Vestibule Case Study. Vestibule Requirement Intent [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, , ]
|
|
|
- Ferdinand Haynes
- 10 years ago
- Views:
Transcription
1 Vestibule Case Study [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, , ] Vestibule Requirement Intent Page 1 of 14
2 The primary intent behind the requirement for a vestibule is to reduce infiltration into a space that includes doors with high volume of pedestrian traffic. These doors are typically used by the general public to access public areas and have a higher usage rate than a door classified for personnel use. Vestibules reduce the infiltration losses (or gains) from wind and stack effect by creating an air lock entry. The stack effect caused by naturally occurring warm air rising, is greater in taller buildings than in low rise construction but under the provisions of the 2003 and 2006 IECC no allowance is made for building height or number of stories. Wind exposure is dependant on the orientation of the building and greater infiltration driver in low-rise commercial buildings verses stack effect. When Is A Vestibule Required? Vestibules are required in Chapter 8 of the 2003 IECC (Section ), Chapter 5 of the 2006 IECC (Section ), ANSI/ASHRAE/IESNA Standard (Section ), and Standard (Section ). Essentially a vestibule is required on the primary entrance doors leading from spaces in a building greater than or equal to 3000 ft². Both the IECC and 90.1 have similar requirements for when a vestibule is required and the configuration of the vestibule. However, and exempt vestibules in buildings less than four stories. Page 2 of 14
3 A lobby surrounded by floor-to-ceiling partitions, a roof/ceiling assembly and floor assembly could be considered a space. The lobby walls can contain operable windows and doors that isolate the space from the adjoining spaces or the exterior. The IECC, and [1] require vestibules for "spaces" that are 3000 ft² or greater. This is not the building area but a space within a building. For example, an entrance to a 2000 ft² retail store with a 1,500 ft² storage area, closed off by doors, would not require a vestibule. However, a 4000 ft² retail space with an entrance door to a sales area of 3000 ft² would be required to have a vestibule. In some circumstances, it is difficult to define where one space ends and another begins for the purposes of calculating whether the size of the space with an outside entrance door requires a vestibule. An example of this is a 2000 ft² lobby with one wall substantially open to a larger adjacent lounge. In such a case, the two areas should probably be considered a single space, and a vestibule should be required. The following definition is offered by and and provides some guidance: Space. The following definition is offered by and : "A volume substantially surrounded by solid surfaces such as walls, floors, roofs and openable devices such as doors and operable windows." Page 3 of 14
4 The word "substantially" must be interpreted for the purpose of determining the need for a vestibule. Unfortunately, the IECC has no such definition. Doors. Based on the exceptions that apply to the IECC, Standard and Users Manual, and Standard and Users Manual, the doors that are affected by this requirement are doors intended as entrances to the building that receive pedestrian traffic from both the general public and building occupants. For example, the doors leading into a public lobby would be required to have a vestibule where doors leading to service areas, mechanical rooms, electrical rooms or exits from fire stairways would be exempt. Personnel doors adjacent to doors used to facilitate vehicular movement or material handling are exempt. For example, a door adjacent to a loading dock would be exempt. Page 4 of 14
5 Page 5 of 14
6 If the building has more than one entrance into a space 3000 ft² or greater, each of the doors must have a vestibule. For example, a gas station/convenience store may include two entrances into the open store area. If the space is 3000 ft² or greater each of the entrances would be required to have a vestibule. Page 6 of 14
7 Page 7 of 14
8 The 2003 and 2006 IECC, and the and provide an exemption from the vestibule requirement in entrances that use revolving doors as they provide adequate protection against infiltration into the space. If a revolving door is used in place of a vestibule, the 2003 and 2006 IBC Section require that a side-hinged swinging door must also be installed within 10 feet of the revolving door. Doors are also required to have self closing devices. A door closure system on a swinging door would meet the intent of the requirement as would a power operated door -- such as a door with a motion-actuated mechanism to open the door upon the approach of a person. Page 8 of 14
9 Vestibule Dimensions. The IECC provides guidance to determine the minimum depth of the vestibule by requiring that the vestibule must be designed so that it is not necessary to open doors leading into and out of the vestibule at the same time in order to pass through. This requirement allows a person to enter the vestibule, have the door shut behind them and then exit the vestibule while maintaining an air lock to reduce infiltration. The requirements in and are identical except that a minimum of seven feet is also required between the doors leading out of the vestibule when the doors are in the closed position. Page 9 of 14
10 ICC/ANSI A Accessible and Usable Buildings and Facilities (A ), referenced in the 2003 IBC (see Code Reference section), provides a requirement for minimum distances between two doors in a series, such as in a vestibule configuration. A requires that the distance between the two hinged or pivoted doors that are in series must have a minimum distance of 48" between them plus the width of the door swinging into the space. For example, if the door swing into the space is 34" the minimum distance that would be required would be 82". In addition to the minimum depth of the vestibule, A also places requirements on the minimum width that a vestibule can be. A minimum of a 60" turning diameter is required to be able to turn a wheelchair in the vestibule. Compliance with the Code The first step in determining compliance with the envelope requirements of the IECC is to determine the boundary of the building envelope. The vestibule requirement specifies that a door that separates conditioned space from the exterior is to have a vestibule. Because the door is specified as an exterior door, the wall assembly that contains the door is considered part of the building envelope and therefore must comply with the IECC. Page 10 of 14
11 Two common vestibule configurations are provided as examples on defining the building envelope. A common vestibule installation example is to have the vestibule protruding from the exterior of the building to protect the exterior doors. In this example the items associated with the red walls are considered to be part of the building envelope and therefore must comply with the IECC. Because the vestibule now forms an unconditioned space, the wall, window and door assemblies that separate the conditioned space from the vestibule can meet the interior wall requirement. The walls must meet the R-value requirements based on construction type. In addition, the windows and doors must meet the maximum U-factor and SHGC requirements based on the 0 10% glazing percentage. The glazing, doors and opaque surfaces associated with the vestibule itself are not covered under the provisions of the IECC. Page 11 of 14
12 Another example of a vestibule configuration is to have the vestibule come into the conditioned space instead of protruding from the building. In this scenario, the walls and glazing assemblies that surround the vestibule (see red assemblies) must meet the interior wall requirements (Chapter 8 of the 2003 IECC and Chapter 5 of the 2006 IECC). The door and wall assemblies that form the wall between the vestibule and the exterior (see grey assemblies) would be exempt. Compliance with the International Building Code In addition to meeting the requirements of the IECC or / , vestibules must also be designed to meet the requirements of the International Building Code for means of egress and accessibility. Code Citations* IECC 2003 Section and IECC 2006 Section Vestibules A door that separates conditioned space from the exterior shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing devices. Vestibules shall be designed so that in passing through the vestibule it is not necessary for the interior and exterior doors to open at the same time. Exceptions: 1. Buildings in Climate Zones 1a through 4b as indicated in Table (See Energy Code Climate Zones ) [2003 IECC]; Buildings in Climate Zones 1 and 2 as indicated in Table [2006 Page 12 of 14
13 IECC]. 2. Doors not intended to be used as a building entrance door, such as doors to mechanical or electrical equipment rooms. 3. Doors opening directly from a guestroom or dwelling unit [2003 IECC]; Doors opening directly from a sleeping unit or dwelling unit [2006 IECC]. 4. Doors that open directly from a space less than 3,000 square feet (298 m²) in area. 5. Revolving doors. 6. Doors used primarily to facilitate vehicular movement or material handling and adjacent personnel doors. ANSI/ASHRAE/IESNA Standard Section and Section Vestibules A door that separates conditioned space from the exterior shall be protected with an enclosed vestibule, with all doors opening into and out of the vestibule equipped with self-closing devices. Vestibules shall be designed so that in passing through the vestibule it is not necessary for the interior and exterior doors to open at the same time. Interior and exterior doors shall have a minimum distance between them of not less than 7 ft when in the closed position. Exceptions: 1. Doors in buildings in climates that have less than 1800 HDD65 [ ]; Buildings in Climate Zones 1 and 2 [ ]. 2. Doors in buildings less than four stories above grade 3. Doors not intended to be used as a building entrance door, such as mechanical or electrical equipment rooms 4. Doors opening directly from a dwelling unit 5. Doors that open directly from a space less than 3000 ft² in area 6. Doors in building entrances with revolving doors 7. Doors used primarily to facilitate vehicular movement or material handling and adjacent personnel doors and 2006 IBC Section Adjoining spaces. Where rooms and spaces without openings to the outdoors are ventilated through an adjoining room, the opening to the adjoining rooms shall be unobstructed and shall have an area not less than 8 percent of the floor area of the interior room or space, but not less than 25 square feet (2.3 m²). The minimum openable area to the outdoors shall be based on the total floor area being ventilated. ICC/ANSI A Two Doors In Series Distance between two hinged or pivoted doors in series shall be 48 inches minimum plus the width of any door swinging into the space. The space between the doors shall provide a turning space complying with Section 304. Page 13 of 14
14 2003 and 2006 IBC Section Revolving doors Revolving doors shall comply with the following: Each revolving door shall have a side-hinged swinging door which complies with Section in the same wall and within 10 feet (3048 mm) of the revolving door IBC Section and 2006 IBC Section General Exception 2. A maximum of 50 percent of the number and capacity of the exit enclosures is permitted through a vestibule provided all of the following are met: 1. The entire area of the vestibule is separated from the areas below by construction conforming to the fire-resistance rating for the exit enclosure. 2. The depth from the exterior of the building is not greater than 10 feet (3048 mm) and the length is not greater than 30 feet (9144 mm). 3. The area is separated from the remainder of the level of exit discharge by construction providing protection at least the equivalent of approved wired glass in steel frames. 4. The area is used only for means of egress and exits directly to the outside. Note: [1] ASHRAE and have an exemption for the number of floors in the building. See Section and Section * 2003 IECC Reference and link *Copyright, 2003, International Code Council, Inc. Falls Church, Virginia. Reproduced with permission. All rights reserved International Energy Conservation Code 2003 International Energy Conservation Code ; 2006 IECC Reference and link *Copyright, 2006, International Code Council, Inc. Falls Church, Virginia. All rights reserved International Energy Conservation Code International Energy Conservation Code ; 2003 IECC Reference and link *Copyright, 2003, International Code Council, Inc. Falls Church, Virginia. Reproduced with permission. All rights reserved International Energy Conservation Code 2003 International Building Code ; 2006 IECC Reference and link *Copyright, 2006, International Code Council, Inc. Falls Church, Virginia. All rights reserved International Energy Conservation Code International Building Code ; ASHRAE Reference and link Copyright, 2001, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Atlanta, GA. ASHRAE Standard Reproduced with permission. All rights reserved. ; ASHRAE Reference and link Copyright, 2004, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Atlanta, GA. ASHRAE Standard Reproduced with permission. All rights reserved.. Page 14 of 14
Building Codes Update: The 2009 International Fire Code and the Apartment Industry
! Building Codes Update: The 2009 International Fire Code and the Apartment Industry Apartment operators and developers should be aware of organizational changes in the 2009 edition of the International
BUILDING PERMIT SPECIFICATIONS
BUILDING PERMIT SPECIFICATIONS The below noted requirements are based upon La Plata County Building Code. These specifications are not intended as a complete set of requirements, but are intended to provide
IECC Compliance Guide for Homes in Virginia
IECC Compliance Guide for Homes in Virginia Amended Version of 2012 International Energy Conservation Code July 14, 2014 Climate Zone Since the entire state of Virginia falls in the IECC Climate Zone 4,
http://www.iccsafe.org/
Sections R311 and R312 from the 2006 International Residential Code These sections of Chapter 3 of the 2006 International Residential Code for One and Two Family Dwellings (R311 and R312) including the
Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013
Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems April 2013 The National Multi Housing Council and the National Apartment Association (NMHC/NAA) have
CITY PLAN REVIEW AND INSPECTION. Lisa Fleming Brown, CPM
CITY PLAN REVIEW AND INSPECTION Lisa Fleming Brown, CPM Houston Commercial Energy Conservation Code (2011) A choice of 2009 IECC or ASHRAE 90.1-2007 with amendments. Effective September 2, 2011. Complete
The replacement or modification of existing windows shall comply with the following requirements:
City of La Habra Heights Building Division 1245 N. Hacienda Road La Habra Heights, CA 90631 Office: (562) 694-6302 ext. 228 Fax: (562) 690-5010 WINDOW REPLACEMENT 2010 CALIFORNIA RESIDENTIAL CODE (CRC)
A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS
A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS International Code Council National Fire Protection Association Underwriters Laboratories Inc. 5203 Leesburg Pike, Suite 600 1 Batterymarch
PLAN REVIEW SERVICES CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW
CONSTRUCTION DOCUMENTS NECESSARY FOR A THOROUGH PLAN REVIEW PRELIMINARY BUILDING REVIEW two sets of the following: Architectural/engineering design development drawings indicating size of the building,
2009 IECC Update. Scope. Content. International Energy Conservation Code
2009 IECC Update International Energy Conservation Code Scope The code applies to both residential and commercial buildings. In the code, the United States is divided into eight climate zones which are
New York City Department of Buildings
The New NYC Building Code Chapter 10 Means of Egress New York City Department of Buildings Technical Affairs Fatma M. Amer, P.E. Copyright Materials This presentation is protected by US and International
Building Energy Codes 101 October 23, 2013. Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance
Building Energy Codes 101 October 23, 2013 Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance OVERVIEW 1. Introduction 2. Energy Code Development 3. Adoption Process 4. Elements
Area of Rescue Assistance Communication System ADA Code Applicable excerpts:
Area of Rescue Assistance Communication System ADA Code Applicable excerpts: CONTENTS (Guidelines and Definitions) Page 1 Area of Rescue Assistance Requirements Page 2 Emergency Communication Equipment
Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS
Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS 1009.1 Stairway width. The width of stairways shall be determined as specified in Section 1005.1, but such width shall not be less than 44
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov BUILDING CODE REQUIREMENTS FOR CHILD DAY CARE The purpose of this document is to provide the user with a basic level
Current as of 11/10/08 1 of 1
BEST PRACTICES STANDARDS FOR SCHOOLS UNDER CONSTRUCTION OR BEING PLANNED FOR CONSTRUCTION I. Site Layout A. School buildings shall be provided with a securable perimeter. A securable perimeter means that
Building Control Guidance Note
Issued 01/01/13 Rev Page 1 of 5 If you intend to convert an existing loft space into additional rooms you will need to apply for Building Regulation Approval. You may also need Planning Permission if you
Automatic Door Selection Guide
Automatic Door Selection Guide AAADM 1300 Sumner Avenue Cleveland, OH 44115 P: 216-241-7333 F: 216-241-0105 [email protected] Automatic Door Selection Guide General: The members of AAADM manufacture an assortment
2012 Ontario Building Code Requirements for New Construction. Bradford West Gwillimbury Building Division March 5, 2012
2012 Ontario Building Code Requirements for New Construction Bradford West Gwillimbury Building Division March 5, 2012 1 Ontario Building Code changes Applicable to permits applied for after December 31,
MEANS OF EGRESS CHAPTER 10
CHAPTER 10 MEANS OF EGRESS SECTION BC 1001 ADMINISTRATION 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this
Excerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
Building Code Clarifications - 7. Fire Resistance
Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,
FIRE-RESISTANCE-RATED CONSTRUCTION
CHAPTER 7 FIRE-RESISTANCE-RATED CONSTRUCTION SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials and assemblies used for structural fire resistance and fire-resistance-rated
Code Requirements for Existing Buildings
Code Requirements for Existing Buildings Kevin S. Hastings, P.E., LEED AP R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com R.W. Sullivan Engineering (RWS)
GENERAL FIRE SAFETY TERMS & DEFINITIONS
UCL Fire Technical Note - TN006 Fire Safety Technical Guide GENERAL FIRE SAFETY TERMS & DEFINITIONS Reference: BS4422-2005 Fire Safety Vocabulary - for further information and definitions BS EN ISO 13943-2000:
Walking and Working Surface Checklist:
Walking and Working Surfaces Purpose: This information is presented to improve the level of safety in our operations, and to inform you that we will comply with the OSHA Standard 29 CFR 1910.23. Responsibility:
Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls
PCA R&D Serial No. 415 Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls by John Gajda and Martha VanGeem 000 Portland Cement Association KEYWORDS Concrete,
MEANS OF EXIT / ESCAPE / EGRESS SELF INSPECTION CHECKLIST
OPTIONAL INFORMATION Name of School: Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: MEANS OF EXIT / ESCAPE / EGRESS Guidelines: This checklist covers some of the regulations
24.301.161 INCORPORATION BY REFERENCE OF INTERNATIONAL. (1) The Department of Labor and Industry adopts and incorporates by
24.301.161 INCORPORATION BY REFERENCE OF INTERNATIONAL ENERGY CONSERVATION CODE (1) The Department of Labor and Industry adopts and incorporates by reference the International Code Council's International
MINNESOTA DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division STATEMENT OF POLICY. State Fire Marshal
MINNESOTA DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division STATEMENT OF POLICY Policy #: Subject of Policy: INS-04 (2007) Escape Windows Revised and Approved By: Title: Jerry Rosendahl State Fire
FIRE AND LIFE SAFETY REQUIREMENTS FOR EXISTING BUILDINGS
CHAPTER 46 FIRE AND LIFE SAFETY REQUIREMENTS FOR EXISTING BUILDINGS SECTION 4601 GENERAL 4601.1 Scope. The provisions of this chapter shall apply to existing buildings constructed prior to a state building
Building Permit Application Packet. BUILDING CODES Adopted by La Plata County For Enforcement In The Unincorporated Areas Of La Plata County
Building Permit Application Packet The purpose of Building Codes is to establish the minimum requirements to safe guard the public health, safety and general welfare through structural strength, means
FIRE-RESISTANCE-RATED CONSTRUCTION
CHAPTER 7 FIRE-RESISTANCE-RATED CONSTRUCTION SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials and assemblies used for structural fire resistance and fire-resistance-rated
MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY
MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/201-7200 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us
NC Rehab Code Case Study Cheerwine Building January 17, 2002; rev 4/12/02
NC Rehab Code Case Study Cheerwine Building January 17, 2002; rev 4/12/02 PART A: Project Data and Classification 1. Project name & location Renovation of the Cheerwine Building, 322 East Council St.,
BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS
DCD-0304 Identification # Rev. 9/08 County Date of Inspection NAME OF OPERATION BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS ADDRESS TELEPHONE: CITY STATE ZIP BUILDING INSPECTORS CERTIFICATE
LOW-RISE RESIDENTIAL BUILDINGS ADDITIONS AND ALTERATIONS IN EXISTING LOW-RISE RESIDENTIAL BUILDINGS
SUBCHAPTER 9 LOW-RISE RESIDENTIAL BUILDINGS ADDITIONS AND ALTERATIONS IN EXISTING LOW-RISE RESIDENTIAL BUILDINGS SECTION 150.2 ENERGY EFFICIENCY STANDARDS FOR ADDITIONS AND ALTERATIONS IN EXISTING BUILDINGS
MEANS OF EGRESS CHAPTER 10
CHAPTER 10 MEANS OF EGRESS SECTION 1001 ADMINISTRATION 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this
Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer
Residential HVAC Load Sizing Training October 14, 2015 David Kaiser Green Code Plan Reviewer DCRA - Green Building Division Regulations of green codes including: Green Building Act Green Construction Code
City of Douglas Commercial Building Permit Site Application
City of Douglas Commercial Building Permit Site Application *Complete the following information including a complete site plan and floor plan. *Incomplete information may result in delay and/or rejection
REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N
PLAN REVIEW FOR: PROJECT NAME: OWNER: ARCH/DESIGNER: ADDRESS: Ph/Fx: Plans Dated: E-mail: Sealed By: Estimated Project Cost - $ REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N
Healthcare Engineering. Code Summary Report
American Society for Healthcare Engineering Code Summary Report CODE SUMMARY HEALTH CARE NEW BUILDINGS This code summary is based on the following codes: 2000 Edition NFPA 101, The Life Safety Code (LSC),
SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon)
SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon) SECTION SR101 GENERAL SR101.1 General. Group SR occupancies shall comply with the provisions of this appendix
Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM STORY HEIGHT
Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE Sec. 58.1. Division D-O occupancies. 58.2. Separation and mixed occupancy. OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM
Number of Sides Required to Have a Handrail
Excerpt from 2012 B.C. Building Code HANDRAILS & GUARDS 9.8.7. Handrails 9.8.7.1. Required Handrails 1) Except as provided in Sentences (2) to (4), handrails shall be installed on stairs and ramps in accordance
CHAPTER 4 VENTILATION
CHAPTER 4 VENTILATION SECTION 401 GENERAL 401.1 Scope. This chapter, in conjunction with the building code, shall govern the ventilation of spaces within a building intended to be occupied. Mechanical
MEANS OF EGRESS CHAPTER 10
CHAPTER 10 MEANS OF EGRESS SECTION 1001 ADMINISTRATION 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this
WINDOW AND DOOR REPLACEMENT REQUIREMENTS
WINDOW AND DOOR REPLACEMENT REQUIREMENTS Should you have any questions after reading the following information, please call the Building Inspection Department at 651-439-4439 to discuss the topics of concern.
MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS
CHAPTER 93 MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS Note: Chapter 93 is entirely Seattle amendments to the International Fire Code and is not underlined. Point of Information The requirements of this
This notice sets forth interim guidance, pending the issuance of regulations,
Part III - Administrative, Procedural, and Miscellaneous Deduction for Energy Efficient Commercial Buildings Notice 2006-52 SECTION 1. PURPOSE This notice sets forth interim guidance, pending the issuance
Comparison of Standard 90.1-2010 and the 2012 IECC with Respect to Commercial Buildings
BUILDING TECHNOLOGIES PROGRAM Comparison of Standard 90.1-2010 and the 2012 IECC with Respect to Commercial Buildings September 2011 Authors: Eric Makela Jennifer Williamson Erin Makela Prepared by Pacific
BUILDING SAFETY UNIT
POLICY Page 1 of 5 SUBMITTAL REQUIREMENTS FOR ONE AND TWO FAMILY DWELLINGS, ADDITIONS AND RENOVATIONS All submittals shall be site specific and designed to the provisions of the 2012 International Residential
Residential Plan Review Emergency Vehicle Access and Water Supply Permit Information Packet
Residential Plan Review Emergency Vehicle Access and Water Supply Permit Information Packet 1. Definitions a. AHJ Authority Having Jurisdiction. The Fire Chief or Fire Marshal of a given Fire District
Charter Township of Shelby Harry Reese Building Director
Charter Township of Shelby Harry Reese Building Director Phone: (586) 731-5969 52700 Van Dyke Fax: (586) 803-2099 Shelby Township, MI 48316-3572 E-mail: [email protected] OUTLINE PROCEDURES FOR PRIVATE
Indiana Building Rehabilitation Standard
Rule 8. Indiana Building Rehabilitation Standard 675 IAC 12-8-1 Definitions Sec. 1. The following definitions apply throughout this rule: (1) "Building code" means the Indiana Building Code under 675 IAC
New York City Department of Buildings
The New NYC Building Code Chapter 11 Accessibility New York City Department of Buildings Technical Affairs Keith Wen, R.A. Copyright Materials This presentation is protected by US and International Copyright
2014 British Columbia Building Code Changes
District of Houston 250-845-2238 2014 British Columbia Building Code Changes A District of Houston interpretation of the 2014 Building Code Changes for 9.36 & 9.32 The following changes reflect the most
MEANS OF EGRESS CHAPTER 10
CHAPTER 10 MEANS OF EGRESS SECTION 1001 ADMINISTRATION 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this
This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
I N T E R N A T I O N A L R E S I D E N T I A L CO D E
Visual Interpretation Of The I N T E R N A T I O N A L R E S I D E N T I A L CO D E 2006 STAIR BUILDING CODE Portions of this document reproduce sections from the 2006 International Residential Code, International
Certification: Building Plans Examiner. Exam ID: B3
Certification: Building Plans Examiner Exam ID: B3 Scope: A Building Plans Examiner will be responsible for reviewing submitted plans to determine if they meet the requirements of the various Building
PROJECT SUMMARY. Scope of work details: (If phased construction, please see plan submittal guidelines.)
APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL FIRE RESTORATION PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) (Reproduce the following data on the building plans sheet 1 or 2) Name of
INDIANA COMMERCAL ENERGY CODE BASELINE STUDY
INDIANA COMMERCAL ENERGY CODE BASELINE STUDY March 21, 2005 Report Prepared for Indiana Department of Commerce, Energy and Recycling Division One North Capitol Avenue, Suite 700 Indianapolis, IN 46204
Continuous Insulation Using Polyiso Wall Sheathing
PIMA Technical Bulletin #403 Continuous Insulation Using Polyiso Wall Sheathing What it is, what it does, and why you need it About Polyiso Insulation Polyiso is a rigid foam insulation used in over 70%
Heating Load Calculation
Heating Load Calculation ME 425 Air Conditioning System Design Keith E. Elder, P.E. Heating Load Calculation The heating load calculation begins with the determination of heat loss through a variety of
Single Family Residential Basement Finish
How to Use This Guide Building Guide Pottawattamie County Planning & Development Department Building & Safety Division Single Family Residential Basement Finish Provide two (2) sets of plans and complete
FIRE SAFETY INSPECTION REPORT
FIRE SAFETY INSPECTION REPORT SINCERE KNIT GARMENTS LTD UNIT-1 EAST ISDAIR, CHANDMARI, FATULLAH OTHER FACTORIES: FAKIR KNIT LTD. July 20, 2014 Page 2 SUMMARY was surveyed for fire safety on 7/20/2014 by
Commercial Building Valuation Report
INSURED University of Houston - Victoria Effective Date: Expiration Date: Cost as of: 09/2010 BUILDING 1 217 - University Center 77901 Location Adjustments Climatic Region: High Wind Region: Seismic Zone:
City of Wichita, Kansas Americans with Disabilities Act Transition Plan Main Library Address
City of Wichita, Kansas Americans with Disabilities Act Transition Plan Main Library Address July 005 Prepared by DMCG Disability Management Consulting Group L.L.C. 801 Jonquil Place Columbia, MO 650 In
General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission
General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission Local Fire Alarm 064. FIRE ALARM SYSTEMS 01. Scope 02. Definitions 03.
HCD DSA OSHPD 1 2 1/AC AC SS SS/CC 1 2 3 4 2013 CALIFORNIA BUILDING CODE 199
CALIFORNIA BUILDING CODE MATRIX ADOPTION TABLE CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter for state agency
- 5 - Table1. Maximum Compartment Volumes
- 5 - Part II - SPECIFIC REQUIREMENTS 5. Compartmentation 5.1 Every building should be divided into compartments by walls and floors to inhibit the spread of fire. 5.2 Compartment walls, compartment floors,
Compliance Software COMcheck 2 and ENVSTD 3
CMU walls comply with energy codes for commercial buildings in many climates WITHOUT the addition of continuous insulation Here are compliance options for above grade, non residential, single wythe CMU
Civil Engineering and Architecture (CEA) Detailed Outline
Civil Engineering and Architecture (CEA) Detailed Outline Unit 1: Overview of Civil Engineering and Architecture (23 days) Lesson 1.1: History of Civil Engineering and Architecture 1. Many features of
AEDG Implementation Recommendations: Interior Lighting Sample Layouts for Office Buildings
AEDG Implementation Recommendations: Interior Lighting Sample Layouts for Office Buildings The Advanced Energy Design Guide (AEDG) seeks to achieve 30 percent savings over Standard 90.1-1999. This guide
CHILD CARE CENTER INFORMATION SHEET
CHILD CARE CENTER INFORMATION SHEET SECTION 1 INTRODUCTION This fire safety information sheet is based on the 2007 Minnesota State Fire Code (MSFC) and the 2007 Minnesota State Building Code (MSBC). It
THERMAL LOSSES Thermal Losses Calculations
Calculations -1- THERMAL LOSSES Thermal Losses Calculations Employer : 4M SA Project Location : ASHRAE Office Room : Example from ASHRAE 2013 Handbook - Fundamentals : Chapter 18, Single Room Example Peak
Fire Alarm Systems Requirements by Occupancy Type
WALT WHITE Fire Chief 5770 Freeport Blvd., Suite 200 Sacramento, CA 95822-3516 Ph: (916) 808-1300 Fax: (916) 808-1629 www.sacfire.org Fire Alarm Systems Requirements by Occupancy Type 2013 California Building
RULING OF THE MINISTER OF MUNICIPAL AFFAIRS AND HOUSING
BUILDING CODEACT, 1992 RULING OF THE MINISTER OF MUNICIPAL AFFAIRS AND HOUSING Pursuant to clause 29(l)(b) of the Building Code Act, 1992. as amended, the Director of the Building and Development Branch
H:\forms\handouts\bldg049 1 of 11 Revised Mar 2/15/dh
Accessory Apartment Construction Guide For Single Detached Dwelling and Semi-Detached Dwellings that have been in existence for at least five (5) years Notes: Buildings that are less than five (5) years
New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings
New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings Note: This information addresses complex issues in a summary fashion. Consideration should be given to the official version of the
How To Protect A Swimming Pool
County of Gloucester Codes Compliance Building Department Building Three P. O. Box 329 Gloucester, Virginia 23061 Building Code Guidelines Residential Swimming Pools & Spas KEEP YOUR POOL SAFE CODE REQUIREMENTS
Guidance on loft conversions in two-storey houses
Guidance on loft conversions in two-storey houses Technical guidance for building control surveyors, designers and installers 01 Guidance on loft conversions in two-storey houses Technical guidance for
1/9/2013. Terminology Calculating Heat Transfer Code Requirements Design Examples and Sustainability
1/9/13 By Brett T. Fagan, P.E. Presented by Marie Horan, P.E. Building Diagnostics, Inc. Building Diagnostics Terminology Calculating Heat Transfer Code Requirements Design Examples and Sustainability
2012 IECC Commercial Electrical Power and Lighting Systems July 2011
BUILDING ENERGY CODES UNIVERSITY 2012 IECC Commercial Electrical Power and Lighting Systems July 2011 PNNL-SA-82199 Commercial Compliance Options 2012 IECC 2012 IECC 1 90.1-2010 2 C402 - Envelope C403
MEANS OF EGRESS CHAPTER 10
CHAPTER 10 MEANS OF EGRESS SECTION 1001 ADMINISTRATION 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this
FIRE AND SMOKE PROTECTION FEATURES
CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated
Preparation for 2015 Residential Code Changes Discussion with Local Builders and Designers
City of Duluth Preparation for 2015 Residential Code Changes Discussion with Local Builders and Designers Thank you for taking the time to join us today. We know you are busy and your time is valuable.
9.8.1.1. General (1) This Section applies to the design and construction of interior and exterior stairs, steps, ramps, railings and guards.
Section 9.8. Stairs, Ramps, Handrails and Guards 9.8.1. Application 9.8.1.1. General (1) This Section applies to the design and construction of interior and exterior stairs, steps, ramps, railings and
A Code Review for Emergency Generators and Indoor Use of Portable Generators
A Code Review for Emergency Generators and Indoor Use of Portable Generators By: the Fire and Life-Safety Group (FLS) Fire Code requires that emergency generators be stationary generators. Therefore, a
REQUIREMENT 3. Usable Doors
Chapter Three: REQUIREMENT 3 Usable Doors 3...covered multifamily dwellings with a building entrance on an accessible route shall be designed in such a manner that all the doors designed to allow passage
Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application
February 2014 Code Requirements and Inspections in Educational Occupancies Presented By: Barry W. Rickert Douglas M. Schanne Fire Marshal Training Program Supervisor Office of Education & Data Management
Classroom Door Security & Locking Hardware
Classroom Door Security & Locking Hardware The ability to protect students and teachers while in the classroom is a high priority in all educational institutions. Many schools and school districts have
CODE NOTES. Insulation Requirements in Commercial Buildings for Mechanical and Service Hot-Water Piping
BUILDING TECHNOLOGIES PROGRAM Insulation Requirements in Commercial Buildings for Mechanical and Service Hot-Water Piping The intent of the pipe insulation requirements is to reduce temperature changes
Overview of Hotel Fire Safety Requirements
Overview of Hotel Fire Safety Requirements in the Fire Code Susan Clarke, P.Eng. Office of the Fire Marshal - January 10, 2012 1 Agenda Regulation History - Hotels Fire Code Overview (Parts 1 to 8) Defined
Control filling, grading, dredging, and other development which may increase erosion or flood damage; and
ARTICLE 16. FLOOD DAMAGE PREVENTION Section 16-1: Findings of Fact The flood hazard areas of the Town of Lillington are subject to periodic inundation which results in loss of life and property, health