MODULATING LIGHT OIL BURNERS RL/M SERIES RL 28/M 95/166 332 kw RL 38/M 11/237 45 kw RL 5/M 13/296 593 kw RL 7/M 261/474 143 kw RL 1/M 332/711 1482 kw RL 13/M 498/948 1779 kw RL 19/M 534/1423 2431 kw The RL/M series of burners covers a firing range from 166 to 2431 kw, and they have been designed for use in hot or superheater water boilers, hot air or steam generators, diathermic oil boilers. Operation can be two stage progressive or, alternatively, modulating with the installation of a PID logic regulator and respective probes. RL/M series burners guarantees high efficiency levels in all the various applications, thus reducing fuel consumption and running costs. Optimisation of sound emissions is guaranteed by the use of fans with forward inclined blades and sound deadening material incorporated in the air suction circuit. The exclusive design ensures reduced dimensions, simple use and maintenance. A wide range of accessories guarantees elevated working flexibility. TS12UK4
TECHNICAL DATA Model RL 28/M RL 38/M RL 5/M RL 7/M RL 1/M RL 13/M RL 19/M Approval Emissions Electrical data Fuel / air data Burner operation mode Modulation ratio at max. output Servomotor run time Heat output Working temperature Net calorific value Viscosity Pump delivery type s kw Mcal/h kg/h C min./max. kwh/kg kcal/kg mm 2 /s (cst) type kg/h Atomised pressure bar Fuel temperature Max. C Fuel preheater Fan type Air temperature Max. C Electrical supply Ph/Hz/V Auxiliary electrical supply Ph/Hz/V Control box type Total electrical power kw Auxiliary electrical power kw Heaters electrical power kw Protection level IP Pump motor electrical power kw Rated pump motor current A Pump motor start up current A Pump motor protection level IP Fan motor electrical power kw Rated fan motor current A Fan motor start up current A Fan motor protection level IP type Ignition transformer V1 V2 I1 I2 Operation Sound pressure db(a) Sound power W CO emission mg/kwh Grade of smoke indicator N Bacharach CxHy emission mg/kwh NOx emission mg/kwh Directive Conforming to Certification Modulating (with regulator and probes accessories) 3 1 SQN9 SQN31 24 42 95/166 332 11/237 45 13/296 593 261/474 143 332/711 1482 498/948 1779 534/1423 2431 81,7/143 286 87/24 387 112/255 51 224/48 897 286/612 1275 428/816 153 459/1224 291 8/14 28 8,5/2 38 11/25 5 22/4 88 28/6 125 42/8 45/12 25 /4 11,8 12 4 6 (at 2 C) AL 75C 74 (2 bar) AL 95C 99 (2 bar) J 7C 19 (2 bar) TA 3 665 (2 bar) 2 5 Centrifugal with reverse curve blades Forward curve blades 6 1/5/23~(±1%) 3N/5/4~(±1%) 3/5/23~(±1%) 1/5/23~(±1%) LAL 1.25 LAL 1.25 (Intermittent working) LOK 16 (Continuous working),4,15,6,15,8,15 1,4,3 44,25 2,1 1,45 2 1,2 9,5 5,5,65 3 1,7 13,8 8 1,1 4,8 2,8 25 14,6 4 54 23V 2x5 kv 1,9A 3 ma 2,1,3 1,8 7,3 4,2 37,6 21,8 2,6,4 2,2 8,8 5,1 57,2 33,2 5,5 1 4,5 15,8 9,1 126 73 23V 2x5 kv 1,9A 35 ma Intermittent (at least one stop every 24 h) Intermittent (at least one stop every 24 h) Continuous (at least one stop every 72 h) 68 7 75 75 77 78,5 84,9 < 4 < 1 <1 (after the first 2 s) < 2 73/23 89/336/EC 24/18/EC 98/37 92/42 EC EN 267 CE5792231 Reference conditions: Temperature: 2 C Pressure: 113,5 mbar Altitude: 1 m a.s.l. Noise measured at a distance of 1 meter. Since the Company is constantly engaged in the production improvement, the aesthetic and dimensional features, the technical data, the equipment and the accessories can be changed. This document contains confidential and proprietary information of RIELLO S.p.A. Unless authorised, this information shall not be divulged, nor duplicated in whole or in part. 2
FIRING RATES 1 9 8 RL 38/M RL 5/M 7 6 RL 28/M 5 4 3 hpa (mbar) 2 1 1 1 2 3 4 5 6 kg/h 1 2 3 4 5 6 7 kw 16 15 RL 19/M 14 13 12 11 RL 1/M RL 13/M 1 9 RL 7/M 8 7 6 5 4 3 hpa (mbar) 2 1 1 3 5 7 9 11 13 17 19 21 kg/h 1 2 3 4 5 6 7 8 9 1 11 12 13 14 16 17 18 19 2 21 22 23 24 25 kw Useful working field for choosing the burner Modulation range Test conditions conforming to EN 267: Temperature: 2 C Pressure: 113,5 mbar Altitude: 1 m a.s.l. 3
FUEL SUPPLY HYDRAULIC CIRCUITS Various hydraulic circuits are available, depending on fuel output asset according to local norms of steam generators. The burners are fitted with two valves for oil output from the pump: a pressure regulator on the return circuit from the nozzle allows varying the quantity of burnt fuel. A safety valve on the return circuit impedes oil leakage from the nozzle when the burner is in stand by and prepurge phases. Beginning with the RL 1/M model, the burners have a double safety valve on the return circuit. The models fitted with a minimum pressure switch on the oil delivery circuit can be installed on steam generators according to TRD72 standard (Germany) and NBN standard (Belgium). Example of the hydraulic circuit on RL7/M burners EN 267 < 1 Kg/h P VS VF VR POmax M SM RO MR U P VS VF PO min U MR SM RO PO max VR VR1 Pump with filter and pressure regulator on the output circuit Safety valve on the output circuit Working valve on the output circuit Min. Oil pressure switch on the output circuit Nozzle Pressure gauge on the return circuit Servomotor Pressure regulator on the return circuit Max. Oil pressure switch on the return circuit 1st safety valve on the return circuit 2nd safety valve on the return circuit EN 267 > 1 Kg/h Versions for TRD72, NBN steam generators VS VF VS VF POmin M SM MR U M SM MR U VR1 VR POmax RO VR1 VR POmax RO P P 4
SELECTING THE FUEL SUPPLY LINES The fuel feed must be completed with the safety devices required by the local norms. The table shows the choice of piping diameter for the various burners, depending on the difference in height between the burner and the tank and their distance. Model Diameter piping +H, H (m) +4, +3, +2, + +1, +,5,5 1, 2, 3, 4, Ø1mm 83 55 48 44 4 37 33 29 25 21 17 1 4 MAXIMUM EQUIVALENT LENGTH FOR THE PIPING L[m] RL28/M RL385/M RL7113/M RL19/M Ø12mm 144 127 111 12 94 86 78 7 82 63 45 29 12 Ø14mm 133 118 13 88 58 28 Ø1mm 51 46 39 35 32 29 26 23 2 16 13 7 2 Ø12mm 112 99 86 79 73 65 6 54 47 4 34 21 8 Ø14mm 147 144 132 12 16 96 83 71 46 21 Ø12mm 71 62 58 51 44 4 36 32 28 23 19 1 3 Ø14mm 138 122 16 98 9 82 74 66 56 49 42 26 1 Ø16mm 137 123 19 95 81 53 25 Ø16mm 6 5 4 35 3 25 2 18 15 13 1 5 3 Ø18mm 8 7 6 55 5 45 4 35 3 25 2 1 6 6 7 1 9 5 V P +H 1 cm 8 4 7 5 3 9 2 1 H Difference in height pumpfoot valve Ø Internal pipe diameter P Height 1 m V Height 4 m 1 Burner 2 Burner pump 3 Filter 4 Manual shut off valve 5 Suction pipework 6 Bottom valve 7 Remote controlled rapid manual shut off valve (compulsory in Italy) 8 Type approved shut off solenoid valve (compulsory in Italy) 9 Return pipework 1 Check valve H 6 note With ring distribution oil systems, the feasible drawings and dimensioning are the responsibility of specialised engineering studios, who must check compatibility with the requirements and features of each single installation. 5
VENTILATION The ventilation circuit produces low noise levels with high performance pressure and air output, in spite of the compact dimensions. Except for the RL 19/M model, the use of reverse curve blades and sound proofing material keeps noise level very low. In the RL 19/M model, sound has been reduced by the special design of the air suction circuit. A variable profile cam connects fuel and air setting, ensuring high fuel efficiency in all firing ranges. Example of the servomotor for air/oil setting COMBUSTION HEAD Different lengths of the combustion head can be chosen for the RL/M series of burners. The choice depends on the thickness of the front panel and the type of boiler. Depending on the type of generator, check that the penetration of the head into the combustion chamber is correct. The internal position of the combustion head can easily be adjusted to the maximum defined output by adjusting a screw fixed to the flange. Example of a RL/M burner combustion head Flame dimensions 4 3 L max L min 2 D L Flame lenght (m) 2 1 D max D min 1 2 3 4 Burner output (MW) 1,5 Flame diameter (m) Example: Burner thermal output = 2 kw; L flame (m) = 2,7 m (medium value); D flame (m) =,8 m (medium value) 6
OPERATION BURNER OPERATION MODE The RL/M series of burners can have twostage progressive or modulating operation. On twostage progressive operation, the burner gradually adapts the output to the requested level, by varying between two preset levels (see picture A). Example of a regulator Twostage progressive operation Output Controlled variable Picture A C bar MAX MIN time time On modulating operation, normally required in steam generators, in superheater boilers or diathermic oil burners, a specific regulator and probes are required. These are supplied as accessories that must be ordered separately. The burner can work for long periods at intermediate output levels (see picture B). Modulating operation Output Controlled variable Picture B C bar MAX MIN time time START UP CYCLE RL 28/M 38/M 5/M TL TR M 72,5 8 VS VF 75 VR 29 51 max M 71 min 5 2 75 9 1 The burner begins the firing cycle: the motor starts turning. 5 29 The servomotor opens the air damper. 29 51 Prepurge with the air damper open. 51 71 The servomotor takes the air damper to the firing position. 72.5 Preignition. 75 Firing: all the oil solenoid valves are supplied. 9 Output can be increased. 8 time (s) RL 7/M 1/M 13/M 19/M VS VF M TL TR M VR VR1 max min 2 1 18 116 111 47 69 16 5 111 126 The burner begins the firing cycle: the motor starts turning. 5 47 The servomotor opens the air damper. 47 69 Prepurge with the air damper open. 69 16 The servomotor takes the air damper to the firing position. 18 Preignition. 111 Firing: all the oil solenoid valves are supplied. 126 Output can be increased. 116 time (s) 7
WIRING DIAGRAMS Electrical connections must be made by qualified and skilled personnel, according to the local norms. Example of the terminal board for electrical connections for the RL 711319/M models TWOSTAGE PROGRESSIVE OPERATION RL 28/M RL 38/M 5/M 7/M 1/M 13/M 19/M MB N L 1 2 3 4 U N M B1 B3 B4 W1 W2 Q H C AL AL1 MB L1 L2 L3 N L 1 2 3 4 U N M B1 B3 B4 W1 W2 Q H C AL AL1 T6A TS ϑ P S TL ϑ P TR ϑ P T6A TS ϑ P S TL ϑ P TR ϑ P IN F IN mm 2 PE N L ~ 5Hz 23V MB Burner terminal board TS Safety thermostat S External lockout signal IN Manual switch TL Threshold thermostat TR High/low flame setting thermostat T6A 6A fuse L PE L1 L2 L3 3N ~ 5Hz 4/23V 3 5Hz 23V N L ~ 5Hz 23V M 3~ MB Burner terminal board TS Safety thermostat S External lockout signal IN Manual switch TL Threshold thermostat TR High/low flame setting thermostat T6A 6A fuse F Fuse (see table A) L Lead section (see table A) MODULATING OPERATION temperature probe RL 28/M RL 38/M 5/M 7/M 1/M 13/M 19/M RWF 4 N L1 M1 I1G1+U1 G G+ Q Y1 Y2 Q13 Q14 TE RWF 4 N L1 M1 I1G1+U1 G G+ Q Y1 Y2 Q13 Q14 TE MB N L 1 2 3 4 N U M B1B3 B4 W1 W2 Q H C AL AL1 MB L1 L2 L3 N L 1 2 3 4 N U M B1B3 B4 W1 W2 Q H C AL AL1 T6A TS ϑ P S a b c d BT IN T6A a b c d TS S IN BT ϑ P F mm 2 PE N L ~5Hz 23V MB Burner terminal board TS Safety thermostat S External lockout signal IN Manual switch BT Temperature probe T6A 6A fuse RWF4 Regulator (fitted to the burner) L PE L1 L2 L3 3N 3 ~ 5Hz 4/23V 5Hz 23V N L ~ 5Hz 23V 3~ M MB Burner terminal board TS Safety thermostat S External lockout signal IN Manual switch BT Temperature probe T6A 6A fuse F Fuse (see table A) L Lead section (see table A) RWF4 Regulator (fitted to the burner) 8
MODULATING OPERATION pressure probe RL 28/M RWF 4 N L1 M1 I1G1+U1 G G+ Q Y1 Y2 Q13 Q14 TE RL 38/M 5/M 7/M 1/M 13/M 19/M RWF 4 N L1 M1 I1G1+U1 G G+ Q Y1 Y2 Q13 Q14 TE MB N L 1 2 3 4 N U M B1B3 B4 W1 W2 Q H C AL AL1 MB L1 L2 L3 N L 1 2 3 4 N U M B1B3 B4 W1 W2 Q H C AL AL1 T6A TS 2 1 S ϑ P BP 4/2mA IN T6A TS S BP 2 1 4/2mA IN ϑ P F mm 2 PE N L ~5Hz 23V MB Burner terminal board TS Safety thermostat S External lockout signal IN Manual switch BP Pressure probe T6A 6A fuse RWF4 Regulator (installed on the burner) L PE L1 L2 L3 3N~ 5Hz 4/23V 3 5Hz 23V ~ ~ N L 5Hz 23V M 3~ MB Burner terminal board TS Safety thermostat S External lockout signal IN Manual switch BP Pressure probe T6A 6A fuse F Fuse (see table A) L Lead section (see table A) RWF4 Regulator (fitted on the burner) The following table shows the supply lead sections and the type of fuse to be used. Model RL 28/M RL 38/M RL 5/M RL 7/M RL 1/M RL 13/M RL 19/M F L A mm 2 23V T6 23V T6 4V T6 23V T6 4V T6 23V T1 4V T6 23V T16 4V T1 23V T16 4V T1 23V T25 2,5 4V T25 2,5 Table A 9
EMISSIONS mg/kwh 25 2 NO2 EMISSIONS 1 5 RL 28/M RL 38/M RL 5/M RL 7/M RL 1/M RL 13/M RL 19/M mg/kwh 5 4 CO EMISSIONS 3 2 1 RL 28/M RL 38/M RL 5/M RL 7/M RL 1/M RL 13/M RL 19/M db(a) 1 8 NOISE EMISSIONS 6 4 2 RL 28/M RL 38/M RL 5/M RL 7/M RL 1/M RL 13/M RL 19/M The emission data has been measured in the various models at maximum output, according to EN 267 standard. 1
OVERALL DIMENSIONS (mm) BURNER RL 28/M 38/M 5/M RL 7/M 1/M 13/M 19/M A B C E F F(1) A E F F(1) H H D I D I O O (1) O O (1) Model A B C D RL 28/M RL 38/M RL 5/M RL 7/M RL 1/M RL 13/M RL 19/M 476 476 476 663 679 75 813 (1) Length with extended combustion head 296 312 338 366 367 367 367 447 474 474 474 555 555 555 555 E 468 468 468 68 68 68 696 F 241 241 241 272 272 272 37 F (1) 351 351 351 385 385 385 H 14 14 152 179 179 189 222 I 352 352 352 43 43 43 43 O O (1) 672 87 672 87 672 87 951 186 951 186 951 186 112 BURNER BOILER MOUNTING FLANGE 45 45 D1 D2 Ø Model RL 28/M RL 38/M RL 5/M RL 7/M RL 1/M RL 13/M RL 19/M D1 16 16 16 185 185 195 23 D2 224 224 224 275325 275325 275325 325368 Ø M8 M8 M8 M12 M12 M12 M16 PACKAGING Z X X (1) Y Model RL 28/M RL 38/M RL 5/M RL 7/M RL 1/M RL 13/M RL 19/M (1) Length with extended combustion head X X (1) 872 872 872 1 1 1 12 Y 54 54 54 792 792 792 8 Z 55 55 55 6 6 6 85 kg 39 41 42 65 68 71 95 11
INSTALLATION DESCRIPTION Installation, start up and maintenance must be carried out by qualified and skilled personnel. All operations must be performed in accordance with the technical handbook supplied with the burner. BURNER SETTING All the burners have slide bars, for easier installation and maintenance. After drilling the boilerplate, using the supplied gasket as a template, dismantle the blast tube from the burner and fix it to the boiler. Adjust the combustion head. Refit the burner casing to the slide bars. Install the nozzle, choosing this on the basis of the maximum boiler output and following the diagrams included in the burner instruction handbook. Check the position of the electrodes. Close the burner, sliding it up to the flange, keeping it slightly raised to avoid the flame stability disk rubbing against the blast tube. HYDRAULIC / ELECTRICAL CONNECTIONS AND STARTUP The burners are supplied for connection to two pipes fuel supply system. Connect the ends of the flexible pipes to the suction and return pipework using the supplied nipples. Make the electrical connections to the burner following the wiring diagrams included in the instruction handbook. Prime the pump by turning the motor (after checking rotation direction if it is a three phase motor). On start up, check: Pressure pump and valve unit regulator (to max. and min.) Combustion quality, in terms of unburned substances and excess air. 12
BURNER ACCESSORIES Nozzles The return nozzles must be ordered separately. The following table shows the features and codes on the basis of the maximum required fuel output. Nozzles type A3 45 Burner RL 28/M RL 28/M 38/M RL 28/M 38/M 5/M RL 38/M 5/M 7/M RL 5/M 7/M RL 7/M 1/M RL 7/M 1/M RL 1/M 13/M RL 1/M 13/M RL 1/M 13/M RL 13/M RL 13/M 19/M RL 13/M 19/M RL 19/M RL 19/M RL 19/M RL 19/M Rated delivery (kg/h) (*) 15 2 3 4 5 6 7 8 9 1 11 12 13 14 16 18 2 Nozzle code 3985 39851 39852 39853 39854 39855 39856 39857 39858 39859 3986 39861 39862 39863 39864 39865 39866 (*) Nozzle rated delivery is referred to atomised pressure Extended head kit Standard head burners can be transformed into extended head versions, by using the special kit. The kits available for the various burners, giving the original and the extended lengths, are listed below. Extended head kit Burner RL 28/M Standard head length (mm) 241 Extended head length (mm) 351 Kit code 3112 RL 38/M 241 351 31121 RL 5/M 241 351 31122 RL 7/M 272 385 31159 RL 1/M 272 385 3116 RL 13/M 272 385 31161 RL 19/M 37 13
Spacer kit If burner head penetration into the combustion chamber needs reducing, varying thickness spacers are available, as given in the following table: Spacer kit S Burner RL 28/M 38/M 5/M RL 7/M 1/M 13/M RL 19/M Spacer thickness S (mm) 9 135 11 Kit code 3195 31129 3722 Sound proofing box If noise emission needs reducing even further, soundproofing boxes are available, as given in the following table: Sound proofing box Burner Box type Average noise reduction [db(a)] (*) RL 28/M 38/M 5/M RL 7/M 1/M 13/M 19/M C1/3 C4/5 1 1 Box code 3143 3144 (*) according to EN 361 standard Degasing unit To solve problem of air in the oil sucked, two versions of degasing unit are available. Degasing unit Burner Filter Filtering degree (μm) Degasing unit code RL 28/M 38/M 5/M RL 7/M 1/M With filter 5 75 3155 RL 28/M 38/M 5/M RL 7/M 1/M Without filter 3154 14
Head kit for reverse flame chamber In certain cases, the use of the burner on reverse flame boilers can be improved by using an additional cylinder. Head kit for reverse flame chamber Burner Standard head length with cylinder (mm) Extended head length with cylinder(mm) Kit code RL 28/M 38/M 319 429 31178 RL 5/M 319 429 31179 RL 7/M 1/M 375 488 3118 RL 13/M 375 488 31183 RL 19/M 493 31241 Connection flange kit A kit is available for use where the burner opening on the boiler is of excessive diameter. Connection flange kit Burner RL 28/M 38/M 5/M Kit code 31138 15
Accessories for modulating operation To obtain modulating operation, the RL/M series of burners requires a regulator with three point outlet controls. The following table lists the accessories for modulating operation with their application range. Burner RL 28/M 38/M 5/M RL 7/M 1/M 13/M 19/M Regulator type RWF 4 Regulator code 31212 The relative temperature or pressure probes fitted to the regulator must be chosen on the basis of the application. Probe type Temperature PT 1 Pressure 4 2 ma Pressure 4 2 ma Range ( C) (bar) 1 5 C 2,5 bar 16 bar Probe code 3111 31213 31214 Depending on the servomotor fitted to the burner, a threepole potentiometer (1 Ω) can be installed to check the position of the servomotor. The KITS available for the various burners are listed below. Burner RL 28/M 38/M 5/M RL 7/M 1/M 13/M 19/M Potentiometer kit code 3119 3121 16
SPECIFICATION A specific index guides your choice of burner from the various models available in the RL/M series. Below is a clear and detailed specification description of the product. DESIGNATION OF SERIES Series : R Fuel : S Natural Gas L Light oil LS Light oil/natural Gas N Heavy oil Size Setting : /1 One stage... Two stage /M Modulating Emission :... Class 1 EN267 EN676 MZ Class 2 EN267 EN676 BLU Class 3 EN267 EN676 MX Class 1 EN267 Class 3 EN676 Head : TC Standard head TL Extended head Diagnostic : LP Led panel ST Status panel Flame control system : FS1 Standard (1 stop every 24 h) FS2 Continuous working (1 stop every 72 h) Electrical supply to the system : 1/23/5 1/23V/5Hz 3/23/5 3/23V/5Hz 3/4/5 3N/4V/5Hz 3/234/5 3/23V/5Hz 3N/4V/5Hz 3/22/6 3/22V/6Hz 3/38/6 3N/38V/6Hz 3/2238/6 3/22V/6Hz 3N/38V/6Hz Auxiliary voltage : 23/56 23V/56Hz 11/56 11V/56Hz ID : Differential switch R L 5 /M TC FS1 3/234/5 23/56 BASIC DESIGNATION EXTENDED DESIGNATION 17
AVAILABLE BURNER MODELS RL 28/M TC FS1 1/23/5 23/56 RL 28/M TL FS1 1/23/5 23/56 RL 38/M TC FS1 3/234/5 23/56 RL 38/M TL FS1 3/234/5 23/56 RL 5/M TC FS1 3/234/5 23/56 RL 5/M TL FS1 3/234/5 23/56 RL 7/M TC FS1 3/234/5 23/56 RL 7/M TL FS1 3/234/5 23/56 RL 7/M TC FS2 3/234/5 23/56 RL 7/M TL FS2 3/234/5 23/56 Other versions are available on request. RL 1/M TC FS1 3/234/5 23/56 RL 1/M TL FS1 3/234/5 23/56 RL 1/M TC FS2 3/234/5 23/56 RL 1/M TL FS2 3/234/5 23/56 RL 13/M TC FS1 3/234/5 23/56 RL 13/M TL FS1 3/234/5 23/56 RL 13/M TC FS2 3/234/5 23/56 RL 13/M TL FS2 3/234/5 23/56 RL 19/M TC FS1 3/234/5 23/56 RL 19/M TC FS2 3/234/5 23/56 PRODUCT SPECIFICATION Burner: Monoblock forced draught oil burner with two stage progressive or modulating setting, with a specific kit, fully automatic, made up of: air suction circuit lined with soundproofing material fan with reverse curve blades (forward curve blades on the 19/M model) high performance with low sound emissions air damper for air setting and automatic oil output regulator controlled by a servomotor with variable cam starting motor at 28 rpm, threephase 4V with neutral, 5Hz (singlephase, 23V and 5Hz for the 28/M model) combustion head, that can be set on the basis of required output, fitted with: stainless steel end cone, resistant to corrosion and high temperatures ignition electrodes flame stability disk gears pump for high pressure fuel supply, fitted with: filter pressure regulator connections for installing a pressure gauge and vacuometer internal bypass for single pipe installation valve unit with a double oil safety valve on the output circuit and safety valve on the return circuit; double safety valve on the return circuit for models RL 1/M, RL 13/M, RL 19/M and for all models in the TRD72, NBN version safety oil pressure switch for stop the burner in case of problems in the return circuit minimum oil pressure switch in the output circuit for the TRD72, NBN versions photocell for flame detection flame control panel, fitted with control function for the correct positioning of the servomotor and possibility of postventilation by just changing the electric wiring burner on/off switch flame inspection window manual or automatic output increase/decrease switch slide bars for easier installation and maintenance protection filter against radio interference IP 44 electric protection level. Conforming to: 89/336/EC 24/18/EC directive (electromagnetic compatibility) 73/23/EC directive (low voltage) 92/42/EC directive (performance) 98/37/EC directive (machinery) EN 267 (liquid fuel burners). 18
Standard equipment: 2 flexible pipes for connection to the oil supply network 2 gaskets for the flexible pipes 2 nipples for connection to the pump 4 screws for fixing the burner flange to the boiler 1 thermal screen wiring loom fittings for electrical connections 2 slide bar extensions (for the extended head models and the RL 19/M model) instruction handbook for installation, use and maintenance spare parts catalogue. Available accessories to be ordered separately: return nozzles extended head kit (except for the RL 19/M model) spacer kit soundproofing box degasing unit head kit for reverse flame chamber connection flange kit RWF 4 output regulator temperature probe 1 5 C pressure probe 2.4 bar pressure probe 16 bar potentiometer kit for the servomotor. 19
TS12UK4 11/27 RIELLO S.p.A. Via Ing. Pilade Riello, 5 3745 Legnago (VR) Italy Tel. ++39.44263111 Fax ++39.4422198 Internet: http://www.rielloburners.com Email: info@rielloburners.com Since the Company is constantly engaged in the production improvement, the aesthetic and dimensional features, the technical data, the equipment and the accessories can be changed. This document contains confidential and proprietary information of RIELLO S.p.A. Unless authorised, this information shall not be divulged, nor duplicated in whole or in part.