Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers



Similar documents
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

The following components are common to most cubicles; this example is an ABB HK cubicle.

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

Houston Service Center Medium Voltage Service and Aftermarket Solutions

MEDIUM VOLTAGE METAL CLAD SWITCHGEAR

Sample - No Commercial Use

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

The Intelligent AX1 Switchgear for Medium Voltage

01.4IB.51200B PowlVac-AR Arc Resistant Switchgear. 5kV & 15kV 1200A, 2000A, 3000A, & 4000A Forced Cooled. Powered by Safety

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET

Voltage Rated operating voltage [kv] Rated power frequency withstand voltage [kv] Rated lightning impulse withstand voltage [kv]

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

DOCUMENT ADDENDUM NO. 2. Issued to all Bidders: Date: February 3, Contract Name: 13,800-Volt and 480-Volt Switchgear

Masterclad Medium Voltage Passive Arc-Resistant Switchgear

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

SECTION 16346A METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR

PIP ELSSG02 Design and Fabrication of Medium Voltage Metal-Clad Switchgear from 4.76 kv to 38 kv

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

Engineers Edge, LLC PDH & Professional Training

3.0 CHARACTERISTICS. AR Auxiliary Relay High Speed, High Threshold C

Power IT MV Air Insulated Switchgear. Technical Information and Application Guide Featuring Advance TM and SafeGear TM Technology

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

Extend the Life of Existing Switchgear

PowlVac Vacuum Integrity Tester

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

Unified requirements for systems with voltages above 1 kv up to 15 kv

Vacuum Circuit Breaker Type VAD-3

COMPARISON OF ANSI/IEEE AND IEC REQUIREMENTS FOR LOW- VOLTAGE SWITCHGEAR

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

Advantages of Fixed Circuit Breaker Switchgear

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

Hyperlinks are Inactive

IB PowlVac-ND ITE-HK 5kV Replacement Vacuum Circuit Breaker. Replacement for ABB Type ITE-HK Air Circuit Breaker.

SUGGESTED SPECIFICATION For Medium Voltage Automatic Transfer Switches

Primary and Secondary Electrical Distribution Systems

New Arc Resistant, Compact Metal Clad Switchgear: Meeting ANSI / UL Design Challenges By Ashok Kulkarni and Predrag Milovac

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

SECTION HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

Section 9: Power Distribution Equipment Bill Brown, P.E., Square D Engineering Services

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Instructions for Installation, Operation and Maintenance of 24kV Type W-VAC Vacuum Circuit Breaker

Emirates Aluminium starts up World s first fully integrated power distribution system from ABB

ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

PowlVac Type PVDST Replacement Vacuum Circuit Breaker Replacement for Federal Pacific Type DST Air-Magnetic Circuit Breakers

How To Build A Germany Power Plant

SECTION MEDIUM VOLTAGE SWITCHGEAR

Diesel Engine Driven Generators Page 1 of 6

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

New SACE Emax 2 for UL 1066 From Circuit Breaker to Power Manager

Defining the Needs of Modern Data Center Power Systems, Low Voltage Circuit Breaker Application

15VHK-VR Model 20 Replacement Circuit Breaker

A Comparison of Contemporary Electrical Distribution Equipment Standards. San Francisco IEEE Industry Applications Society May 26, 2009

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

Contents. Description. Product Selection Guide

Short Circuit Current Calculations

Low Voltage Switchgear

e 2 ALPHA Medium Voltage Switchgear Data Sheet K EN

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A

Masterclad 5 15 kv Arc Resistant Metal-Clad Indoor Switchgear

Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services.

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA

Electrical Shore Connections / Cold Ironing

SECTION SWITCHBOARDS

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE:

Alternate Methods to Short Circuit Breaker Coordination

Customer Substation Manual 08/05/02

Cable/Conduit Conversion

This section applies to the design and installation of transformers.

Installation, Operation and Maintenance Instructions. Uniflex ABB PTMV

Installation Instructions

Eaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical

understanding medium frequency induction melting furnace and its components

IRRIGATION PUMPING Table of Contents - Section 900

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

DESIGN CLARIFICATION (DC)

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

Trade of Electrician. Three-phase Distribution Boards And Socket Circuits

Power-Zone 4 Arc Resistant Low Voltage Switchgear

Interconnection Application For Residential and Commercial Power Systems 10 kw or Smaller

FAQs-Main switchboard design criteria

Type K current limiting fuse canister Technical information and installation guide

SUPPLEMENT TO SPECIFICATIONS FOR ELECTRICAL INSTALLATIONS

Application Bulletin NEC Reference Guide for SolarBridge-Enabled AC Module Installers

2004 TRANSMISSION SYSTEMS SEMINAR MEDIUM VOLTAGE, METAL-CLAD ARC RESISTANT SWITCHGEAR: ENHANCING WORKPLACE SAFETY

Secondary Unit Substations

SECTION POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

Bypass transfer switch mechanisms

MCC Ratings. Voltage Rating

INTERNATIONAL POWER DISTRIBUTION CONGRESS CIDEL ARGENTINA 2002

Medium Voltage Motor Control Assemblies

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

Fusible Disconnect Switch

Transcription:

Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers

Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element Construction...4 5.0 Roll-in Replacement Circuit Breaker Construction...5 6.0 Installation Conformance...6 7.0 Documentation and Drawing Requirements...6

1.0 General Work Scope This specification covers the design, testing, manufacturing requirements, on-site installation and installation conformance of medium voltage replacement circuit breakers. The medium voltage replacement circuit breakers shall be functional replacements (both mechanically and electrically) for the existing medium voltage circuit breakers listed in this specification. This specification defines the requirements for the replacement of existing air magnetic circuit breakers with circuit breakers of the same or greater interrupting rating using vacuum interrupter technology. The replacement breakers shall be directly interchangeable between the breaker cells of the same ampere class and interrupting rating of the original equipment without cell modifications. The new replacement circuit breakers shall be fully compatible with the existing switchgear compartments and the identical interlocks and mechanism operated cell (MOC) switches. The replacement circuit breaker shall be a magnetically actuated ABB RVAC medium voltage replacement breaker or approved equal. 2.0 Standards The replacement circuit breaker elements shall be designed, fabricated and tested in accordance with the latest applicable standards of the American National Institute (ANSI), National Electrical Manufacturers Association (NEMA), and the Institute of Electrical and Electronics Engineers, Inc. (IEEE) unless otherwise stated herein. 2.1 ANSI C37.04 Standard Rating Structure for AC High Voltage Circuit Breakers 2.2 ANSI C37.06 AC High Voltage Circuit Breakers Rated on a Symmetrical Current Basis - Preferred Ratings and Related Required Capabilities 2.3 ANSI C37.09 Standard Test Procedure For AC High-voltage Circuit Breakers Rated On A Symmetrical Current Basis 2.4 ANSI C37.010 Application Guide for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis 2.5 ANSI C37.11 Requirement for Electrical Control for AC High Voltage Circuit Breakers 2.6 ANSI C37.12 Guide to Specifications for AC High Voltage Circuit Breakers Rated on A Symmetrical Current Basis or a Total Current Basis 2.7 ANSI C37.20.2 Metal Clad and Station Type Cubicle Switchgear (above 1000V) 2.8 ANSI C37.59 Requirements for Conversion of Power Switchgear Equipment

3.0 Supplier Qualifications 3.1 The supplier shall have replacement circuit breakers in service for a minimum of five (5) years. 3.2 The supplier shall be able to demonstrate experience in replacement breaker design for a minimum of five (5) years. 3.3 The supplier shall be the original manufacturer of the circuit breaker element being applied to the replacement circuit breaker. 4.0 Circuit Breaker Element Construction 4.1 The circuit breaker element shall be an ABB VKBR or VHKR, three-pole, electrically operated with spring-stored energy operating mechanism or approved equal. 4.2 Opening and closing speed shall be independent of the operator or of the control voltage within the rated control voltage range. 4.3 Manual provisions shall be provided for closing, tripping and charging the breaker. These provisions shall be installed and easily accessible at the front of the breaker element. 4.4 When fully installed as a replacement breaker, the breaker element shall be provided with self-aligning, fully automatic secondary coupling system to connect and disconnect all control wiring during circuit breaker insertion and withdrawal. 4.5 The secondary disconnect shall require no manual intervention to attain proper position when the breaker is racked to the connected, test or disconnected positions. 4.6 Secondary contacts shall use a tin-lead contact finish. 4.7 The circuit breaker element shall include eight on-board auxiliary contacts (4 a, 4 b ) for customer use, wired through the secondary disconnect. All breaker-mounted contacts shall operate in both connected and test positions. Nine additional contacts (5 a, 4 b ) shall be installed on the breaker and wired through the secondary disconnect, for a total of 17 onboard contacts. 4.8 The breaker element shall have flags to indicate open or closed position, and spring charge status. Only the correct status flag for any single function shall be visible. Pointer systems shall not be used to indicate status. 4.9 The springs in the stored energy operating mechanism for the breaker element shall be automatically discharged prior to removing a circuit breaker from a compartment. 4.10 The circuit breaker element shall have a five-digit, non-resetting operation counter clearly visible from the front of the breaker. The operation counter shall advance when the breaker opens. 4.11 Each primary lead assembly shall consist of a vacuum interrupter housed in a glass-polyester support, with copper upper and lower leads, and shall use tulip-type self-aligning primary disconnects. 4.12 Current transfer to moving interrupter stems shall be via flexible connectors or brush contacts with no moving parts.

4.13 Primary disconnects and contact surfaces of other current carrying parts shall be silver-plated. 4.14 Interrupters shall have a contact wear indication for evaluation by contact measurement tools. 5.0 Roll-in Replacement Circuit Breaker Construction 5.1 The roll-in replacement circuit breaker shall have a complete ANSI-tested mechanism. The element shall be mounted in a steel frame structure which interfaces with the existing cell levering system and has primary connections which match the existing inter and intra-phase spacing. 5.2 The replacement circuit breaker frame shall be constructed from steel. A combination of bolting and welding to assemble the frame is acceptable. The frame and associated interlocks shall be provided with a painted or zinc-plated with a yellow dichromate, protective coating to prevent the corrosive effects of the atmosphere. All hardware shall be a minimum grade five (5), zinc-plated or black oxide to prevent the corrosive effects of the atmosphere. 5.3 The circuit breaker manufacturer must have a test cubicle located in their factory to verify cell interlocks and racking system of the new replacement breaker. 5.4 The replacement breaker shall be suitable for use in the existing metalclad switchgear. Only vacuum interrupter and mechanism assemblies that have jointly passed appropriate ANSI design tests listed in C37.09 shall be used in the circuit breaker. 5.5 Main current-carrying parts, insulators, supports, and housing of the circuit breaker shall have sufficient mechanical strength to withstand the effects of rated short circuit currents without damage. 5.6 The replacement breaker shall be held trip free during breaker levering. Safety interlocks shall interface with the existing breaker cell to prevent the breaker levering into the primary contacts in the closed position. 5.7 Control wiring shall be #14 gauge, type SIS as a minimum. 5.8 The primary connections and/or finger clusters shall be new, designed and tested to carry the full nameplate rating of the replacement circuit breaker without exceeding the allowable temperature rise as indicated by ANSI. 5.9 The primary contacts shall be capable of withstanding the full rated short circuit current rating of the circuit breaker as defined by ANSI. 5.10 The new secondary contact block shall be new and shall be capable of interfacing with the existing contact block located in the existing cell. Cell modifications of the enclosure are unacceptable. 5.11 The breaker shall be capable of operating all truck-operated contacts (TOC); mechanism operated contacts (MOC), and cubicle shutter functions and shall be fully function tested according to ANSI C37.20.2. 5.12 The functionality of the existing metal dead front barrier shall be maintained.

5.13 Closing and tripping mechanisms for the replacement breaker shall operate satisfactorily over the voltage range in accordance with ANSI C37.06 Table 10. 5.14 Each new circuit breaker shall retain the copper connection to the ground bus throughout the levering process. 5.15 The circuit breaker shall retain the existing racking mechanism and interlocks and be capable of moving the breaker and operating the mechanical interlocks between the CONNECT, TEST, and DISCONNECT positions as originally designed. This shall include, but not limited to, the interlocks that prevent removal or insertion of a closed breaker, operation of cubicle shutter and positioning. 5.16 The operating mechanism shall be readily accessible for maintenance. 6.0 Installation Conformance 6.1 The replacement breaker manufacturer shall verify functional operation of all circuit breaker interlocks, cell interfaces and levering assembly in a cell structure in the replicated cell at the factory and again verify the same at each cell location for which the replacement breaker is installed. The service of factory trained service technicians shall be included to accomplish and verify this conformance. 6.2 The supplier shall also set all trip unit settings on each replacement circuit breaker as required for each circuit breaker being replaced under this project. The owner shall furnish the supplier with a recent coordination study for this purpose. 7.0 Documentation and Drawing Requirements 7.1 The circuit breaker element shall be supplied with certificates of type tests on similar devices performed by the manufacturer. 7.2 Copies of the design tests of the replacement breaker shall be supplied. 7.3 Copies of the production tests of the replacement breaker shall be supplied. 7.4 Outline drawings of the replacement circuit breaker shall be supplied. 7.5 Schematic wiring diagram of the circuit breaker element and connection diagram shall be supplied. 7.6 Schematic and wiring diagram of the replacement circuit breaker shall be supplied. 7.7 Instruction books for the replacement circuit breaker shall be provided. The instruction book shall also include the circuit breaker element.