Interfacing Elevators with Fire Alarm and Sprinklers



Similar documents
rpsa FIRE PROTECTION ENGINEERS

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

Interfacing Fire Alarm Systems and Elevator Controls

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

Original Document 10/16/07 Revised 01/30/09 2 nd Revision rd Revision- 12/18/14

Life Safety Code Enabling References

Module 4, Lesson 12 Fire Alarm Systems

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION

B. NICET: National Institute for Certification in Engineering Technologies.

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS

PLAN REVIEW GUIDE FOR FIRE ALARM

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS

Mobile Fire Rescue Department Bureau of Fire Prevention

2007 ICC FINAL ACTION AGENDA

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

The Mission Critical Fire Protection Experts

2.4 Protected Elevators For Egress And Access During Fires In Tall Buildings

HERNANDO COUNTY FIRE ALARM GUIDELINES

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

NFPA 72. Exception No. 1: Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted.

FVSU REPAIR & UPGRADE FIBER OPTIC SECTION FIRE ALARM SYSTEM CONNECTIVITY

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011

SECTION FIRE ALARM AND DETECTION SYSTEM

Reference numbers following checklist statements represent an NFPA code section unless otherwise specified.

City of Bettendorf Fire Alarm System Requirements

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION

Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) Fire Alarm Permit Application

FIRE ALARM APPLICATION

EXETER TOWNSHIP DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT

Module 5. Fire and Emergency Alarm System Part I- Basics

CHAPTER 8. Village of Caledonia Alarm Systems Ordinance ( /01/13)

Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013

CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE

Fire Alarm System Plans Review Checklist Property location Date of Review

Bold items are particular to the City of Euless

FIRE DETECTION AND ALARM

FIRE ALARM PLAN REVIEW. Office of the State Fire Marshal Massachusetts Department of Fire Services December 2009

Construction Warehouse. Culminating Experience in Fire Protection Engineering FPE 596 Prepared by Ben Johnson

Errata has been identified as follows:

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

Area of Rescue Assistance Communication System ADA Code Applicable excerpts:

EXHIBIT A SCOPE OF WORK

CFAA NCR CHAPTER ANNUAL SENINAR. Commonly Overlooked Fire Alarm Requirements

Michael Catalano 24 Nassau Avenue, Islip NY Phone (631) Chief Fire Marshal Fax (631)

CBD-233. Fire Alarm and Detection Systems

Sam Docknevich, PSP, Security Service Portfolio Manager. Are You Prepared? The impending impact of Code on Servicing Security Systems

The Jefferson County Board of Supervisors does ordain as follows:

Fire Alarm Systems Permit Packet. City of Greer Fire Department

FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual

AETNA FIRE ALARM SERVICE CO., INC.

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM

2012 Ontario Building Code Changes Affecting Fire Alarm Systems

CHAPTER 9 FIRE PROTECTION SYSTEMS

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

University of Houston Master Construction Specifications Insert Project Name

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST

CITY AND COUNTY OF DENVER POLICY DENVER FIRE DEPARTMENT SUBMITTAL OF CONVEYANCE INSTALLATION/ALTERATION PLANS

1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri.

Elevating and Amusement Devices Safety Division Elevating Devices Code Adoption Document - Amendment

TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS

Sprinkler and Fire Alarm Systems for the Building Official

FIRE-FIGHTING DESIGN BRIEF REPORT

Understanding Fire Alarm Requirements & Inspections. Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc

SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective

Fire Pump Plan Review March 2010

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS

c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.

University Design Standard. Fire Alarm Systems

Fire Alarm Log Book. Any activity regarding this system must be documented in writing.

Building Codes Update: The 2009 International Fire Code and the Apartment Industry

MODIFIED INDUSTRY STANDARDS FOR ELEVATORS AND CONVEYING SYSTEMS

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need?

Danville, IN Code of Ordinances CHAPTER 90: ALARM SYSTEMS, SMOKE DETECTORS AND THE LIKE. Alarm Systems. Smoke Detectors. Key and Data Storage Boxes

MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

ENGINEERING SPECIFICATIONS

ENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar

NATIONAL FIRE ALARM AND SIGNALING CODE

Chapter 9 Fire Protection Systems

Proposed Residential Complex At Holding No. - 98, B.T. Road, Kolkata Developer Premier Mica Mining And Manufacturing Company

Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

COMMISSIONING OF FIRE ALARM SYSTEMS

Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007

Agenda. Agenda (continued) Fundamentals of Fire Alarm Systems

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

Winnipeg Fire Department Fire Prevention Branch

Transcription:

Interfacing Elevators with Fire Alarm and Sprinklers IEEE Atlanta Chapter May 15, 2006 Brian K Fabel, PE

Agenda Today s Codes NFPA, ASME, IBC/IFC Conflicts/Issues Tomorrow s Codes?

Applicable Codes NFPA 1, 13, 70, 72 IFC Building Codes IBC, NFPA 101 Atlanta, Georgia Elevator & Escalator Safety Code ASME/ANSI A17.1

Problem! Can t find all the requirements in one place! Must use Codes together!

Bigger Problem! Codes are out of Synch! ASME A17.1 A17.1 1996 A17.1a 1997 A17.1b 1998 A17.1c 1999 A17.1d 2000 A17.1a 2002 A17.1b 2003 A17.1-2004 NFPA 13 & 72 1996 1999 2002 2007

ASME A17.1 Safety Code for Elevators and Escalators Provides Operational Sequences for: Phase 1 - Emergency Recall Operation Power Shutdown Shunt Trip Operation

ASME A17.1 Phase 1 - Emergency Recall Operation The Operation of an elevator wherein it is automatically or manually recalled to a specific landing and removed from normal service because of activation of firefighters service

ASME A17.1 Power Shutdown (Shunt Trip) Mainline elevator power is disconnected from the elevator to eliminate potential problems as a result of sprinkler actuation in the hoistway or elevator machine room

ASME A17.1 Added in 2004 Section 2.27 - Emergency Operation and Signaling Devices 2.27.3.2 Phase 1 Emergency recall operation by fire alarm initiating devices

ASME A17.1-2004 Section 2.8 Equipment in Hoistways, Machinery Spaces, Machine Room, Control Spaces and Control Rooms 2.8.2.3.2 Shunt Trip/Power Disconnect Requirement

International Building Code- 2003 Chapter 30 Elevators and Conveying Systems Section 3003 Emergency Operations Section 3006 Machine Rooms

International Fire Code- 2002 Section 607 Elevator Recall and Maintenance 607.1 Required.

NFPA 1-2002 Chapter 13 Fire Protection Systems 13.7 Detection Alarm & Communication Systems

NFPA 72-2002 Chapter 6 Protected Premises 6.15 Protected Premises Fire Safety Functions 6.15.3 - Elevator Recall for Fire Fighters Service 6.15.4 Elevator Shutdown

NFPA 13-2002 Chapter 8 Installation Requirements 8.14 Special Situations 8.14.5 Elevator Hoistway and Machine Rooms

Code of Ordinances, Atlanta ARTICLE C. ELECTRICITY* Sec. 8-2102. Elevator code; adopted by reference.

ASME A17.1 2004 2.27.3.2.1 In Jurisdiction not enforcing the NBCC, fire alarm initiating devices used to initiate Phase 1 Emergency Recall Operation shall be installed in conformance with the requirements of NFPA 72, and shall be located (a) At each floor served by the elevator; (b) in the associated elevator machine room; and (c) in the elevator hoistway, when sprinklers are located in those hoistways.

International Building Code- 2003 Chapter 30 Elevators and Conveying Systems Section 3003 Emergency Operations 3003.2 Fire Fighter s emergency operation. Elevators shall be provided with Phase I emergency recall operation in accordance with ASME A17.1.

International Building Code- 2003 Chapter 30 Elevators and Conveying Systems Section 3006 Machine Rooms 3006.5 Shunt Trip. Where elevator hoistways or elevator machine rooms containing elevator control equipment are protected with automatic sprinklers, a means installed in accordance with NFPA 72, Section 3-8.15, Elevator Shutdown, (now 6.15.4) shall be provided to disconnect automatically the main line power supply to the affected elevator prior to the application of water. This means shall be self-resetting. The activation of sprinklers outside the hoistway or machine room shall not disconnect the main line power supply.

International Fire Code- 2002 Section 607 Elevator Recall and Maintenance 607.1 Required. Existing elevators with a travel distance of 25 feet or more above or below the main floor or other level of a building and intended to serve the needs of emergency personnel for fire-fighting or rescue purposes shall be provided with emergency operation in accordance with ASME A17.3. New elevators shall be provided with Phase I emergency recall operation and Phase II emergency in-car operation in accordance with ASME A17.1.

Code of Ordinances, Atlanta ARTICLE C. ELECTRICITY* Sec. 8-2102. Elevator code; adopted by reference. CHAPTER IADMINISTRATIONSECTION 101 TITLE AND SCOPE, 101.2 The provisions of this code shall apply to the construction, installation, alteration, repair, location, use, and maintenance of all new and existing elevators, escalators, manlifts, personnel hoists, and related equipment unless specifically exempted by statute or ordinance within the corporate limits of the City of Atlanta, Georgia.The scope of this code does not apply to Georgia laws regulating and licensing carnival rides (see title 34 of the Official Code of Georgia Annotated).This code is hereby declared to be remedial; other codes and ordinances affecting the construction installation, alteration, repair, location, use, and maintenance of elevators, escalators, manlifts, personnel hoists, and related equipment are as follows: (j) Georgia Fire Safety Law: For regulations governing means of egress and safety to life requirements, see the Georgia Fire Safety Law and the rules of the Georgia Safety Fire Commissioner pertaining thereto, Bureau of Buildings, Building Inspection Division.

NFPA 1-2002 NFPA 1-2002 13.7 Detection Alarm & Communication Systems 13.7.1.4.9.2.1* Elevator lobby, hoistway, and associated machine room smoke detectors used solely for elevator recall, and heat detectors used solely for elevator power shutdown, shall not be required to activate the building evacuation alarm if the power supply and installation wiring to such detectors are monitored by the building fire alarm system, and if the activation of such detectors initiates a supervisory signal at a constantly attended location.

NFPA 1-2002 13.7 Detection Alarm & Communication Systems 13.7.1.4.9.5.6 Visible signals shall not be required in elevator cars. 13.7.1.4.9.6.6 The general evacuation signal shall not be required to operate in elevator cars.

NFPA 72-2002 6.15.3 Elevator Recall 6.15.3.1 System-type smoke detectors or other automatic fire detection as permitted by 6.15.3.7 located in elevator lobbies, elevator hoistways, and elevator machine rooms including machine space, control room and control space used to initiate fire fighters service recall shall be connected to the building fire alarm system.

NFPA 72 2002 6.15.3 Elevator Recall 6.15.3.7 If ambient conditions prohibit installation of automatic smoke detection, other automatic fire detection shall be permitted.

NFPA 72-2002 5.7.1.8 Special Conditions 5.7.1.8* - Unless specifically designed and listed for the expected conditions, smoke detectors shall not be installed if any of the following ambient conditions exist: (1) Temperature below 0ºC (32 ºF) (2) Temperature above 38ºC (100 ºF) (3) Relative Humidity above 93 percent (4) Air velocity greater than 1.5 m/sec (300 ft/min)

NFPA 72-2002 6.15.3 Elevator Recall 6.15.3.6 Smoke detectors shall not be installed in unsprinklered elevator hoistways unless they are installed to activate the elevator hoistway smoke relief equipment

NFPA 72 2002 6.15.3 Elevator Recall 6.15.3.2* - In facilities without a building fire alarm system, these smoke detectors shall be connected to a dedicated fire alarm system control unit that shall be designated as elevator recall control and supervisory panel permanently identified on the control unit and on the record drawings.

NFPA 72-2002 6.15.3 Elevator Recall 6.15.3.3 Unless otherwise required by the authority having jurisdiction, only the elevator lobby, elevator hoistway, and the elevator machine room smoke detectors shall be used to recall elevators for firefighters service.

NFPA 72-2002 6.15.3 Elevator Recall 6.15.3.5* - A lobby smoke detector shall be located on the ceiling within 21 ft. of the centerline of each elevator door within the elevator bank under control of the detector. Exception; for lobby ceiling configurations exceeding 15 ft. in height or that are other than flat and smooth, detector locations shall be determined in accordance with Chapter 5.

Smoke Detector Location

NFPA 72-2002 6.15.3 Elevator Recall 6.15.3.9 Actuation from elevator hoistway and elevator machine room smoke detectors shall cause separate and distinct visible annunciation at the control unit and required annunciators to alert fire fighters and other emergency personnel that the elevators are no longer safe to use.

ASME A17.1-2004 2.27.3.2 Phase 1 Emergency Recall Operation by Fire Alarm Initiating Devices 2.27.3.2.6 When activated, a fire alarm initiating device in the machine room shall cause the visual signal to illuminate intermittently only in car(s) with equipment in that machine room.

ASME A17.1-2004 2.27.3.2 Phase 1 Emergency Recall Operation by Fire Alarm Initiating Devices 2.27.3.2.6 When activated, a fire alarm initiating device in the machine room shall cause the visual signal to illuminate intermittently only in the car(s) with equipment in that machine room. When activated, a fire alarm initiating device in the hoistway shall cause the visual signal to illuminate intermittently only in car(s) with equipment in that hoistway.

ASME A17.1 2.27.3 Firefighters Emergency Operation Automatic Elevators FIG. 2.27.3.1.6(h) Visual Signal

NFPA 72-2002 6.15.3 Elevator Recall 6.15.3.10* - For each group of elevators within a building, a minimum of three separate elevator control circuits shall be terminated at the designated elevator controller within the group s elevator machine room(s) the smoke detectors shall actuate the elevator control circuits as follows:

NFPA 72-2002 6.15.3 Elevator Recall 6.15.3.10* cont d (1) The smoke detector located in the designated elevator recall lobby shall actuate the first elevator control circuit. In addition, if the elevator is equipped with front and rear doors, or if the elevator machine room is located at the designated level, the required detectors shall actuate the first elevator control circuit. The detectors in both lobbies at the designated level shall actuate the first elevator control circuit.

NFPA 72-2002 6.15.3 Elevator Recall 6.15.3.10* cont d (2) The detectors in the remaining elevator lobbies shall actuate the second elevator control circuit. (3) The detectors in elevator hoistways and the elevator machine room(s) shall actuate the third elevator control circuit.

NFPA 72-2002 6.15 Protected Premises Fire Safety Functions 6.15.2.2 A listed relay or other listed appliance connected to the fire alarm system used to initiate control of protected premises fire safety functions shall be located within 3 ft of the controlled circuit or appliance. 6.15.2.3 The relay or other appliance shall function within the voltage and current limitations of the fire alarm control unit.

NFPA 72-2002 6.15 Protected Premises Fire Safety Functions 6.15.2.4 The installation wiring between the fire alarm control unit and the relay or other appliance shall be monitored for integrity. Exception: Relays or appliances that operate on loss of power shall be considered selfmonitoring for integrity.

Addressable Control Relays

Addressable Control Relays

NFPA 72-2002 6.15.3 Elevator Recall A.6.15.3.10 It will be necessary sometimes to provide more than three (3) signals to the elevator controller. A17.1 requires differentiation between separate hoistways that share a common elevator machine room.

NFPA 72-2002 6.15.3 Elevator Recall A.6.15.3.10 It will be necessary sometimes to provide more than three (3) signals to the elevator controller. A17.1 requires differentiation between separate hoistways that share a common elevator machine room. For instance, in a situation where there is more than one single hoistway sharing the same elevator machine room, a separate signal must be derived from each hoistway.

NFPA 13-2002 8.14.5 Elevator Hoistway and Machine Rooms 8.14.5.4* - Upright or pendent spray sprinklers shall be installed at the top of elevator hoistways. 8.14.5.5 The sprinkler required a the top of the elevator hoistway by 8.14.5.4 shall not be required where the hoistway for passenger elevators is noncombustible and the car enclosure matierials meet the requirements of ASME A17.1.

NFPA 13-2002 8.14.5 Elevator Hoistway and Machine Rooms 8.14.5.1* - Sidewall spray sprinklers shall be installed at the bottom of each elevator hoistway not more than 2 ft above the floor of the pit. 8.14.5.2 The sprinkler required at the bottom of the elevator hoistway by 8.14.5.1 shall not be required for enclosed, noncombustible elevator shafts that do not contain combustible hydraulic fluids.

ASME A17.1-2004 2.8 Equipment in Hoistways and Machine Rooms 2.8.2.3.2 means shall be provided to automatically disconnect the main line power supply to the affected elevator upon or prior to the application of water from the sprinklers located in the machine room or in the hoistway more than 24 in. above the pit floor.

NFPA 72-2002 6.15.4 Elevator Shutdown 6.15.4.3* - If pressure or waterflow switches are used to shut down elevator power immediately upon or prior to the discharge of water from sprinklers, the use of devices with time-delay switches or time-delay capability shall not be permitted.

NFPA 72-2002 6.15.4 Elevator Shutdown 6.15.4.1* - Where heat detectors are used to shut down elevator power prior to sprinkler operation, the detector shall have both a lower temperature rating and a higher sensitivity as compared to the sprinkler.

Recommendation- Use 165ºF, ordinary temperature rated sprinkler head Use 135 ºF, thermistor-type heat detector Or maintain similar relationship on ambient temperatures Note: Sprinklers in elevator machine rooms and hoistways must be of ordinary or intermediate temperature rating. (NFPA 13 (2002), 8.14.5.3)

NFPA 72-2002 6.15.4 Elevator Shutdown 6.15.4.2 If heat detectors are used to shutdown elevator power prior to sprinkler operation, they shall be placed within 2 ft of each sprinkler head and be installed in accordance with the requirements of Chapter 5.

NFPA 72-2002 6.15.4 Elevator Shutdown 6.15.4.2 If heat detectors are used to shutdown elevator power prior to sprinkler operation, they shall be placed within 2 ft of each sprinkler head and be installed in accordance with the requirements of Chapter 5. Alternatively, engineering methods, such as specified in Annex B shall be permitted to be used to select and place heat detectors to ensure response prior to any sprinkler head operation under a variety of fire growth scenarios.

NFPA 72-2002 6.15.4 Elevator Shutdown 6.15.4.5 The initiating devices described in 6.15.4.2 (WFS) and 6.15.4.3 (HD) shall be monitored for integrity by the control unit required in Section 6.15.3.

Background- Water from sprinklers in the hoistway and elevator machine room presents a hazard to safe elevator operation: Shorts on circuit conductors Uncontrolled elevator operation Wet brakes (traction elevators) Uncontrolled stopping

Shunt Trip Operation (theoretical) Smoke detector activates, causing elevator recall Elevators arrive at the recall floor and open doors Heat buildup causes heat detector to activate Shunt trip operates, removing power from elevator Sprinkler operates

Concern! Potential of passengers becoming entrapped in the elevator if a heat detector or waterflow switch actuates (to cause shunt trip ) prior to the completion of the recall function!

Sprinkler/Power Shutdown Concerns A17.1 Task Group addressed Shunt Trip and Sprinklers Risk Analysis was performed Concern of over-temperature of elevator controller Equipment stops Equipment runs erratically/uncontrollably Concern water from sprinklers may cause: Brake Failure Shorting out of an electrical safety or control circuit

Sprinkler/Power Shutdown Concerns A17.1 Task Group Recommendations: Exemption of sprinklers in elevator machine rooms If sprinklers are installed in elevator machine rooms, then the delay of the release of water from sprinklers will be required so recall can be completed first. The delay strategy Consideration of Earthquake Mode strategy Stop at next floor

NFPA 72-2002 6.15.4 Elevator Shutdown A.6.15.4.4 Upon activation of the heat detector used for elevator power shut down, there should be a delay in the activation of the power shunt trip.

NFPA 72-2002 6.15.4 Elevator Shutdown A.6.15.4.4 Upon activation of the heat detector used for elevator power shut down, there should be a delay in the activation of the power shunt trip. This delay should be the time that it takes the elevator cab to travel from the top of the hoistway to the lowest recall level.

NFPA 72 2002 6.15.4 Elevator Shutdown 6.15.4.4* - Control circuits to shut down elevator power shall be monitored for presence of operating voltage. The loss of voltage to the control circuit for disconnecting means shall cause a supervisory signal to be indicated at the control unit and required remote annunciators.

THANK YOU!?QUESTIONS?