Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Size: px
Start display at page:

Download "Rancho Cucamonga Fire Protection District Prevention Bureau Standard"

Transcription

1 Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent of this standard is to provide regulations consistent with local needs for the installation, repair, modification, inspection, testing, and maintenance of fire alarm systems, sprinkler waterflow and supervisory systems, and the devices and programming associated with these systems. AUTHORITY This standard is in accordance with RCFPD Ordinance FD 54, the 2013 California Fire Code, and the applicable Standards of the National Fire Protection Association (NFPA). DEFINITIONS The terms used in this standard are intended to be consistent with the Building Code, the Fire Code, NFPA 72, and state regulations and have the same definitions as the definitions contained in those documents. ADOPTED STANDARD 1. General Automatic and/or manual fire alarm systems and sprinkler waterflow and supervisory systems shall be designed, installed, inspected, tested, and maintained in accordance with the provisions of the Fire Code, NFPA 72, and this standard. 2. Combination Systems a. Combination systems shall be in accordance with the Fire Code and NFPA 72. Exception: Burglar/intrusion security system features and/or devices shall not be integrated with fire alarm systems or sprinkler waterflow and supervisory systems. b. Burglar/intrusion alarm systems shall not include fire detection and/or notification features or devices unless the system control unit and all devices are listed by the State Fire Marshal for fire alarm use. c. Previously approved combination fire alarm or sprinkler waterflow and supervisory systems that contain security system features and/or devices may remain in service if: i. The security devices and the control unit have been approved by the State Fire Marshal as fire alarm system components, and ii. The burglar/intrusion devices and/or features do not cause false or unwanted fire alarms. d. Required alterations to a previously approved combination system shall be in accordance with Item 7 of this standard. RCFPD Standard #

2 3. Detectors a. Automatic fire detectors installed for the protection of the fire alarm system control unit or sprinkler waterflow and supervisory system control unit shall be combination fixed temperature and rate of rise heat detectors where ambient conditions are such that the installation of smoke detectors could reasonably be expected to result in false alarms. For example, when the system control unit is installed in a room required by Section 509 of the Fire Code as amended, a heat detector shall be installed for the protection of the system control unit. b. To comply with the Fire Code s notification requirements for duct detectors installed in occupancies that do not require a fire alarm system, duct detectors may be connected to a sprinkler waterflow and supervisory system. c. When monitored by the system control unit, duct detectors shall be provided with remote annunciator lamps and remote test switches located on the ceiling or wall in the vicinity of the detector. d. Unless otherwise required by the Building Code, the Fire Code, NFPA 72, or other state regulation, the activation of a duct detector shall cause a supervisory signal only. Such signals shall be consistent with the provisions of NFPA 72 for supervisory signals. e. All smoke and heat detectors, including those installed for elevator recall, door release service, and/or smoke spread control, shall be installed and function in accordance with the Fire Code and NFPA Elevator Recall a. Elevator recall shall be in accordance with the Building Code, the Fire Code, applicable state regulations, and NFPA 72. b. In buildings without a fire alarm system, elevator recall service shall not be provided by the sprinkler waterflow and supervisory system. A separate elevator recall control and supervisory control unit shall be provided for elevator recall service. 5. Identification of Alarm Zones and Device Locations a. A diagram that corresponds to the floor plan for the building or space in which a monitored system is installed shall be posted in a conspicuous and readily accessible location acceptable to the fire code official. This diagram shall identify the location of each system component and shall use the same identifying language that is programmed into the system for the individual zones and/or devices. See Item 10 below. Existing diagrams will need to be updated when fire alarm systems are modified. b. Doors providing access to rooms or areas where the fire alarm control unit is located shall be labeled FACU Inside. For exterior doors, this identification shall consist of a permanent, weather-resistant sign or letters. The lettering shall be at least three inches in height. Signs shall have a red background with white lettering. Adhesive or stenciled letters are typically red but can be any color approved by the fire code official which contrasts with the color of the door or door glazing. Interior doors shall be identified in a manner acceptable to the fire code official. 6. Inspection, Testing, and Maintenance a. Upon completion of any repairs and/or modifications for which a permit was required and issued, the contractor shall provide the fire code official with a record of completion that is equivalent to the Fire Alarm and Emergency Communication System Record of Completion contained in NFPA 72. RCFPD Standard #

3 b. Inspection, testing, and maintenance of fire alarm and sprinkler waterflow and supervisory systems shall be in accordance with the Fire Code and the applicable NFPA standards. c. Inspection, testing, and maintenance shall be performed only by personnel who meet one or more of the service personnel qualifications found in NFPA 72. d. Prior to commencing any inspection, testing, and/or maintenance, the supervising station shall be notified that authorized work is being performed on the system and that alarm signals received at the supervising station shall not be transmitted to the Fire Dispatch Center until such time that the supervising station has been notified that the work on the system is completed. Building occupants shall also be notified prior to and after the completion of authorized work. Failure to notify the supervising station prior to commencing work on a system will result in the contractor being billed for the cost of any responses to alarms transmitted by the supervising station. Only the supervising station shall be notified of authorized work on the system. Service personnel are not authorized to contact the Fire Dispatch Center. Contacting the Fire Dispatch Center for non-emergency reasons will result in the service person being billed for the cost of a non-emergency call for service to the dispatch center. e. Personnel performing required inspections, testing, and maintenance shall provide the fire code official with a report that is equivalent to the Fire Alarm and Emergency Communication System Inspection and Testing Form contained in NFPA 72 or the Fire District s Fire Alarm Service/Test Report. f. Acceptance test reports shall include a copy of the supervising station s activity report for the protected premise. This report shall include the entire time period of the acceptance test. 7. Installation, Alteration, or Replacement of Equipment a. As required by the Fire Code and NFPA 72, the fire code official shall be notified, by means of a plan submittal, of all installations of and alterations to a fire alarm system or sprinkler waterflow and supervisory system. Plan submittals shall be in accordance with Appendix A of this standard. b. Plans shall be submitted and approved when it is necessary to replace a fire alarm control unit. When approved by the fire code official, emergency replacement of a fire alarm control unit can precede the submittal of as-built documents. c. Documentation satisfactory to the fire code official shall be provided when obsolescence or similar circumstances require the installation of replacement detection, initiating, and/or notification devices that differ from the originally installed devices. d. Upon completion of an installation, alteration, or replacement of equipment that required a permit, the contractor shall provide the fire code official with a record of completion that is equivalent to the Fire Alarm and Emergency Communication System Record of Completion contained in NFPA Large Family Day Care The fire alarm signaling equipment required by the Fire Code to be installed in a large family day care shall consist of a manual fire alarm box that when operated activates an electrically powered horn or bell notification device. These devices do not need to be interconnected with any other fire alarm device or system, do not require a control unit, do not need to be electrically supervised, and do not need emergency power. The manual fire alarm box and the notification device shall be attached to the structure. An electrical permit issued by the Building & Safety Department is required to install this fire alarm signaling equipment. RCFPD Standard #

4 9. Manual Fire Alarm Boxes and Protective Covers a. Manual fire alarm boxes shall not be installed on sprinkler waterflow and supervisory systems or elevator recall control systems. b. When the Fire Code allows the elimination of manual fire alarm boxes due to the installation of fire sprinklers, manual fire alarm boxes shall not be installed. c. In existing buildings that are protected throughout with a fire sprinkler system, manual fire alarm boxes may be removed upon approval of the fire code official if the current Fire Code would not otherwise require the installation of manual fire alarm boxes. d. Listed, non-alarming manual fire alarm box protective covers conforming to the specifications of the Fire Code shall be installed over all new manual fire alarm boxes. e. Listed, non-alarming manual fire alarm box covers shall be installed over existing manual fire alarm boxes when in the opinion of the fire code official such boxes are in locations that make nuisance and unwanted alarms likely or when there is a history of false or unwanted alarms originating from a manual fire alarm box. 10. Monitoring a. Monitoring of fire alarm systems, fire sprinkler systems, standpipe systems, alternative automatic fire extinguishing systems, fire extinguishers, elevator recall, smoke detection systems, partial or selective systems, and non-required systems shall be in accordance with the Fire Code and NFPA 72. b. All monitored systems shall include visible annunciation acceptable to the fire code official. Systems installed after the effective date of this standard shall utilize alphanumeric display visible annunciation. Systems shall be designed, installed, and programmed such that all signals from all components report (describe/identify) the exact location of the component or device. This can be accomplished by the use of addressable devices and a compatible control unit or point-specific control units that are limited to a single device per point or zone. c. Monitoring shall be performed by a listed central station service or by a qualified remote supervising station that meets all of the criteria in NFPA 72. A proprietary supervising station may provide the required monitoring when approved by the fire code official. 11. Notification Delay Features The inclusion and/or enabling of a pre-signal feature, positive alarm sequence, and/or alarm verification shall be approved by the fire code official. 12. Annunciation a. Annunciation in multi-tenant buildings without a main entrance or common lobby shall be provided by the control unit. In cases where the control unit is not capable of annunciation and device identification as required by Item 10 of this standard, a remote annunciator with such capability shall be provided in the proximity of the control unit. b. Remote annunciators shall be capable of providing the device-specific information required by Item 10 of this standard (see above). c. Remote annunciation shall be provided near the main entrance to single-tenant buildings. d. Remote annunciation shall be provided near the main entrance or common lobby of multitenant buildings. 13. Emergency Service An emergency, on-demand service capable of responding to requests by the fire code official for resetting, troubleshooting, maintaining, repairing, or servicing a monitored system shall be provided by or contracted to a fire alarm service - local company. Emergency service shall include, RCFPD Standard #

5 as a minimum level of service, one or more qualified technicians available 24 hours a day who are capable of responding to alarm and supervisory signals within two hours of a request by the fire code official and capable of responding to trouble signals within four hours of a request by the fire code official. 14. Silencing and Resetting a. In Group A, E, I, R-1, and R-2 occupancies, silencing and/or resetting the system shall be accomplished by a key-operated switch or other similar method acceptable to the fire code official that provides equivalent protection against unauthorized silencing and/or resetting. b. Copies of keys and/or special tools required to access and/or reset system components are required to be locked in the Knox Box. These keys and/or tools shall be made available to the fire code official at the time of the acceptance test. c. A fire department reset code shall be programmed into each monitored system. The reset code shall be An additional 1 shall be included at the end of the reset code for each additional digit beyond four that is required to reset the system. d. Reset instructions shall be posted in a location that is readily accessible to Fire District personnel. This provision does not imply a requirement for the reset instructions to be posted in a location accessible to the public. e. Reset instructions shall include all information necessary to completely reset the system and all features, devices, and components of the system. Reset instructions that are posted in publicly accessible locations should not include reset codes. 15. Third Party Verification The installing contractor of a new fire alarm system or sprinkler waterflow and supervisory system shall provide a verification of compliant installation as allowed by NFPA 72. The fire code official may require third party verification for additions, alterations, and/or modifications to a previously approved fire alarm system depending on the extent and nature of the permitted work. Acceptable verifications are UL Certification, FM Certificate of Compliance, or written verification by an independent third-party acceptable to the fire code official. This provision does not imply a requirement to maintain such verification beyond its initial expiration date. RCFPD Standard #

6 Appendix A Rancho Cucamonga Fire Construction Services Fire Alarm Submittal Information 1. General: a. An acceptable submittal package is four (4) sets of plans and two (2) sets of submittal documents required herein and/or by the Standard. Documents with date restrictions must be current. b. Documents that must be submitted with the plans include, but are not limited to: i. Manufacturer s cut sheets for all equipment and devices. ii. Verification of California State Fire Marshal listing for all equipment and devices. c. Documents required to be submitted in order to obtain a final approval include but are not limited to: i. A diagram that corresponds to the floor plan for the building or space in which a monitored system is installed. This diagram shall identify the location of each system component. See Item 5 in the Standard. The minimum acceptable size of this diagram is 8 ½ inches by 11 inches. More detailed diagrams or diagrams of large facilities may need to be larger so that the diagram is legible. The diagram will be posted in a location acceptable to the fire code official. Existing diagrams will need to be updated when fire alarm systems are modified. ii. Instructions for contacting and requesting the emergency, on-demand service required by Item 13 of the Standard. iii. Silencing and reset instructions in accordance with Item 14 of the Standard. iv. Third party verification in accordance with Item 15 of the Standard. v. A document comparable to the Fire Alarm System Record of Completion contained in NFPA 72. vi. A copy of the supervising station s activity report for the acceptance test. This report shall include the entire time period of the acceptance test. d. The system designer and the system installer are required to have a current fire alarm permit issued by RCFPD. If the designer and/or installer do not already have this permit, a permit must be issued by the fire code official before plan submittals will be accepted. Contact the Prevention Bureau at with any question about this permit. 2. Each set of plans must contain the following information: a. The legal business name, business address, telephone number, license class, and license number of the system designer and the system installer (when the system installer is not the system designer). addresses are desirable but nor required. b. Scope of Work This statement needs to be conspicuously located on the plans and needs to clearly explain the proposed work. In some cases it may be necessary to explain what work is not proposed so that that Scope of Work is clear. c. Notes referencing which codes and versions of the code are being applied to the design and installation. d. Sequence of Operation chart. e. Complete battery calculations and/or details on how secondary power will be provided. f. Building information to include the construction type, number of floors, total square footage, occupancy classification(s), occupant load(s), etc. g. Single line diagram. h. Point to Point diagram. i. The floor plan diagram required in Item 1c.i above needs to be reproduced on the plans in addition to being submitted as a separate document. j. A complete legend that identifies the quantity, type, function, and California State Fire Marshal listing of each component and device. Continues on the Next Page RCFPD Standard #

7 3. The following notes need to be provided verbatim on the plans: a. Unless otherwise required by the Building Code, the Fire Code, NFPA 72, or other state regulation, the activation of a duct detector shall cause a supervisory signal only. Such signals shall be consistent with the provisions of NFPA 72 for supervisory signals. b. Knox Boxes are not required to be electrically supervised. c. All junction boxes (J-boxes) used for the fire alarm system or sprinkler waterflow and supervisory system shall be painted red and marked with the words fire alarm. d. Batteries must be marked by the manufacturer with the month and year of manufacture. The date of installation must be indicated on the battery. e. Exterior doors providing access to the control unit shall be labeled with the wording FACU Inside. This identification shall consist of a permanent, weather-resistant sign or letters. The lettering shall be at least three inches in height. Signs shall have a red background with white lettering. Adhesive or stenciled letters are typically red but can be any color approved by the fire code official which contrasts with the color of the door or door glazing f. Interior doors providing access to the control unit shall be identified in a manner acceptable to the fire code official. g. The circuit breaker protecting the circuit that powers the control unit shall be equipped with an approved lock-out device. The location of the circuit breaker shall be indicated at the control unit in a manner acceptable to the fire code official. h. The telephone connections or other communication equipment, including the phone numbers assigned, shall be identified in a manner acceptable to the fire code official. i. Third party verification shall be presented at the time of the acceptance test. j. RCFPD labels reminding service technicians to contact the supervising station prior to commencing service or repair work shall be installed on devices in locations specified by the fire code official. k. Copies of keys and/or special tools required to access and/or reset system components are required to be locked in the Knox Box. These keys and/or tools shall be made available to the fire code official at the time of the acceptance test. l. Listed and approved protective covers shall be installed over every manual fire alarm box. Protective covers shall be in accordance with the Fire Code. Covers that emit a local alarm are prohibited unless specifically approved by the fire code official. m. Fire alarm and sprinkler waterflow supervisory systems shall not be placed in service until the acceptance test is completed and the fire code official has given final approval of the system. 4. Plan Review Times and Requirements: a. The first submittal turn around time is approximately 10 working days. The turn around time for the second and subsequent submittals is approximately 5 working days. Working days are Monday through Thursday excluding holidays. b. At the time of plan check submittal, a Permit Application Worksheet must be completed by the submitting contractor. c. Permit and plan check fees, except for expedited service, are based on the type of system and the number of devices. d. Expedited plan check requests shall be made in writing and approved prior to the plans being submitted. The cost of expedited plan checks will be the actual fully burdened cost of the service based on the time required to complete the plan check. e. Question regarding plan submittals or plan checks and requests for inspections or acceptance tests should be directed to Fire Construction Services at Business hours are Monday through Thursday 7:00 a.m. to 6:00 p.m. Voice mail is available 24 hours. RCFPD Standard #

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted

More information

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions

More information

Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines

Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Red Oak Fire Rescue Office of the Fire Marshal 547 N. Methodist Red Oak, TX 75154 Phone: 469-218-7713 Fax: 468-218-7719

More information

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY

More information

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,

More information

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. Protected Property Information Name of property: Description

More information

Fire Alarm System Plans Review Checklist Property location Date of Review

Fire Alarm System Plans Review Checklist Property location Date of Review Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include

More information

FIRE ALARM APPLICATION

FIRE ALARM APPLICATION FIRE ALARM APPLICATION ENUMCLAW FIRE DEPARTMENT 1330 Wells St, Enumclaw, WA 98022 Phone: 360-825-5544 Fax: 360-825-9442 COMMUNITY DEVELOPMENT, BUILDING DEPARTMENT 1309 Myrtle Ave Enumclaw WA 98022 Phone:

More information

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 1.1 To acquire an installation

More information

City of Bettendorf Fire Alarm System Requirements

City of Bettendorf Fire Alarm System Requirements City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section

More information

HERNANDO COUNTY FIRE ALARM GUIDELINES

HERNANDO COUNTY FIRE ALARM GUIDELINES HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a

More information

Module 4, Lesson 12 Fire Alarm Systems

Module 4, Lesson 12 Fire Alarm Systems Student Manual Module 4, Lesson 12 Fire Alarm Systems Performance Objectives At the conclusion of this lesson, you will be able to: Identify the components and functions of a fire alarm system and determine

More information

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL

More information

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:

More information

Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14

Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14 North Collier Fire Control & Rescue District Greater Naples Fire Rescue District Immokalee Fire Control & Rescue District 2800 North Horseshoe Drive Naples, Florida 34104 SYSTEM REHABILITATION PLAN CHECKLIST

More information

BELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM-10-011

BELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM-10-011 Fire Alarm System plan(s) MUST be reviewed and approved by the Belmont Fire Department prior to the start of construction. The design and any changes must be fully compliant with NFPA 1, NFPA 101, NFPA

More information

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according

More information

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM 1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this

More information

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION PERMITS AND INSPECTIONS FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION 911 Assigned PROJECT LOCATION Subdivision: Lot: Blk: Sec: PROJECT New Construction Addition/Remodel Demolition Other: Number

More information

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this

More information

Fire Alarm Systems Permit Packet. City of Greer Fire Department

Fire Alarm Systems Permit Packet. City of Greer Fire Department Fire Alarm Systems Permit Packet City of Greer Fire Department Updated July 2004 If you have any questions or comments regarding the information contained within; or of you need assistance interpreting

More information

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0

More information

Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007

Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 FIRE ALARM SYSTEMS POLICY TELLURIDE FIRE PROTECTION DISTRICT TABLE OF CONTENTS FIRE ALARM PROTECTION POLICY PLAN REVIEW SUBMITTAL

More information

University Design Standard. Fire Alarm Systems

University Design Standard. Fire Alarm Systems University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval. Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's

More information

Commercial Fire Alarm Standards July 1, 2010 Edition Page 1 of 14

Commercial Fire Alarm Standards July 1, 2010 Edition Page 1 of 14 City of Mercer Island Development Services Group Fire Code Review and Inspection 9611 SE 36 th Street Mercer Island, WA 98040-3732 PHONE (206) 275-7605 FAX (206) 275-7726 www.mercergov.org Commercial Fire

More information

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT The purpose of these specifications is to insure that there are minimum

More information

EXHIBIT A SCOPE OF WORK

EXHIBIT A SCOPE OF WORK EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,

More information

Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application

Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application PERMIT FEE: $ Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application PAYMENT TYPE: Check Credit Card Charge to Job #: (Please complete all of the

More information

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier

More information

Michael Catalano 24 Nassau Avenue, Islip NY 11751 Phone (631) 224-5477 Chief Fire Marshal fireprevention@islipny.gov Fax (631) 224-5458

Michael Catalano 24 Nassau Avenue, Islip NY 11751 Phone (631) 224-5477 Chief Fire Marshal fireprevention@islipny.gov Fax (631) 224-5458 OFFICE OF THE FIRE MARSHAL BUREAU OF FIRE PREVENTION Michael Catalano, Phone Chief Fire Marshal fireprevention@islipny.gov Fax To whom it may concern: Enclosed please find the NFPA 72 forms needed for

More information

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment

More information

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting

More information

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline

More information

Life Safety Code Enabling References

Life Safety Code Enabling References SUPPLEMENT 4 Life Safety Code Enabling References Editor s Note: Supplement 4 provides users of NFPA 72, National Fire Alarm and Signaling Code, with a summary of requirements from NFPA 101, Life Safety

More information

FIRE ALARM SYSTEM PLAN SUBMITTAL CHECKLIST

FIRE ALARM SYSTEM PLAN SUBMITTAL CHECKLIST FIRE ALARM SYSTEM PLAN SUBMITTAL CHECKLIST All fire alarm system plan submittals must include this Fire Alarm System Plan Submittal Checklist. PLAN APPROVAL - No work shall be performed until plans are

More information

Agenda. Agenda (continued) Fundamentals of Fire Alarm Systems

Agenda. Agenda (continued) Fundamentals of Fire Alarm Systems Fundamentals of Fire Alarm Systems Sponsored by UL SFPE Austin/San Antonio Chapter San Marcos, Texas 7 January 2015 Agenda Introduction and Administration Historical Context of Today s NFPA 72 Fire Alarm

More information

ENVIRONMENTAL HEALTH & SAFETY 6 East Dr., Amherst MA 01002-5000

ENVIRONMENTAL HEALTH & SAFETY 6 East Dr., Amherst MA 01002-5000 AMHERST COLLEGE ENVIRONMENTAL HEALTH & SAFETY 6 East Dr., Amherst MA 01002-5000 Michael Zlogar April 11, 2001 Assistant Fire Chief Amherst Fire Department 68 North Pleasant St. Amherst, MA 01004 FIRE ALARM

More information

FIRE SPRINKLER SYSTEM SUPERVISORY SERVICE User s Guide (DamarNet RAR Service)

FIRE SPRINKLER SYSTEM SUPERVISORY SERVICE User s Guide (DamarNet RAR Service) FIRE SPRINKLER SYSTEM SUPERVISORY SERVICE User s Guide (DamarNet RAR Service) The information provided in this user guide pertains to fire suppression sprinkler system monitoring service provided over

More information

2007 ICC FINAL ACTION AGENDA

2007 ICC FINAL ACTION AGENDA 907.2.1.1 System initiation in Group A occupancies with an occupant load of 1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal

More information

CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002

CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 Three new chapters were added. What was chapter 1 in 1999 was reorganized into chapters 1 (Fundamentals), 2 (Referenced Publications), and 3 (Definitions).

More information

PLAN REVIEW GUIDE FOR FIRE ALARM

PLAN REVIEW GUIDE FOR FIRE ALARM PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical

More information

C. Conform to requirements of Americans with Disabilities Act (ADA).

C. Conform to requirements of Americans with Disabilities Act (ADA). SECTION 28 31 00 - FIRE ALARM AND DETECTION SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire alarm and detection systems 1.2 REFERENCES A. NFPA 70 - National Electrical Code B. NFPA 72 - National

More information

How To Install A Carbon Monoxide Detector

How To Install A Carbon Monoxide Detector NASSAU COUNTY FIRE COMMISSION OFFICE OF THE FIRE MARSHAL Nassau County Public Safety Center 1194 Prospect Avenue Westbury, New York 11590 (516) 573-9900 / nassaucountyny.gov Chief Fire Marshal Scott D.

More information

FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY

FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY FVSU-33201301 REPAIR & UPGRADE FIBER OPTIC 280000-1 SECTION 280000 FIRE ALARM SYSTEM CONNECTIVITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Addressable interface

More information

NATIONAL FIRE ALARM AND SIGNALING CODE

NATIONAL FIRE ALARM AND SIGNALING CODE GAP.11.1.1.0 A Publication of Global Asset Protection Services LLC NATIONAL FIRE ALARM AND SIGNALING CODE INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection

More information

FIRE ALARM SYSTEMS INFORMATION PACKET

FIRE ALARM SYSTEMS INFORMATION PACKET FIRE ALARM SYSTEMS INFORMATION PACKET Exeter Township Fire Department Office of the Fire Official 2010 1 TABLE OF CONTENTS PURPOSE, SCOPE, DEFINITIONS...3 GUIDELINES...3 I. INTRODUCTION...3 A. APPLICABLE

More information

SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon)

SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon) SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon) SECTION SR101 GENERAL SR101.1 General. Group SR occupancies shall comply with the provisions of this appendix

More information

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS 527 CMR 24.00: FIRE WARNING SYSTEMS INSTALLED IN BUILDINGS WITHIN THE COMMONWEALTH OF MASSACHUSETTS Section 24.01: Purpose 24.02: Scope 24.03: Definitions 24.04: Approval of Design 24.05: Power Supply

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat

More information

REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING APPLICATION PACKET

REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING APPLICATION PACKET REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING FIRE ALARM SYSTEMS APPLICATION PACKET CITY OF NAPERVILLE 400 S EAGLE STREET NAPERVILLE, Il 60540 PHONE: 630.420.6070 FAX: 630.420.6657 Fire Alarm

More information

LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809

LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809 LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3 Fire

More information

Rhode Island State Fire Marshal Fire Protection Systems Narrative Reports. What is a Narrative Report?

Rhode Island State Fire Marshal Fire Protection Systems Narrative Reports. What is a Narrative Report? RHODE ISLAND DIVISION OF STATE FIRE MARSHAL 1951 Smith Street, North Providence, RI 02911 Telephone: (401) 383-7717 Fax: (401) 383-8879 John E. Chartier, EFO, CFI State Fire Marshal Rhode Island State

More information

Design Standards Fire Alarm Systems Division 13860 (1995 CMS); 283100 (2004 CMS) Amended Feb 2015

Design Standards Fire Alarm Systems Division 13860 (1995 CMS); 283100 (2004 CMS) Amended Feb 2015 Design Standards Fire Alarm Systems Division 13860 (1995 CMS); 283100 (2004 CMS) Amended Feb 2015 13860 (283100) FIRE ALARM SYSTEM The following standard shall be followed for the design of University

More information

General Fire Code Requirements Within Commercial Tenant Spaces

General Fire Code Requirements Within Commercial Tenant Spaces FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding

More information

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January 2014

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January 2014 Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January 2014 1.1 To acquire an installation

More information

The Evolution of Requirements for Supervising Station Alarm Systems

The Evolution of Requirements for Supervising Station Alarm Systems The Evolution of Requirements for Supervising Station Alarm Systems Fire Marshal s Association of Colorado January 18, 2013 Warren Olsen, CFPS CBCO FSCI wolsen@firesafetyfsci.com 1 Disclaimer: The comments

More information

Fire Alarm Submittal Requirements and Acceptance Testing

Fire Alarm Submittal Requirements and Acceptance Testing Lubbock Fire Marshal s Office 1601 Mac Davis Lane Lubbock, Texas 79401 806-775-2646 Fax 806-775-3508 fireprevention@mylubbock.us Fire Alarm Submittal Requirements and Acceptance Testing To all Registered

More information

SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM

SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM SECTION 16853 ZONED (DC LOOP) FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1

More information

Invitation to Bid FIRE ALARM & DETECTION SYSTEM

Invitation to Bid FIRE ALARM & DETECTION SYSTEM Invitation to Bid FIRE ALARM & DETECTION SYSTEM Responses to an Invitation to Bid will be received by the Purchasing Supervisor, Sumner County Board of Education, 1500 Airport Road, Gallatin, TN 37066

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM SECTION 16721 FIRE ALARM AND DETECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification

More information

FIRE ALARM /FIRE PROTECTION OUTAGE/IMPAIRMENT RESPONSE GUIDELINE

FIRE ALARM /FIRE PROTECTION OUTAGE/IMPAIRMENT RESPONSE GUIDELINE Page 1 of 10 FIRE ALARM /FIRE PROTECTION OUTAGE/IMPAIRMENT RESPONSE GUIDELINE SYSTEM TESTING 1. Testing of the Fire Alarm and Fire Protection Systems 1.1. The Building Engineer, Electrician, Plumber (or

More information

FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual

FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual P/N 315-049403-1 Siemens Building Technologies Fire Safety Table Of Contents Introduction...1 The Access levels...1 User Level...1 Maintenance

More information

FIRE DETECTION AND ALARM

FIRE DETECTION AND ALARM Scope Provide a fire alarm system, or expand the existing system, as required by Code, the requirements in the Special Instructions to Designers (SID) of the Design Guidelines, and/or as noted in the Program

More information

CHAPTER 8. Village of Caledonia Alarm Systems Ordinance (2013-11 07/01/13)

CHAPTER 8. Village of Caledonia Alarm Systems Ordinance (2013-11 07/01/13) CHAPTER 8 Village of Caledonia Alarm Systems Ordinance (2013-11 07/01/13) Section Title Number 5-8-1 Title 5-8-2 Declaration of Purpose 5-8-3 Definitions 5-8-4 Administrative Rules 5-8-5 Supervised Fire

More information

ORDINANCE REGARDING ALARMS IN THE TOWN OF PLAINVILLE

ORDINANCE REGARDING ALARMS IN THE TOWN OF PLAINVILLE ORDINANCE REGARDING ALARMS IN THE TOWN OF PLAINVILLE SECTION I. PURPOSE AND INTENT. The purpose of this ordinance is to encourage Alarm Users and Alarm Businesses to maintain the operational reliability

More information

FIRE ALARM PLAN REVIEW. Office of the State Fire Marshal Massachusetts Department of Fire Services December 2009

FIRE ALARM PLAN REVIEW. Office of the State Fire Marshal Massachusetts Department of Fire Services December 2009 FIRE ALARM PLAN REVIEW Office of the State Fire Marshal Massachusetts December 2009 SURPRISE QUIZ 1. A fire alarm system is required to be installed by the MSBC, what edition of NFPA 72 do you use? 2.

More information

Mobile Fire Rescue Department Bureau of Fire Prevention

Mobile Fire Rescue Department Bureau of Fire Prevention 222 Mobile Fire Rescue Department Bureau of Fire Prevention Samuel L. Jones Mayor Stephen A. Dean Fire Chief February 2011 2009 International Fire Code Fire Alarm and Detection Systems 907.1 General. This

More information

Program No. 1.6.1. Section Heading

Program No. 1.6.1. Section Heading ENVIRONMENTAL HEALTH AND SAFETY EHS PROGRAM MANUAL Program Title 1.0 INTRODUCTION The New York City Fire Department (FDNY) is responsible for approving and/or inspecting fire alarm systems, buildings,

More information

Fire Alarm System Monitoring - CAN/ULC-S561-03

Fire Alarm System Monitoring - CAN/ULC-S561-03 Fire Alarm System Monitoring - CAN/ULC-S561-03 Brian McBain ULC Regulatory Services May 4, 2011 Copyright 1995-2007 Underwriters' Laboratories of Canada. All rights reserved. No portion of this material

More information

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 KNOXVILLE, TENNESSEE SECTION 16050 PAGE 1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 16050 A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1

More information

Fire Alarm System Submissions

Fire Alarm System Submissions Gypsum Fire Protection District Fire Alarm System Submissions As of July 1 st, 2007 all Fire Alarm Submissions will be required to be signed by a NICET Level 3 or higher. Fire Alarm System Submissions

More information

1.0 General. Inspection, Testing, and Maintenance 1 of 8

1.0 General. Inspection, Testing, and Maintenance 1 of 8 1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus

More information

Module 5. Fire and Emergency Alarm System Part I- Basics

Module 5. Fire and Emergency Alarm System Part I- Basics Module 5 Fire and Emergency Alarm System Part I- Basics 1 This module will describe: 1. Components and the arrangements of components in fire and emergency alarm systems. 2. How these systems work. 3.

More information

STATEMENT OF WORK FOR FIRE ALARM SYSTEM TESTING & MAINTENANCE. Project No. SAQMMA-07-C0060 ***OUAGA, BURKINA FASO***

STATEMENT OF WORK FOR FIRE ALARM SYSTEM TESTING & MAINTENANCE. Project No. SAQMMA-07-C0060 ***OUAGA, BURKINA FASO*** STATEMENT OF WORK FOR FIRE ALARM SYSTEM TESTING & MAINTENANCE Project No. SAQMMA-07-C0060 ***OUAGA, BURKINA FASO*** CONTENTS: 1.0 Introduction 2.0 Objectives 3.0 General Requirements 4.0 Specific Requirements

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

OBOA 2009 Huntsville, ON Overview of ULC Standards Affecting Building Occupancy Alan Cavers Area Manager Fire & Security Systems Group

OBOA 2009 Huntsville, ON Overview of ULC Standards Affecting Building Occupancy Alan Cavers Area Manager Fire & Security Systems Group OBOA 2009 Huntsville, ON Overview of ULC Standards Affecting Building Occupancy Alan Cavers Area Manager Fire & Security Systems Group Course Title: Rev Date Agenda Introduction to Underwriters Laboratories

More information

NFPA 72. Exception No. 1: Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted.

NFPA 72. Exception No. 1: Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted. NFPA 72 3.3.7.2 3.3.7.2 False Alarm. Activation or reporting of an alarm for which no such alarm condition, fire or emergency actually exists. Additionally, False Alarm is the willful and knowing initiating

More information

1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri.

1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. GENERAL: 1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. 2. Fire alarm systems are Life Safety Systems

More information

CBD-233. Fire Alarm and Detection Systems

CBD-233. Fire Alarm and Detection Systems Page 1 of 5 CBD-233. Fire Alarm and Detection Systems Originally published August 1984. R.H.L. McEwen Fire alarm systems are normally required by building codes. In the case of new buildings, this is usually

More information

TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS

TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS The following information regarding testing frequencies for fire detection and alarm systems. All of the following

More information

COMMONWEALTH OF MASSACHUSETTS STATE BUILDING CODE 780 CMR, 6 th Edition FIRE PROTECTION SYSTEMS CHAPTER 9

COMMONWEALTH OF MASSACHUSETTS STATE BUILDING CODE 780 CMR, 6 th Edition FIRE PROTECTION SYSTEMS CHAPTER 9 COMMONWEALTH OF MASSACHUSETTS STATE BUILDING CODE 780 CMR, 6 th Edition FIRE PROTECTION SYSTEMS CHAPTER 9 GUIDELINES FOR THE PREPARATION OF FIRE PROTECTION SYSTEM NARRATIVE REPORTS 780 CMR 903.1.1 State

More information

COMMISSIONING OF FIRE ALARM SYSTEMS

COMMISSIONING OF FIRE ALARM SYSTEMS COMMISSIONING OF FIRE ALARM SYSTEMS OWNER FURNISHED The owner directly contracts an independent third party commissioning agent for this project. This Commissioning Plan has been included for reference

More information

Request For Board Action

Request For Board Action Request For Board Action REFERRED TO BOARD: November 2, 2015 AGENDA ITEM NO: 7 ORIGINATING DEPARTMENT: Administration SUBJECT: Consideration of an Amendment to Village Code Section 9-6 relating to Emergency

More information

CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning

CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning Presentation To: Canadian Fire Alarm Association (CFAA) Alberta Technical Seminar

More information

2012 Ontario Building Code Changes Affecting Fire Alarm Systems

2012 Ontario Building Code Changes Affecting Fire Alarm Systems 2012 Ontario Building Code Changes Affecting Fire Alarm Systems CFAA Annual Technical Seminar May 31, 2013 Ken Baird VP Systems www.lrifire.com LRI 2010 Developments in Life Safety Introduction Code Development

More information

CHAPTER. Fire Alarm Systems APPROVAL AND ACCEPTANCE. Shop Drawings

CHAPTER. Fire Alarm Systems APPROVAL AND ACCEPTANCE. Shop Drawings Fire Alarm Systems CHAPTER 2 The information contained in this chapter is intended to assist the registered design professional (RDP), commissioning agent, authority having jurisdiction (AHJ), and the

More information

The Mission Critical Fire Protection Experts

The Mission Critical Fire Protection Experts The Mission Critical Fire Protection Experts Protection Systems Protection Systems HFC-227ea / FM200 / FE-227 FE-25 / ECARO-25 Novec 1230 Inergen / Argonite Halon Drop-in Systems High and Low Pressure

More information

EXETER TOWNSHIP DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS

EXETER TOWNSHIP DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS POLICY STATEMENT This policy applies to NEW Dry or Wet chemical fire suppression systems. The Authority Having Jurisdiction will not waive major criteria in

More information

Security Systems Intrusion Alarm

Security Systems Intrusion Alarm Dufferin-Peel Catholic District School Board STANDARD TEXT GUIDELINE FOR Security Systems for SECONDARY AND ELEMENTARY SCHOOLS Prepared by the Plant Department With Assistance from Vision Dynamics Formatted

More information

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION

SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION SECTION 16721 FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION A. This section of the specifications includes the furnishing, installation, and connection of the microprocessor-controlled

More information

BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS

BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS BUILDING OWNERS - SERVICE RELATED ISSUES FOR FIRE ALARM SYSTEMS Owners have numerous responsibilities as it pertains to the maintenance and operation of a building s fire safety equipment. The liabilities

More information

Automatic Fire Sprinkler Submittal Requirements

Automatic Fire Sprinkler Submittal Requirements Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance

More information

Fire Alarm Systems Certification

Fire Alarm Systems Certification Fire Alarm Systems Certification The skills and knowledge listed under each task are suggestive of those involved in that task, but are not intended to constitute an exhaustive listing. 2.1 Submittal Preparation

More information

CAN/ULC-S561-03 Installation and Services for Fire Signal Receiving Centres and Systems- Ottawa 2013

CAN/ULC-S561-03 Installation and Services for Fire Signal Receiving Centres and Systems- Ottawa 2013 CAN/ULC-S561-03 Installation and Services for Fire Signal Receiving Centres and Systems- Ottawa 2013 Alan Cavers, Engineering Manager Underwriters Laboratories of Canada Dec. 2013 Copyright 1995-2007 Underwriters'

More information

INSPECTION AND TESTING OF FIRE ALARM SYSTEMS

INSPECTION AND TESTING OF FIRE ALARM SYSTEMS Page 1 January 2, 2009 INSPECTION AND TESTING OF FIRE ALARM SYSTEMS Introduction Early warning plays a key role in a healthcare facility s ability to safely evacuate its residents during a fire emergency.

More information