GE Multilin technical note



Similar documents
Shunt Capacitor Bank Fundamentals and Protection

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

Chapter 24. Three-Phase Voltage Generation

Introduction to Paralleling of LTC Transformers by the Circulating Current Method

IAV. Time Delay Voltage. For AC and DC circuit applications. GE Multilin 1. Protection and Control. Features and Benefits.

System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems

Equipment: Power Supply, DAI, Variable resistance (8311), Variable inductance (8321)

Figure. 1 - Split Phase 240/120V circuit (180 phase shift)

TESLA Recorder Power Metering Setup Configuration for 3 and 2 Element Watt/VAR Metering

BJT AC Analysis. by Kenneth A. Kuhn Oct. 20, 2001, rev Aug. 31, 2008

THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating.

ECE 431. Experiment #1. Three-Phase ac Measurements. PERFORMED: 26 January 2005 WRITTEN: 28 January Jason Wells

ELECTRONIC POWER SYSTEMS

SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

Protection of Phase Angle Regulating Transformers

How To Wire A Three Phase, Single Phase, Wye Transformer

Lecture Notes ELE A6

Motor Protection Principles. Craig Wester GE Multilin

CT Application Guide for the 489 Generator Management Relay

BALANCED THREE-PHASE CIRCUITS

1 Introduction. 2 Two Phases. J.L. Kirtley Jr.

Radial Distribution Test Feeders

1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr.

SIMULATIONS OF PARALLEL RESONANT CIRCUIT POWER ELECTRONICS COLORADO STATE UNIVERSITY

DNP Points List and Implementation

S&C BankGuard PLUS Control

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES

Open Phase Conditions in Transformers Analysis and Protection Algorithm

= (0.400 A) (4.80 V) = 1.92 W = (0.400 A) (7.20 V) = 2.88 W

Fault Analysis I PowerWorld Corporation

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

Transformer circuit calculations

Grounding of AC generators and switching the neutral in emergency and standby power systems

Loss of ac Voltage Considerations For Line Protection

Measurement, Modeling and Simulation of Capacitor Bank Switching Transients

Preamble. Kirchoff Voltage Law (KVL) Series Resistors. In this section of my lectures we will be. resistor arrangements; series and

30. Bode Plots. Introduction

Percentage Restrained Differential, Percentage of What?

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

Installation manual. Generator Paralleling Controller GPC multi-line C

Chapter 12: Three Phase Circuits

Transformer protection

Product Guide. Low voltage grounding system. Answers for industry.

TYPE TEST CERTIFICATE OF SHORT-CIRCUIT PERFORMANCE. A three-phase outdoor oil-immersed distribution transformer

Type SA-1 Generator Differential Relay

Hyperlinks are Inactive

Differential Amplifier Offset. Causes of dc voltage and current offset Modeling dc offset R C

Product Data Bulletin

Table of Contents. TransformerIQ FAQs 1

VOLTAGE REGULATOR AND PARALLEL OPERATION

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

Ground Fault Protection on Ungrounded and High Resistance Grounded Systems

Power Technology Issue 104. Modeling of Two-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v Spring web.itu.edu.tr/yumakk. Distance Protection

Power Technology Issue 106. Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

Three phase circuits

THREE PHASE CIRCUITS

Introduction to PowerWorld Simulator: Interface and Common Tools

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

Eaton s E-Series protective relay family

ET 332b Ac Electric Machines and Power Systems

FIT TIER 2 Application

WHITE PAPER GROUND FAULT. Lowering the Limits for Ground Fault Detection

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Three-Phase Electric Power Distribution for Computer Data Centers

Definition AC Power Distribution

3-Phase AC Calculations Revisited

Generator Differential Relay Electrical Apparatus

Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS

NC-12 Modbus Application

Voltage Regulator SPAU 341 C. Product Guide

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Series and Parallel Circuits

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.

Transmission Protection Overview

Series-Parallel Circuits. Objectives

Both variants can be used for measuring the positive sequence voltage Up or the negative sequence voltage Un.

ACCURACY OF POTENTIALTRANSFORMERS

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument D

Chapter 4 AC to AC Converters ( AC Controllers and Frequency Converters )

Protection Based on Dynamic State Estimation (a.k.a. Setting-less Protection): Status and Vision

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

Three-Phase AC Power Circuits

Chapter 3 AUTOMATIC VOLTAGE CONTROL

RC NETWORKS SALES GUIDE

Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka

INTERNATIONAL STANDARD

Neutral to Earth Voltage Reduction Methods in Three-Phase Four Wire Distribution Systems

Series and Parallel Circuits

Three-phase AC circuits

Transistor Characteristics and Single Transistor Amplifier Sept. 8, 1997

GE Protection and Control Business Department. Page 1 Date 5/11/99

Unified requirements for systems with voltages above 1 kv up to 15 kv

The following table shows approximate percentage wise the

Loading Considerations When Paralleling Transformers

Buffer Op Amp to ADC Circuit Collection

Transcription:

Digital Energy Multilin GE Multilin technical note eutral voltage unbalance function at grounded wye capacitor banks GE publication number: GET-8544 Copyright 00 GE Multilin eutral voltage unbalance function at grounded wye capacitor banks Introduction The C70 neutral overvoltage unbalance function (ASI 59U) compensates for both the system unbalance ( 0 ), and the bank inherent unbalance using balancing factors k AB and k AC. The operating quantity equation for a perfectly balanced bank (k AB = k AC = ) takes the following familiar simplified form. op = X 0 (Eq ) In this equation, X is a bank neutral point voltage and 0 is a bus (system voltage) which can either calculated from phase voltages or supplied externally from broken delta T. It is preferable to have the bus voltage supplied from a three-phase voltage T, since the C70 can compensate for bank inherent unbalance by applying balancing coefficients. The auto-setting procedure is available to automatically calculate these coefficients. For greater sensitivity and security, the relay applies the differential principle with the restraint quantity rest calculated as follows. rest = X + 0 The neutral overvoltage unbalance element operates if: (Eq ) op > S rest (Eq 3) Where S is a user-programmable slope factor. The neutral overvoltage unbalance element can be applied to both ungrounded and grounded capacitor banks. Applying neutral overvoltage unbalance to ungrounded banks appears logical and simple. However, it may not be so obvious for grounded banks. In this case, the banks are grounded through a neutral capacitor with a single-phase T across the capacitor or grounded through a CT to measure the neutral current or equivalent neutral voltage. This application note attempts to clarify the C70 application for these type of grounded bank configurations. GE MULTILI TECHICAL OTE EUTAL OLTAGE UBALACE FUCTIO AT GOUDED WYE CAPACITO BAKS

eutral point voltage equivalent The following figure depicts two possible grounding arrangements for the capacitor bank. Grounded through neutral capacitor. Grounded through neutral CT. In any configuration the value of the resistor has to be chosen so that the voltage which appears at the neutral point (one phase voltage at the bus equals zero) across resistor through the CT/auxiliary T input matches the bus 0 value. Figure : eutral arrangement for grounded wye banks Alternative: measured bus 30 Phase CT bank T Phase T bank C70 Capacitor Bank Protection and Control System T Alternative CT In the case of neutral CT configuration, it can be achieved by calculating value of the resistor in neutral CT secondary as follows: 834769A.CD BLL ( ) CT = ------------------------------ 3 S B T (Eq 4) In the above equation: B(LL) is bus phase-to-phase bus voltage (in k). S B is the bank reactive power rating (in MA). T is the auxiliary T input ratio setting, which may be same as bus T ratio or used to achieve balance if an exact resistor value is not possible. CT is the neutral CT ratio. The voltage derived from the current in the neutral secondary resistor is shifted 90 from the bus 0 voltage. The relay automatically compensates for this if the eutral oltage Unbalance Ground setting is programmed as CTx (grnd). GE MULTILI TECHICAL OTE EUTAL OLTAGE UBALACE FUCTIO AT GOUDED WYE CAPACITO BAKS

GEEAL CALCULATIOS Application example Consider a capacitor bank with the following ratings. Bus phase-to-phase bus voltage B(LL) =69k. Bank reactive power rating S B =6.MA. 900 ka capacitor can rated 9.9 k. Phase T ratio is 600:. T secondary = 67. eutral CT is 75/5A. Each capacitor can consists from = 0 capacitor sections. Two capacitors cans are connected in series (P = ) and there are three parallel strings (S = 3) in each phase. Figure : Sample bank configuration 69 k Measured bus 30 000/5A Phase CT bank 6. MA total T C70 Capacitor Bank Protection and Control System 4000/67 75/5A T 834770A.CD General calculations The nominal current of the capacitor bank is calculated as follows. S I B 0 3 6. MA 0 3 nom = --------------------------- = -------------------------------------- = 33.55 A 3 BLL ( ) 3 69 The impedance of the healthy phase capacitors stack is calculated as follows. (Eq 5) Z P -------------- BLL ( ) ( 69 ) = = ----------------------- = 93.89 Ω S B 6. MA (Eq 6) The impedance of the capacitor can is calculated as follows. Z Z P S 93.89 Ω 3 C = -------------- = -------------------------------- = 440.84 Ω P (Eq 7) GE MULTILI TECHICAL OTE EUTAL OLTAGE UBALACE FUCTIO AT GOUDED WYE CAPACITO BAKS 3

UBALACE CALCULATIOS The impedance of the capacitor section is calculated as follows. Z Z C S = ----- = 440.84 ----------------------- Ω = 44.084 Ω 0 (Eq 8) From the formula above, the value of resistor in the neutral CT secondary is estimated as follows. BLL ( ) CT ( 69 ) 5 = ------------------------------ = 3 S B T 3 ------------------------------------------------ = 6. MA 600.449 Ω (Eq 9) In the above equation, the voltage auxiliary input ratio is assumed same as the phase voltage input ratio. The calculations of and 0(bus) provide a quick check that the resistor value for one system phase voltage is equal to zero. The value is calculated as follows. I nom 33.55 A.449 Ω = ------------------- = ------------------------------------------------ =.3 CT 5 (Eq 0) The 0(bus) value is calculated as follows. ( BLL ( ) 0 3 ) ( 3) 69000 3 0( bus) = -------------------------------------------------- = 3 T ------------------------------- = BUS 3 600.3 (Eq ) The and 0(bus) values are practically the same. Unbalance calculations For a fuseless sample bank as shown above with S C = P = 0 = 0 series capacitor sections in one string and S = 3 parallel strings, the general equation to calculate ground current for n failed sections is shown below. n I G = I ( -------------------------------------- S C n) S + n nom ( S C n) S (Eq ) The neutral point secondary voltage with one failed section (n = ) is calculated as follows. ( n = ) n = I G -------- 33.55 A (Eq 3) CT ( -------------------------------------- 0 ) 3 + ( 0 ) 3.449 Ω = = -------------------- = 0.385 5 ( n = ) This can also be expressed in per-unit values as ( pu) = 0.385 / 67 = 0.0057 pu. The neutral point secondary voltage with two failed sections (n = ) is calculated as follows. ( n = ) ( ) ( n = ) I G -------- 33.55 A CT ( -------------------------------------- 0 ) 3 + ( 0 ) 3.449 Ω = = -------------------- = 0.8076 5 (Eq 4) ( n = ) This can also be expressed in per-unit values as ( pu) = 0.8076 / 67 = 0.0 pu. The neutral point secondary voltage with three failed sections (n = 3) is calculated as follows. ( n = 3) ( n = 3) I G -------- 33.55 A CT ( -------------------------------------- 0 3) 3 + 3 ( 0 3) 3.449 Ω = = -------------------- =.86 5 (Eq 5) ( n = 3) This can also be expressed in per-unit values as ( pu) =.86 / 67 = 0.09 pu. From the calculations above, the alarm pickup setting is chosen for the failure of one section as follows. ( n = ) 59U alarm = 0.9 = 0.9 0.0057 pu = 0.005 pu (Eq 6) 4 GE MULTILI TECHICAL OTE EUTAL OLTAGE UBALACE FUCTIO AT GOUDED WYE CAPACITO BAKS

ELAY COFIGUATIO The trip pickup setting is chosen as midway between the second and third capacitor section failures as follows. ( n = ) ( n = 3) 59U + trip = ---------------------------------------- = 0.0 -------------------------------------------------------- pu + 0.09 pu = 0.056 pu (Eq 7) elay configuration If the external 3 0 voltage is brought into the relay, then the C70 model with two T banks must be ordered to protect capacitor bank according to the application example. One T bank is sufficient for calculated 3 0. For externally brought 3 0 and two type L CT/T modules in the F and M slots. Program the following settings in the System Setup > AC Inputs > Current menu. Program the following settings in the System Setup > AC Inputs > oltage menu. Program the following settings in the System Setup > Signal Sources menu. GE MULTILI TECHICAL OTE EUTAL OLTAGE UBALACE FUCTIO AT GOUDED WYE CAPACITO BAKS 5

ELAY COFIGUATIO Program the following settings in the Grouped Elements > Group > oltage Elements > eutral oltage Unbalance menu. Appendix As was mentioned above in the case of neutral CT connections, the value of resistor must be chosen so that the voltage drop across at the neutral point through the CT/auxiliary T input transformation matches the bus 0 value for a single phase to ground fault. This value is derived as follows. If the fault occurs on phase A, then 0 is calculated as follows. 0 = -- ( 0 + 3 B + C ) = -- ( 3 B + C ) The impedance of each leg of bank is calculated as follows. (Eq 8) Z = -------------- BLL ( ) S B (Eq 9) The neutral current is calculated as follows. I B + = ----------------------- C BLL ( ) S B The secondary current in neutral resistor is calculated as follows. I sec ( ) -------- B + C = ----------------------- CT BLL ( ) S B The voltage across secondary resistor is calculated as follows. (Eq 0) (Eq ) sec ( ) -------- B + C = ----------------------- CT BLL ( ) S B (Eq ) Assume that the voltage setting for the auxiliary T ratio, T, is set the same as the bus T ratio. It is desired that following magnitudes are equivalent. T -------- B + C ----------------------- = CT 0 = -- ( BLL ( ) S 3 B + C ) B (Eq 3) 6 GE MULTILI TECHICAL OTE EUTAL OLTAGE UBALACE FUCTIO AT GOUDED WYE CAPACITO BAKS

ELAY COFIGUATIO We therefore have: CT ----------------------- BLL ( ) S B = -- 3 CT -------- BLL ( ) = -------------- T 3 S B (Eq 4) GE MULTILI TECHICAL OTE EUTAL OLTAGE UBALACE FUCTIO AT GOUDED WYE CAPACITO BAKS 7