND PROCEDURES 3-4

More information

FIELD TESTING SERVICES

FIELD TESTING SERVICES FIELD TESTING SERVICES Chris Leach Director of Testing Baton Rouge, Louisiana Destin, Florida Scott Leach David Nichols Field Testing Representative Field Testing Representative 17485 Opportunity Avenue

More information

Environment of Care Fire Safety Management Plan 2014

Environment of Care Fire Safety Management Plan 2014 Environment of Care Fire Safety Management Plan 2014 Updated 4.29.2014 PURPOSE The purpose of the Fire Safety Management Plan is to ensure that all facilities are designed, constructed, maintained, and

More information

Building Permit Application Packet. BUILDING CODES Adopted by La Plata County For Enforcement In The Unincorporated Areas Of La Plata County

Building Permit Application Packet. BUILDING CODES Adopted by La Plata County For Enforcement In The Unincorporated Areas Of La Plata County Building Permit Application Packet The purpose of Building Codes is to establish the minimum requirements to safe guard the public health, safety and general welfare through structural strength, means

More information

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL

More information

PREVENTING GROUNDWATER POLLUTION: SECONDARY CONTAINMENT

PREVENTING GROUNDWATER POLLUTION: SECONDARY CONTAINMENT PREVENTING GROUNDWATER POLLUTION: SECONDARY CONTAINMENT PREVENTING GROUNDWATER POLLUTION IS EVERYONE S JOB! Even if our drinking water comes from rivers, lakes, or reservoirs, we need to be mindful of

More information

Flood Checklist ACTION TO BE TAKEN BEFORE THE FLOOD SEASON

Flood Checklist ACTION TO BE TAKEN BEFORE THE FLOOD SEASON Flood Checklist The following may serve as a checklist when preparing for a flood. This checklist should be tailored to processes/operations, flood protection equipment and flood potentials at your specific

More information

OVERVIEW SCOPE DEFINITIONS

OVERVIEW SCOPE DEFINITIONS Procedure No 400.10 Subject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: March 2008 Distribution All Employees Review Date: April 2008 Purpose: To establish

More information

TechPractices: Home Front Homes:

TechPractices: Home Front Homes: TechPractices: Home Front Homes: PATH's Technologies in Practice are large scale housing projects throughout the U.S. where innovative technologies are being installed and used. Information is presented

More information

Movie star Brad Pitt helps Make It Right rebuild the Lower Ninth Ward with affordable LEED Platinum homes

Movie star Brad Pitt helps Make It Right rebuild the Lower Ninth Ward with affordable LEED Platinum homes Make It Right Movie star Brad Pitt helps Make It Right rebuild the Lower Ninth Ward with affordable LEED Platinum homes Few can forget the horrific images from Hurricane Katrina. In 2005, the hurricane

More information

providing documentation that validates the year of construction. Acceptable documents include

providing documentation that validates the year of construction. Acceptable documents include 902. WINDSTM MITIGATION FEATURES A. For policies that cover the peril of Windstorm or Hail, a premium credit may be available if one or more of the following loss mitigation features or construction techniques

More information

FIRE RISK ASSESSMENT SW13 0HA

FIRE RISK ASSESSMENT SW13 0HA FIRE RISK ASSESSMENT at Carmichael Court Grove Road London SW13 0HA ON BEHALF OF Farrar Property Management Date of assessment: 14/01/2013 Recommended review date: January 2015 CONTENTS 1.0 INTRODUCTION

More information

Disaster Ready. By: Katie Tucker, Sales Representative, Rolyn Companies, Inc

Disaster Ready. By: Katie Tucker, Sales Representative, Rolyn Companies, Inc By: Katie Tucker, Sales Representative, Rolyn Companies, Inc Are you and your facility disaster ready? As reported by the Red Cross, as many as 40 percent of small businesses do not reopen after a major

More information

MTA UNIVERSAL STATION PEDESTRIAN BRIDGE Los Angeles, CA. Project Manual and Specification 100% PE SUBMITTAL TABLE OF CONTENTS

MTA UNIVERSAL STATION PEDESTRIAN BRIDGE Los Angeles, CA. Project Manual and Specification 100% PE SUBMITTAL TABLE OF CONTENTS Los Angeles, CA Project Manual and Specification DIVISION 1 GENERAL CONDITIONS 01 01 10 STATEMENT OF WORK 01 11 00 SUMMARY OF THE WORK 01 14 05 METRO (OWNER) - DIRECTED STOPPAGES 01 20 00 PRICE AND PAYMENT

More information

CHAPTER 7: Building Systems ROOFING SYSTEMS

CHAPTER 7: Building Systems ROOFING SYSTEMS ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen

More information

FIRE ALARM /FIRE PROTECTION OUTAGE/IMPAIRMENT RESPONSE GUIDELINE

FIRE ALARM /FIRE PROTECTION OUTAGE/IMPAIRMENT RESPONSE GUIDELINE Page 1 of 10 FIRE ALARM /FIRE PROTECTION OUTAGE/IMPAIRMENT RESPONSE GUIDELINE SYSTEM TESTING 1. Testing of the Fire Alarm and Fire Protection Systems 1.1. The Building Engineer, Electrician, Plumber (or

More information

SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION

SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION As of October 1, 2007, this mitigation form must be submitted as part of the roofing permit application package. Secondary water barrier (if applicable)

More information

Inspecting to a higher standard.

Inspecting to a higher standard. Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com [email protected]

More information

Fire Alarm and Protection Impairment Policy and Procedures

Fire Alarm and Protection Impairment Policy and Procedures 1.0 Policy Statement The University of New Haven has developed a Fire Alarm and Protection Impairment Plan in accordance with the National Fire Protection Associations (NFPA) codes. Specific codes referenced

More information

KODAK VERSAMARK, INC.

KODAK VERSAMARK, INC. KODAK VERSAMARK, INC. PREPARED BY : Gary Rowland 6/6/06 Kodak Versamark, Inc. 3000 Research Blvd. Dayton, Ohio 45420 APPROVED BY : Fire Suppression System Inspection, Testing and Maintenance SHEET 1 OF

More information

COMMERCIAL BUILDING APPLICATIONS

COMMERCIAL BUILDING APPLICATIONS EXPANDED POLYSTYRENE FOR COMMERCIAL BUILDING APPLICATIONS www.falconfoam.com Commercial Building Ap Expanded Polystyrene Insulation Falcon Foam leads the commercial building industry with products that

More information

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings

More information

Notes. Material 1. Appropriate Flammable Liquids

Notes. Material 1. Appropriate Flammable Liquids 29 CFR 1910.106 Flammable Materials Flammable Liquids Preparation 1. Read Applicable Background information and related Company Policy Chapter. 2. Make Copies of this Lesson Plan for Personnel 3. Make

More information

29 Broadway- 14 th Fl Tel: 212.888.8334 New York NY 10006 Fax: 212.419.1939. Due Diligence Report. New York, New York

29 Broadway- 14 th Fl Tel: 212.888.8334 New York NY 10006 Fax: 212.419.1939. Due Diligence Report. New York, New York Due Diligence Report New York, New York Prepared for Mr. On February 8, 2010 P a g e 1 Table of Contents PAGE 3.. GENERAL INFORMATION PAGE 4 FILINGS PERMITS AND ENCUMBRANCES PAGE 6. CORE AND SHELL PAGE

More information

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600 OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done

More information

Name Of Occupancy Date. Yes No Describe

Name Of Occupancy Date. Yes No Describe FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address

More information

LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.

LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. LIFE SAFETY UPDATE FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. The purpose of this update is as follows: Remind all state

More information

DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS

DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS NOTICE TO BIDDERS BID FORM INSTRUCTIONS TO BIDDERS CONTRACTOR S BID FOR PUBLIC WORK - FORM 96 MINORITY AND WOMEN S BUSINESS ENTERPRISE PARTICIPATION

More information

ALLEGANY WIND POWER PROJECT CONSTRUCTION SPILL PREVENTION PLAN

ALLEGANY WIND POWER PROJECT CONSTRUCTION SPILL PREVENTION PLAN ALLEGANY WIND POWER PROJECT CONSTRUCTION SPILL PREVENTION PLAN Best Management Practices (BMPs) will be implemented during construction of the Allegany Wind Power Project to prevent and contain spills.

More information

REQUIREMENTS FOR SUBMITTING PLANS FOR NEW CONSTRUCTION

REQUIREMENTS FOR SUBMITTING PLANS FOR NEW CONSTRUCTION RESIDENTIAL: REQUIREMENTS FOR SUBMITTING PLANS FOR NEW CONSTRUCTION 2 COMPLETE SETS OF PRINTS WITH ENGINEERS STAMP ON FOUNDATION PLAN INCLUDING ELECTRICAL, PLUMBING, ETC. SITE PLAN SHOWING HOUSE LOCATION

More information

Radioactive Waste Storage Facility and Tank System Design Criteria Standards

Radioactive Waste Storage Facility and Tank System Design Criteria Standards UCRL-AR-133355 Rev 1 Radioactive Waste Storage Facility and Tank System Design Criteria Standards John Wood Rich Michalik Karen Doiron May 1999 DISCLAIMER This document was prepared as an account of work

More information

CITIZENS PROPERTY INSURANCE CORPORATION BUILDING TYPE II AND III MITIGATION VERIFICATION AFFIDAVIT

CITIZENS PROPERTY INSURANCE CORPORATION BUILDING TYPE II AND III MITIGATION VERIFICATION AFFIDAVIT CITIZENS PROPERTY INSURANCE CORPORATION BUILING TYPE II AN III MITIGATION VERIFICATION AFFIAVIT This affidavit must be completed to capture mitigation features applicable to a Type II (4 to 6 story) or

More information

IGNITION-RESISTANT CONSTRUCTION: THE WHY BEHIND THE WHAT

IGNITION-RESISTANT CONSTRUCTION: THE WHY BEHIND THE WHAT IGNITION-RESISTANT CONSTRUCTION: THE WHY BEHIND THE WHAT WHAT IS THE RATIONALE BEHIND THE REQUIREMENTS FOR IGNITION RESISTANT CONSTRUCTION? The wildfires of 2003 and 2007 were the largest in California

More information

Dollars & Sense of Compliance!

Dollars & Sense of Compliance! CRCA s 29 th Annual Trade Show Oakbrook k Terrace, IL January 19 20, 2012 Dollars & Sense of Compliance! Mark S. Graham Associate ExecutiveDirector Director, Technical Services National Roofing Contractors

More information

LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809

LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809 LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3 Fire

More information

TABLE OF CONTENTS. Roof Decks 172 B, BA, BV Deck N, NA Deck. Form Decks 174.6 FD,.6 FDV Deck 1.0 FD, 1.0 FDV Deck 1.5 FD Deck 2.0 FD Deck 3.

TABLE OF CONTENTS. Roof Decks 172 B, BA, BV Deck N, NA Deck. Form Decks 174.6 FD,.6 FDV Deck 1.0 FD, 1.0 FDV Deck 1.5 FD Deck 2.0 FD Deck 3. Pages identified with the NMBS Logo as shown above, have been produced by NMBS to assist specifiers and consumers in the application of New Millennium Building Systems Deck products. Pages identified with

More information

Data Center Due Diligence List

Data Center Due Diligence List Data Center Due Diligence List Name and address of site facility Date constructed Building owner/date purchased by current owner Name of previous owner Adjacent Property Descriptions North South East West

More information

CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.

CLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C. CLIENT Inspection Report 271 Front St. Alert Bay, B.C. Island Building Inspections 2013 V ANCOUVER I SLAND B. C. Elevation Photos For the Property at 271 Front Street Alert Bay, BC ELEVATION PICTURES Front

More information

ACTIVITY NAME. Training Requirements for Spill Prevention Control and Countermeasures (SPCC) 40 CFR Part 112 Naval Air Station Corpus Christi Texas

ACTIVITY NAME. Training Requirements for Spill Prevention Control and Countermeasures (SPCC) 40 CFR Part 112 Naval Air Station Corpus Christi Texas ACTIVITY NAME Training Requirements for Spill Prevention Control and Countermeasures (SPCC) 40 CFR Part 112 Naval Air Station Corpus Christi Texas CY 2014 BOTTOM LINE UP FRONT To prevent oil discharges

More information

FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING

FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING insulation installed on foundation walls must be separated from the building interior with a code approved thermal barrier. Foam

More information

Civil Engineering Sector Labour-Management Health and Safety Committee

Civil Engineering Sector Labour-Management Health and Safety Committee PROCEDURE FOR THE STORAGE AND HANDLING OF FUEL ON CONSTRUCTION SITES Civil Engineering Sector Labour-Management Health and Safety Committee July 2008 PROCEDURE FOR THE STORAGE AND HANDLING OF FUEL ON CONSTRUCTION

More information

Maintenance Matters. Building Envelope Maintenance and Renewals Planning. Building Envelope. Maintenance Bulletin

Maintenance Matters. Building Envelope Maintenance and Renewals Planning. Building Envelope. Maintenance Bulletin Maintenance Matters Building Envelope 7 Maintenance Bulletin No. The primary focus of this bulletin is on the importance of being proactive rather than reactive in the maintenance and care of buildings.

More information

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection

More information

CF-Mesa, CF-Light Mesa, CF-Flute, CF-Metl-Plank, CF-Striated, CF-Santa Fe, CF-Architectural Flat, CF...

CF-Mesa, CF-Light Mesa, CF-Flute, CF-Metl-Plank, CF-Striated, CF-Santa Fe, CF-Architectural Flat, CF... Building Insulations - Walls and Ceilings (FM Approval Numbers 4411, 4651, 4880, 4881, 4882) Insulating materials may occur in building construction to reduce heat or sound transmission through a wall,

More information

GUIDANCE FOR DEVELOPMENT OF SPILL AND SLUG PREVENTION CONTROL PLANS AND FACILITIES FOR THE CITY OF ATTLEBORO SEWER USERS

GUIDANCE FOR DEVELOPMENT OF SPILL AND SLUG PREVENTION CONTROL PLANS AND FACILITIES FOR THE CITY OF ATTLEBORO SEWER USERS Company Name: Address: The City of Attleboro s Rules and Regulations for the use of Wastewater Facilities require each user to provide protection from accidental discharge of prohibited materials and substances

More information

WINDOW AND DOOR REPLACEMENT REQUIREMENTS

WINDOW AND DOOR REPLACEMENT REQUIREMENTS WINDOW AND DOOR REPLACEMENT REQUIREMENTS Should you have any questions after reading the following information, please call the Building Inspection Department at 651-439-4439 to discuss the topics of concern.

More information

HERNANDO COUNTY FIRE ALARM GUIDELINES

HERNANDO COUNTY FIRE ALARM GUIDELINES HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a

More information

Maintenance Matters. Window and Door Replacement

Maintenance Matters. Window and Door Replacement Number 13 Maintenance Matters building maintenance bulletin Window and Door Replacement As part of the ongoing maintenance of your home or multi-unit residential building, windows and doors will eventually

More information

BP WIND ENERGY POLICIES AND PROCEDURES

BP WIND ENERGY POLICIES AND PROCEDURES BP WIND ENERGY POLICIES AND PROCEDURES Document Control Details 1.0 Purpose/Scope 1.1 This procedure provides the minimum requirements to be followed for the storage of flammable or combustible materials

More information