Loading Considerations When Paralleling Transformers



Similar documents
1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr.

The following table shows approximate percentage wise the

Introduction to Paralleling of LTC Transformers by the Circulating Current Method

Low Voltage Transformer Through-Fault Protection: A System Approach

Low Voltage Transformers Sealed, General Purpose, Dry Type

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

Step Voltage Regulators

THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating.

Power Technology Issue 104. Modeling of Two-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

ACCURACY OF POTENTIALTRANSFORMERS

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

How To Wire A Three Phase, Single Phase, Wye Transformer

TRANSFORMER: THREE PHASE

SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta

System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems

Current Transformers

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Bill is the author of 15 papers and lectures on transmission lines and other power system topics.

Power System Harmonics

VOLTAGE REGULATOR AND PARALLEL OPERATION

Power Technology Issue 106. Modeling of Three-Winding Voltage Regulating Transformers for Positive Sequence Load Flow Analysis in PSS E

BALANCED THREE-PHASE CIRCUITS

1 Introduction. 2 Two Phases. J.L. Kirtley Jr.

Chapter 3 AUTOMATIC VOLTAGE CONTROL

Product Data Bulletin

Chapter 24. Three-Phase Voltage Generation

Corner-Grounded Delta (Grounded B Phase) Systems

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

Rule Fast Track Analysis for National Life Insurance Co.

7. Reactive energy compensation

Motor Protection Voltage Unbalance and Single-Phasing

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

Three phase circuits

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

WINDING RESISTANCE TESTING

Short Circuit Current Calculations

SYNCHRONOUS MACHINES

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

Three-phase AC circuits

Module Title: Electrotechnology for Mech L7

DHANALAKSHMI COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE ELECTRICAL MACHINES II UNIT-I SYNCHRONOUS GENERATOR

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

SAMPLE OF THE STUDY MATERIAL PART OF CHAPTER 3. Symmetrical Components & Faults Calculations

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA

7CURRENT TRANSFORMERS

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP

> Executive summary. The Role of Isolation Transformers in Data Center UPS Systems. White Paper 98 Revision 0. Contents.

SHORT CIRCUIT CURRENT CALCULATION AND PREVENTION IN HIGH VOLTAGE POWER NETS

Effective: September 10, 2006 Vermont Attachment 1 to Rule Public Service Board Page 1 of 6

MV/LV transformer substations: theory and examples of short-circuit calculation

EEL303: Power Engineering I - Tutorial 4

(3 )Three Phase Alternating Voltage and Current

How To Choose A Transformer

Power Factor The Basics

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS

Full representation of the real transformer

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

JEFFERSON ELECTRIC, INC. Buck-Boost Transformer Application Manual

Physical Address: City: State: Zip Code:

V out. Figure 1: A voltage divider on the left, and potentiometer on the right.

A Guide to Performing An Arc Flash Hazard Assessment Using Power Analysis Software

Power Quality Paper #3

Science and Reactor Fundamentals Electrical CNSC Technical Training Group. Table of Contents

WHY DIFFERENTIAL? instruments connected to the circuit under test and results in V COMMON.

Power transformers. Special transformers Railway

Request for Payment Instructions Wholesale Distribution Access Tariff (WDAT) Attachment I - GIP

Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

Harmonics in your electrical system

S-Parameters and Related Quantities Sam Wetterlin 10/20/09

GUIDE FOR TESTING POWER TRANSFORMERS

EE 221 Circuits II. Chapter 13 Magnetically Coupled Circuits

Power System Harmonic Fundamental Considerations: Tips and Tools for Reducing Harmonic Distortion in Electronic Drive Applications

Buck - Boost Transformers

Instrument Transformers Application Guide

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS

VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES

Errors Due to Shared Leadwires in Parallel Strain Gage Circuits

Primary Electric Distribution for Industrial Plants

Pierre Archambault, PEng. VP Engineering Power Survey International Inc. 16 September 2009

RLC Resonant Circuits

APPLICATION NOTE. Increasing PV Hosting Capacity on LV Secondary Circuits with the Gridco System empower TM Solution

Power System review W I L L I A M V. T O R R E A P R I L 1 0,

Radial Distribution Test Feeders

High Efficiency Motor Protection. Industry White Paper

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

Technical Information Requirement for MV transformers and transformer for internal power supplies for SUNNY CENTRAL

Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION

Electrical Fault Level Calculations Using the MVA Method

Transformer protection

Hyperlinks are Inactive

Coupled Inductors. Introducing Coupled Inductors

4.5 Transformer Connections

Figure. 1 - Split Phase 240/120V circuit (180 phase shift)

Transformer Calculations

Transcription:

Application Guide 7400DB0701 02/2007 Nashville, TN, USA Loading Considerations When Paralleling Transformers Class 7400 Retain for future use. Introduction Principles of Paralleling This application guide addresses the limiting conditions of connecting transformers in parallel and loading considerations when turn ratios, impedances, and kva ratings are different. Most transformers installed in parallel have the same kva, turn ratios, and impedances, which can make it difficult for power engineers in industrial and commercial facilities to understand circulating currents and load sharing. However, as systems change over time, and transformers are replaced or added, users need to know the impact of paralleling transformers using different parameters. Electrical systems have been using paralleled transformers for many years. Existing transformers are sometimes paralleled in industrial and commercial facilities when facility engineers, consultants, or maintenance staffs are looking for ways to make power systems more reliable, provide better power quality, prevent voltage sags, or add load requirements. Electrical utilities are ideal examples of these applications. Their main objectives are reliability and power quality, along with keeping consumers on-line. Many times auto-tap transformers are used to adjust voltage levels due to loading conditions. Oftentimes, these tap changes produce circulating current in parallel-operated transformers. Most engineers know that these parameters are important when paralleling transformers, but there are some misconceptions of when circulating currents actually exist. This application guide addresses these issues in the following sections. Principles of Paralleling on page 1 Limiting Conditions and Transformer Parallel Connection Types on page 2 Equal Impedances Equal Ratios on page 3 Equal Impedances Equal Ratios on page 5 Impedances Equal Ratios on page 5 Impedances Equal Ratios on page 5 Equal Impedances Ratios on page 6 impedances ratios on page 7 Delta Delta-to-Delta Wye on page 8 Transformers connected in parallel have the same voltage on each primary and the same voltage on each secondary. The difference in the voltage between the primary and secondary windings is the turn ratios. For these terminal voltages to be the same for the paralleled transformers, their impedance drops must be identical. Therefore, under any condition of load, the current will be divided such that the product of impedance and current in one transformer is equal to the product of impedance and current in the other. Also, if the turn ratios of the transformers are different, but the primary and secondary terminal voltages are the same in both transformers, then circulating currents must flow between the transformers, even at no load. 1

Loading Considerations When Paralleling Transformers 7400DB0701 Application Guide 02/2007 Limiting Conditions and Transformer Parallel Connection Types Transformers are suitable for parallel operation when their turn ratios, percent impedances, and X/R ratios are the same. Connecting transformers when one of these parameters is different results in either circulating currents or unwanted current division. Both of these situations lower the efficiency and reduce the maximum amount of load the combined transformers can carry. Typically, transformers should not be operated in parallel when: The division of load is such that, with the total load current equal to the combined kva rating of the transformers, one of the transformers is overloaded. The no-load circulating currents in any transformer exceed 10% of the full load rating 1. The combination of the circulating currents and full load current exceed the full load rating of either transformer. From the list above, the circulating currents represent the current flowing at no load in the high and low voltage windings, excluding exciting currents. Full load current is the current flowing in the transformer with a load connected, absent of exciting and circulating currents. Table 1 is an overall summary of different connection types of parallel transformers. Refer to the appropriate section in the following pages for explanations and calculations specific to these different connection types. Table 1: Overall Connection Summary Transformer Parallel Connection Types Equal impedances Equal ratios Equal impedances Equal ratios impedances Equal ratios impedances Equal ratios impedances ratios impedances ratios Equal Loading Loading Overloading Concerns Circulating Currents Recommended Connection Yes No No No Yes No Yes No No Yes No Yes Yes No No No Yes Yes No No Yes No Yes Yes No No Yes Yes Yes No 1 L. F. Blume & A. Boyajian, Transformer Connections, Chapter VII (Schnectady: General Electric, 1940). 2 2007 Schneider Electric All Rights Reserved

7400DB0701 Loading Considerations When Paralleling Transformers 02/2007 Application Guide Equal Impedances Equal Ratios Same kva The standard method of connecting transformers in parallel is to have the same turn ratios, percent impedances, and kva ratings. Paralleling is typically accomplished by maintaining a tie breaker in the normally closed (N.C.) position. Connecting transformers in parallel with the same parameters results in equal load sharing and no circulating currents in the transformer windings. Example 1 on page 4 shows calculations for this scenario. See Figure 1 and Figure 2 for this typical arrangement. Figure 1: Typical Parallel Operation 2 MVA 13.2 kv 480 V 5.75% Z 2 MVA 13.2 kv 480 V 5.75% Z TIE N.C. 2000 kva load 2000 kva load Figure 2: Typical Single-Phase Parallel Operation SOURCE T1 I 1 Z 1 I L LOAD I 2 T2 Z 2 It can be seen by using equations (1) and (2) below, that if the percent impedances in each transformer are the same, as shown in Figure 1, that there will be equal current division and load sharing on each transformer. (1) I 1 = Z 2 x I L Z 1 + Z 2 I 2 = Z 1 x I (2) L Z 1 + Z 2 Where: I 1 = load current from transformer 1 I 2 = load current from transformer 2 Z 1 = % impedance of transformer 1 Z 2 = % impedance of transformer 2 The total load current I L = I 1 + I 2 2007 Schneider Electric All Rights Reserved 3

Loading Considerations When Paralleling Transformers 7400DB0701 Application Guide 02/2007 Substituting for Z 1 and Z 2 below into equations (1) and (2) produces the following equations (3) and (4). (3) I 1 = kva 1 / %Z 1 x I L kva 1 / %Z 1 + kva 2 / %Z 2 (4) I 2 = kva 2 / %Z 2 x I L kva 1 / %Z 1 + kva 2 / %Z 2 Where: I 1 = load current from transformer 1 I 2 = load current from transformer 2 Z 1 = % impedance of transformer 1 Z 2 = % impedance of transformer 2 kva 1 = kva rating of transformer 1 kva 2 = kva rating of transformer 2 The total load current I L = I 1 + I 2 Since current has a direct relationship with kva, substituting kva for current into equation (3) and (4) above, the same comparison can be made using load kval as shown in equations (5) and (6). (5) kva 1 = kva 1 / %Z 1 x kva L kva 1 / %Z 1 + kva 2 / %Z 2 (6) kva 2 = kva 2 / %Z 2 x kva L kva 1 / %Z 1 + kva 2 / %Z 2 The above equations are arithmetically correct only when the ratios between the reactances and resistances of the transformers are equal. They give accurate results when X/R ratios are large. In other cases, the sum of the individual load current will be greater than the current in the line. This is because of the phase difference between the currents in the different transformers. Example 1 Connecting two 2000 kva, 5.75% impedance transformers in parallel, each with the same turn ratios to a 4000 kva load. What is the loading on the transformers? Using equations (5) and (6) above shows that there is equal load division between the transformers. kva 1 = kva 2 = 348 / (348 + 348) x 4000 kva = 2000 kva 4 2007 Schneider Electric All Rights Reserved

7400DB0701 Loading Considerations When Paralleling Transformers 02/2007 Application Guide Equal Impedances Equal Ratios Example 2 Impedances Equal Ratios Example 3 Impedances Equal Ratios Example 4 Although it s not common practice for new installations, sometimes two transformers with different kvas and the same percent impedances are connected to one common bus. In this situation, the current division causes each transformer to carry its rated load. There will be no circulating currents because the voltages (turn ratios) are the same. Connecting 3000 kva and 1000 kva transformers in parallel, each with 5.75% impedance, each with the same turn ratios, connected to a common 4000 kva load. What is the loading on each transformer? Using equations (3) and (4) on page 4: kva 1 = 522 / (522 + 174) x 4000 = 3000 kva kva 2 = 174 / (522 + 174) x 4000 = 1000 kva It can be seen in the calculations that even though there are different kva ratings on transformers connected to one common load, that current division causes each transformer to only be loaded to its kva rating. The key here is that the percent impedances are the same. Frequently in practice, engineers try to enhance their plant power system by connecting existing transformers in parallel that have the same kva rating, but with different percent impedances. This is common when budget constraints limit the purchase of a new transformer with the same parameters. What the engineer needs to understand is that the current divides in inverse proportions to the impedances, and larger current flows through the smaller impedance. Thus, the lower percent impedance transformer can be overloaded when subjected to heavy loading while the other higher percent impedance transformer will be lightly loaded. Connecting two 2000 kva transformers in parallel, one with 5.75% impedance and the other with 4% impedance, each with the same turn ratios, connected to a common 3500 kva load. What is the loading on each transformer? Using equations (5) and (6) on page 4: kva 1 = 348 / (348 + 500) x 3500 = 1436 kva kva 2 = 500 / (348 + 500) x 3500 = 2064 kva It can be seen in the example that because transformer percent impedances do not match, they cannot be loaded to their combined kva rating. Load division between the transformers is not equal. At below combined rated kva loading, the 4% impedance transformer is overloaded by 3.2%, while the 5.75% impedance transformer is loaded by 72%. Seldom are transformers in industrial and commercial facilities connected to one common bus with different kva and unequal percent impedances. However, there may be that one situation where two single-ended substations may be tied together via bussing or cables to provide better voltage support when starting large motors. If the percent impedances and kva ratings are different, care should be taken when loading these transformers. As with the unequal percent impedances shown in Impedances Equal Ratios on page 5, the load current carried by the combined transformers will be less than their rated kva. This can be seen in Example 4 below. Cable impedances between the transformers are ignored. Connecting two transformers in parallel with one 3000 kva (kva 1 ) with 5.75% impedance, and the other a 1000 kva (kva 2 ) with 4% impedance, each with the same turn ratios, connected to a common 3500 kva load. What is the loading on each transformer? 2007 Schneider Electric All Rights Reserved 5

Loading Considerations When Paralleling Transformers 7400DB0701 Application Guide 02/2007 Using equations (5) and (6) on page 4: kva 1 = 522 / (522 + 250) x 3500 = 2366 kva kva 2 = 250 / (522 + 250) x 3500 = 1134 kva As similar to Example 3 because the percent impedance is less in the 1000 kva transformer, it is overloaded with a less than combined rated load. Equal Impedances Ratios A good example of a system with circulation currents would be a double-ended substation (similar to Figure 1 on page 3) that normally has the tie breaker "open." The operator has decided to close the tie breaker to provide loading and voltage support for a heavily loaded transformer on the right side. The heavily loaded transformer's taps have been adjusted to raise the operating voltage, and the transformer on the left side has been lightly loaded. What happens when these two transformers are paralleled without changing the tap on the right transformer to match the left? See Figure 3 for a single-phase diagram of circulating currents described above with no load connected. Figure 3: 0 Single-Phase Diagram with Circulating Currents Ratios 0 SOURCE 0 13.2 kv.48 kv ΔV=12 V NO LOAD 0 T1 13.2 kv.492 kv T2 To calculate the circulating currents, the difference in ratios must be expressed in the percentage of the normal ratio. The circulating current is obtained by dividing this value by the sum of the impedances of the two transformers. This would be the total impedance through which the circulating current is flowing. Using the following equation (7) 1 : (7) %I C = %e x 100 (%R' + k%r'') 2 + (%Z' + k%z'') 2 %I C = circulating current in the transformers in percentage of the rated current. %R', %Z', %R", and %Z" are the percentage resistances and reactances based on the X/R ratio on units kva' and kva". k = kva' / kva" %e = difference in voltage ratio expressed in percentage of normal. The following approximate expression is accurate for most cases. It is exact when the X/R ratios in the transformers are equal 1. (8) %I C %e x 100 %Z' + k% Z" 1 L. F. Blume & A. Boyajian, Transformer Connections, Chapter VII (Schnectady: General Electric, 1940). 6 2007 Schneider Electric All Rights Reserved

7400DB0701 Loading Considerations When Paralleling Transformers 02/2007 Application Guide Example 5 shows the percent of circulating currents to the full load that occur when the tap connection on one transformer is different. Example 5 Using two 2000 kva transformers connected in parallel, each with 5.75% impedance, same X/R ratio (8), transformer #1 with tap adjusted 2.5% from nominal and transformer #2 tapped at nominal. What is the percent circulating current (%I C ) using equations (7) and (8) on page 6. %Z' = 5.75, therefore %R' = %Z' / [(X/R) 2 + 1)] 1/2 %R' = 5.75 / ((8) 2 + 1) 1/2 %R' = %R" =.713 Solving for %X': %X' = %R x (X/R) %X' = %X" =.713 x 8 = 5.7 Using equation (7): % I C = 2.5 x 100 (.713 + (2000/2000) x.713) 2 + (5.7+ (2000/2000) x 5.7) 2 %I C = 250 / 11.5 = 21.7 Using equation (8): %I C = 2.5 x 100 5.75 + ((2000/2000) x 5.75) %I C = 250 / 11.5 = 21.7 The circulating current is 21.7% of the full load current. This example shows that small differences in voltage cause a large amount of current to circulate. It is important to point out that paralleled transformers should always be on the same tap connection. Circulating current is completely independent of the load and load division. If transformers are fully loaded there will be a considerable amount of overheating due to circulating currents. Remember, since circulating currents do not flow on the line, they cannot be measured if monitoring equipment is upstream or down stream of the common connection points. impedances ratios Although it appears highly unlikely that all of these parameters would be different in practice, we will address this situation by looking at circulating currents. Impedances Equal Ratios on page 5 addressed different kva, but ignored the X/R ratios of the transformer. If both the ratios and the impedances are different, the circulating current (because of the unequal ratio) should be combined with each transformer's share of the load current to obtain the actual total current in each unit. For unity power factor, 10% circulating current (due to unequal turn ratios) results in only half percent to the total current. At lower power factors, the circulating current will change dramatically 1. Example 6 shows the effect of having parallel transformers with different percent impedances, along with different turn and X/R ratios connected to one common load. Example 6 Using two transformers connected in parallel, 2000 kva 1 with 5.75% impedance, X/R ratio of 8, 1000 kva 2 with 4% impedance, X/R ratio of 5, 2000 kva 1 with tap adjusted 2.5% from nominal and 1000 kva 2 tapped at nominal. What is the percent circulating current (%I C )? 1 L. F. Blume & A. Boyajian, Transformer Connections, Chapter VII (Schnectady: General Electric, 1940). 2007 Schneider Electric All Rights Reserved 7

PRELIMINARY DRAFT: DO NOT COPY OR DISTRIBUTE FOR USE Loading Considerations When Paralleling Transformers 7400DB0701 Application Guide 02/2007 ENGLISH %Z' = 5.75, therefore %R' = %Z' / [(X/R) 2 + 1)] 1/2 %R' = 5.75 / ((8) 2 + 1) 1/2 %R' =.713 Solving for %X': %X'= %R x (X/R) %X' =.713 x 8 = 5.7 %Z" = 4, therefore %R" = %Z" / [(X/R) 2 + 1)] 1/2 %R" = 4 / ((5) 2 + 1) 1/2 %R" =.784 Solving for %X": %X" = %R x (X/R) %X" =.784 x 5 = 3.92 Using equation (7) on page 6: %I C = 2.5 x 100 (.713 + (2000/1000) x.784) 2 + (5.7+ (2000/1000) x 3.92) 2 %I C = 250 / 13.73 = 18.21 The example above shows that the combined load of the transformers will be limited to [3000 - (.1821 x 3000 = 546 kva)] 2454 kva before a load is connected. Delta Delta-to-Delta Wye Paralleling delta-delta to delta-wye transformers should never be attempted because secondary line-ground voltages (assuming balanced voltages) are shifted by 30 in the wye transformer compared to the delta. This causes extremely high circulating currents in the transformers. Using Example 5 on page 7, equation (6) on page 4, and Figure 4 vectors, this voltage difference calculates to.517 PU at - 75. The percent circulating current calculates to %I C = 51.7 x 100 / 11.5 = 449.5. These circulating currents would overheat the transformers. Figure 4: Secondary Voltage Difference Between Delta and Wye 1 PU 30 =.517-75 1 PU Subtract voltages between delta and wye secondaries Conclusions Schneider Electric USA 1010 Airpark Center Drive Nashville, TN 37217 USA 1-888-SquareD (1-888-778-2733) www.us.squared.com Loading considerations for paralleling transformers are simple unless kva, percent impedances, or ratios are different. When paralleled transformer turn ratios and percent impedances are the same, equal load division will exist on each transformer. When paralleled transformer kva ratings are the same, but the percent impedances are different, then unequal load division will occur. The same is true for unequal percent impedances and unequal kva. Circulating currents only exist if the turn ratios do not match on each transformer. The magnitude of the circulating currents will also depend on the X/R ratios of the transformers. Delta-delta to delta-wye transformer paralleling should not be attempted. Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. 2007 Schneider Electric All Rights Reserved