EXETER TOWNSHIP DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS
|
|
- Iris Chrystal Cannon
- 8 years ago
- Views:
Transcription
1 DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS POLICY STATEMENT This policy applies to NEW Dry or Wet chemical fire suppression systems. The Authority Having Jurisdiction will not waive major criteria in the applicable standards or codes. The codes and standards provide minimum acceptable standards. Equipment and designs that do not meet the minimum standards shall be considered substandard. Whenever provisions of the adopted or reference codes or standards conflict, the more stringent requirement shall prevail. 1. A CONSTRUCTION PERMIT shall be obtained before any dry or wet chemical fire suppression system is installed, enlarged, extended or replaced. Plans and specifications shall be reviewed by the AHJ prior to issuance of permit. (IFC, 2009). 2. All dry or wet chemical fire suppression systems shall be designed, installed and maintained in accordance with the requirements of the IFC, applicable NFPA and local ordinances. (IFC section 101.3) 3. Two (2) sets of construction documents including elevations and details on the suppression system shall be submitted for review. One set of plans will be returned to the applicant upon permit issuance. 4. The plan review fee for dry or wet chemical fire suppression systems shall be 1½ % of the project cost or a $ minimum. The plan review fee shall accompany the plan submission. (Resolution #10-03) 5. The owner or occupant in charge of the premises shall maintain a complete written record of all tests and inspections required under the Fire Code on the premises for a minimum of 3 years. Accurate logs shall be maintained, indicating the number, location and type of device tested. All defects, modification or repair shall be logged, and the log shall be available to the code official. (IFC 2009 edition Section ).
2 DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS MINIMUM REQUIREMENTS FOR CONSTRUCTION DRAWINGS Plans that do not contain the minimum in formation required will not be accepted for plan check. Plans shall be of sufficient clarity to indicate the location; nature and extent of the work proposed and show that it will conform to the provisions of the adopted International Codes and ordinances. Construction drawings shall be 18" x 24", 24" x 36", or 30" x 42". Plans shall be drawn in indelible ink. Plan sheets that are cut and pasted, taped, or that have been altered by any means (pen, pencil, marking pen, etc.) will not be accepted for plan check. Any registered professional who prepares or supervises the preparation of drawings and construction documents shall stamp and sign such documents. PROJECT NAME General 1) Owner s name, address, telephone and fax numbers. 2) Occupant s name, address, telephone number, if different from owner. 3) Contractor s name, address, fax number, telephone number. Documentation 1) For pre-engineered local application or total flooding systems, submit a manufacturer s installation manual. 2) Type of construction and occupancy classification of building. WORKING DRAWINGS General Information 1) Compass direction and clearly marked scale. 2) Three-dimensional representation of hazard to be protected, including volume of enclosure, if applicable. Permanently mounted equipment or structures that materially reduce the volume, shall be identified and computed. 3) For engineered systems, a statement on the plans reading, There Shall Be No Deviations from the Plans without Approval form the Authority Having Jurisdiction
3 System Information 1) Make, model and type of fire extinguishing system, including system capacity and UL listing. 2) Cylinder mounting location. 3) Type, size and configuration of discharge piping... 4) Location and configuration of all ells, tees and distributors 5) Location and configuration of system actuation equipment, including temperature ratings of fusible links. 6) Type, location and configuration of all discharge nozzles 7) Location and number of flow restricting or balancing devices. 8) Manual pull station location(s) and mounting height(s). FOR SYSTEMS PROTECTING COMMERCIAL COOKING EQUIPMENT: Location and type of cooking appliances and char-broilers. Clearances of surface nozzles above cooking appliances. Location, make and model of automatic fuel shut-off devices. Location, make and model of all reset relays. FOR TOTAL FLOODING SYSTEMS PROTECTING THREE-DIMENSIONAL RISKS: Method used to close doors, windows, etc. prior to agent discharge, if applicable. Method used to shut off forced ventilation systems prior to agent discharge, if applicable. If closure or shut-down cannot be accomplished, the amount of additional agent needed to protect the risk.
4 FIRE PREVENTION PERMIT CONSTRUCTION Fee is 1½% of total job cost or $ minimum Today s Date: Business Starting Date: Business Name: Business Street Address: Business Contact Person: Phone: Location / Address of work performed: Reason for Application: New Business Change of ownership Change of address Previously operating without permits New location Other than yours, is there another business operating at this address? Yes No If yes, provide the name of the business: A Fire Code Permit is required to maintain, use, store, or handle materials, or to conduct processes, which produce conditions hazardous to life or property, or to install equipment used in connection with such activities. If your business intends upon engaging in any of the following activities, operations, practices or functions, a Fire Code Permit may be required. Please identify all of your business intended activities by placing an X in the box provided. If you require assistance, or would like more information, contact us at When issued, the permit shall be posted in a conspicuous location on the premises and shall be kept on the premises until removed/replaced by the Fire Official or AHJ. The permit shall be renewed annually. Changes in use or owner will require issuance of a new Fire Code Permit. This section is for application approval only. Inspector Date This section is for on-site final approval only. Inspector Date Items below for Fire Official's Office Use Only Permit # AMOUNT RECEIVED Check No.
5 FIRE PROTECTION SYSTEMS APPLICATION (ALTERATION, INSTALLATION, REPAIR, MODIFY, ENLARGE, EXTEND, REPLACE) DATE: FEE $ CHECK NO. PROJECT DESCRIPTION: NEW INSTALL UPGRADE / RETROFIT FIRE ALARM SPRINKLER #13 SPRINKLER #13R / D FIRE DETECTION FIRE SUPPRESSION STANDPIPE HOOD / DUCT SPECIAL HAZARD FIRE PUMP OTHER PROJECT INFORMATON: Project Name: Project Address: City: State: Zip: SQ. FT.: NO. Of Stories: Construction Type: Use Group / Occupancy Type: Hazard Class: CONTRACTOR INFORMATION: Name of Company: Address: City: State: Zip: Contact Name: Phone: Fax: INSTALLER INFORMATION: Name of Company: Address: City: State: Zip: Contact Name: Phone: Fax: APPLICANT INFORMATION: (If different from above) Name of Company: Address: City: State: Zip: Contact Name: Phone: Fax:
6
2014 Limited Plan Submittal Checklist
City of Aurora Public Works Department WET AND DRY CHEMICAL HOOD SUPPRESSION SYSTEM 2014 Limited Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420
More informationPLAN SUBMITTAL REQUIREMENTS FOR KITCHEN HOOD AND DUCT EXTINGUISHING SYSTEMS
March 1996 PLAN SUBMITTAL REQUIREMENTS FOR KITCHEN HOOD AND DUCT EXTINGUISHING SYSTEMS PLAN REVIEW 1. Submit a completed permit application and a minimum of three sets of shopquality plans and calculations
More informationNMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet
This Commercial Kitchen Automatic Fire has been created to assure all documentation has been submitted to assist you in assuring proper plans and documentations has been submitted and reviewed by New Mexico
More informationPLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS
January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit
More informationAutomatic fire-extinguishing systems for commercial cooking
Automatic fire-extinguishing systems for commercial cooking Leading Items First Ignited in Eating and Drinking Establishment Structure Fires, 2000-2004 Annual Averages Cooking materials, incl. food and
More informationcity of edmonds development information
#B17 city of edmonds development information Commercial Kitchen Hood & Hood Fire Suppression System Permit Submittal Requirements PERMIT REQUIRED: CODES: FEES: A Commercial Kitchen Hood Mechanical Permit
More informationRhode Island State Fire Marshal Fire Protection Systems Narrative Reports. What is a Narrative Report?
RHODE ISLAND DIVISION OF STATE FIRE MARSHAL 1951 Smith Street, North Providence, RI 02911 Telephone: (401) 383-7717 Fax: (401) 383-8879 John E. Chartier, EFO, CFI State Fire Marshal Rhode Island State
More informationEXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
More informationpresents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Monday, 17 June, 13
presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Who is the AFSA? Safe and Secure Alberta Fire Safety Association Fire industry members working together to improve
More informationTAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
More informationLOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809
LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3 Fire
More informationSARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions
More informationCOMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
More informationWinnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
More informationMaintaining Fire Protection Systems
Maintaining Fire Protection Systems Fire continues to be a major threat to your business and your personal safety. Each year several thousand people are injured or killed by fires and billions of dollars
More informationREGULATIONS for INSTALLATION, MAINTENANCE, and TESTING APPLICATION PACKET
REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING FIRE SUPPRESSION SYSTEMS APPLICATION PACKET CITY OF NAPERVILLE 400 S. EAGLE STREET NAPERVILLE, Il 60540 PHONE: 630.420.6070 FAX: 630.420.6657 Fire
More informationALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for
More informationCity of Bettendorf Fire Alarm System Requirements
City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section
More informationCOMMONWEALTH OF MASSACHUSETTS STATE BUILDING CODE 780 CMR, 6 th Edition FIRE PROTECTION SYSTEMS CHAPTER 9
COMMONWEALTH OF MASSACHUSETTS STATE BUILDING CODE 780 CMR, 6 th Edition FIRE PROTECTION SYSTEMS CHAPTER 9 GUIDELINES FOR THE PREPARATION OF FIRE PROTECTION SYSTEM NARRATIVE REPORTS 780 CMR 903.1.1 State
More informationProgram No. 1.6.1. Section Heading
ENVIRONMENTAL HEALTH AND SAFETY EHS PROGRAM MANUAL Program Title 1.0 INTRODUCTION The New York City Fire Department (FDNY) is responsible for approving and/or inspecting fire alarm systems, buildings,
More informationFire Alarm Submittal Requirements and Acceptance Testing
Lubbock Fire Marshal s Office 1601 Mac Davis Lane Lubbock, Texas 79401 806-775-2646 Fax 806-775-3508 fireprevention@mylubbock.us Fire Alarm Submittal Requirements and Acceptance Testing To all Registered
More informationAutomatic Fire Sprinkler System Checklist
Fire Prevention rd Location: 701 E. 3 Avenue Mail to: P.O. Box 1579 Moses Lake, WA 98837 (509) 765-2204 www.ci.moses-lake.wa.us Automatic Fire Sprinkler System Checklist Please print in Black or Blue ink
More informationOriginal Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14
North Collier Fire Control & Rescue District Greater Naples Fire Rescue District Immokalee Fire Control & Rescue District 2800 North Horseshoe Drive Naples, Florida 34104 SYSTEM REHABILITATION PLAN CHECKLIST
More informationDEPARTMENT OF CONSUMER AND INDUSTRY SERVICES DIRECTOR'S OFFICE
DEPARTMENT OF CONSUMER AND INDUSTRY SERVICES DIRECTOR'S OFFICE CERTIFICATION OF FIRMS FOR FIRE ALARM SYSTEMS AND FIRE SUPPRESSION SYSTEMS IN STATE-REGULATED FACILITIES (By authority conferred on the state
More informationCONSTRUCTION FIRE SAFETY PLANNING GUIDELINES
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES Review the following information pertaining to Construction Fire Safety Planning: B.C. Building Code Sections 8.1 up to and including Subsection 8.2.3 B.C.
More informationAutomatic Fire Sprinkler Submittal Requirements
Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance
More informationHERNANDO COUNTY FIRE ALARM GUIDELINES
HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a
More informationCITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL
More informationRancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent
More informationDivision 21. Fire Suppression
21 00 00. Fire Suppression For campus projects that require a fire suppression system shut down in a campus facility, a Shut Down Procedure of Fire Safety System Sheet must be completed and filed seven
More informationGeneral Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
More informationCLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services
CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline
More informationOVERVIEW SCOPE DEFINITIONS
Procedure No 400.10 Subject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: March 2008 Distribution All Employees Review Date: April 2008 Purpose: To establish
More informationCOMMERCIAL KITCHEN SUPPRESSION SYSTEMS INFORMATION PACKET
COMMERCIAL KITCHEN SUPPRESSION SYSTEMS INFORMATION PACKET Colorado Springs Fire Department Division of the Fire Marshal February 2014 Table of Contents PURPOSE... 3 SCOPE... 3 DEFINITIONS... 3 GUIDELINES...
More informationMERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS
MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS COMMERCIAL FIRE SPRINKLER SYSTEMS Page 1-5 SCOPE: Fire sprinkler systems in the City of Mercer Island shall meet the criteria as set forth
More informationFOR CERTIFICATION AS PRESCRIBED BY THE STATE FIRE PREVENTION COMMISSION ON NOVEMBER 11, 2009 IN ACCORDANCE WITH THE STATE FIRE PREVENTION REGULATIONS
EXAMINATION REQUIREMENTS FOR FIRE SUPPRESSION SYSTEM CERTIFICATION AS PRESCRIBED BY THE STATE FIRE PREVENTION COMMISSION ON NOVEMBER 11, 2009 IN ACCORDANCE WITH THE STATE FIRE PREVENTION REGULATIONS REGULATION
More informationBELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM-10-011
Fire Alarm System plan(s) MUST be reviewed and approved by the Belmont Fire Department prior to the start of construction. The design and any changes must be fully compliant with NFPA 1, NFPA 101, NFPA
More informationENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS
ENGINEERING SPECIFICATIONS FOR CO2 EXTINGUISHING AGENT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS SECTION 1 GENERAL SPECIFICATIONS I. SCOPE This specification outlines the requirements for a pre-engineered
More informationModel: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering
Model: 400E-2M Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Application Engineering BERMAD 1. Safety First BERMAD believes that the safety
More informationENGINEERING SPECIFICATIONS
ENGINEERING SPECIFICATIONS FM-200 CLEAN-AGENT FIRE SUPPRESSION SYSTEM with PYRO-CHEM DETECTION/RELEASE SYSTEM March 2001 SECTION 1 - GENERAL I. SCOPE This specification outlines the requirements for a
More informationINSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT
CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS
More informationButch Browning State Fire Marshal, Bobby Jindal Governor - Licensing Requirements
LOUISIANA DEPARTMENT OF PUBLIC SAFETY AND CORRECTIONS OFFICE OF STATE FIRE MARSHAL, CODE ENFORCEMENT AND BUILDING SAFETY H. Butch Browning State Fire Marshal Bobby Jindal Governor Licensing Law and Rules
More informationFire Alarm System Standpipes Sprinkler Systems Fire Drills Commercial Cooking Hood and more
FIRE PROTECTION SYSTEMS Fire protection systems, measures and equipment are all related to the safety of the occupants and the protection of the property. As part of a building design and its intended
More informationName Of Occupancy Date. Yes No Describe
FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address
More informationBERMAD Fire Protection
400E-2M/700E-2M IOM Bermad Electrically Controlled Deluge Valve with EasyLock Manual Reset Model: 400E-2M/700E-2M INSTALLATION OPERATION MAINTENANCE Application Engineering BERMAD 400E-2M/700E-2M Bermad
More informationFire Alarm Log Book. Any activity regarding this system must be documented in writing.
CASTLE ROCK FIRE AND RESCUE DEPARTMENT 300 Perry Street Castle Rock, Colo. 80104 303-660-1066 Do not remove from the premises: Fire Alarm Log Book Any activity regarding this system must be documented
More informationBERMAD Fire Protection
Model: 400E-2M BERMAD Electrically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with and around
More informationENGINEERING SPECIFICATION. Engineering Specification SAPPHIRE 42 Bar
Engineering Specification SAPPHIRE 42 Bar PART 1 GENERAL 1.1 DESCRIPTION OF WORK This specification outlines the requirements for a "Total Flood" SAPPHIRE Clean Agent Fire Suppression System. The work
More information1.0 General. Inspection, Testing, and Maintenance 1 of 8
1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus
More informationPLAN REVIEW GUIDE FOR FIRE ALARM
PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical
More informationFinance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application
PERMIT FEE: $ Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application PAYMENT TYPE: Check Credit Card Charge to Job #: (Please complete all of the
More informationFIRE ALARM SYSTEMS INFORMATION PACKET
FIRE ALARM SYSTEMS INFORMATION PACKET Exeter Township Fire Department Office of the Fire Official 2010 1 TABLE OF CONTENTS PURPOSE, SCOPE, DEFINITIONS...3 GUIDELINES...3 I. INTRODUCTION...3 A. APPLICABLE
More informationInterfacing Elevators with Fire Alarm and Sprinklers
Interfacing Elevators with Fire Alarm and Sprinklers IEEE Atlanta Chapter May 15, 2006 Brian K Fabel, PE Agenda Today s Codes NFPA, ASME, IBC/IFC Conflicts/Issues Tomorrow s Codes? Applicable Codes NFPA
More informationUL 300 Standard. RS 1021 (9/13) 2013 Nationwide Mutual Insurance Company Page 1 of 6 All Rights Reserved
Summary Fire test standard UL 300 has been a major factor in significant changes in how commercial cooking operations are protected from fire. This report looks at the background of UL 300 and changes
More informationORDINANCE NO. 199 ORDINANCE OF THE WOODSTOCK FIRE/RESCUE DISTRICT ESTABLISHING CHARGES FOR PLAN REVIEW SERVICES
ORDINANCE NO. 199 ORDINANCE OF THE WOODSTOCK FIRE/RESCUE DISTRICT ESTABLISHING CHARGES FOR PLAN REVIEW SERVICES WHEREAS, the Woodstock Fire/Rescue District (hereinafter "District") is a fire protection
More informationUniversity of Houston Master Construction Specifications Insert Project Name
SECTION 21 22 13 - SAPPHIRE CLEAN-AGENT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and this Section
More informationEthanol Vehicle and Infrastructure Codes and Standards Citations
Ethanol Vehicle and Infrastructure Codes and Standards Citations This document lists codes and standards typically used for U.S. ethanol vehicle and infrastructure projects. To determine which codes and
More informationINSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
More informationImportant Ontario Fire Code Information for Building Owners in the City of Windsor
Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact
More informationFIRE CODE INTERPRETATION
FIRE CODE INTERPRETATION February 2014 FCI-14-02 Page 1 of 6 ISSUE: Fixed Fire Suppression & Exhaust Systems Cooking A number of queries from owners, designers and safety codes officers have been received
More informationANSUL. Restaurant Fire Suppression Systems ANSUL UL 300 ANSUL. LOW ph
Restaurant Fire Suppression Systems UL 300 LOW ph The Ansul R-102 System. State-of-the-art in restaurant fire protection. Meeting the fire protection challenge. In 1962, Ansul recognized that there was
More informationDepending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use.
Large Facility Fire Safety Checklists and Logs This package contains checklists to ensure that all fire and life safety equipment are properly inspected. There are also logs on which to record the inspections
More informationORDINANCE NO. 2010-O-01
ORDINANCE NO. 2010-O-01 AN ORDINANCE AMENDING ORDINANCE 2009-O-05 REGULATING AND CODIFYING THE AUTOMATIC FIRE ALARM AND DETECTION SYSTEM CODE OF THE DEERFIELD-BANNOCKBURN FIRE PROTECTION DISTRICT WHEREAS,
More informationBuilding Permit Application
Building Permit Application Administrative Use Only PARENT PERMIT NUMBER (Required if part of another project) PERMITTEE: PERMITTEE ADDRESS: E-MAIL ADDRESS: ARCHITECT/ENGINEER: PHONE: PHONE: ARCHITECT/ENGINEER
More informationResidential Plan Review Emergency Vehicle Access and Water Supply Permit Information Packet
Residential Plan Review Emergency Vehicle Access and Water Supply Permit Information Packet 1. Definitions a. AHJ Authority Having Jurisdiction. The Fire Chief or Fire Marshal of a given Fire District
More informationFire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS
Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting
More informationBUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS
DCD-0304 Identification # Rev. 9/08 County Date of Inspection NAME OF OPERATION BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS ADDRESS TELEPHONE: CITY STATE ZIP BUILDING INSPECTORS CERTIFICATE
More informationFire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
More informationFIRE ALARM APPLICATION
FIRE ALARM APPLICATION ENUMCLAW FIRE DEPARTMENT 1330 Wells St, Enumclaw, WA 98022 Phone: 360-825-5544 Fax: 360-825-9442 COMMUNITY DEVELOPMENT, BUILDING DEPARTMENT 1309 Myrtle Ave Enumclaw WA 98022 Phone:
More informationBold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted
More informationBuilding Permit Application Packet. BUILDING CODES Adopted by La Plata County For Enforcement In The Unincorporated Areas Of La Plata County
Building Permit Application Packet The purpose of Building Codes is to establish the minimum requirements to safe guard the public health, safety and general welfare through structural strength, means
More informationPrime Power Services, Inc. Georgia, Carolinas 800 741 0128. NFPA 110 Standards for Emergency & Stand by Generators June 1, 2010
Prime Power Services, Inc. Georgia, Carolinas 800 741 0128 NFPA 110 Standards for Emergency & Stand by Generators June 1, 2010 NFPA Disclaimer The views and opinions expressed in this seminar are purely
More informationInspection, Testing and Maintenance
Page 18 ABOUT CODE CORNER CCFS would like to remind you to check with your local Authority Having Jurisdiction (AHJ) for questions and opinions concerning your local Fire and Building Codes. The information
More informationLICENSE CATEGORIES. (2) A demolition contractor class II may demolish any building not more than three stories in height.
CONTRACTOR LICENSING & CERTIFICATION REQUIREMENTS INFORMATION BULLETIN NO. 118 -- June 2, 1997 (Revised May 1, 2012) City of Kansas City, Missouri http://www.kcmo.org/codes/ CONTRACTOR LICENSING & CERTIFICATION
More informationELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1
KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1
More informationAppendix B Forms for Inspection, Testing, and Maintenance
Appendix B Forms for Inspection, Testing, and Maintenance This appendix is not a part of the requirements of this NFPA document but is included for informational purposes only. Forms need to be complete
More informationMetropolitan Washington Airports Authority Office of Public Safety Fire & Rescue Department. Fire Code Enforcement Division
Metropolitan Washington Airports Authority Office of Public Safety Fire & Rescue Department Fire Code Enforcement Division Fire Protection System Impairment Requirements For Contractors and Service Personnel
More informationModule 4, Lesson 12 Fire Alarm Systems
Student Manual Module 4, Lesson 12 Fire Alarm Systems Performance Objectives At the conclusion of this lesson, you will be able to: Identify the components and functions of a fire alarm system and determine
More informationFire Alarm Systems Certification
Fire Alarm Systems Certification The skills and knowledge listed under each task are suggestive of those involved in that task, but are not intended to constitute an exhaustive listing. 2.1 Submittal Preparation
More informationRequired Certification Documentation. Contractor's installation certification for range hood fire suppression systems.
OFFICE OF UNIVERSIT BUILDING OFFICIAL PROJECT/CONSTRUCTION MAGER: Sample Manager Required Aboveground only Required Certification Documentation Contractor s material and test certifications for both above
More informationATTENTION BUILDERS, CONTRACTORS AND DEVELOPERS
ATTENTION BUILDERS, CONTRACTORS AND DEVELOPERS Wellington Fire Protection District Development and Construction Plan Review Fee Policy. For any questions, contact the Fire Marshal at (970) 568-3232, ext
More informationCommercial Fire Inspections
Commercial Fire Inspections Fire Department Inspection Requests and Procedures The following guidelines shall be used when calling for inspection requests: 1. All inspection requests shall be coordinated
More informationFIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION
FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this
More informationHealth Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE
Health Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE CHAPTER 420-5-22 SUBMISSION OF PLANS AND SPECIFICATIONS FOR HEALTH CARE FACILITIES TABLE OF
More informationDevelopment Services Guidelines
Dear Customer/Developer: Balcones Heights 3300 Hillcrest San Antonio, Texas 78201 210-735-9148 ext 246 Fax: 210-735-9409 Development Services Guidelines Welcome to the City of Balcones Heights, we look
More informationSECTION 16721 FIRE ALARM AND DETECTION SYSTEM
1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this
More informationTelluride Fire Protection District Fire Alarm Systems Policy Version 03/2007
Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 FIRE ALARM SYSTEMS POLICY TELLURIDE FIRE PROTECTION DISTRICT TABLE OF CONTENTS FIRE ALARM PROTECTION POLICY PLAN REVIEW SUBMITTAL
More informationPOSITION STATEMENT THE ENGINEER AND THE ENGINEERING TECHNICIAN DESIGNING FIRE PROTECTION SYSTEMS. July 28, 2008
SOCIETY OF FIRE PROTECTION ENGINEERS (SFPE) NATIONAL SOCIETY OF PROFESSIONAL ENGINEERS (NSPE) NATIONAL INSTITUTE FOR CERTIFICATION IN ENGINEERING TECHNOLOGIES (NICET) POSITION STATEMENT THE ENGINEER AND
More informationINSPECTION AND TESTING OF FIRE ALARM SYSTEMS
Page 1 January 2, 2009 INSPECTION AND TESTING OF FIRE ALARM SYSTEMS Introduction Early warning plays a key role in a healthcare facility s ability to safely evacuate its residents during a fire emergency.
More informationCHAPTER 150: BUILDING REGULATIONS. Adoption of Regulatory Codes by Reference
CHAPTER 150: BUILDING REGULATIONS Section Adoption of Regulatory Codes by Reference 150.01 Scope 150.02 Commercial Construction Code 150.03 Commercial Plumbing Code 150.04 Heating, Air Conditioning, Refrigeration
More information527 CMR: BOARD OF FIRE PREVENTION REGULATIONS
527 CMR 31.00: CARBON MONOXIDE ALARMS Section 31.01: Purpose and Scope 31.02: Definitions 31.03: General Installation Provisions 31.04: Specific Installation Provisions 31.05: Carbon Monoxide Protection:
More informationMedicine Hat Fire Department. Special Event Requirements. medicinehat.ca/fire. August 2012
Medicine Hat Fire Department Special Event Requirements August 202 medicinehat.ca/fire The following is a standard guide for event organizers to ensure occupant safety and compliance with the Alberta Fire
More informationVACANT BUILDING REGISTRATION FORM (Please complete and return ONE form per property within twenty (20) days Must be typed or legibly printed.
CITY OF ALBANY DIVISION OF BUILDINGS & REGULATORY COMPLIANCE ROOM 303 - CITY HALL 24 EAGLE STREET ALBANY, NEW YORK 12207 PHONE: (518) 434-5165 FAX: (518) 434-6015 Official Use Only Reg. No. Date Rec d
More informationC I T Y O F S E L M A F I R E D E P A R T M E N T
C I T Y O F S E L M A F I R E D E P A R T M E N T Informational Bulletin Regarding Residential Fire Sprinkler Systems for One and Two Family Homes: Frequently Asked Questions ADMINISTRATIVE PROVISIONS:
More informationFire Alarm and Protection Impairment Policy and Procedures
1.0 Policy Statement The University of New Haven has developed a Fire Alarm and Protection Impairment Plan in accordance with the National Fire Protection Associations (NFPA) codes. Specific codes referenced
More informationFire Safety Plan (Single-Stage Fire Alarm System - Small Establishment)
1 Fire Safety Plan (Single-Stage Fire Alarm System - Small Establishment) Fire Safety Plan Single-Stage Fire Alarm System (small establishment) for: (Business Name) (Business Address) The reproduction
More informationMOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
More informationFire Alarm Systems Permit Packet. City of Greer Fire Department
Fire Alarm Systems Permit Packet City of Greer Fire Department Updated July 2004 If you have any questions or comments regarding the information contained within; or of you need assistance interpreting
More information