UFGS-28 33 00.00 40 (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS



Similar documents
UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UFGS (August 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UFGS (August 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

UNIFIED FACILITIES GUIDE SPECIFICATIONS

CalMod Design-Build Electrification Services

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

C. Conform to requirements of Americans with Disabilities Act (ADA).

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

Conventional Fire Detection and Extinguishant Control System Specification

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

TABLE OF CONTENT

Fire Alarm System Accessories

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

UNIFIED FACILITIES GUIDE SPECIFICATIONS

FVSU REPAIR & UPGRADE FIBER OPTIC SECTION FIRE ALARM SYSTEM CONNECTIVITY

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

DTW Works Master Specification Version 2006

Manual for Fire Suppression & Methane Detection System

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

UFGS (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

SECTION FIRE ALARM AND DETECTION SYSTEM

UNIFIED FACILITIES GUIDE SPECIFICATIONS ************************************************************************** SECTION TABLE OF CONTENTS

SECTION FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL

Overview of Standards for CO Detection Products

Buckeye Detection Systems Fixed Detection Systems Application Survey

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

SECTION ZONED (DC LOOP) FIREALARM SYSTEM

Security Systems Intrusion Alarm

Q U A D S C A N I I GENERAL User Interface Enclosure Display QUADSCAN II Temperature Range RECEIVER DISPLAY Sensor Weight Optional Relay Enclosure

DIVISION 28 ELECTRONIC SAFETY AND SECURITY SECTION SECURITY AND ACCESS CONTROL SYSTEM

HERNANDO COUNTY FIRE ALARM GUIDELINES

ENGINEERING SPECIFICATIONS

Element D Services Plumbing

SECTION FIRE ALARM AND DETECTION SYSTEM

The Breather Box. High Performance Grade-D Breathing Air Filtration system. BB50-cO

SPECIFICATION FOR A TOTAL FLOOD HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE Cheetah Xi CONTROL PANEL SYSTEM

Introduction. Refrigerant Leak Detecting System. Feature and Benefits

SINGLE-CHANNEL GAS-DETECTOR GAS ALARM DG510/1P

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 19

NATIONAL FIRE ALARM AND SIGNALING CODE

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

Original Document 10/16/07 Revised 01/30/09 2 nd Revision rd Revision- 12/18/14

H.V.A.C. Design Plumbing Design

A.1. a Division of Pittway Corporation. Documento: M MGAS-ENG. Edizione: 01/1997 Rev.:

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Design and Construction Standards SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

Using your LED Plus keypad

Fire Alarm Control Panel. Family. Operating Manual

SECTION ( ) FIRE DETECTION AND ALARM SYSTEM

UNIFIED FACILITIES GUIDE SPECIFICATIONS ************************************************************************** SECTION TABLE OF CONTENTS

SECTION DETECTION AND ALARM

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description

University of Houston Master Construction Specifications Insert Project Name

Module 4, Lesson 12 Fire Alarm Systems

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

HM-W536 Install Guide

PLAN REVIEW GUIDE FOR FIRE ALARM

1.0 General. Inspection, Testing, and Maintenance 1 of 8

SECTION FIRE ALARM SYSTEM

DIGITAL ALARM II FOR HOSPITALS AND LABORATORIES INSTALLATION AND OPERATING INSTRUCTIONS

Fire Alarm System Plans Review Checklist Property location Date of Review

OPL BASIC. Dosing System for Professional Laundry machines. Contents

Protection Systems. A UTC Fire & Security Company F Linear Heat Detector FEATURES DESCRIPTION APPLICATIONS BENEFITS

SECTION PROGRAMMABLE LOGIC CONTROLLERS AND COMPUTER CONTROL SYSTEM PART 1 GENERAL Summary. A. Section Includes:

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

B. Equipment shall be furnished and installed as specified. No substitutions will be allowed.

SECTION NOx, CO AND NATURAL GAS DETECTION, MONITORING AND ALARM CONTROL SYSTEMS

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

Stationary Storage Battery Systems

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank

Application Requirement

SECTION ACCESS CONTROL SYSTEM. CONDITIONS OF THE CONTRACT AND DIVISION 1, as applicable, apply to this Section.

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

Fire Pump Controllers Remote Alarm Panels

SECTION FIRE ALARM AND DETECTION SYSTEMS

ACS-30-EU-EMDR-10-MOD

Alarm and Detection/Suppression

Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007

Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines

Fire & Security DETECTORS

Transcription:

USACE / NAVFAC / AFCEC / NASA UFGS-28 33 00.00 40 (February 2014) ----------------------------------- Preparing Activity: NASA Superseding UFGS-28 33 00.00 40 (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References are in agreement with UMRL dated July 2015 SECTION TABLE OF CONTENTS DIVISION 28 - ELECTRONIC SAFETY AND SECURITY SECTION 28 33 00.00 40 FUEL-GAS DETECTION AND ALARM 02/14 PART 1 GENERAL 1.1 REFERENCES 1.2 SUBMITTALS 1.3 ADMINISTRATIVE REQUIREMENTS 1.3.1 Pre-Installation Meetings 1.4 MAINTENANCE MATERIALS 1.5 WARRANTY PART 2 PRODUCTS 2.1 SYSTEM DESCRIPTION 2.1.1 Design Requirements 2.1.1.1 Schematics 2.1.1.2 Combustible Gas Environments 2.1.1.3 Oxygen Deficient Atmospheres 2.1.2 Performance Requirements 2.1.3 Electromagnetic Compatibility 2.2 COMPONENTS 2.2.1 Control Unit 2.2.1.1 Control Circuits 2.2.1.2 Power Supply Component 2.2.1.3 Indicator Light and Reset 2.2.1.4 Malfunction Circuits 2.2.1.5 Alarm 2.2.2 Detectors 2.2.2.1 Circuit Design 2.2.2.2 Combustible Gas Detector 2.2.2.3 Oxygen Detector 2.2.3 Power Supply 2.3 EQUIPMENT PART 3 EXECUTION 3.1 INSTALLATION 3.1.1 Combustible Gas Systems SECTION 28 33 00.00 40 Page 1

3.1.2 Oxygen Deficiency Systems 3.1.3 Grounding 3.2 FIELD QUALITY CONTROL 3.3 CLOSEOUT ACTIVITIES 3.3.1 Warranty 3.3.2 Record drawings -- End of Section Table of Contents -- SECTION 28 33 00.00 40 Page 2

USACE / NAVFAC / AFCEC / NASA UFGS-28 33 00.00 40 (February 2014) ----------------------------------- Preparing Activity: NASA Superseding UFGS-28 33 00.00 40 (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References are in agreement with UMRL dated July 2015 SECTION 28 33 00.00 40 FUEL-GAS DETECTION AND ALARM 02/14 NOTE: This guide specification covers the requirements for equipment, performance, and testing of stationary electrical instruments used for sensing the presence of combustible gases, or the deficiency of oxygen, in ambient air. Adhere to UFC 1-300-02 Unified Facilities Guide Specifications (UFGS) Format Standard when editing this guide specification or preparing new project specification sections. Edit this guide specification for project specific requirements by adding, deleting, or revising text. For bracketed items, choose applicable items(s) or insert appropriate information. Remove information and requirements not required in respective project, whether or not brackets are present. Comments, suggestions and recommended changes for this guide specification are welcome and should be submitted as a Criteria Change Request (CCR). PART 1 GENERAL NOTE: If Section 26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS is not included in the project specification, applicable requirements therefrom should be inserted and the following paragraph deleted. Section 26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS applies to work specified in this section. 1.1 REFERENCES NOTE: This paragraph is used to list the SECTION 28 33 00.00 40 Page 3

publications cited in the text of the guide specification. The publications are referred to in the text by basic designation only and listed in this paragraph by organization, designation, date, and title. Use the Reference Wizard's Check Reference feature when you add a RID outside of the Section's Reference Article to automatically place the reference in the Reference Article. Also use the Reference Wizard's Check Reference feature to update the issue dates. References not used in the text will automatically be deleted from this section of the project specification when you choose to reconcile references in the publish print process. The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only. COMPRESSED GAS ASSOCIATION (CGA) CGA P-39 (2015) Oxygen-Rich Atmospheres; 2nd Edition ELECTRONIC COMPONENTS INDUSTRY ASSOCIATION (ECIA) ECIA EIA/ECA 310-E (2005) Cabinets, Racks, Panels, and Associated Equipment INTERNATIONAL SOCIETY OF AUTOMATION (ISA) ANSI/ISA 12.13.01 (2002) Performance Requirements for Combustible Gas Detectors NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) NFPA 110 (2013) Standard for Emergency and Standby Power Systems NFPA 70 (2014; AMD 1 2013; Errata 1 2013; AMD 2 2013; Errata 2 2013; AMD 3 2014; Errata 3-4 2014; AMD 4-6 2014) National Electrical Code NFPA 72 (2013) National Fire Alarm and Signaling Code U.S. DEPARTMENT OF DEFENSE (DOD) MIL-STD-461 (2007; Rev F) Requirements for the Control of Electromagnetic Interference Characteristics of Subsystems and Equipment 1.2 SUBMITTALS SECTION 28 33 00.00 40 Page 4

NOTE: Review Submittal Description (SD) definitions in Section 01 33 00 SUBMITTAL PROCEDURES and edit the following list to reflect only the submittals required for the project. The Guide Specification technical editors have designated those items that require Government approval, due to their complexity or criticality, with a "G." Generally, other submittal items can be reviewed by the Contractor's Quality Control System. Only add a G to an item, if the submittal is sufficiently important or complex in context of the project. For submittals requiring Government approval on Army projects, a code of up to three characters within the submittal tags may be used following the "G" designation to indicate the approving authority. Codes for Army projects using the Resident Management System (RMS) are: "AE" for Architect-Engineer; "DO" for District Office (Engineering Division or other organization in the District Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project Office. Codes following the "G" typically are not used for Navy, Air Force, and NASA projects. An "S" following a submittal item indicates that the submittal is required for the Sustainability Notebook to fulfill federally mandated sustainable requirements in accordance with Section 01 33 29 SUSTAINABILITY REPORTING. Choose the first bracketed item for Navy, Air Force and NASA projects, or choose the second bracketed item for Army projects. Government approval is required for submittals with a "G" designation; submittals not having a "G" designation are [for Contractor Quality Control approval.][for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.] Submittals with an "S" are for inclusion in the Sustainability Notebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES: SD-01 Preconstruction Submittals Material, Equipment, and Fixture Lists[; G[, [ ]]] Manufacturer's Sample Warranty[; G[, [ ]]] SD-02 Shop Drawings Connection Diagrams[; G[, [ ]]] SD-03 Product Data SECTION 28 33 00.00 40 Page 5

[ SD-04 Samples Manufacturer's Catalog Data[; G[, [ ]]] Spare Parts Data[; G[, [ ]]] ] Samples[; G[, [ ]]] SD-07 Certificates Listing of Product Installations[; G[, [ ]]] SD-10 Operation and Maintenance Data Operation and Maintenance Manual[; G[, [ ]]] SD-11 Closeout Submittals Warranty[; G[, [ ]]] Record Drawings[; G[, [ ]]] 1.3 ADMINISTRATIVE REQUIREMENTS 1.3.1 Pre-Installation Meetings Within [30] [ ] days of Contract Award submit the following to the Contracting Officer for review: a. Material, equipment, and fixture lists b. Listing of product installations c. Manufacturer's sample warranty d. Manufacturer's catalog data e. Connection Diagrams f. Spare parts data When submitting Listing of Product Installations for combustible gas detection systems, include identification of at least 5 units, include identification of at least 5 units, similar to those proposed for use, that have been in successful service for a minimum period of 5 years. Also include such data as number of false alarms and malfunctions experienced while in service over a period of [ ] [2] years. 1.4 MAINTENANCE MATERIALS Submit [ ] [four] copies of an operation and maintenance manual giving complete instructions for the operation, inspection, testing, and maintenance of the system, including wiring diagrams and equipment malfunction checklist. 1.5 WARRANTY Submit a sample warranty for approval by the Contracting Officer. SECTION 28 33 00.00 40 Page 6

PART 2 PRODUCTS 2.1 SYSTEM DESCRIPTION NOTE: Local policies may dictate more elaborate procedures for qualification or approval of detector samples. 2.1.1 Design Requirements 2.1.1.1 Schematics Submit schematic drawings showing the specific equipment to be furnished; no "typical's". 2.1.1.2 Combustible Gas Environments Provide system with electrically supervised detection and [ ] [noncoded] alarm for combustible gas in Class I, Division 1, Group [ ] [C and D] locations, conforming to the applicable requirements of NFPA 70, NFPA 72, [and [ ]]. 2.1.1.3 Oxygen Deficient Atmospheres Provide system with electrically supervised detection and [ ] [noncoded] alarm of oxygen deficient atmospheres[, conforming to the applicable requirements of [ ]]. 2.1.2 Performance Requirements Provide system with performance conforming to the requirements of FM Approval Standard for Combustible Gas Detectors (Class Number 6310 and 6320), and [ ] [ANSI/ISA 12.13.01]. Ensure the operation of any detection device results in control unit relays automatically activating [remote alarms] [, and lights]. Ensure the name of the manufacturer and the serial numbers appear on all major components. Submit the following: a. Connection diagrams showing a complete conduit and wiring layout for the equipment to be furnished, including AWG size and type of wire, and number of conductors and connections to the equipment. b. Manufacturer's catalog data for the [combustible gas] [oxygen deficient atmospheres] detection systems including special tools necessary for the maintenance of the equipment. c. Material, equipment, and fixture lists including manufacturer's style or catalog numbers, specification and drawing reference numbers, independent testing laboratory reports, and related descriptive matter on the devices to be installed. 2.1.3 Electromagnetic Compatibility Ensure design of electrical and electronic systems operate without causing electromagnetic interference to, or malfunctioning due to electromagnetic interference from, other systems or equipment, and in accordance with SECTION 28 33 00.00 40 Page 7

applicable requirements of [ANSI/ISA 12.13.01] [ ] [MIL-STD-461]. 2.2 COMPONENTS 2.2.1 Control Unit Provide [ ] [dual] channel control unit, operating over a temperature range of [ ] [0 to 51] degrees C [32 to 125] degrees F, capable of monitoring [ ] [two] detectors. Provide control unit housed in a [ ] [weatherproof] cabinet suitable for [ ] [wall] mounting [in a Class I, Division 1, Group [ ] location] with [ ] [solid state] [plug-in] type relays and solid state rectifiers. 2.2.1.1 Control Circuits Provide control unit with plug-in type circuit boards, in a housing [conforming to ECIA EIA/ECA 310-E,] suitable for [Class 1, Group [ ]] [non-hazardous] locations. 2.2.1.2 Power Supply Component Provide [control unit with transformer,, rectifier, resistors, charger, batteries and other required power-supply components incorporated][a separate power-supply unit as approved for the application]. 2.2.1.3 Indicator Light and Reset Provide each control unit with [buttons for test, and] indicator lights for Power, [Malfunction,] and Alarm. Color code indicator lamps as follows: Power (green), [Malfunction [(yellow)] [[ ],] and Alarm [[ ]] [[red]]]. Zero, Alarm, with adjustable calibration settings. 2.2.1.4 Malfunction Circuits Ensure sensing circuits are monitored by individual malfunction circuits. Open circuit will activate malfunction light and operate relays for [remote] warning signal [and lights]. 2.2.1.5 Alarm NOTE: Exercise care to ensure options selected properly satisfy project requirements. Arrange the unit to operate alarm relays, activating audible and visible alarms, and continue operation until [[reset by a keyed switch] [silenced by a switch] [in] [on] the unit cabinet] [or] [the atmosphere returns to set conditions]. [Ensure reset key is not be removable until conditions have returned to normal.] [Ensure cabinet is locked by the same key used to reset the alarm relays.] [Ensure operation of the silencing switch lights an indicator lamp, which is plainly visible when the cabinet is closed.] Provide audible alarm and [ ] [red] rotating alarm beacon [as indicated]. SECTION 28 33 00.00 40 Page 8

Provide alarm system with capability to transmit individual alarms [to the base-wide fire reporting system] [to security] and/or [base-wide utility monitoring system]. 2.2.2 Detectors If detectors have not been previously qualified and approved for installation at this project location, submit samples of detectors. 2.2.2.1 Circuit Design Ensure detector circuit design is suitable for the types and numbers of detectors, as approved, and detector circuit current does not exceed ratings of the individual detectors and associated relays. Electrically supervise the circuits to the detectors for [grounds] [opens] and/or [shorts]. 2.2.2.2 Combustible Gas Detector Provide [ ] [diffusion] [sample draw] type Combustible Gas Detector (CGD) [with] [ ] [catalytic] sensor [meeting the requirements of ANSI/ISA 12.13.01,] in a housing suitable for the environment, and intrinsically safe for use in Class I, Division 1, Group [ ] locations. Provide combustible gas detector that detects combustible vapors that are produced from flammable liquids such as gasoline, ethanol, etc. Provide CGD with [ ] [4-20 ma] output signal, with an operating range of [ ] [minus 40 to 74] degrees C [minus 40 to 165] degrees F. Provide CGD with a visible and audible alarm that actuates at [ ] percent of LEL. [Provide CGD that includes a pre-alarm that actuates at [ ] percent.] 2.2.2.3 Oxygen Detector Provide [ ] [a paramagnetic] [an electrochemical] cell Oxygen Detector (OD) [meeting the requirements of CGA P-39], with a minimum shelf life of [ ] [6] months, and the following:. a. Output signal: [ ] [4-20 ma] b. Operating range: [ ] [4 to 33] degrees C [40 to 90] degrees F, [ ] [10 to 100] percent relative humidity c. Measurement: adjustable through a range of [ ] [0 to 25] percent oxygen-in-air d. Actuation level: set at 19.5 percent oxygen 2.2.3 Power Supply Provide with a [ ] [120]-volt, 60 Hz source power supply, and an alternate source of power, arranged to become energized automatically within at least [ten] [ ] seconds upon loss of normal power, in accordance with NFPA 110. SECTION 28 33 00.00 40 Page 9

2.3 EQUIPMENT Furnish fuses of each type and size required, and a [ ] [hydrogen] gas calibration kit. PART 3 EXECUTION 3.1 INSTALLATION 3.1.1 Combustible Gas Systems Ensure installation of combustible gas detection and alarm systems complies with NFPA 70 and applicable requirements of NFPA 72 [, and [ ]]. 3.1.2 Oxygen Deficiency Systems Ensure installation of oxygen detection and alarm systems complies with NFPA 70 [and] [ ]. 3.1.3 Grounding Install grounding in accordance with NFPA 70. 3.2 FIELD QUALITY CONTROL Conduct performance tests in accordance with ANSI/ISA 12.13.01 [ ]. Test operation of the entire system in operational and alarm modes. Activate each detector by [ ] [a hydrogen gas bottle representing the adjusted Lower Flammable Limit (LFL)]. Test malfunction feature for each control unit. 3.3 CLOSEOUT ACTIVITIES 3.3.1 Warranty Submit [3] [ ] signed original warranties to the Contracting Officer. 3.3.2 Record drawings Provide current factual information including deviations and amendments to the drawings, and concealed and visible changes in the work. When spot-type detectors are used, show by number the detectors in the exact sequence in which they are installed in the circuit. -- End of Section -- SECTION 28 33 00.00 40 Page 10