Winnipeg Fire Department Fire Prevention Branch
|
|
|
- Edgar Barker
- 10 years ago
- Views:
Transcription
1 Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of the fire safety equipment maintenance requirements for all existing buildings from Division B of the Manitoba Fire Code (MFC 2012). Please contact the Fire Prevention Branch through for any additional questions or concerns. Owner responsibilities as identified in the Manitoba Fire Code (2012) Unless otherwise specified, the owner or the owner s authorized agent shall be responsible for carrying out the provisions of this Code. (Division C ) Before tests, repairs or alterations are made to fire protection installations, a procedure of notification shall be established which shall include notifying the Fire Department and the building occupants, where necessary, for safety in the event of an emergency. ( ) A written record shall be kept of all tests, inspection, maintenance or operational procedures for a period of two years after they are made and the record shall be made available upon request of the Authority Having Jurisdiction. (Division C ) Manitoba Fire Code Life-Safety Equipment Maintenance Requirements Page 1 of 10
2 Definitions: CHECK visual observation to ensure the device or system is in place and is not obviously damaged or obstructed. INSPECT physical examination to determine the device or system will apparently perform in accordance with its intended function. TEST operation of device or system to ensure that it will perform in accordance with its intended function. OWNER - lessee, person in charge, person who has care and control, person who holds out that the person has the powers and authority of ownership or who, for the time being, exercises the powers and authority of ownership. AUTHORITY HAVING JURISDICTION (AHJ) a safety code officer in the fire discipline exercising authority pursuant to the designation of power and terms of employment in accordance with the Safety Codes Act. SUPERVISORY STAFF those occupants of a building who have some delegated responsibility for the fire safety of other occupants under the fire safety plan. WATER-BASED FIRE PROTECTION SYSTEMS sprinkler system, standpipes, private hydrants, hose systems, water spray fixed systems, foam water sprinkler systems and spray systems and fire pumps. Notes and Fire Prevention By-Law (150/2004) requirements: 1) Written records for all inspections and maintenance performed on the Fire Protection and Life safety Systems shall be retained for a period of two years and retained on premises for examination by the AHJ. Records for the current servicing and for the period immediately preceding shall be available. 2) Inspection, testing and maintenance of Fire Protection and Life Safety Equipment as required by the MFC shall be conducted by qualified service personnel acceptable to the AHJ. The City of Winnipeg requires persons performing inspection, testing and servicing on these systems to be licensed** to perform those functions through the Fire Prevention Branch of the City of Winnipeg Fire Department. **For additional information regarding Service Person licensing and qualifications, see City of Winnipeg By-Law 150/ ) Smoke alarms shall be installed, tested and maintained in accordance with By-Law 150/2004. At least one acceptable smoke alarm shall be installed in every residential rental unit. Acceptable smoke alarm means either: a) Has a permanent connection to an electrical circuit, or b) Is powered by a ten-year lithium battery. Manitoba Fire Code Life-Safety Equipment Maintenance Requirements Page 2 of 10
3 Building Owner Responsibility Schedule DAILY MFC ref. # (1) Fire Alarm System CHECK AC power lamp (2) Central Alarm and Control Facility CHECK to ensure that no trouble is indicated (3) Fire Pump Rooms CHECK temperature during cold weather. (4) Fire Protection Water Tanks CHECK tank heating equipment, enclosure and water temperature during heating season in systems without low temperature alarms. (5) Exit Signs CHECK to ensure they are in clean and legible condition (6) Fire Doors CHECK doors in fire separation to ensure they remain closed (1) (7) Exit Lights CHECK to ensure they are illuminated and in good repair (2) (8) Torches, Regulators and Welding Equipment CHECK for leakage or defects WEEKLY * These articles require written records (Division C ) MFC ref. # (1) Fire Pump CHECK fuel and oil level. (2) Fire Pump CHECK water level in reservoirs. (3) Fire Pump INSPECT and operate. (4) Sprinkler System CHECK that the control valves are open. (5) Dry Pipe Sprinkler System CHECK pressure gauge to ensure that air pressure is being maintained. (6) Fire Protection Water Tanks CHECK tank heating equipment, enclosure and water temperature during heating season in systems with low temperature alarms. (7) Emergency Generator System INSPECT, TEST and MAINTAIN as per Table 2 of CAN/ CSA-C Emergency Electrical Power Supply For Buildings. (8) Hoods, Filters and Ducts in Ventilation Systems CHECK for accumulation of combustible deposits and clean as required * Manitoba Fire Code Life-Safety Equipment Maintenance Requirements Page 3 of 10
4 MONTHLY * These articles require written records (Division C ) MFC ref. # (1) Fire Alarm System TEST system and check all components on emergency power supply including standby power batteries * (2) Voice Communication System TEST the system * (3) Water-Based Fire Protection Systems INSPECT all control valve tamper switches. (4) Fire Protection Water Tanks INSPECT the water level in tanks not equipped with supervised water level alarms connected to a constantly attended location. (5) Emergency Generator System - INSPECT, TEST and MAINTAIN as per Table 3 of CAN/ CSA-C * (6) Portable Fire Extinguishers INSPECT and sign tag * (7) Exit Doors TEST all doors forming part of a means of egress to ensure they are operable (8) Emergency Lighting Systems INSPECT and TEST batteries, units and lamps (9) Fire Doors OPERATE all doors in fire separations (3) (10) Fire Alarm Drills CONDUCT drills for supervisory staff in day care and health care facilities * EVERY THREE MONTHS *These articles require written records (Division ) MFC ref. # (1) All Fire Emergency Systems in High Buildings as defined by Subsection of the Building Code TEST * (2) Sprinkler Alarm Devices INSPECT verify they are free of physical damage. (3) Water-Based Fire Protection Systems TEST all system water flow alarm devices. * (4) Water-Based Fire Protection Systems TEST all pre-action/deluge valves. * (5) Water-Based Fire Protection Systems TEST all dry pipe valves/quick-opening devices. * (6) Fire Department Connections INSPECT. (7) Main Drain TEST the main drain of at least one system downstream of a device that has the sole water supply through a backflow preventer and/or pressure reducing valves. (8) Fire Protection Tanks INSPECT water level in tanks with supervised water level alarms that are connected to a constantly attended location. (9) CLEAN hoods, grease removal devices, fans and ducts on commercial equipment used in deep fat cooking, charbroiling or similar cooking operations. * * Manitoba Fire Code Life-Safety Equipment Maintenance Requirements Page 4 of 10
5 EVERY SIX MONTHS * These articles require written records. (Division C ) MFC ref. # (1) Fire Protection Systems TEST supervisory control valves. * (2) Special Fire Suppression Systems TEST, INSPECT and MAINTAIN systems as per the appropriate National Fire Protection Association (NFPA) code. (3) Commercial Cooking Equipment Suppression System INSPECT and MAINTAIN. (4) CLEAN hoods, grease removal devices, fans and ducts on commercial cooking equipment (other than deep frying or charbroiling) shall be cleaned as required but annually as minimum. (5) Emergency Generator System INSPECT, TEST and MAINTAIN as per Table 4 of CAN/ CSA (6) Fire Alarm Drills CONDUCT in schools attended by children, three times in both spring and fall terms * * * * (7) Fire Alarm Drill CONDUCT for supervisory staff in all high-rise buildings * Manitoba Fire Code Life-Safety Equipment Maintenance Requirements Page 5 of 10
6 ANNUALLY * These articles require written records. (Division C ) MFC ref. # (1) Fire Alarm System CONDUCT a test of the system by qualified personnel acceptable to the AHJ. (2) Voice Communication System CONDUCT a test of the system by qualified personnel acceptable to the AHJ. (3) Water-Based Fire Protection System INSPECT, TEST, OPERATE and MAINTAIN components of each system as required by the appropriate NFPA or CAN/ULC document referenced in the MFC (4) Fire Pump CONDUCT a flow test. (5) Water-Based Fire Protection System Riser TEST the main drain of each riser to determine whether there has been a change in the condition of the water supply piping and control valves. (6) Hydrants INSPECT and flow test all private hydrants. (7) Standpipe Hose INSPECT and re-rack. (8) Fire Extinguishers CONDUCT maintenance procedures by qualified personnel acceptable to the AHJ (9) Electromagnetic Door Locks TEST to ensure they work properly * (10) Sliding Doors TEST sliding doors that are required to swing on their vertical axis in the direction of egress when pressure is applied * (11) Revolving Doors TEST safety features * (12) Mechanical Air Conditioning and Ventilation Systems OPERATE disconnect switches (13) Fire Dampers and Fire Stop Flaps INSPECT (14) Sprinkler Heads INSPECT supply of spare sprinkler heads and replace as required. (15) Emergency Generator System INSPECT, TEST and MAINTAIN as per Table 5 of CAN/CSA * (16) Chimneys, Flues and Flue Pipes INSPECT (17) Chimney Spark Arrestors INSPECT and CLEAN (18) Fire Alarm Drills CONDUCT for supervisory staff in buildings with fire alarm systems. (19) Exhaust and make up air system TEST and MAINTAIN system initiating devices (i.e. carbon monoxide detector) in enclosed parkades * * Manitoba Fire Code Life-Safety Equipment Maintenance Requirements Page 6 of 10
7 EVERY TWO YEARS MFC ref. # (1) Fire Protection Water Tanks CHECK steel tanks for corrosion. (2) Fire Protection Water Tanks INSPECT all tanks, connected to a non-potable water supply for sediment. (3) Pressurization Systems TEST systems in high buildings as defined by Subsection of the Building Code EVERY THREE YEARS MFC ref. # (1) Dry Pipe Sprinkler Systems TEST the dry pipe valve with the control valve fully open and the quick-opening device, if provided, in service. EVERY FIVE YEARS * These articles require written records. (Division C ) MFC ref. # (1) Sprinkler System TEST extra-high temperature sprinkler heads as per NPFA document. * (2) Standpipe System Flow TEST systems. * (3) Standpipe System Hydrostatically TEST system. * (4) Standpipe System TEST pressure control and pressure reducing valves. * (5) Standpipe System TEST standpipe hose. * (6) Water-Based Fire Protection Systems TEST all gauges. * (7) Private Hydrant Flow TEST exposed and underground piping. * (8) Fire Extinguishers Hydrostatically TEST carbon dioxide and water type extinguishers. (9) Water-Based Fire Protection System INSPECT fire protection water tank for corrosion. (10) Emergency Generator System INSPECT, TEST, and MAINTAIN as per Table 6 of CAN/CSA * * EVERY SIX YEARS MFC ref. # (1) Fire Extinguishers REPLACE the extinguishing agent in dry chemical fire extinguishers * EVERY TWELVE YEARS MFC ref. # (1) Fire Extinguishers Hydrostatically TEST dry chemical and vaporizing liquid fire extinguishers. Manitoba Fire Code Life-Safety Equipment Maintenance Requirements Page 7 of 10
8 EVERY TWENTY YEARS MFC ref. # (1) Sprinkler System TEST fast response sprinkler heads. AS REQUIRED MFC ref. # (1) Fire Department Access ENSURE streets, yards and private roadways that are provided for fire department access are kept clear. (2) Dry Pipe Sprinkler Systems TEST the dry pipe valve with the control valve fully open and the quick-opening device, if provided, in service. (3) Spray Booths CLEAN residue in walls, ceilings, floors, etc. from spray booths. (4) Means of Egress CHECK exterior passageways and exterior exit stairs and ensure they are maintained free of snow, ice and obstructions. (5) Smoke Control Equipment MAINTAIN equipment in a manner that ensures satisfactory operation (6) Sprinkler System INSPECT auxiliary drains. (7) Fire Doors CHECK doors in fire separations to ensure they are closed (8) Dust Producing Operations CLEAN any combustible dust-producing operations. (9) Dry-powder Finishing Operations VACUUM, CLEAN and DUST any drypowder finishing operations. (10) Industrial Ovens INSPECT clean and maintain all industrial ovens and associated ductwork (11) CHECK lint traps in laundry equipment Manitoba Fire Code Life-Safety Equipment Maintenance Requirements Page 8 of 10
9 Fire Safety Plan The building owner is responsible for preparing a fire safety plan, acceptable to the Fire Prevention Branch, and appointing supervisory staff to carry out the same in all public assembly buildings, care or detention buildings, all buildings equipped with a fire alarm, demolition and construction sites, storage areas, areas where flammable liquids or combustible liquids are stored or handled and areas where hazardous processes or operations occur. Section 2.8 of the Manitoba Fire Code must be referred to in order to get the exact regulations as it applies to your building. SECTION 2.8 Subsection General The requirements of this Section apply to every building containing a Group A or Group B occupancy, and to every building required by the Building Code to have a fire alarm system (1) Supervisory staff shall be trained in the fire emergency procedures as described in the fire safety plan before they are given any responsibility for fire safety. A (1) Except in hospitals and nursing homes, it is not necessary that the supervisory staff be in the building on a continuous basis, but they shall be available to fulfill their obligations as described in the fire safety plan on notification of a fire emergency Subsection Fire Safety Plan (1) A fire safety plan acceptable to the Fire Marshal which includes the following measures shall be prepared in buildings regulated by Article : a) the emergency procedures to be used in case of fire including: i) sounding the fire alarm, ii) notifying the fire department, iii) instructing occupants on procedures to be followed when the fire alarm sounds, iv) evacuating occupants, including special provisions for persons requiring assistance, v) confining, controlling and extinguishing the fire. b) the appointment and organization of designated supervisory staff to carry out fire safety duties, c) the training of supervisory staff and other occupants in their responsibilities for fire safety, Manitoba Fire Code Life-Safety Equipment Maintenance Requirements Page 9 of 10
10 d) documents, including diagrams, showing the type, location and operations of the building fire emergency systems, e) the holding of fire drills, f) the control of fire hazards in the building, and g) the inspection and maintenance of building facilities provided for the safety of occupants (2) The fire safety plan shall be reviewed at intervals not greater than 12 months to ensure that it takes account of change in the use and other characteristics of the building (1) A sufficient number of supervisory staff shall be on duty in care or detention occupancies to perform the tasks outlined in the fire safety plan (1) In Group 1, Division 1 assembly occupancies containing more than 60 occupants, there shall be at least one supervisory staff member on duty in the building to perform the tasks outlined in the fire safety plan whenever the building is open (1) In buildings within the scope of Subsection of Division B of the Manitoba Building Code, the fire safety plan shall, in addition to the requirements of Sentence (1), include: a) the training of supervisory staff in the use of the voice communication system, b) the procedures for use of elevators, c) the action to be taken by supervisory staff in initiating any smoke control or other fire emergency systems installed in a building in the event of fire until the fire department arrives, d) the instructions to the supervisory staff and fire department for the operation of the systems referred to in Clause (c), and e) the procedures established to facilitate fire department access to the building and fire location within the building (1) The fire safety plan shall be kept in the building for reference by the fire department, supervisory staff and other personnel (2) The fire safety plan for a building within the scope of Subsection of Division B of the Manitoba Building Code 2006 shall be kept at the central alarm and control facility (1) A copy of the fire emergency procedures and other duties for supervisory staff as laid down in the fire safety plan, shall be given to all supervisory staff (1) At least one copy of the fire emergency procedures shall be prominently posted on each floor area. Manitoba Fire Code Life-Safety Equipment Maintenance Requirements Page 10 of 10
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for
Important Ontario Fire Code Information for Building Owners in the City of Windsor
Important Ontario Fire Code Information for Building Owners in the City of Windsor This information is intended to be used a reference only. For a complete listing consult the Ontario Fire Code or contact
Fire Alarm System Standpipes Sprinkler Systems Fire Drills Commercial Cooking Hood and more
FIRE PROTECTION SYSTEMS Fire protection systems, measures and equipment are all related to the safety of the occupants and the protection of the property. As part of a building design and its intended
BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS
BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS Owners have numerous responsibilities as it pertains to the maintenance and operation of a building s fire safety equipment. The liabilities
INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT
CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES Review the following information pertaining to Construction Fire Safety Planning: B.C. Building Code Sections 8.1 up to and including Subsection 8.2.3 B.C.
Dennis Fire Department Fire Prevention Mark Dellner Fire Chief
Dennis Fire Department Fire Prevention Mark Dellner Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES (MA Fire Prevention Regulations 527 CMR, MGL Chapter 148) FIRE PREVENTION CHECKLIST-
Name Of Occupancy Date. Yes No Describe
FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address
FIRE SAFETY PLAN 123 TOWER STREET CAMBRIDGE, ONTARIO
S A M P L E FIRE SAFETY PLAN 123 TOWER STREET CAMBRIDGE, ONTARIO This sample Fire Safety Plan can be used to assist in developing a Fire Safety Plan for your building. TABLE OF CONTENTS 1. HUMAN RESOURCES
Depending on your facility and the equipment contained within, all or part of the checklists/logs can be printed for use.
Large Facility Fire Safety Checklists and Logs This package contains checklists to ensure that all fire and life safety equipment are properly inspected. There are also logs on which to record the inspections
General Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
Fire Safety Plan (Single-Stage Fire Alarm System) (Small Establishment):
Fire Safety Plan (Single-Stage Fire Alarm System) (Small Establishment): Fire Safety Plan Single-Stage Fire Alarm System for: (Business Name) (Business Address) Submission Date - Submitted by - Signature
Fire Safety Plan (Single-Stage Fire Alarm System - Small Establishment)
1 Fire Safety Plan (Single-Stage Fire Alarm System - Small Establishment) Fire Safety Plan Single-Stage Fire Alarm System (small establishment) for: (Business Name) (Business Address) The reproduction
VOLUNTEER FIRE WARDENS
FIRE PRE-PLAN FACILITIES SERVICES VOLUNTEER FIRE WARDENS & EMERGENCY RESPONSE MEMBERS KEELE CAMPUS & GLENDON CAMPUS Ken Wong, P.Eng. SFPE. Mgr., Building Code / Fire Protection Code Compliance Facilities
Maintaining Fire Protection Systems
Maintaining Fire Protection Systems Fire continues to be a major threat to your business and your personal safety. Each year several thousand people are injured or killed by fires and billions of dollars
We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors.
September 14, 2012 Dear AMM Member: Please see the attached Fire Code Frequently Asked Questions. This document was compiled by the Office of the Fire Commissioner at the AMM s request to help clarify
Automatic fire-extinguishing systems for commercial cooking
Automatic fire-extinguishing systems for commercial cooking Leading Items First Ignited in Eating and Drinking Establishment Structure Fires, 2000-2004 Annual Averages Cooking materials, incl. food and
PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS
January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit
FIRE SAFETY PLAN FOR KITCHENER, ONTARIO
FIRE SAFETY PLAN FOR KITCHENER, ONTARIO Additional information of fire safety plans may be found at our website at www.kitchener.ca/fire.htm. Before submission, please read and change all sections to address
Required Certification Documentation. Contractor's installation certification for range hood fire suppression systems.
OFFICE OF UNIVERSIT BUILDING OFFICIAL PROJECT/CONSTRUCTION MAGER: Sample Manager Required Aboveground only Required Certification Documentation Contractor s material and test certifications for both above
(Single Stage Fire Alarm System)
1 Fire Safety Plan (Single Stage Fire Alarm System) Fire Safety Plan Single Stage Fire Alarm System for: (Business Name) (Business Address) Signature of Individual Responsible For Implementing this Fire
Environment of Care Fire Safety Management Plan 2014
Environment of Care Fire Safety Management Plan 2014 Updated 4.29.2014 PURPOSE The purpose of the Fire Safety Management Plan is to ensure that all facilities are designed, constructed, maintained, and
Fire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS
Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
Inspection, Testing and Maintenance
Page 18 ABOUT CODE CORNER CCFS would like to remind you to check with your local Authority Having Jurisdiction (AHJ) for questions and opinions concerning your local Fire and Building Codes. The information
FIRE-FIGHTING DESIGN BRIEF REPORT
P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM
Fire Safety Plan University Stadium
Fire Safety Plan University Stadium Building # 53 Safety, Health, Environment Effective: March 14, 2018 Revised: December 2014 Revision: 1 Approved on: Pending Approval WILFRID LAURIER UNIVERSITY Contact:
presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Monday, 17 June, 13
presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Who is the AFSA? Safe and Secure Alberta Fire Safety Association Fire industry members working together to improve
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT
SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection
PART 1 FIRE SAFETY PLAN
Fire Safety Plan This sample fire safety plan has been developed to help owners and managers of small apartment buildings maintain compliance with Section 2.8 of the B.C. Fire Code. The plan is intended
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS. 1. All Floors (inspect from top floor to basement): Yes No
General Inspection FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS 1. All Floors (inspect from top floor to basement): Yes are fire exits and directional signs properly illuminated? is the emergency
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS The attached self-inspection form is intended for staff use at regular, frequent intervals. It should not take the place of two other vital measures
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
Overview of Hotel Fire Safety Requirements
Overview of Hotel Fire Safety Requirements in the Fire Code Susan Clarke, P.Eng. Office of the Fire Marshal - January 10, 2012 1 Agenda Regulation History - Hotels Fire Code Overview (Parts 1 to 8) Defined
Minnesota State Department of Public Safety
Minnesota State Department of Public Safety 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/215-0500 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us Inspection
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result
FIRE SAFETY PLAN FOR SMALL ASSEMBLY FACILITIES
Insert Picture of Building FIRE SAFETY PLAN FOR SMALL ASSEMBLY FACILITIES Address: Lock Box Location: Fire Safety Plan Location: Approved: Fire Department (dd /mm/yyyy) Building Owner (dd /mm/yyyy) Reviewed
EXHIBIT A SCOPE OF WORK
EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,
Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL
HERNANDO COUNTY FIRE ALARM GUIDELINES
HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a
Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application
February 2014 Code Requirements and Inspections in Educational Occupancies Presented By: Barry W. Rickert Douglas M. Schanne Fire Marshal Training Program Supervisor Office of Education & Data Management
Safe Operating Procedure
Safe Operating Procedure (Revised 07/09) HOT WORK PERMIT OPERATIONS (For assistance, please contact EHS at (402) 472-4925, or visit our web site at http://ehs.unl.edu/) Authority In recognition of the
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or
Spray Booth Guideline
Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that
EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM
EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM REGULATORY STANDARD: OSHA - 29CFR1910.36-29CFR1910.38-29CFR1910.157-29CFR1910.165 NFPA-10 BASIS: The OSHA Emergency Action Planning and the
CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning
CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning Presentation To: Canadian Fire Alarm Association (CFAA) Alberta Technical Seminar
FIRE SAFETY PROCEDURES
FIRE SAFETY PROCEDURES No: Category: Name: Subject: Effective/Version Date: Page: 1 of 20 1.0 PURPOSE The purpose of this procedure is to define the business processes by which (Housing Provider) will
Fire Alarm Log Book. Any activity regarding this system must be documented in writing.
CASTLE ROCK FIRE AND RESCUE DEPARTMENT 300 Perry Street Castle Rock, Colo. 80104 303-660-1066 Do not remove from the premises: Fire Alarm Log Book Any activity regarding this system must be documented
EXETER TOWNSHIP DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS
DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS POLICY STATEMENT This policy applies to NEW Dry or Wet chemical fire suppression systems. The Authority Having Jurisdiction will not waive major criteria in
Fire Safety Plan (No Fire Alarm System):
Fire Safety Plan (No Fire Alarm System): Fire Safety Plan No Fire Alarm System for: (Business Name) (Business Address) I,, have read and understand my responsibilities under this Fire Safety Plan. Signature
The Basics of Commercial Kitchen Exhaust Cleaning
The Basics of Commercial Kitchen Exhaust Cleaning ANSI/IKECA C 10 ANSI/IKECA C 10: Standard for Cleaning of Commercial Exhaust Systems IKECA Introduces the Kitchen Exhaust Cleaning Industry s First American
Emergency Evacuation Plan: 232 King St.
Emergency Evacuation Plan: 232 King St. Effective Date: July 2003 Revisions: 0 Approved on: April 20, 2004 Table of Contents 1.0 Building Resources... 1 2.0 Human Resources... 2 3.0 Definitions... 3 4.0
Commercial Fire Inspections
Commercial Fire Inspections Fire Department Inspection Requests and Procedures The following guidelines shall be used when calling for inspection requests: 1. All inspection requests shall be coordinated
DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION
Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier
Proposed Residential Complex At Holding No. - 98, B.T. Road, Kolkata - 700090 Developer Premier Mica Mining And Manufacturing Company
RISK MANAGEMENT PLAN is an integral part of a modernized and sophisticated residential complex. No efforts will be spared in identifying the all possible risks and disasters, evaluating them, installing
Program No. 1.6.1. Section Heading
ENVIRONMENTAL HEALTH AND SAFETY EHS PROGRAM MANUAL Program Title 1.0 INTRODUCTION The New York City Fire Department (FDNY) is responsible for approving and/or inspecting fire alarm systems, buildings,
City of Bettendorf Fire Alarm System Requirements
City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section
Risk Control Bulletin Inspection, Testing & Maintenance (ITM) of Water-Based Fire Protection Systems
Risk Control Bulletin Inspection, Testing & Maintenance (ITM) of Water-Based Fire Protection Systems Introduction Fire protection systems are provided in or at a building to safeguard the lives of building
Bold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted
Inspection, Testing and Preventive Maintenance
Fire Protection Systems and Equipment Introduction HSB Professional Loss Control Two Crossroads Drive Bedminster, NJ 07921 1-800-472-1866 www.hsbplc.com The owners and operators of industrial plants, shopping
Fire Alarm System Plans Review Checklist Property location Date of Review
Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include
FIRE PREVENTION & INVESTIGATION DIVISION 125 Idylwyld Drive South Saskatoon, SK S7M 1L4 Phone: (306) 975-2578 Fax: (306) 975-2589.
FIRE PREVENTION & INVESTIGATION DIVISION 125 Idylwyld Drive South Saskatoon, SK S7M 1L4 Phone: (306) 975-2578 Fax: (306) 975-2589 Bulletin 17-12 Fire Safety Plan The purpose of this bulletin is to assist
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the
Notes. Material 1. Appropriate Flammable Liquids
29 CFR 1910.106 Flammable Materials Flammable Liquids Preparation 1. Read Applicable Background information and related Company Policy Chapter. 2. Make Copies of this Lesson Plan for Personnel 3. Make
2007 ICC FINAL ACTION AGENDA
907.2.1.1 System initiation in Group A occupancies with an occupant load of 1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal
FIRE CODE INTERPRETATION
FIRE CODE INTERPRETATION February 2014 FCI-14-02 Page 1 of 6 ISSUE: Fixed Fire Suppression & Exhaust Systems Cooking A number of queries from owners, designers and safety codes officers have been received
F.Y.I. Specifying Fire Protection Systems Using Division 13
F.Y.I. Specifying Fire Protection Systems Using Division 13 Automatic fire sprinkler systems and fire alarm and detection systems are increasingly installed in modern buildings. Even where building codes
Restaurant & café guide
'Helping our customers stay in business by reducing risk' NZI Risk Solutions TM About NZI Risk Solutions NZI has extensive experience in providing expert risk management advice to help our commercial customers
Life Safety Code Enabling References
SUPPLEMENT 4 Life Safety Code Enabling References Editor s Note: Supplement 4 provides users of NFPA 72, National Fire Alarm and Signaling Code, with a summary of requirements from NFPA 101, Life Safety
Rancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent
Building Permit Application
Building Permit Application Administrative Use Only PARENT PERMIT NUMBER (Required if part of another project) PERMITTEE: PERMITTEE ADDRESS: E-MAIL ADDRESS: ARCHITECT/ENGINEER: PHONE: PHONE: ARCHITECT/ENGINEER
Inspection and Testing Program Fire Protection Equipment
I. Introduction Inspection and Testing Program Fire Protection Equipment State of Minnesota Emergencies seldom give warning before they strike. Thus, it is essential that fire protection equipment be inspected,
c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.
Walmart Standards for Suppliers Section 7. Health and Safety 7. Health and Safety Suppliers must provide workers with a safe and healthy work environment. Suppliers must take proactive measures to prevent
city of edmonds development information
#B17 city of edmonds development information Commercial Kitchen Hood & Hood Fire Suppression System Permit Submittal Requirements PERMIT REQUIRED: CODES: FEES: A Commercial Kitchen Hood Mechanical Permit
CANTON FIRE DEPARTMENT
CANTON FIRE DEPARTMENT Dean Floyd Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES FIRE PREVENTION CHECKLIST- To review prior to your inspection. 1. Is the address of your property
ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600
OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done
UNIFIED FACILITIES CRITERIA (UFC) OPERATION AND MAINTENANCE: INSPECTION, TESTING, AND MAINTENANCE OF FIRE PROTECTION SYSTEMS
UNIFIED FACILITIES CRITERIA (UFC) OPERATION AND MAINTENANCE: INSPECTION, TESTING, AND MAINTENANCE OF FIRE PROTECTION SYSTEMS APPROVED FOR PUBLIC RELEASE; DISTRIBUTION UNLIMITED UNIFIED FACILITIES CRITERIA
Fire Alarm and Protection Impairment Policy and Procedures
1.0 Policy Statement The University of New Haven has developed a Fire Alarm and Protection Impairment Plan in accordance with the National Fire Protection Associations (NFPA) codes. Specific codes referenced
Automatic Fire Sprinkler Submittal Requirements
Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance
Module 4, Lesson 12 Fire Alarm Systems
Student Manual Module 4, Lesson 12 Fire Alarm Systems Performance Objectives At the conclusion of this lesson, you will be able to: Identify the components and functions of a fire alarm system and determine
Health Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE
Health Chapter 420-5-22 ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE CHAPTER 420-5-22 SUBMISSION OF PLANS AND SPECIFICATIONS FOR HEALTH CARE FACILITIES TABLE OF
FIVE YEAR CERTIFICATION REPORT
GARDEN GROVE FIRE DEPARTMENT FIRE PREVENTION DIVISION FIVE YEAR CERTIFICATION REPORT Service and maintenance report of automatic fire extinguishing systems, including fire sprinklers, dry, deluge, and
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions
FIRE PROTECTION SYSTEMS
CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall apply to the inspection, operation, testing and maintenance of all fire protection systems. 901.2.
Manual Document Page Issue Date TABLE OF CONTENTS
, Manual USQ #15-1163-D ESHQ 1 of 23 TABLE OF CONTENTS 1.0 PURPOSE AND SCOPE... 2 2.0 IMPLEMENTATION... 2 3.0 STANDARD... 2 3.1 Facility Management Support Requirements... 3 3.2 Fire System Discrepancy
Fire Alarm System Monitoring - CAN/ULC-S561-03
Fire Alarm System Monitoring - CAN/ULC-S561-03 Brian McBain ULC Regulatory Services May 4, 2011 Copyright 1995-2007 Underwriters' Laboratories of Canada. All rights reserved. No portion of this material
FIRE PROTECTION SYSTEMS ACCEPTANCE INSPECTION AND TESTING PROCEDURE
ACCEPTANCE INSPECTION AND TESTING PROCEDURE Wet Pipe Sprinkler Systems...2 Dry Pipe Sprinkler Systems...2 Clean Agent Fire Extinguishing System...4 Total Flooding Systems...4 Fire Dampers...5 Smoke Dampers...5
ELECTRICAL EMERGENCY SYSTEM PLAN REVIEW OVERVIEW OF CODE REQUIREMENTS
ELECTRICAL EMERGENCY SYSTEM PLAN REVIEW What to Look for during Plan Review OVERVIEW OF CODE REQUIREMENTS First determine the type of emergency power system; is the system designed for Emergency or Legally
Inspection and Testing of Water-Based Systems
Inspection and Testing of Water-Based Systems Standard Model/Computer-Based Testing Level III Content Outline The candidate for NICET certification at Level III in the Inspection and Testing of Water-Based
UNIVERSITY OF TOLEDO
UNIVERSITY OF TOLEDO SUBJECT: INTERIM LIFE SAFETY MEASURES AND INFECTION Procedure No: LS-08-008 CONTROL PROCEDURE STATEMENT Interim life safety and infection control measures will be implemented to protect
FIRE ALARM AND DETECTION SYSTEMS SECTION 16721
PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected
Fire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
A. Fire Protection Plan. B. Access and Parking
Standards for Construction Site Fire Safety For Use by Unidocs Member Agencies or where approved by your Local Jurisdiction Authority Cited: California Fire Code (CFC) These standards are intended to prescribe