1 Fire Alarm Systems Permit Packet City of Greer Fire Department Updated July 2004 If you have any questions or comments regarding the information contained within; or of you need assistance interpreting these requirements, please contact City of Greer Fire Department Fire Marshal s Office 103 W. Poinsett Street Greer, South Carolina Tel: (864) Fax: (864)
2 TABLE OF CONTENTS I. PURPOSE 3 II. SCOPE 3 III. DEFINATIONS 3 IV. INTRODUCTION 3 V. TYPES OF SYSTEMS 4 VI. SUBMITTAL INFORMATION 4 VII. PLAN INFORMATION 5 VIII. INSTALLATION ANS TESTING 7 IX. ROOMS REQUIRING NOTIFICATION 8 X. FIRE ALARM SUBMITTAL SHEET 9 XI. FIRE ALARM PERMIT APPLICATION 10
3 I. PURPOSE This handout has been developed in an effort to provide the highest level of service to the customers of the City of Greer Fire Department. The major goal of the fire alarm plan review is to insure the design of the fire alarm system meets the minimum requirements of the adopted codes and/or ordinances. To meet this goal, the submitted plans and supporting documentation must contain all the necessary information needed to conduct a comprehensive plan review, as indicated in this document. This information packet outlines the requirements set forth in the adopted codes and standards (International Fire Code and NFPA) as they relate to the installation and maintenance of a fire alarm system. Also provided within this packet is information that is required to be included on the shop drawings and supporting documents. It is not our intent to cover all phases of the fire alarm system design or the generation of the plan it self. II. SCOPE The City of Greer has adopted the International Fire Code and related Standards published by the National Fire Protection Association. The type and design of the proposed fire alarm is dependent upon the requirements set forth within the adopted codes. This fire alarm packet is intended for contractors who will submit fire alarm system plans to the City of Greer and purchase City of Greer fire alarm permits. III. GFD NFPA IFC IBC FCP FSAP DEFINITIONS City of Greer Fire Department National Fire Protection Association International Fire Code International Building Code Fire Control Panel Fire System Annunciator Panel IV. INTRODUCTION 1. Fire alarm systems shall meet the criteria of the 2000 edition of The International Fire Code and all applicable requirements of the most recent edition of the NFPA standards. 2. Plan submittal, City of Greer Fire Marshal approval and permits shall be completed before any fire alarm work begins.
4 V. TYPES OF SYSTEMS One of the first items to determine prior to designing the fire alarm system is what type of system is required? Fire alarm systems shall be submitted to The City of Greer Fire Marshal for review of all buildings with the exception of one and two family dwellings. The GFD has divided fire alarm systems into three major categories: 1. Required / Approved This is an alarm system that is required by adopted codes and the installation is intended to meet the current code requirements. This type of system is required to be submitted for review to The City of Greer Fire Marshal and permit will be issued. 2. Non-Required / Approved This is an alarm system that is NOT required to be installed by adopted codes. The system is being installed at the request of the building owner and/or occupant and the installation is intended to meet current code requirements. This type of system is required to be submitted for review to The City of Greer Fire Marshal and a permit will be issued. 3. Non-Required / Non- Approved An example of this type of system is a building that is not required to have a fire alarm system but the occupant requests one or more detection devices to be installed. This type of system is required to be submitted to The City of Greer Fire Marshal and a permit will be issued. VI. SUBMITTAL INFORMATION This section provides information as to documentation that is to be provided at the time of plan submittal. This information is required to assure the plan submittal package contains the necessary documentation for a complete plan review. The supporting documents and cut sheet shall be included with the submitted plans. Items to be provided as part of the plan submittal documentation are as follows: A. Number of Plans to be Submitted. A minimum of two sets of fire alarm plans shall be provided for review. After plans have been reviewed and approved by the Fire Marshal, one set of the approved plans will be maintained on file within the Fire Marshal s office and the remaining set(s) will be available for pick-up by the submitting contractor.
5 SUBMITTAL INFORMATION CONTINUED a. Manufacturers Product Information One set of the manufacturer s product information sheets shall be provided. The devices being used shall be highlighted. This is to include the information on all devices that are part of, or being connected to, the fire alarm system. The product data sheets will be returned with the approved plans. The product data sheets are to be kept with the approved plans, on the job site, for reference use by fire department inspectors during inspections and/or tests. b. Battery Calculations Two sets of the battery calculations shall be provided for all power supplies being installed within the system. This is to include the voltage and amperage information on all batteries being installed within the main panel and any supplemental power panels being provided. The secondary power supply shall have sufficient capacity to operate the fire alarm system in a non-alarm condition for a minimum of 24 hours and at the end of that period, shall be capable of operating all alarm notification appliances used for evacuation or to direct aid to the location of an emergency for 5 minutes. (2002 NFPA ) One set will be kept on file and the other set shall be kept with the approved set of plans. c. Voltage Drop Calculation Two sets of voltage drop calculations shall be submitted. One set will be kept on file and the other set shall be kept with the approved set of plans. This information shall include: 2. The total number of devices on each wiring circuit, 3. The current draw of each device. 4. The maximum length of wire utilized on each circuit. 5. The wire size being used. 6. Intelligent Horn/ Strobes: Must show the manufacturers information of how voltage drops shall be calculated. 7. Adjustable Multi-Candela Horn/ Strobes: The battery calculations shall be calculated according to the candela rating on the fire alarm plans. For example, if the fire alarm plans indicate the candela rating is a 110 candela, the battery calculation shall calculate for a 110 candela. VII. PLAN INFORMATION When submitting for review, the shop drawings must contain sufficient information to allow a complete plan review. This section of the handout will provide a listing of information required for the review.
6 General Information Regardless of the size or type of fire alarm system being installed, there is a minimum amount of information that shall be provided. The following is a listing of general information required: 1. The drawings need to be scaled to 1/8 or ¼ inch to the foot. To insure accuracy if the shop drawings have been reduced, please provide a graphic representation of the scale on the plan. 2. The address of the project, including the suite number and business name is to be shown within the title block. 3. A detailed paragraph describing the scope of work shall be placed on the front sheet of the plans. The scope of work should describe if the project is new construction, tenant up-fit, remodel, new addition, fire alarm panel upgrade, etc. 4. City of Greer Fire Alarm submittal sheet shall be included with shop drawings. 5. Please provide the information as to the type of communication system being utilized. Provide the name, address and type (central, remote, etc.) of the monitoring agency. 6. All buildings containing a fire alarm system will be required to provide: a. A fire alarm panel or annunciator at the main entrance. b. A Knox key box on the exterior of the building in an approved location. Information concerning the ordering and mounting may be obtained by contact the City of Greer Fire Marshal s office at (864) The location of all elevators and elevator equipment rooms shall be indicated. 8. The location of HVAC system duct smoke detectors shall be indicated. This information is to include the location of the remote test switch, when the remote test switch is required, in accordance with NFPA 72. Note: Upon detector activation the duct detectors are to indicate a supervisory condition. The general evacuation signal of the building is not to be activated (NFPA 90A). 9. Rated corridors and/or area separation walls shall be indicated on the plans. The location of electromagnetic door holders and the smoke detectors that release those doors shall be shown. The ceiling elevation in front of these doors must be indicated on the plans. 10. Locations of all initiating devices shall be shown on the plans. This information is to include point-to-point wiring and the address or zone of the device. On intelligent systems, the address of the device shall be placed next to the device on the plans. On zone systems, the zone circuit shall be identified on the plans next to the device.
7 11. The locations of all system notification appliances shall be provided. Include the point-to-point wiring and circuit number between devices on the plans. The candela rating of each device shall be indicated on the plans next to the device. a. For addressable notification circuits, provide the full address for each device next to the device on the plans. 12. A zoned fire alarm system shall include the zone identification of each zone to be displayed at the FCP. In addition, a listing of the zones shall be included. 13. All addressable fire alarm systems are to provide a listing of the addresses being used on each indicating device. This information is to include the device identification number, type of device, location of the device and the location description to be displayed at the FCP. 14. Information as to the type and size wiring being installed shall be provided. Refer to NFPA 70 for proper wiring for fire alarm systems. Wiring Requirements- Zoned systems 1. Each floor of a multi floor building shall be zoned separately. 2. Manual and automatic initiation devices located within the same fire zone or floor zone may be wired on the same zone. Duct detectors shall be zoned separately from manual and automatic devices. 3. Automatic fire suppression systems shall be monitored by the fire alarm system. VIII. INSTALLATION AND TESTING Installation 1. The installation of the fire alarm system is not to commence, including any pre-wiring until working plans have been reviewed and approved by the City of Greer Fire Marshal and a City of Greer Fire Alarm Permit has been issued. The permit and plans are required to be on the job site at all times. 2. Smoke detectors shall not be installed until final clean up of the entire project. The shipping covers that come with the smoke detectors are not considered listed dust covers and are not to be considered as protection against dust or other contaminants. (NFPA 72) Testing Prior to scheduling an inspection with the City of Greer, the installing company shall complete the following items: 1. Conduct a full operational pre-test of the fire alarm system. The test is to follow the requirements as outlined in NFPA The Fire Alarm System Record of Completion form is to be provided to the City of Greer Fire Inspector at the time of inspection. This form is located in chapter 10 of the 2003 NFPA 72.
8 Completion Documents Upon final acceptance of the system, the installing contractor is to deliver the following items to the building owner or owner s representative: 1. An owner s manual and installation instructions covering the fire alarm systems equipment. IX. Rooms Requiring Notification Devices The City of Greer Fire Marshal has established a list of rooms that will be used as guidelines but not limited to when designing a fire alarm system. Reception lobbies Waiting lobby/area Conference/ meeting rooms Corridors Restrooms Elevator lobbies School office areas School health/ nurse rooms Theater, auditorium, Gymnasium Classrooms Accessible rooms: Hotels, Hearing impaired rooms, etc. Lockers/shower rooms Indoor pool areas Break/lunch rooms Dining/ cafeteria areas Sales floors/ customer areas Mechanical, electrical, data, phone, utility rooms greater than 300 sq ft. Medical exam/ treatment/patient care areas Copy/mail rooms greater than 100 sq ft. Dressing rooms Open work areas greater than 100 sq ft.
FIRE ALARM SYSTEMS INFORMATION PACKET
FIRE ALARM SYSTEMS INFORMATION PACKET Exeter Township Fire Department Office of the Fire Official 2010 1 TABLE OF CONTENTS PURPOSE, SCOPE, DEFINITIONS...3 GUIDELINES...3 I. INTRODUCTION...3 A. APPLICABLE
FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011
Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 1.1 To acquire an installation
Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines
Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Red Oak Fire Rescue Office of the Fire Marshal 547 N. Methodist Red Oak, TX 75154 Phone: 469-218-7713 Fax: 468-218-7719
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,
Rancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
BELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM-10-011
Fire Alarm System plan(s) MUST be reviewed and approved by the Belmont Fire Department prior to the start of construction. The design and any changes must be fully compliant with NFPA 1, NFPA 101, NFPA
FIRE ALARM APPLICATION
FIRE ALARM APPLICATION ENUMCLAW FIRE DEPARTMENT 1330 Wells St, Enumclaw, WA 98022 Phone: 360-825-5544 Fax: 360-825-9442 COMMUNITY DEVELOPMENT, BUILDING DEPARTMENT 1309 Myrtle Ave Enumclaw WA 98022 Phone:
Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application
PERMIT FEE: $ Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application PAYMENT TYPE: Check Credit Card Charge to Job #: (Please complete all of the
LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809
LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3 Fire
Fire Alarm System Plans Review Checklist Property location Date of Review
Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include
City of Bettendorf Fire Alarm System Requirements
City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions
Bold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted
FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION
PERMITS AND INSPECTIONS FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION 911 Assigned PROJECT LOCATION Subdivision: Lot: Blk: Sec: PROJECT New Construction Addition/Remodel Demolition Other: Number
HERNANDO COUNTY FIRE ALARM GUIDELINES
HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a
PLAN REVIEW GUIDE FOR FIRE ALARM
PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical
Fire Alarm Submittal Requirements and Acceptance Testing
Lubbock Fire Marshal s Office 1601 Mac Davis Lane Lubbock, Texas 79401 806-775-2646 Fax 806-775-3508 [email protected] Fire Alarm Submittal Requirements and Acceptance Testing To all Registered
University Design Standard. Fire Alarm Systems
University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit
Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14
North Collier Fire Control & Rescue District Greater Naples Fire Rescue District Immokalee Fire Control & Rescue District 2800 North Horseshoe Drive Naples, Florida 34104 SYSTEM REHABILITATION PLAN CHECKLIST
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:
FIRE ALARM SYSTEM RECORD OF COMPLETION
FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL
FIRE ALARM SYSTEM RECORD OF COMPLETION
FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. Protected Property Information Name of property: Description
FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.
Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's
SECTION 16721 FIRE ALARM AND DETECTION SYSTEM
1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this
Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007
Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 FIRE ALARM SYSTEMS POLICY TELLURIDE FIRE PROTECTION DISTRICT TABLE OF CONTENTS FIRE ALARM PROTECTION POLICY PLAN REVIEW SUBMITTAL
REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING APPLICATION PACKET
REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING FIRE ALARM SYSTEMS APPLICATION PACKET CITY OF NAPERVILLE 400 S EAGLE STREET NAPERVILLE, Il 60540 PHONE: 630.420.6070 FAX: 630.420.6657 Fire Alarm
FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January 2014
Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January 2014 1.1 To acquire an installation
DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION
Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier
FIRE DETECTION AND ALARM
Scope Provide a fire alarm system, or expand the existing system, as required by Code, the requirements in the Special Instructions to Designers (SID) of the Design Guidelines, and/or as noted in the Program
Life Safety Code Enabling References
SUPPLEMENT 4 Life Safety Code Enabling References Editor s Note: Supplement 4 provides users of NFPA 72, National Fire Alarm and Signaling Code, with a summary of requirements from NFPA 101, Life Safety
City of Columbus Department of Building and Zoning Services
City of Columbus Department of Building and Zoning Services Introduction This manual is designed to provide you, the contractor, owner or design professional with a step-by-step guide to our process, beginning
NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems
NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0
How To Get A Fire Alarm Permit In Vail
Fire and Emergency Services 2399 N. Frontage Road W. Vail, Colorado 81657 Tel: 970-479-2252 www.vailgov.com Fire Marshal FIRE ALARM PERMIT Commercial and Residential Fire Alarm shop drawings are required
1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri.
GENERAL: 1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. 2. Fire alarm systems are Life Safety Systems
EXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
527 CMR: BOARD OF FIRE PREVENTION REGULATIONS
527 CMR 24.00: FIRE WARNING SYSTEMS INSTALLED IN BUILDINGS WITHIN THE COMMONWEALTH OF MASSACHUSETTS Section 24.01: Purpose 24.02: Scope 24.03: Definitions 24.04: Approval of Design 24.05: Power Supply
Fire Alarm System Submissions
Gypsum Fire Protection District Fire Alarm System Submissions As of July 1 st, 2007 all Fire Alarm Submissions will be required to be signed by a NICET Level 3 or higher. Fire Alarm System Submissions
Commercial Fire Alarm Standards July 1, 2010 Edition Page 1 of 14
City of Mercer Island Development Services Group Fire Code Review and Inspection 9611 SE 36 th Street Mercer Island, WA 98040-3732 PHONE (206) 275-7605 FAX (206) 275-7726 www.mercergov.org Commercial Fire
DTW Works Master Specification Version 2006
Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4
Fire Alarm Systems Certification
Fire Alarm Systems Certification The skills and knowledge listed under each task are suggestive of those involved in that task, but are not intended to constitute an exhaustive listing. 2.1 Submittal Preparation
Mobile Fire Rescue Department Bureau of Fire Prevention
222 Mobile Fire Rescue Department Bureau of Fire Prevention Samuel L. Jones Mayor Stephen A. Dean Fire Chief February 2011 2009 International Fire Code Fire Alarm and Detection Systems 907.1 General. This
General Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
Reference numbers following checklist statements represent an NFPA code section unless otherwise specified.
Fire Alarm System Plan Review Checklist 2010 OFC and 2007 NFPA 72 This checklist is for jurisdictions that permit the use of the 2007 NFPA 72 in lieu of IFC s referenced 2002 NFPA 72. Date of Review: Permit
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT
SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum
Rhode Island State Fire Marshal Fire Protection Systems Narrative Reports. What is a Narrative Report?
RHODE ISLAND DIVISION OF STATE FIRE MARSHAL 1951 Smith Street, North Providence, RI 02911 Telephone: (401) 383-7717 Fax: (401) 383-8879 John E. Chartier, EFO, CFI State Fire Marshal Rhode Island State
Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need?
5/2/2014 Fire Alarm FAQs Question Answer Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need? A: The size of a fire alarm panel is determined by a number of factors,
COMMONWEALTH OF MASSACHUSETTS STATE BUILDING CODE 780 CMR, 6 th Edition FIRE PROTECTION SYSTEMS CHAPTER 9
COMMONWEALTH OF MASSACHUSETTS STATE BUILDING CODE 780 CMR, 6 th Edition FIRE PROTECTION SYSTEMS CHAPTER 9 GUIDELINES FOR THE PREPARATION OF FIRE PROTECTION SYSTEM NARRATIVE REPORTS 780 CMR 903.1.1 State
FIRE ALARM SYSTEM PLAN SUBMITTAL CHECKLIST
FIRE ALARM SYSTEM PLAN SUBMITTAL CHECKLIST All fire alarm system plan submittals must include this Fire Alarm System Plan Submittal Checklist. PLAN APPROVAL - No work shall be performed until plans are
How To Install A Carbon Monoxide Detector
NASSAU COUNTY FIRE COMMISSION OFFICE OF THE FIRE MARSHAL Nassau County Public Safety Center 1194 Prospect Avenue Westbury, New York 11590 (516) 573-9900 / nassaucountyny.gov Chief Fire Marshal Scott D.
FIRE ALARM PLAN REVIEW. Office of the State Fire Marshal Massachusetts Department of Fire Services December 2009
FIRE ALARM PLAN REVIEW Office of the State Fire Marshal Massachusetts December 2009 SURPRISE QUIZ 1. A fire alarm system is required to be installed by the MSBC, what edition of NFPA 72 do you use? 2.
C. Conform to requirements of Americans with Disabilities Act (ADA).
SECTION 28 31 00 - FIRE ALARM AND DETECTION SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire alarm and detection systems 1.2 REFERENCES A. NFPA 70 - National Electrical Code B. NFPA 72 - National
2007 ICC FINAL ACTION AGENDA
907.2.1.1 System initiation in Group A occupancies with an occupant load of 1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal
rpsa FIRE PROTECTION ENGINEERS
R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, Massachusetts 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Sample Fire Alarm System Calculations 1. A fire alarm manufacturer specifies
SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS
SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment
527 CMR: BOARD OF FIRE PREVENTION REGULATIONS
527 CMR 31.00: CARBON MONOXIDE ALARMS Section 31.01: Purpose and Scope 31.02: Definitions 31.03: General Installation Provisions 31.04: Specific Installation Provisions 31.05: Carbon Monoxide Protection:
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
The Mission Critical Fire Protection Experts
The Mission Critical Fire Protection Experts Protection Systems Protection Systems HFC-227ea / FM200 / FE-227 FE-25 / ECARO-25 Novec 1230 Inergen / Argonite Halon Drop-in Systems High and Low Pressure
Understanding Fire Alarm Requirements & Inspections. Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc
Understanding Fire Alarm Requirements & Inspections Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc Introduction Fire Alarm Requirements are structured through a system of codes.
CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002
CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 Three new chapters were added. What was chapter 1 in 1999 was reorganized into chapters 1 (Fundamentals), 2 (Referenced Publications), and 3 (Definitions).
FIRE ALARM AND DETECTION SYSTEMS SECTION 16721
PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected
NYC Department of Education Building Condition Assessment Survey 2014-2015 P.S. 64 (OLD 71) - MANHATTAN, 600 EAST 6 STREET, MANHATTAN, NY, 10009
School: InspectionId Asset Data Inspection Type Building Assessment Survey 204-205 P.S. 64 (OLD 7) - MANHATTAN, 600 EAST 6 STREET, MANHATTAN, NY, 0009 Time In Last Edited 095 ELECTRICAL 205-0-6 08:45AM
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat
Automatic Fire Sprinkler Submittal Requirements
Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance
COMMISSIONING OF FIRE ALARM SYSTEMS
COMMISSIONING OF FIRE ALARM SYSTEMS OWNER FURNISHED The owner directly contracts an independent third party commissioning agent for this project. This Commissioning Plan has been included for reference
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this
Module 5. Fire and Emergency Alarm System Part I- Basics
Module 5 Fire and Emergency Alarm System Part I- Basics 1 This module will describe: 1. Components and the arrangements of components in fire and emergency alarm systems. 2. How these systems work. 3.
Agenda. Agenda (continued) Fundamentals of Fire Alarm Systems
Fundamentals of Fire Alarm Systems Sponsored by UL SFPE Austin/San Antonio Chapter San Marcos, Texas 7 January 2015 Agenda Introduction and Administration Historical Context of Today s NFPA 72 Fire Alarm
NYC Department of Education Building Condition Assessment Survey 2014-2015 2015-02-10 08:37AM 2015-02-23 08:14AM. Description
School: InspectionId Asset Data Inspection Type Building Assessment Survey 204-205 P.S. 83 - MANHATTAN, 49 EAST 66 STREET, MANHATTAN, NY, 002 Time In Last Edited 352 ELECTRICAL 205-02-0 08:37AM 205-02-23
SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines
PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting
v 1.42b Conceal-Alarm Information Packet for Fire Alarm System Contractors & Installers Conceal -Alarm
v 1.42b Conceal-Alarm Information Packet for Fire Alarm System Contractors & Installers Conceal -Alarm Quick Reference Sheet Important Items to Understand > The Conceal-Alarm series product family is compatible
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM
SECTION 13850 (28 31 00) FIRE DETECTION AND ALARM SYSTEM ENGINEERING SPECIFICATION INTELLIGENT REPORTING FIRE DETECTION SYSTEM PART 1 GENERAL 1.1 DESCRIPTION A. This specification includes the furnishing,
TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS
TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS The following information regarding testing frequencies for fire detection and alarm systems. All of the following
Carbon Monoxide Detection in Commercial Buildings (
1 Technical Guideline for School Districts and BOCES to comply with regulations for Carbon Monoxide Detection in Commercial Buildings (Section 1228.4 of Part 1228 of Title 19 NYCRR). General: This document
SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM
SECTION 16853 ZONED (DC LOOP) FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1
1.0 General. Inspection, Testing, and Maintenance 1 of 8
1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus
rpsa FIRE PROTECTION ENGINEERS www.rpsa-fire.com
www.-fire.com R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, MA 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Elevator Fire Safety: Elevator Recall and Elevator Power Shutdown Disclaimer:
FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY
FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Addressable interface
city of edmonds development information
#B17 city of edmonds development information Commercial Kitchen Hood & Hood Fire Suppression System Permit Submittal Requirements PERMIT REQUIRED: CODES: FEES: A Commercial Kitchen Hood Mechanical Permit
Module 4, Lesson 12 Fire Alarm Systems
Student Manual Module 4, Lesson 12 Fire Alarm Systems Performance Objectives At the conclusion of this lesson, you will be able to: Identify the components and functions of a fire alarm system and determine
Engineers Edge, LLC PDH & Professional Training
510 N. Crosslane Rd. Monroe, Georgia 30656 (770) 266-6915 fax (678) 643-1758 Engineers Edge, LLC PDH & Professional Training Copyright, All Rights Reserved Engineers Edge, LLC An Introduction to Communication
SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective
SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective The National Fire Alarm Code, NFPA 72, sets the minimum requirements of performance, selection, use and location of automatic detection
Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application
February 2014 Code Requirements and Inspections in Educational Occupancies Presented By: Barry W. Rickert Douglas M. Schanne Fire Marshal Training Program Supervisor Office of Education & Data Management
Fire Alarm Systems Requirements by Occupancy Type
WALT WHITE Fire Chief 5770 Freeport Blvd., Suite 200 Sacramento, CA 95822-3516 Ph: (916) 808-1300 Fax: (916) 808-1629 www.sacfire.org Fire Alarm Systems Requirements by Occupancy Type 2013 California Building
CAL FIRE/San Luis Obispo County Fire Fire Prevention Bureau
CAL FIRE/San Luis Obispo County Fire Fire Prevention Bureau g GUIDELINE FOR SAFETY REQUIREMENTS FOR HAUNTED HOUSES PURPOSE This guide is intended to provide safety standards and regulations for the construction
FIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION
Building Name/Location: Installing Company: Observation By: Date: Time: 1 Building Occupants, Authorities and Alarm Monitoring Co Have Been Notified 2 FACP Manufacturer and Panel is Approved for NCSU Campus
Occupancy: Assembly (A-3) and Business -Includes offices, seminar rooms, classrooms, and café facility. Duke University Medical School
Introduction Background The Duke School of Nursing building offers a new three-story state of the art facility that has helped strengthen the quality and integrity of the School of Nursing at Duke. The
FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851
FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
Danville, IN Code of Ordinances CHAPTER 90: ALARM SYSTEMS, SMOKE DETECTORS AND THE LIKE. Alarm Systems. Smoke Detectors. Key and Data Storage Boxes
Danville, IN Code of Ordinances CHAPTER 90: ALARM SYSTEMS, SMOKE DETECTORS AND THE LIKE Section Alarm Systems 90.01 Purpose 90.02 Definitions 90.03 Exemptions 90.04 Registration 90.05 Violations; fines
CHAPTER 9 FIRE PROTECTION SYSTEMS
CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. Provisions of this chapter shall govern the application, design, installation, testing and maintenance of automatic sprinklers, standpipes
AETNA FIRE ALARM SERVICE CO., INC.
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM To be completed by the system inspector or tester at the inspection or test. It shall be permitted to modify this form as needed
2014 Limited Plan Submittal Checklist
City of Aurora Public Works Department WET AND DRY CHEMICAL HOOD SUPPRESSION SYSTEM 2014 Limited Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM INSPECTION AND TESTING FORM To be completed by the system inspector or tester at the time of the inspection or test. It shall be permitted to modify this form
Interfacing Elevators with Fire Alarm and Sprinklers
Interfacing Elevators with Fire Alarm and Sprinklers IEEE Atlanta Chapter May 15, 2006 Brian K Fabel, PE Agenda Today s Codes NFPA, ASME, IBC/IFC Conflicts/Issues Tomorrow s Codes? Applicable Codes NFPA
University of Houston Master Construction Specifications Insert Project Name
SECTION 21 22 13 - SAPPHIRE CLEAN-AGENT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and this Section