FIBER OPTIC SYSTEM TEST PROCEDURES



Similar documents
Removing the Mystery from OTDR Measurements. Keith Foord Product Manager Greenlee Communications

Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables. Steve Swanson May 5, 2009

Optical Fiber Data Center Field Testing. ANSI/BICSI Data Center Design and Implementation Best Practices

Attaching the PA-A1-ATM Interface Cables

Field Measurements of Deployed Fiber

Technical Bulletin. Guidelines For Testing And Troubleshooting Fiber Optic Installations

Four Ways To Test Installed Fiber Optic Cables And How The Results Will Differ With Each Method

Accurately Testing fibre Optic Cables

Module 13 : Measurements on Fiber Optic Systems

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE FOR TRAFFIC SIGNAL INTERCONNECT JANUARY 19, 2007

The following terms are defined within the context of the fiber optic industry

Measuring of optical output and attenuation

The Conversion Technology Experts. Fiber Optics Basics

Cabling & Test Considerations for 10 Gigabit Ethernet LAN

Module Connectors and Cable Specifications

White Paper: 10GbE Fiber A Practical Understanding and Functional Approach

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION STRUCTURE CABLING TESTING

What testing is required for PREMISES Fiber Optic Cabling and the standards used

MTS/T-BERD Platforms Very Long Range (VLR) OTDR Module

SECTION TESTING OF FIBER OPTIC CABLES

Fibre optic testing best practices

Special Specification 6033 Computerized Transportation Management System

Guide to Industrial Fiber Optics

Testing and troubleshooting enterprise fiber-optic cabling. Presenter: Neftali Usabal Fluke Networks - LATAM

SECTION TELECOMMUNICATIONS ACCEPTANCE TESTING

Fiber Optic Connections in the Sea

Cable Network Transparency Fiber Optic Monitoring

Designing Fiber Optic Systems David Strachan

Best Practices for Ensuring Fiber Optic System Performance. David Zambrano

CamSplice Assembly Manual

Splicing and Fiber Assembly Compatibility for Non-Zero Dispersion-Shifted Fiber and Standard Single-Mode Fiber

CISCO 10GBASE X2 MODULES

How To Get A Better Signal From A Fiber To A Coax Cable

Optical Fibres. Introduction. Safety precautions. For your safety. For the safety of the apparatus

Fibre Channel Fiber Cabling

Polymer Coated Fiber Cable (PCF)

SECTION 680 FIBER OPTIC CABLE DESCRIPTION

home site map help ECMS Project: Standard / Federal Oversight Advertised

Will Your Fiber Optic Cable Plant Support Gigabit Ethernet?

What are Fibre Optics?

Cisco - Calculating the Maximum Attenuation for Optical Fiber Links

Insertion Losses of Fiber Optical Connectors

INTRODUCTION FIGURE 1 1. Cosmic Rays. Gamma Rays. X-Rays. Ultraviolet Violet Blue Green Yellow Orange Red Infrared. Ultraviolet.

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

Fiber Optic Specifications

Graphical User Interface Capabilities of MATLAB in Centralized Failure Detection System (CFDS)

Structured Connectivity Solutions Field Testing Guidelines for Fiber-Optic Cabling Systems

APPLICATION NOTE POLARIZATION MEASUREMENTS

OPTICAL FIBERS INTRODUCTION

Fiber-to-the-Home/FTTH

Fiber Optics: Engineering from Global to Nanometer Dimensions

FTB-720 LAN/WAN Access OTDR OPTIMIZED FOR MULTIMODE AND SINGLEMODE ACCESS NETWORK TESTING

DIRECTIONAL FIBER OPTIC POWER MONITORS (TAPS/PHOTODIODES)

Guidelines. LANscape Solutions Recommended Fiber Optic Test Guidelines. Table of Contents. 1. Introduction. 2. Why Test? 1. Introduction...

Laser-Optimized Fiber

SINGLEMODE OR MULTIMODE FIBER OPTIC PATCHCORDS

Explanation of Reflection Features in Optical Fiber as Sometimes Observed in OTDR Measurement Traces

Why Expanded Beam types are essential in military and other harsh environment applications

Gigabit Switching Ethernet Media Converters - Product User Guide

FTB-720 LAN/WAN Access OTDR OPTIMIZED FOR MULTIMODE AND SINGLEMODE ACCESS NETWORK TESTING

Loss & Continuity Testing with MPO/ MTP Connectors

This sale agreement is between (buyer) and William Graham (seller) of Mississauga Training Consultants. Authored by: William Graham, Owner

12 Fibre MTP Jumper, MTP (non-pinned) to MTP (pinned)

Fiber Optics: Fiber Preparation and Fiber Connectors

Optocore Guideline for Fiber Optical Cabling in Permanent Installations

A Quick Start Guide to Fiber Inspection, Cleaning, and Test INSPECT BEFORE YOU CONNECT SM

Kit Highlights and Key Features

Fiber Optic Training Guide By Sarkis Abrahamian

Fiber Characterization Service

Patch Cords for Data Center Applications

TURBOTEST 400 Fiber Optic Certification Test Set User s Guide

Fiber Optic Terminus End Face Quality Standards

Overcoming OM3 Performance Challenges

École Supérieure d'optique

M310 Data Center OTDR

With the advent of Gigabit Ethernet

Reliable, Consistent, Quality

Inspection and Cleaning Procedures for Fiber Optic Connections

Network Design. Yiannos Mylonas

palmotdr Series Handheld OTDR

PURE : REliable planning of data center cabling

RF Video Distribution System. Why Z-Band is The Right Choice for Quality Video

Technical Bulletin. User s Guide To Fiber Optics

Manual for Fiber Optics Experiments

Cabling Services (price per pull) Zone 1 Zone 2 Zone 3 Zone 4 Zone 5

Displayport Extender via 2 multimode fibers LC Duplex Connector Extends Displayport Link up to 200 meters

How To Read A Fiber Optic Sensor

TESTING PROCEDURE FOR NETWORK DEPLOYMENT

AQ7275 OTDR Optical Time Domain Reflectometer

On Cables and Connections A discussion by Dr. J. Kramer

Oscar E. Morel UtilX Corporation

Security & Surveillance Cabling Systems

Gigabit Passive Optical Networks

Fiber Optic Technology

Optical Power Meter. Specification & User Manual

Experiment 5. Lasers and laser mode structure

Transcription:

FIBER OPTIC SYSTEM TEST PROCEDURES Data Systems Performance Engineering LLC performs three tests in order to determine fiber optic cable adequacy. The order in which the tests are to be performed is not particularly critical. This document is not intended to be training material for optical testing. A. Optical Power Loss Test. Many testing services rely on data from an Optical Time Domain Reflectometer (OTDR) to determine optical power los through a fiber optic cable. OTDR measurements are calculations and are not as accurate as measurements made with the Double-Ended Loss Test shown immediately below. Equipment required: Fiber Optic Light source (850 nanometer or 1310 nanometer as required for multimode cables) Fiber Optic Power meter Two known good reference cables Two couplers In a double-ended loss test, the cable to be tested is connected between two reference cables, one attached to the source and one to the meter. Using this test, the cumulative losses of two connectors is measured: one on each end, plus the loss of all the cable or cables in between. The cables need to be tested at the wavelength of the signal to be transmitted through the fiber: 850 or 1310 nanometers. It is necessary to know the length of the cable to be tested before conducting the test. This may require measuring the cable length with an Optical Time Domain Reflectometer. Step One: Clean the ends of the reference cables with an isopropyl alcohol soaked wipe. Step Two: Insert one test cable into the light source. Step Three: Insert the other test cable into the power meter Step Four: Connect the open ends of the cables together with a coupler.

Step Five: Turn on the light source and the power meter. Measure the db loss of the reference cable-coupler assembly. Record this number. Please see Figure 1 below. Figure 1 Step Six: Connect the cable to be tested (usually patch cable on one end to patch cable on the other end including all intermediate patch panels and premise wiring) between the ends of the reference cables using couplers. Record this db loss. Subtract the measurement recorded from the reference cable from the total measurement. This will be the db loss for the cable under test. Please see Figure 2 below.

Figure 2 The loss measured should be less than the calculated loss. In order to obtain a calculated loss value, it is necessary to know the cable length and the manufacturer s specifications for cable loss per foot or per meter. To obtain the calculated loss value, one multiplies the cable length by the loss per unit of measurement, then adds a factor in to account for connector and coupler losses. For example, a typical multimode 62.5/125 micron cable has an insertion loss of 3.5 db per kilometer. Each multimode connector has an insertion loss of 0.3 db. Each coupler has an insertion loss of 0.2 db. Using these values, a 500 foot total length fiber optic cable with a patch cable at each end and two patch panels between the ends would have the following calculated loss:

3.5 db/kilometer X 0.1524 kilometer = 0.533 db for the cable. There are 6 connectors X 0.3 db per connector = 1.8 db There are two couplers X 0.2 db per coupler = 0.4 db So total calculated loss is 0.533 + 1.8 db + 0.4 db = 2.733 db. If the measured loss value was greater than the calculated loss value there is a cable or connector problem to be resolved. B. Optical Time Domain Reflectometer Test Fiber OTDR s are useful for determination of overall cable quality. The OTDR can check for cable problems such as defective cables, splice problems, inadequate bend radius, fiber cable microcracks, etc. The Fiber Optic TDR is especially useful to determine overall cable length. It should be noted, however, that it is necessary to have some idea of how long the cable actually is before trying to get cable length information from the OTDR. Anomalies shown at the cable end point on the OTDR display can be misleading and confusing. Fiber optic TDR units can check for cable and splice attenuation, but these measurements are not as accurate as the power meter-light source measurement. Step 1. Set the test parameters into the OTDR. Depending on the OTDR used, the test parameters may include the laser wavelength (1310 nanometers for this application), the distance range (in kilometers), the pulse width of the test pulse (depending on length of the fiber to be measured), the acquisition time (the longer the acquisition time the better the image resolution), the index of refraction of the fiber optic cable, and the helix factor of the fiber optic cable (if available). Step 2. Connect the OTDR to one end of a launch cable (may also be called a dead band cable). Launch cables are necessary for most OTDR units because the OTDR is effectively blind for some distance from the light launch point. A launch cable is typically 200 meters in length. Connect the other end of the launch cable to the fiber to be tested (including all interim connections such as patch panels) (length of the dead band cable depends on the OTDR manufacturer). Turn on the OTDR and let it scan the fiber under test. After the image has fully formed, examine it for abnormalities. The splices and junctions should

be apparent but not excessive in attenuation. Individual splice losses may be measured using the four point loss method on the OTDR. Step 3. If there are anomalies found, it is necessary to determine if these anomalies are legitimate or reflections. Connect the OTDR and dead band cable to the other end of the cable under test and repeat the measurement. If the anomalies follow the launch point (for example, an anomaly on a 500 foot cable is 200 feet from the launch point at one end of the cable and 300 feet from the launch point at the opposite end of the cable) the problem is legitimate. If the anomaly does not move it is most likely a reflection of some sort and can be disregarded. There may, of course be other types of anomalies discovered. To assure accurate test results, only experienced operators should use the OTDR. C. Connector Polishing Every connector in the system (including those in patch panels) should be checked by using a 200X fiber optic microscope. This test should be done with both ends of the fiber disconnected. Step 1. Clean the ends of the connectors with an isopropyl alcohol soaked wipe. Allow the connectors to dry. Step 2. Insert the connector end into the fiber microscope. Turn on the light source. Step 3. Observe the end of the fiber. The core should appear as a black dot. The cladding should appear lighter than the core. The end of the connector should appear smooth. Scratches in the connector optical assembly, excess epoxy, or poor connector polishing will require remedial action. Replace cable or connectors determined to be defective. Figure 3 below shows a good fiber optic connector end and several examples of bad fiber optic connector ends.

Figure 3