Module 5. Fire and Emergency Alarm System Part I- Basics

Size: px
Start display at page:

Download "Module 5. Fire and Emergency Alarm System Part I- Basics"

Transcription

1 Module 5 Fire and Emergency Alarm System Part I- Basics 1

2 This module will describe: 1. Components and the arrangements of components in fire and emergency alarm systems. 2. How these systems work. 3. The NFPA standards that govern these components and systems. 2

3 Power Supply A source of electrical operating power, including the circuits and terminations connecting it to the dependent system components. In alarm systems there much be two supplies of power (primary and secondary) NFPA Standards 72: National Fire Alarm and Signaling Code 70: National Electrical Code 3

4 Control Unit A system component that monitors inputs and controls outputs through various types of circuits. NFPA Standards 72: National Fire Alarm and Signaling Code 4

5 Alarm Initiating Devices A system component that originates transmission of a changeof-state condition, such as in a smoke detector, manual fire alarm box, or supervisory switch. Can be manual or automatic NFPA Standards 72: National Fire Alarm and Signaling Code 5

6 Alarm Initiating Devices: Manual Pull Stations Manual Red in color Located about 4 feet above the floor and close to exits 6

7 Alarm Initiating Devices: Smoke Detectors Automatic A listed device that senses visible or invisible particles of combustion Two main types ionization photoelectric Wikimedia Commons 7

8 Alarm Initiating Devices: Heat Detectors Automatic Initiates an alarm when the thermal energy of a fire increases the temperature of a heat sensitive element. Two main types Rate-of-rise Fixed temperature Wikimedia Commons 8

9 Alarm Initiating Devices: Radiant Energy Detectors Automatic Responds to the radiant energy that has traveled from the fire to the detector Two main types Flame detector Smoke or ember detector Desu Systems 9

10 Alarm Initiating Devices: Gas Detectors Automatic Detects the presence of various gases Two main types Fixed Portable Sensidyne 10

11 Alarm Initiating Devices: Combination Detectors A device that: responds to more than one of the fire phenomena; or employs more than one operating principle to sense one of these phenomena. Examples: Heat detector with a smoke detector Rate-of-rise and fixed-temperature heat detector 11

12 Alarm Initiating Devices: Sprinkler Water Flow Switches Automatic Initiates an alarm signal when the flow of water through the wet pipe sprinkler system is greater than that going through one sprinkler head Home Security Store 12

13 Alarm Notification Appliances A fire alarm system component such as a bell, horn, speaker, light or text display that provides audible, tactile or visible outputs, or any combination thereof. A Mircom horn/strobe fire alarm notification appliance The primary purpose is to convey information to building occupants during a fire emergency NFPA Standards 72: National Fire Alarm and Signaling Code 13

14 Alarm Notification Appliances: Audible Horns & Speakers Must be audible and intelligible Fire Alarm-Security 14

15 Alarm Notification Appliances: Visible Strobe lights or illumination Must be accessible and visible Fire Alarm-Security 15

16 Supervision A visual and audible alarm signal given at the central safety station to indicate when the system is in operation or when a condition that would impair the satisfactory operation of the system exists. NFPA 13: Standard for the Installation of Sprinkler Systems 72: National Fire Alarm and Signaling Code 16

17 Supervision: Protected Premises Protected premises are all buildings, structures, facilities, real property, or portions thereof protected by an alarm system. A protected premises alarm system is designed to: Warn building occupants to evacuate the premise Actuate the building s fire-protection features Provide environmental protection 17

18 Supervision: Supervising Station A facility that receives signals and at which personnel are in attendance at all times to respond to these signals Three types Remote supervising-station fire alarm systems Propriety supervising-station systems Central-station fire alarm systems 18

19 Supervision: Remote Station A supervising station: to which alarm, supervisory, or trouble signals or any combination of those signals emanating from protected premises fire alarm systems are received where personnel are in attendance at all times to respond. must have a minimum of two operators on duty at all times to monitor signals 19

20 Supervision: Propriety Supervising Station A supervising station: under the same ownership as the protected premises fire alarm system(s) that it supervises to which alarm, supervisory, or trouble signals are received where personnel are in attendance at all times to supervise operation and investigate signals. May supervise one or more properties. 20

21 Supervision: Central Station A supervising station: that is listed for central station service that commonly provides less stringent supervising station services such as remote supervising station services. It is where the monitoring of the system and signals occurs retransmission of signals to the appropriate emergency-response service and record keeping will occur Wikimedia Commons 21

22 Supervision: Digital Alarm Communicator Transmitter Transmit an alarm signal from the property to the central supervising station. Is connected to the public-switched telephone network upstream of any telephone system on the property. Digital alarm communicator systems are the most widely used means is a digital alarm communicator system. 22

23 Single-Station Smoke Alarms A detector comprising an assembly that incorporates a sensor, control components, and an alarm notification appliance in one unit operated from a power source either located in the unit or obtained at the point of installation. NFPA Standards 72: National Fire Alarm and Signaling Code Wikimedia Commons 23

24 Multiple-Station Smoke Alarms Two or more single station alarm devices that can be interconnected so that actuation of one causes all integral or separate audible alarms to operate; or one single station alarm device having connections to other detectors or to a manual fire alarm box. NFPA Standards 72: National Fire Alarm and Signaling Code 24

25 Zoned Fire Alarm Systems A system where the entire facility is subdivide into into zones all initiating devices in any one particular zone are indicated as that zone on the control panel Often referred to as a conventional system NFPA Standards 72: National Fire Alarm and Signaling Code 25

26 Addressable Fire Alarm Systems A system or a part of a system where one can pinpoint which device has been activated. Each initiating device is assigned a number or address NFPA Standards 72: National Fire Alarm and Signaling Code 26

27 Wireless Fire Alarm Systems A system or a part of a system that can transmit and receive signals without the aid of wire. Two basic forms of commercial wireless systems: True Wireless Only wireless from the initiating point to a receiver NFPA Standards 72: National Fire Alarm and Signaling Code 27

28 Lessons Learned from Module 5 Fire alarm systems require two power supplies. There are many different initiating devices, both manual and automatic, such as pull boxes and heat detectors. A supervising facility is a facility that receives signals and at which personnel are in attendance. Fire alarm systems transmit information back in different ways, such as zoned where all initiating devices in any one particular zone are indicated as that zone on the control panel. 28

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY

More information

FIRE ALARM SYSTEM RECORD OF COMPLETION

FIRE ALARM SYSTEM RECORD OF COMPLETION FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. Protected Property Information Name of property: Description

More information

Module 4, Lesson 12 Fire Alarm Systems

Module 4, Lesson 12 Fire Alarm Systems Student Manual Module 4, Lesson 12 Fire Alarm Systems Performance Objectives At the conclusion of this lesson, you will be able to: Identify the components and functions of a fire alarm system and determine

More information

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

SECTION 16720 - FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines PART 1 -- GENERAL 1.1 WORK OF THIS SECTION SECTION 16720 - City of San Diego, CWP Guidelines A. The WORK of this Section includes providing manual and automatic fire alarm and smoke detection systems meeting

More information

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION

FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. It shall be permitted to modify this

More information

Attachment 9. Trouble signals. Interfaced equipment. Primary (main) power supply

Attachment 9. Trouble signals. Interfaced equipment. Primary (main) power supply FIRE DETECTION, ALARM AND MASS NOTIFICATION SYSTEMS Inspection, testing, and maintenance of fire detection, alarm and Mass Notification systems shall be performed in accordance with the manufacturer's

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted

More information

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems

More information

CBD-233. Fire Alarm and Detection Systems

CBD-233. Fire Alarm and Detection Systems Page 1 of 5 CBD-233. Fire Alarm and Detection Systems Originally published August 1984. R.H.L. McEwen Fire alarm systems are normally required by building codes. In the case of new buildings, this is usually

More information

OHIO BOARD OF BUILDING STANDARDS. Smoke Alarms and Fire Safety

OHIO BOARD OF BUILDING STANDARDS. Smoke Alarms and Fire Safety OHIO BOARD OF BUILDING STANDARDS Smoke Alarms and Fire Safety Updated January 2016 2 UNDERSTANDING THE TERMINOLOGY Detector. An initiation device suitable for connection to a circuit that has a sensor

More information

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier

More information

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS

CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL

More information

Fire Alarm System Basics

Fire Alarm System Basics Fire Alarm System Basics BY STANFORD UNIVERSITY FIRE MARSHAL S OFFICE AT ENVIRONMENT HEALTH & SAFETY DEPT. JOE LEUNG University Fire Marshal Manager, Fire Safety Program AARON MCCARTHY Senior Fire Protection

More information

PLAN REVIEW GUIDE FOR FIRE ALARM

PLAN REVIEW GUIDE FOR FIRE ALARM PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical

More information

Agenda. Agenda (continued) Fundamentals of Fire Alarm Systems

Agenda. Agenda (continued) Fundamentals of Fire Alarm Systems Fundamentals of Fire Alarm Systems Sponsored by UL SFPE Austin/San Antonio Chapter San Marcos, Texas 7 January 2015 Agenda Introduction and Administration Historical Context of Today s NFPA 72 Fire Alarm

More information

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND SMOKE DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire Alarm Control Panels B. Manual Fire Alarm Stations C. Automatic Smoke D. Fire Alarm Notification Appliances E. Auxiliary Fire Alarm Equipment

More information

Fire Alarm System Plans Review Checklist Property location Date of Review

Fire Alarm System Plans Review Checklist Property location Date of Review Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include

More information

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions

More information

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:

More information

City of Bettendorf Fire Alarm System Requirements

City of Bettendorf Fire Alarm System Requirements City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section

More information

FIRE DEPARTMENT CITY OF NEW YORK

FIRE DEPARTMENT CITY OF NEW YORK FIRE DEPARTMENT CITY OF NEW YORK STUDY MATERIAL FOR THE CERTIFICATE OF FITNESS FOR SUPERVISION OF FIRE ALARM SYSTEMS AND OTHER RELATED SYSTEMS S-95 ALSO INCLUDED IN THIS BOOKLET YOU WILL FIND THE FOLLOWING:

More information

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according

More information

HERNANDO COUNTY FIRE ALARM GUIDELINES

HERNANDO COUNTY FIRE ALARM GUIDELINES HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a

More information

How To Install A Carbon Monoxide Detector

How To Install A Carbon Monoxide Detector NASSAU COUNTY FIRE COMMISSION OFFICE OF THE FIRE MARSHAL Nassau County Public Safety Center 1194 Prospect Avenue Westbury, New York 11590 (516) 573-9900 / nassaucountyny.gov Chief Fire Marshal Scott D.

More information

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 PART 1 - GENERAL 1.01 WORK INCLUDED FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 A. Provide a complete fully addressable, power limited, fire detection and evacuation system. The system shall be connected

More information

FIRE-FIGHTING DESIGN BRIEF REPORT

FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM

More information

FIRE DEPARTMENT CITY OF NEW YORK STUDY MATERIAL FOR THE CERTIFICATE OF FITNESS FOR SUPERVISION OF FIRE ALARM SYSTEMS AND OTHER RELATED SYSTEMS S-95

FIRE DEPARTMENT CITY OF NEW YORK STUDY MATERIAL FOR THE CERTIFICATE OF FITNESS FOR SUPERVISION OF FIRE ALARM SYSTEMS AND OTHER RELATED SYSTEMS S-95 Revised 10-13-15 FIRE DEPARTMENT CITY OF NEW YORK STUDY MATERIAL FOR THE CERTIFICATE OF FITNESS FOR SUPERVISION OF FIRE ALARM SYSTEMS AND OTHER RELATED SYSTEMS S-95 ALSO INCLUDED IN THIS BOOKLET YOU WILL

More information

Life Safety Code Enabling References

Life Safety Code Enabling References SUPPLEMENT 4 Life Safety Code Enabling References Editor s Note: Supplement 4 provides users of NFPA 72, National Fire Alarm and Signaling Code, with a summary of requirements from NFPA 101, Life Safety

More information

The Mission Critical Fire Protection Experts

The Mission Critical Fire Protection Experts The Mission Critical Fire Protection Experts Protection Systems Protection Systems HFC-227ea / FM200 / FE-227 FE-25 / ECARO-25 Novec 1230 Inergen / Argonite Halon Drop-in Systems High and Low Pressure

More information

CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002

CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 CHANGES IN NFPA 72 NATIONAL FIRE ALARM CODE 1999 2002 Three new chapters were added. What was chapter 1 in 1999 was reorganized into chapters 1 (Fundamentals), 2 (Referenced Publications), and 3 (Definitions).

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS

SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat

More information

Alarm and Detection/Suppression

Alarm and Detection/Suppression Alarm and Detection/Suppression Fire Safety American Fire Technologies To provide special hazard services world wide to the industrial market through the integration of components and services Clean Agent

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM SECTION 16721 FIRE ALARM AND DETECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification

More information

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM

SECTION 16721 FIRE ALARM AND DETECTION SYSTEM 1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this

More information

TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS

TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS TESTING, INSPECTION, AND MAINTENANCE FREQUENCIES FOR FIRE DETECTION AND ALARM SYSTEMS The following information regarding testing frequencies for fire detection and alarm systems. All of the following

More information

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,

More information

FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual

FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual P/N 315-049403-1 Siemens Building Technologies Fire Safety Table Of Contents Introduction...1 The Access levels...1 User Level...1 Maintenance

More information

Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines

Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Red Oak Fire Rescue Office of the Fire Marshal 547 N. Methodist Red Oak, TX 75154 Phone: 469-218-7713 Fax: 468-218-7719

More information

FIRE DEPARTMENT CITY OF NEW YORK STUDY MATERIAL FOR THE CERTIFICATE OF FITNESS FOR SUPERVISION OF FIRE ALARM SYSTEMS AND OTHER RELATED SYSTEMS

FIRE DEPARTMENT CITY OF NEW YORK STUDY MATERIAL FOR THE CERTIFICATE OF FITNESS FOR SUPERVISION OF FIRE ALARM SYSTEMS AND OTHER RELATED SYSTEMS Revised 8 1 14 FIRE DEPARTMENT CITY OF NEW YORK STUDY MATERIAL FOR THE CERTIFICATE OF FITNESS FOR SUPERVISION OF FIRE ALARM SYSTEMS AND OTHER RELATED SYSTEMS S-95 ALSO INCLUDED IN THIS BOOKLET YOU WILL

More information

2007 ICC FINAL ACTION AGENDA

2007 ICC FINAL ACTION AGENDA 907.2.1.1 System initiation in Group A occupancies with an occupant load of 1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal

More information

Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007

Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 FIRE ALARM SYSTEMS POLICY TELLURIDE FIRE PROTECTION DISTRICT TABLE OF CONTENTS FIRE ALARM PROTECTION POLICY PLAN REVIEW SUBMITTAL

More information

NATIONAL FIRE ALARM AND SIGNALING CODE

NATIONAL FIRE ALARM AND SIGNALING CODE GAP.11.1.1.0 A Publication of Global Asset Protection Services LLC NATIONAL FIRE ALARM AND SIGNALING CODE INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection

More information

Mobile Fire Rescue Department Bureau of Fire Prevention

Mobile Fire Rescue Department Bureau of Fire Prevention 222 Mobile Fire Rescue Department Bureau of Fire Prevention Samuel L. Jones Mayor Stephen A. Dean Fire Chief February 2011 2009 International Fire Code Fire Alarm and Detection Systems 907.1 General. This

More information

BASIC FIRE ALARM TRAINING

BASIC FIRE ALARM TRAINING BASIC FIRE ALARM TRAINING What is a fire alarm system? Per the defini+on in NFPA 72 A system or por+on of a combina+on system that consists of components and circuits arranged to monitor and annunciate

More information

INSPECTION AND TESTING OF FIRE ALARM SYSTEMS

INSPECTION AND TESTING OF FIRE ALARM SYSTEMS Page 1 January 2, 2009 INSPECTION AND TESTING OF FIRE ALARM SYSTEMS Introduction Early warning plays a key role in a healthcare facility s ability to safely evacuate its residents during a fire emergency.

More information

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011

FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 Office of the Fire Marshal 1.0 PERMITS FIRE ALARM SYSTEMS PERMIT APPLICATION, PLAN SUBMITTAL, DESIGN, INSTALLATION AND INSPECTION REQUIREMENTS Effective Date: January, 2011 1.1 To acquire an installation

More information

ENVIRONMENTAL HEALTH & SAFETY 6 East Dr., Amherst MA 01002-5000

ENVIRONMENTAL HEALTH & SAFETY 6 East Dr., Amherst MA 01002-5000 AMHERST COLLEGE ENVIRONMENTAL HEALTH & SAFETY 6 East Dr., Amherst MA 01002-5000 Michael Zlogar April 11, 2001 Assistant Fire Chief Amherst Fire Department 68 North Pleasant St. Amherst, MA 01004 FIRE ALARM

More information

Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14

Original Document 10/16/07 Revised 01/30/09 2 nd Revision 01-23-12 3 rd Revision- 12/18/14 North Collier Fire Control & Rescue District Greater Naples Fire Rescue District Immokalee Fire Control & Rescue District 2800 North Horseshoe Drive Naples, Florida 34104 SYSTEM REHABILITATION PLAN CHECKLIST

More information

EXHIBIT A SCOPE OF WORK

EXHIBIT A SCOPE OF WORK EXHIBIT A SCOPE OF WORK 1. (Contractor) shall provide fire alarm system maintenance/repair/testing services as described herein to the California Department of Veterans Affairs (hereinafter CDVA, CalVet,

More information

FIRE ALARM APPLICATION

FIRE ALARM APPLICATION FIRE ALARM APPLICATION ENUMCLAW FIRE DEPARTMENT 1330 Wells St, Enumclaw, WA 98022 Phone: 360-825-5544 Fax: 360-825-9442 COMMUNITY DEVELOPMENT, BUILDING DEPARTMENT 1309 Myrtle Ave Enumclaw WA 98022 Phone:

More information

SECTION 28 31 11 FIRE ALARM AND DETECTION SYSTEM

SECTION 28 31 11 FIRE ALARM AND DETECTION SYSTEM KNOXVILLE, TENNESSEE SECTION 28 31 11 PAGE 1 PART 1 - GENERAL 1.01 DESCRIPTION OF WORK SECTION 28 31 11 A. Extent of fire alarm and detection system work shall be as described in this specification, as

More information

NY Fire Safety Institute

NY Fire Safety Institute NY Fire Safety Institute Presents the FDNY Coordinator of Fire Safety and Alarm Systems Homeless Shelters (Premise Related) Certificate of Fitness F-80 Definitions and Terminology Established 1995 Preparing

More information

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS 527 CMR 24.00: FIRE WARNING SYSTEMS INSTALLED IN BUILDINGS WITHIN THE COMMONWEALTH OF MASSACHUSETTS Section 24.01: Purpose 24.02: Scope 24.03: Definitions 24.04: Approval of Design 24.05: Power Supply

More information

SECTION 16721 MULTI-FIRE ALARM SYSTEM

SECTION 16721 MULTI-FIRE ALARM SYSTEM PART 1. GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Divisions 1 Specification Sections, apply to this Section.

More information

FIRE DETECTION AND ALARM

FIRE DETECTION AND ALARM FIRE DETECTION AND ALARM GENERAL INFORMATION 1.1 In general, follow the guidelines below when designing and specifying addressable fire alarm systems. Unless specifically indicated otherwise, these guidelines

More information

NFPA 72. Exception No. 1: Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted.

NFPA 72. Exception No. 1: Where ambient conditions prohibit installation of automatic smoke detection, automatic heat detection shall be permitted. NFPA 72 3.3.7.2 3.3.7.2 False Alarm. Activation or reporting of an alarm for which no such alarm condition, fire or emergency actually exists. Additionally, False Alarm is the willful and knowing initiating

More information

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS 527 CMR 31.00: CARBON MONOXIDE ALARMS Section 31.01: Purpose and Scope 31.02: Definitions 31.03: General Installation Provisions 31.04: Specific Installation Provisions 31.05: Carbon Monoxide Protection:

More information

BELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM-10-011

BELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM-10-011 Fire Alarm System plan(s) MUST be reviewed and approved by the Belmont Fire Department prior to the start of construction. The design and any changes must be fully compliant with NFPA 1, NFPA 101, NFPA

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi addressable detection and control system.

More information

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval. Polk School District Specifications for the New Fire Alarm in the Existing Building Eastside Elementary School FIRE ALARM SYSTEM 1.01 SUBMITTALS A. Shop drawings shall be submitted as follows: 1. Manufacturer's

More information

SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM

SECTION 16853 ZONED (DC LOOP) FIREALARM SYSTEM SECTION 16853 ZONED (DC LOOP) FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1

More information

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION

FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION PERMITS AND INSPECTIONS FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION 911 Assigned PROJECT LOCATION Subdivision: Lot: Blk: Sec: PROJECT New Construction Addition/Remodel Demolition Other: Number

More information

DTW Works Master Specification Version 2006

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section 13852 Multiplex Fire Alarm System Page 1 of 10 PART 1 GENERAL 1.1 RELATED WORK.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Procedures..3 Section 01810 Commissioning..4

More information

Sprinkler and Fire Alarm Systems for the Building Official

Sprinkler and Fire Alarm Systems for the Building Official Sprinkler and for the Building Official Randall Kovacs, P.Eng., CP, FEC Gage-Babcock & Associates, Ltd. Topics Coordinated System Testing 1 Wet Dry Pre-action Deluge Wet System: Pipes filled with water

More information

DCSS (ACB) Data Center Fire Suppression Procedures

DCSS (ACB) Data Center Fire Suppression Procedures May 18, 2015 DCSS (ACB) Data Center Fire Suppression Procedures Purpose: This document is intended for all individuals who have access to the data center at 1011 West Springfield Avenue, Advanced Computation

More information

3468-00 Lighting and Fire Alarm Training System Add-On

3468-00 Lighting and Fire Alarm Training System Add-On 3468-00 Lighting and Fire Alarm Training System Add-On LabVolt Series Datasheet Festo Didactic en 06/2016 Table of Contents General Description 2 List of Equipment 2 List of Manuals 2 Additional Equipment

More information

FIRE DETECTION AND ALARM

FIRE DETECTION AND ALARM Scope Provide a fire alarm system, or expand the existing system, as required by Code, the requirements in the Special Instructions to Designers (SID) of the Design Guidelines, and/or as noted in the Program

More information

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 105.8a-6.1 TITLE: FIRE ALARM SYSTEM REQUIREMENTS SCOPE: This guideline

More information

Michael Catalano 24 Nassau Avenue, Islip NY 11751 Phone (631) 224-5477 Chief Fire Marshal fireprevention@islipny.gov Fax (631) 224-5458

Michael Catalano 24 Nassau Avenue, Islip NY 11751 Phone (631) 224-5477 Chief Fire Marshal fireprevention@islipny.gov Fax (631) 224-5458 OFFICE OF THE FIRE MARSHAL BUREAU OF FIRE PREVENTION Michael Catalano, Phone Chief Fire Marshal fireprevention@islipny.gov Fax To whom it may concern: Enclosed please find the NFPA 72 forms needed for

More information

1.0 General. Inspection, Testing, and Maintenance 1 of 8

1.0 General. Inspection, Testing, and Maintenance 1 of 8 1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus

More information

Design Standards Fire Alarm Systems Division 13860 (1995 CMS); 283100 (2004 CMS) Amended Feb 2015

Design Standards Fire Alarm Systems Division 13860 (1995 CMS); 283100 (2004 CMS) Amended Feb 2015 Design Standards Fire Alarm Systems Division 13860 (1995 CMS); 283100 (2004 CMS) Amended Feb 2015 13860 (283100) FIRE ALARM SYSTEM The following standard shall be followed for the design of University

More information

Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System

Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System Amerex CPS FM-200 Waterless Pre-engineered Fire Suppression System A Simple Solution An Affordable Approach An Industry Innovation I N T R O D U C T I O N A SIMPLE SOLUTION. AN AFFORDABLE How many days

More information

Fire Alarm Systems for Life Safety Code Users

Fire Alarm Systems for Life Safety Code Users SUPPLEMENT 2 Fire Alarm Systems for Life Safety Code Users Robert P. Schifiliti, P.E. Editor s Note: This supplement is an introduction to fire alarm systems. It explains the various types of systems addressed

More information

ENGINEERING SPECIFICATIONS

ENGINEERING SPECIFICATIONS ENGINEERING SPECIFICATIONS FM-200 CLEAN-AGENT FIRE SUPPRESSION SYSTEM with PYRO-CHEM DETECTION/RELEASE SYSTEM March 2001 SECTION 1 - GENERAL I. SCOPE This specification outlines the requirements for a

More information

Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need?

Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need? 5/2/2014 Fire Alarm FAQs Question Answer Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need? A: The size of a fire alarm panel is determined by a number of factors,

More information

INSPECTION AND TESTING FORM

INSPECTION AND TESTING FORM INSPECTION AND TESTING FORM SERVICE ORGANIZATION PROPERTY NAME (USER) DATE: 08-04-15 TIME: 8:00 Name: Siemens Industries Inc. Name: Kcvtcs Madisonville Tech, School Bldg. Address: 2700 Stanley Gault Pkwy

More information

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 19

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 19 TECHNICAL SPECIFICATIONS Page 1 of 19 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC analogue addressable, electrically supervised, zone annunciated, fire detection and alarm system as

More information

University Design Standard. Fire Alarm Systems

University Design Standard. Fire Alarm Systems University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit

More information

SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective

SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective The National Fire Alarm Code, NFPA 72, sets the minimum requirements of performance, selection, use and location of automatic detection

More information

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10 TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified

More information

Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems

Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Appendix A Proposed amended Acceptable Solution for Warning Systems s in the grey boxes form part of the proposed

More information

Fire Alarm Systems Training Manual

Fire Alarm Systems Training Manual Fire Alarm Systems Training Manual Manual #8700055 - REV F 4/10 Foreword The history of fire detection and alarm in the United State dates back to the 1800s with the first standards. Since then the science

More information

A. Product Data: For each type of product, including furnished options and accessories.

A. Product Data: For each type of product, including furnished options and accessories. SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Manual fire-alarm boxes. 3. System smoke detectors. 4. Non-system

More information

REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING APPLICATION PACKET

REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING APPLICATION PACKET REGULATIONS for INSTALLATION, MAINTENANCE, and TESTING FIRE ALARM SYSTEMS APPLICATION PACKET CITY OF NAPERVILLE 400 S EAGLE STREET NAPERVILLE, Il 60540 PHONE: 630.420.6070 FAX: 630.420.6657 Fire Alarm

More information

Fire detection equipment

Fire detection equipment PRODUCT CATALOG Fire detection equipment www.apollo-fire.com Apollo Fire Detectors is one of the world s largest manufacturers of fire detectors, modules and notification devices. Established in 1980,

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 21 22 13 - SAPPHIRE CLEAN-AGENT FIRE SUPPRESSION SYSTEM PART 1 GENERAL 1.1 RELATED DOCUMENTS A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and this Section

More information

SPECIFICATION FOR A TOTAL FLOOD HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE Cheetah Xi CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE Cheetah Xi CONTROL PANEL SYSTEM SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood Clean Agent Fire Suppression System with automatic detection and control. The work described in this

More information

NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet

NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet This Commercial Kitchen Automatic Fire has been created to assure all documentation has been submitted to assist you in assuring proper plans and documentations has been submitted and reviewed by New Mexico

More information

C. Conform to requirements of Americans with Disabilities Act (ADA).

C. Conform to requirements of Americans with Disabilities Act (ADA). SECTION 28 31 00 - FIRE ALARM AND DETECTION SYSTEMS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Fire alarm and detection systems 1.2 REFERENCES A. NFPA 70 - National Electrical Code B. NFPA 72 - National

More information

CFAA NCR CHAPTER ANNUAL SENINAR. Commonly Overlooked Fire Alarm Requirements

CFAA NCR CHAPTER ANNUAL SENINAR. Commonly Overlooked Fire Alarm Requirements CFAA NCR CHAPTER ANNUAL SENINAR Commonly Overlooked Fire Alarm Requirements Introduction of Who I Am And My Experience (aka: only legitimate chance to catch a quick nap) Definitions ( if you nap during

More information

A. This Standard outlines the requirements for an addressable fire detection and alarm system.

A. This Standard outlines the requirements for an addressable fire detection and alarm system. 1.00 GENERAL 1.01 Scope: A. This Standard outlines the requirements for an addressable fire detection and alarm system. B. This Standard consists of all materials, equipment and services necessary and

More information

A Practical Guide to Fire Alarm Systems

A Practical Guide to Fire Alarm Systems A Practical Guide to Fire Alarm Systems Provided as a service to the insurance industry and fire protection community by the Central Station Alarm Association Third Edition 8150 Leesburg Pike Suite 700

More information

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE DESCRIPTION The SST Model 5010 Two Channel Smoke/Fire Detection Module provides two independent detection input channels for the NOVA-5000

More information

Understanding Fire Alarm Requirements & Inspections. Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc

Understanding Fire Alarm Requirements & Inspections. Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc Understanding Fire Alarm Requirements & Inspections Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc Introduction Fire Alarm Requirements are structured through a system of codes.

More information

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0

More information

The Evolution of Requirements for Supervising Station Alarm Systems

The Evolution of Requirements for Supervising Station Alarm Systems The Evolution of Requirements for Supervising Station Alarm Systems Fire Marshal s Association of Colorado January 18, 2013 Warren Olsen, CFPS CBCO FSCI wolsen@firesafetyfsci.com 1 Disclaimer: The comments

More information