SINGLE-CHANNEL GAS-DETECTOR GAS ALARM DG510/1P

Size: px
Start display at page:

Download "SINGLE-CHANNEL GAS-DETECTOR GAS ALARM DG510/1P"

Transcription

1 SINGLE-CHANNEL GAS-DETECTOR GAS ALARM DG510/1P 2 Alarm Levels Bargraph + LED Indication of Gas Concentration Visual and Audible Signalization of Activated Alarm Levels 2 SPDT 5A/250V Output Relays Shock-Proof & Ex-Proof Sensor Housing Intrinsically Safe Shunt Barriers Back-up Accumulator Power Supply (optional) I. APPLICATION The single-channel gas-detector GAS ALARM DG510/1P is purposed for signaling anytime, when concentration of flammable and explosion-hazardous gases exceeds permissible limits. Its application includes mounting in pump units, gas stations, filling stations, dyeing cameras and other areas, where gaspowered equipment is used, or where combustible or toxic vapors and gases are found. The device consists of a microprocessor Control Block, which is to be mounted in areas with normal risk of fire, and a Sensor, which is placed in the hazardous zone. There are two programmable alarm levels for the gas concentration - pre-alarm and alarm level. The measured gas concentration is visualized on the LED bargraph indication in % LEL (lower explosion limit). If the gas concentration exceeds 10% LEL the prealarm level (AL1) and relay output LL are activated. LED AL1 is lighted. The relay output may operate a shut-off valve for stopping the gas flow, switch on a siren or fan, etc. If despite all taken measures the gas concentration exceeds 20% LEL the alarm level (AL2) and relay output HL are activated. A local buzzer is switched on if the gas concentration exceeds one of the alarm levels. The pre-alarm and alarm levels can be individually set. The alarm level cannot be set to a level greater than 50% LEL because of safety precautions. In case of Sensor or Cable Fault the LED "FLT" is lighted and the audible alarm is activated. On customer s request there can be mounted additionally a back-up power supply module, thus guaranteeing continuous working conditions for the gas detector. Switching to the back-up power supply is automatic in case of central power supply failure. The recommended capacity of a 12V accumulator is 6-8Аh. A lighted up Accu LED indicates the charging process of the accumulator from the electricity grid. Gas alarm s explosion-proof operation is guaranteed through shock- and explosion-proof Sensor housing EEx d IIC T5 and intrinsically safe shunt barriers ЕEx i a IIC. DELTA INSTRUMENTS Ltd. 23 A. Saharov blvd., Mladost 1, 1784 Sofia, Bulgaria Tel , , ; Fax: Web Site: [email protected]

2 II. TECHNICAL SPECIFICATIONS Power Supply 230V, 50Hz Detected Gas methane (natural gas), propane-butane, hydrogen, ammonia, ethylene, organic dissolvent vapors, fuel vapors, etc. Sensor catalytic (pelistor type) Pre-alarm level /АL1/ 10 % LEL programmable in the range 0 < AL1 < AL2 Alarm level /АL2/ 20 % LEL (in the range AL1 < AL2 50% LEL) Pre-alarm level AL1 output SPDT relay, 5A/250V /LL/ Alarm level AL2 output SPDT relay, 5A/250V /HL/ Indication bargraph, LED, 0-50% LEL Ambient temperature for sensors С Ambient temperature for control unit 0 50 С Reaction delay of sensors 20s Back-up power supply (optional) accumulator 12V DC Dimensions of control unit 1/8 DIN ( 96 x 48 x 132 mm ) Protection degree of control unit IP 30 Explosion-proof sensor housing ЕEx d IIC T5 Intrinsically safe shunt barriers EEx i a IIC CONNECTION SCHEME CONNECTION DIAGRAM Sensor cable connection legend: Vcc red wire INPUT white wire GND blue wire

3 Dimensions 96 ( width 48) 92 ( width 44) III. MOUNTING INSTRUCTIONS 3.1. Mount gas-detector to panel or metal construction in an area with normal risk of fire, fixing it by two supplied attaching clamps Connect the sensor to the blue marked intrinsically safe terminals via a 3-wire cable, according to the connection diagram Mount the sensor in explosion-hazardous area vertically (Sintered Filter downwards). When mounting, the following factors have to be considered: relative weight of the detected gas In case of gases with relative weight lower than that of the ambient air, place Sensor above the possible gas leakage location, or at the top possible place, where gas is accumulating. In case of gases, heavier than ambient air, place Sensor below the leakage location, or at the lowest possible place, where gases may accumulate. If there are airflows present, place Sensor between eventual leakage or accumulation locations, and possible combustion source. dust and water presence In areas with a high degree of dust loading, use a dust-proof filter, which at the same time should not obstruct the freeway from gas to sensor. In damp areas a water drop protection has to be made. vibration presence The Sensor is vibration-sensitive and should either be mounted in a place where vibrations are not present, or measures for their reduction have to be taken.

4 IV. OPERATING INSTRUCTIONS 4.1. CONTROL PANEL DESCRIPTION The control panel of the gas-detector consists of a control block for setting the alarm levels and a bargraph, indicating the actual value of gas concentration in % of LEL (lower explosion limit). The 5 LEDs indicate different gas-detector states, as listed in Table 1: NAME POWER FLT AL1 AL2 ACCU Table 1 FUNCTION After turning on the power supply follows an activation process of the sensor for appr. 1 min. During this time the AL1 and AL2 diodes are blinking. When this initialization has finished the both diodes go off, but the POWER LED remains on while there is power supply available. The FLT LED is activated only in case of faulty sensor or cable. Indicates the state of the output relay, corresponding to the pre-alarm level. Lighted up LED means that the relay LL is activated. After pressing the RESET button to deactivate the sound alarm signal the AL1 diode remains blinking. The LL relay stays active until the concentration drops below the set LEL percentage level. Indicates the state of the output relay, corresponding to the alarm level. Lighted up LED means that the relay HL is activated. After pressing the RESET button to deactivate the sound alarm signal the AL2 diode remains blinking. The HL relay stays active until the concentration drops below the set LEL percentage level. It is turned on only while charging the accumulator (only by existent backup power supply) The bargraph indicates the process value of measured concentration 0-50% of the lower explosion limit (LEL) of the corresponding gas. If the concentration has reached over any of the set alarm levels, the corresponding segment of the bargraph scale starts blinking AUDIBLE SIGNALIZATION By exceeding the concentration of the set pre-alarm and alarm levels is activated an integrated sound alarm. For the pre-alarm level AL1 the buzzer emits a short signal every 3 sec, while for the alarm level AL2 the sound signal is continuous. A short beep is emitted also every time when a button from the keypad is pressed VISUALIZING THE SET ALARM LEVELS By pressing the MODE button while in standard operation mode, the display switches to visualization of the set alarm levels. Only the bargraph s segments which correspond to the set alarm levels remain lighted. If the gas concentration is higher than any of the set alarm levels, the corresponding LED remains blinking as well. Another click on the MODE button leads back to standard operation mode.

5 4.4. TESTING THE ALARM OUTPUT RELAYS The output relays can be activated from the control panel in order to test the functionality of connected control mechanisms (siren, air ventilating system, gas-flow closing valve, power supply switching-off, etc.). By holding the TEST button pressed the relays are activated (AL1 and AL2 diodes become lighted up) and by releasing it the relays get deactivated DEACTIVATION OF THE AUDIBLE SIGNALIZATION By any activated alarm level the operator can use the keypad to turn off the sound alarm until the problem is solved. By active alarm state pressing the RESET button turns off the sound signalization until the concentration drops below the set alarm level. After the deactivation of the sound alarm, the corresponding alarm LED starts blinking. The output relays remain open (active) until normalizing the concentration under the set levels PROGRAMMING THE ALARM LEVELS ATTENTION: In the mode of programming the alarm levels the output relays are deactivated and the different LEDs serve as indication of the ongoing level setting regime. While in standard operation mode simultaneous pressing and holding the buttons MODE and ENT activates the mode for programming the alarm levels. - By simultaneously pressed MODE and ENT buttons the LED AL2 starts blinking, which indicates that the device is ready for adjusting the alarm level. The segment of the bargraph, which corresponds to the set alarm level, starts blinking, while the segment for pre-alarm level remains turned on. With buttons and the operator can move the blinking segment up and down the scale to select a new desired value. To save the newly selected value should be pressed the ENT button. Then if the value has been saved successfully the newly set segment should stop blinking. The alarm level can be set only between the value of pre-alarm level and 50% LEL. If the operator doesn t wish to change the alarm level, it is recommended to proceed to the pre-alarm level setting just by pressing the MODE button. - By pressing MODE after entering the mode for programming the alarm levels, the LED AL1 should start blinking, which indicates that the device is in regime for setting the pre-alarm level. Identically a new desired level can be selected by moving the lower blinking segment of the bargraph with and between 0% and the value of AL2 and saved by pressing ENT. - By pressing the MODE button once again, the indication returns to standard mode of operation and the gas-detector starts functioning with the newly selected level values.

6 V. GENERAL CONDITIONS GAS ALARM DG510/1P gas-detector may be used only in applications, approved by its manufacturer - DELTA INSTRUMENTS Ltd. Test and calibration have to be made every 12 months. The test overall performance will be ensured in a best way through a periodical maintenance servicing contract with the manufacturer. Device safe-operation guarantee is not valid, if DG510/1P is maintained with unauthorized personnel or if the corresponding to the term of question Test and Calibration Report is not available. CAUTION! It is absolutely forbidden to disassemble the explosion-proof sensor housing and change safety fuses or other electronic elements, connected to the proper functionality of the intrinsically safe shunt barriers! VII. REPAIR Any repair activities, concerning GAS ALARM DG510/1P Electronic Block and DGS 510 Sensor have to be carried out only in manufacturer DELTA INSTRUMENTS Ltd laboratories.

Manual for Fire Suppression & Methane Detection System

Manual for Fire Suppression & Methane Detection System Manual for Fire Suppression & Methane Detection System Fogmaker North America Post address: 150 Gordon Dr Exton, PA 19341 Delivery address: 150 Gordon Dr Exton, PA 19341 Tel: 610-265-3610 Fax: 610-265-8327

More information

600-GD & 600-GDL 600 SERIES GAS DETECTOR

600-GD & 600-GDL 600 SERIES GAS DETECTOR 600-GD & 600-GDL 600 SERIES GAS DETECTOR INSTALLATION AND OPERATING INSTRUCTIONS This page has been deliberately left blank. Page 1 Table of Contents 1 WARRANTY...3 2 IMPORTANT...3 3 CAUTIONS WHEN USING

More information

EX 2000/EX 2000 C/ GD 2000/GDP

EX 2000/EX 2000 C/ GD 2000/GDP Gas detectors EX 2000/EX 2000 C/ GD 2000/GDP 2000 Gas Discrimination (GD 2000 / GDP 2000) Explosimeters/ Catharometers Pocket size Long battery life High reliability New design for Enhanced performance

More information

Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors

Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors Continuous Monitoring of Flue and Combustible or Hazardous Gases and Vapors www.static-control.in 1 Introduction The detection or monitoring of flue gases and or hazardous gases has been a complex subject

More information

TMS TANK MANAGEMENT SYSTEM

TMS TANK MANAGEMENT SYSTEM TMS TANK MANAGEMENT SYSTEM Page 1 of 9 Operating Instructions GENERAL The Tank Management System is a bespoke design to control, monitor and accommodate efficient storage and dispensing of TMS. FUNCTIONS

More information

Introduction. Refrigerant Leak Detecting System. Feature and Benefits

Introduction. Refrigerant Leak Detecting System. Feature and Benefits PSC European Refrigeration Controls Catalogue Catalog Section 9 Product Bulletin PD-GAS-E Refrigerant Leak Detecting System Introduction This range of refrigerant leak detecting systems is designed for

More information

Fire Pump Controllers Remote Alarm Panels

Fire Pump Controllers Remote Alarm Panels Fire Pump Controllers Remote Alarm Panels Remote Alarm Panels 1.8 Remote Alarm Panels FDAP-M Electric... DFDAP-M Diesel... Product Specifications... 2 6 9 Features 1-1 DFDAP-M / FDAP-M Remote Alarm Panel

More information

BEP FD-2 CONTOUR MATRIX FUME DETECTOR

BEP FD-2 CONTOUR MATRIX FUME DETECTOR BEP FD-2 CONTOUR MATRIX FUME DETECTOR INSTALLATION AND OPERATING INSTRUCTIONS Table of Contents 1 WARRANTY...3 2 IMPORTANT...3 3 CAUTIONS WHEN USING GAS SENSORS...3 4 FEATURES...4 5 SPECIFICATION...4 6

More information

www.klmtechgroup.com TABLE OF CONTENT

www.klmtechgroup.com TABLE OF CONTENT Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 2 REFERENCES

More information

Buckeye Detection Systems Fixed Detection Systems Application Survey

Buckeye Detection Systems Fixed Detection Systems Application Survey Buckeye Detection Systems Fixed Detection Systems Application Survey Channel Partner Representative : Company Name: Representative: BDS Representative: Client Contact Information : Company Name: Company

More information

Fire & Security DETECTORS

Fire & Security DETECTORS Fire & Security DETECTORS Smoke Sensitivity 0.98 ~.0%/ft Obscuration Ceiling Spacing 50 foot rating for heat sensor Temperature Range 10ºC to 50ºC Humidity 0 to 95% RH, no condensation or icing Dimensions

More information

HUNTER-PRO 32 Ver. 3.8 Intruder Alarm System RXN-9/416 User Guide

HUNTER-PRO 32 Ver. 3.8 Intruder Alarm System RXN-9/416 User Guide HUNTER-PRO 32 Ver. 3.8 Intruder Alarm System RXN-9/416 User Guide PIMA Electronic Systems Ltd. 5 Hatzoref Street, Holon 58856, Israel +972-3-5587722 +972-3-5500442 [email protected] http://www.pima-alarms.com

More information

Conventional Fire Detection and Extinguishant Control System Specification

Conventional Fire Detection and Extinguishant Control System Specification Conventional Fire Detection and Extinguishant Control System Specification Page 1 of 9 Scope Furnish a complete 24VDC Conventional, electrically supervised, combined fire detection and extinguishant release

More information

Fire Alarm System Accessories

Fire Alarm System Accessories Approved by APPROVED Fire Alarm System Accessories FM Approved* Intrinsically Safe Devices Single and Dual Channel Isolated Barrier Modules Features Single or dual channel intrinsically safe, transformer

More information

Triple Waveband Infra-Red Flame Detection

Triple Waveband Infra-Red Flame Detection Minerva S200PLUS Ex ia Intrinsically Safe & Ex d Flameproof Solar Blind Flame Detectors Triple Waveband Infra-Red Flame Detection Key Features Unrivalled black body rejection over a wide range of source

More information

EXPLORER 4 MULTIPOINT

EXPLORER 4 MULTIPOINT EXPLORER 4 MULTIPOINT Sampling gas analyser EXPLORER 4 MULTIPOINT is a sampling gas analyser, with 4 gas detection sensors ( LEL,H2S, O2 CO ) reliable and in accordance of the Rules with 15 sampling points

More information

How To Use A Power Supply Unit (Upu)

How To Use A Power Supply Unit (Upu) BRAVER UPS (Uninterruptible Power System) User s Manual Safety CAUTION! This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user replaceable parts.

More information

UM-X Field display for continous level sensors

UM-X Field display for continous level sensors Technical Documentation Field display for continous level sensors 10/2007 Edition: 1 Item No.: 207120 FAFNIR GmbH Bahrenfelder Str. 19 D-22765 Hamburg Telephone: +49 (0)40-39 82 07-0 Fax: +49 (0)40-3 90

More information

User s Manual Before using the inverter, you need to read and save the safety instructions.

User s Manual Before using the inverter, you need to read and save the safety instructions. User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information

More information

User s Manual AURORA 1.2K/2.2K

User s Manual AURORA 1.2K/2.2K User s Manual AURORA 1.2K/2.2K Uninterruptible Power System Safety CAUTION This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user serviceable

More information

SPL 2-00/-01 OPERATION INSTRUCTIONS

SPL 2-00/-01 OPERATION INSTRUCTIONS SPL 2-00/-01 OPERATION INSTRUCTIONS Powerline Ethernet Adapter 500 Mbps EN Read and keep Operation Instructions SPL 2-00/-01 Safety Notes Do NOT use this product near water, for example, in a wet basement

More information

Q U A D S C A N I I GENERAL User Interface Enclosure Display QUADSCAN II Temperature Range RECEIVER DISPLAY Sensor Weight Optional Relay Enclosure

Q U A D S C A N I I GENERAL User Interface Enclosure Display QUADSCAN II Temperature Range RECEIVER DISPLAY Sensor Weight Optional Relay Enclosure QUADSCAN II SERIES 7400 ONE TO FOUR CHANNEL RECEIVER QUADSCAN II SERIES 7400 ONE TO FOUR CHANNEL RECEIVER Centralizes Monitoring and Alarming for Gas Transmitters and Fire Detectors. The QuadScan II receiver

More information

A.1. a Division of Pittway Corporation. Documento: M-010.1-MGAS-ENG. Edizione: 01/1997 Rev.:

A.1. a Division of Pittway Corporation. Documento: M-010.1-MGAS-ENG. Edizione: 01/1997 Rev.: Documento: M-010.1-MGAS-ENG Edizione: 01/1997 Rev.: A.1 a Division of Pittway Corporation FRONT PANEL & VISUAL INDICATIONS GENERAL TROUBLE GENERAL PROGRAMMING IN PROGRESS ENABLE/ALARM/TROUBLE (ZONE 1 ALARM

More information

Shunt lock function 3066 Operator Instructions

Shunt lock function 3066 Operator Instructions Shunt lock function 3066 Operator Instructions Version: January 2004 Contents Deactivation unit Deactivation unit Deactivation unit Activation unit with configuration MASTER Alarm System 1.0 Shunt lock

More information

WD-AMX Water Detection Controllers

WD-AMX Water Detection Controllers Page 1 of 5 WD-AMX Water Detection Controllers Features: Benefit: LED Status of leak status VFC output Audible alarm Auto or manual reset alarm output Uses an isolated AC signal which prevents oxidation

More information

CO2 Alarm. Operation. Application

CO2 Alarm. Operation. Application CO Alarm 100-77V AC Supply Voltage Two pre-configured alarm and control thresholds Thresholds factory set to customer requirements on dispersive infrared sensing technology Optional internal audible alarm

More information

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10 TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified

More information

UFGS-28 33 00.00 40 (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS

UFGS-28 33 00.00 40 (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-28 33 00.00 40 (February 2014) ----------------------------------- Preparing Activity: NASA Superseding UFGS-28 33 00.00 40 (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

ER-1 Emergency Response System INSTALLATION & PROGRAMMING GUIDE

ER-1 Emergency Response System INSTALLATION & PROGRAMMING GUIDE Emergency Response System INSTALLATION & PROGRAMMING GUIDE Copyright micron 2005 Contents Product Description 3 Console Operation Overview 4 Console Wiring Diagram 5 User Manual 6 Transmitter Assembly

More information

CLASSIFICATION NOTES

CLASSIFICATION NOTES CLASSIFICATION NOTES Type Approval, Installation and Testing of Water Level Detectors on Bulk Carriers and Single Hold Cargo Ships other than Bulk Carriers General Information This edition of the classification

More information

Short Form Catalogue. Alarm Systems. Reliable Supervision and Control

Short Form Catalogue. Alarm Systems. Reliable Supervision and Control Short Form Catalogue Alarm Systems Reliable Supervision and Control Alarm Monitors and Indicators The SELCO product range includes a number of alarm monitors and indicator panels for use in numerous applications.

More information

GSM home alarm system s manual

GSM home alarm system s manual GSM home alarm system s manual I. Main features: 1, Eight wireless LED zone, and four wired zone 2, Two-way to communication 3, The system supports the GSM cell phones, no need the fixed telephone line.

More information

Intruder alarm. Pro 21 TM /Solfà TM. Installation and operating instructions N0064EG2/00

Intruder alarm. Pro 21 TM /Solfà TM. Installation and operating instructions N0064EG2/00 Intruder alarm Pro TM /Solfà TM Installation and operating instructions N00EG/00 Contents General presentation..., Presentation of a system with zones..., Product guide... Typical installation Preparation...

More information

HERZ-Thermal Actuators

HERZ-Thermal Actuators HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01

More information

DALI RC BASIC SO. Control unit Operating instructions

DALI RC BASIC SO. Control unit Operating instructions DALI RC BASIC SO Control unit Operating instructions Contents Safety... 4 General instructions 4 Safety instructions 4 Description... 5 Purpose and application 5 Function 5 Light control 5 Brightness

More information

USER S MANUAL. MaxPower 400-600 UPS. Uninterruptible Power System 28-2MAXPO0018

USER S MANUAL. MaxPower 400-600 UPS. Uninterruptible Power System 28-2MAXPO0018 USER S MANUAL MaxPower 400-600 UPS Uninterruptible Power System 28-2MAXPO0018 IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions for models MaxPower 400 and

More information

CAPTAIN 6. USER GUIDE System ver. 6.0. 6 Zones Intruder Alarm System. PIMA Electronic Systems Ltd. www.pima-alarms.com

CAPTAIN 6. USER GUIDE System ver. 6.0. 6 Zones Intruder Alarm System. PIMA Electronic Systems Ltd. www.pima-alarms.com CAPTAIN 6 6 Zones Intruder Alarm System USER GUIDE System ver. 6.0 PIMA Electronic Systems Ltd. www.pima-alarms.com P/N 4410049, G2 XX en, Jan. 2010 2 CAPTAIN 6 User Guide SAFETY INSTRUCTIONS Your CAPTAIN-i

More information

Business/Home GSM. Alarm System(III) Installation and Users guide

Business/Home GSM. Alarm System(III) Installation and Users guide Business/Home GSM Alarm System(III) Installation and Users guide I. General information: GSM 900/1800/1900 bands, can be used all over the world. Full duplex communication with the base. Monitor environment

More information

PROXIMITY CARD READERS C-10, C-20, C60, C70

PROXIMITY CARD READERS C-10, C-20, C60, C70 Installation Manual PROXIMITY CARD READERS C-10, C-20, C60, C70 VERSION 1.0 CONTENTS 1. General information................................. 3 2. Technical data......................... 4 3. Connection

More information

CBD-233. Fire Alarm and Detection Systems

CBD-233. Fire Alarm and Detection Systems Page 1 of 5 CBD-233. Fire Alarm and Detection Systems Originally published August 1984. R.H.L. McEwen Fire alarm systems are normally required by building codes. In the case of new buildings, this is usually

More information

Chapter 9 N.C. C. N.O. Single-Pole Double-Throw

Chapter 9 N.C. C. N.O. Single-Pole Double-Throw rather than providing multiple choices. The sensor modules used may only be suitable for use with the matching controller so it is wise to read the specifications to make sure the unit suits your application.

More information

Business/Home. GSM Alarm system

Business/Home. GSM Alarm system Business/Home GSM Alarm system Installation and Users guide Profile For a better understanding of this product, please read this user manual thoroughly before using it. I. General information: GSM 900/1800/1900

More information

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply) transmitter (2 wire) / switch for continuous or On/Off Control Indication, monitoring, transmitting and continuous or On/Off control in one device Output signal 4...20 ma, 2-wire for continuous control

More information

ISpac isolators. the perfect system

ISpac isolators. the perfect system ISpac isolators the perfect system 2 safe isolation Handling flammable and potentially explosive substances is part and parcel of everyday operations in many branches of industry. However, it is not possible

More information

EzFlex Combustible Gas Leak Detector Model EZ40

EzFlex Combustible Gas Leak Detector Model EZ40 User's Guide EzFlex Combustible Gas Leak Detector Model EZ40 Introduction Congratulations on your purchase of the Extech EZ40 Combustible Gas Leak Detector. The EZ40 detects the presence of combustible

More information

ACTIVE 5 ENGINEERING MANUAL

ACTIVE 5 ENGINEERING MANUAL ACTIVE 5 ENGINEERING MANUAL C & K Systems Ltd C031-066 Issue 3 THE ACTIVE 5 INSTALLATION MANUAL. Date: Feb 1997 INTRODUCTION. The Active 5 is a microprocessor controlled intruder alarm panel. It features

More information

AC-115 Compact Networked Single Door Controller. Installation and User Manual

AC-115 Compact Networked Single Door Controller. Installation and User Manual AC-115 Compact Networked Single Controller Installation and User Manual December 2007 Table of Contents Table of Contents 1. Introduction...5 1.1 Key Features... 6 1.2 Technical Specifications... 7 2.

More information

SECURITY SYSTEM ADP-CAN

SECURITY SYSTEM ADP-CAN INSTALLATION INSTRUCTION SECURITY SYSTEM ADP-CAN Introduction Motorcar security system ADP-CAN is for motorcars provided with CAN net. It is for the work with the motorcar factory security systems or remote

More information

Intelligent GSM Auto-Dial Alarm System

Intelligent GSM Auto-Dial Alarm System Auto-dial Alarm System Intelligent GSM Auto-Dial Alarm System Profile For a better understanding of this product, please read this user manual thoroughly before using it. 2013.2.V1.0 Auto-dial Alarm System

More information

COLOR VIDEO DOOR PHONE CDV-71BE/D

COLOR VIDEO DOOR PHONE CDV-71BE/D COLOR VIDEO DOOR PHONE CDV-71BE/D 513-11, Sangdaewon-dong, Jungwon-gu, Seongnam-si, Gyeonggi-do, Korea Int l Business Dept. : Tel.; +82-31-7393-540~550 Fax.; +82-31-745-2133 Web site : www.commax.com Printed

More information

Business/Home GSM Alarm System. Installation and User Manual

Business/Home GSM Alarm System. Installation and User Manual Business/Home GSM Alarm System Installation and User Manual Brief Introduction: GSM 900/1800/1900 bands, can be used in most parts of the world Full duplex communication with the host Monitor the scene

More information

NL708 (XWA11V) Walk-In Temp / Door /Alarm / Light Module

NL708 (XWA11V) Walk-In Temp / Door /Alarm / Light Module NL708 (XWA11V) Walk-In Temp / Door /Alarm / Light Module 1. General Description 1 2. General Warnings 1 3. Interface 2 4. Temp Alarms Setting 3 5. Programming 3 6. Light Management 4 7. Installation and

More information

Using your LED Plus keypad

Using your LED Plus keypad Using your LED Plus keypad System 238 System 2316 System 238i System 2316i Part Number 5-051-372-00 Rev B Thank you for purchasing this C&K alarm system Your system is one of the most powerful and advanced

More information

Installation Instructions for Alarm Module Kit A043F059

Installation Instructions for Alarm Module Kit A043F059 Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line

More information

Ferrostat Speed Sensor Series DSF Explosion Proof Versions EEx

Ferrostat Speed Sensor Series DSF Explosion Proof Versions EEx Ferrostat Speed Sensor Series DSF Explosion Proof Versions EEx DSF..10.**.HV Ex ATEX Operating Instructions 374E-64368 Valid from lot nr. 0103 General Function Use in potentially explosive environment

More information

LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL

LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL EPSOLAR LS1024B / LS2024B/ LS3024B Solar Charge Controller USER MANUAL Thank you very much for selecting our product! This manual offers important information and suggestions with respect to installation,

More information

Solution 880 Operators Manual ISSUE 1.10

Solution 880 Operators Manual ISSUE 1.10 Solution 880 Operators Manual ISSUE 1.10 Solution 880 Operators Manual Copyright 2001 by, SYDNEY, AUSTRALIA Document Part Number MA408O DOCUMENT ISSUE 1.10 Printed 25 May 2001 This documentation is provided

More information

GSM ALARM SYSTEM USER MANUAL

GSM ALARM SYSTEM USER MANUAL GSM ALARM SYSTEM USER MANUAL 1. Instruction The alarm system is based on GSM network. With a GSM SIM card, it can be used wherever you want and no need to connect any wire, which is convenient and easy

More information

User s Guide. Security Systems D220

User s Guide. Security Systems D220 User s Guide Security Systems D220 Table of Contents About This User s Guide... 3 Introduction... 3 Security System Basics... 4 Controlled Points... 5 24-Hour Points... 6 Keypad Keys... 6 Keypad Lights...

More information

Inductive sensor NI10-M18-Y1X-H1141

Inductive sensor NI10-M18-Y1X-H1141 ATEX category II 1 G, Ex zone 0 ATEX category II 1 D, Ex zone 20 SIL2 as per IEC 61508 Threaded barrel, M18 x 1 Chrome-plated brass DC 2-wire, nom. 8.2 VDC Output acc. to DIN EN 60947-5-6 (NA- MUR) M12

More information

616, 626, 636 & 646 Keypads

616, 626, 636 & 646 Keypads 616, 626, 636 & 646 Keypads User s Manual TABLE OF CONTENTS 1.0 BASIC OPERATION...2 2.0 ACCESS CODES...4 3.0 ARMING & DISARMING...6 4.0 PANIC ZONES...13 5.0 KEY ACCESS PROGRAMMING.14 6.0 ADDITIONAL FEATURES...15

More information

FIRST ALERT INSTRUCTION MANUAL FOR FA 270 KEYPADS SECURITY SYSTEM

FIRST ALERT INSTRUCTION MANUAL FOR FA 270 KEYPADS SECURITY SYSTEM FIRST ALERT INSTRUCTION MANUAL FOR FA 270 KEYPADS SECURITY SYSTEM Page 0 Table of Contents Introduction 1 System Basics.. 1 Burglary Protection.. 1 Fire Protection.. 1 Security Codes. 1 Zones and Partitions

More information

Advanced Fencing and Security Technologies Ltd

Advanced Fencing and Security Technologies Ltd G.M. Advanced Fencing and Security Technologies Ltd P.O. Box 2327 Kfar Sava Industrial Area 44425, Israel Tel +972-9-7662965 Fax + 972-9-7662964 E-mail: [email protected] Website: www.gmsecurity.com

More information

Ammonia Detection System Codes and Design Specifications

Ammonia Detection System Codes and Design Specifications Ammonia Detection System Codes and Design Specifications December 28, 2015 Revision 5 920 N Trade Winds Pkwy Columbia, MO 65201 Ammonia detection system codes and design specifications Following is a discussion

More information

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL RANCO INSTALLATION INSTRUCTIONS ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL Relay Electrical Ratings PRODUCT DESCRIPTION The Ranco ETC is a microprocessor-based family of electronic temperature controls,

More information

INSTALLATION MANUAL 3RP / 5RP 4-BUTTON SERIES VEHICLE SECURITY SYSTEMS

INSTALLATION MANUAL 3RP / 5RP 4-BUTTON SERIES VEHICLE SECURITY SYSTEMS 3RP / 5RP 4-BUTTON SERIES VEHICLE SECURITY SYSTEMS INSTALLATION MANUAL Before you begin the installation Read the INSTRUCTIONS! Always use a multi-meter when verifying vehicle wiring. Before mounting the

More information

1R / 4-BUTTON SERIES

1R / 4-BUTTON SERIES Button 1 1R / 4-BUTTON SERIES VEHICLE SECURITY SYSTEM Standard Features: Two 4-Button Remote Transmitters Status indicator (LED) Valet / override switch Multi-tone siren Dual stage impact detector Remote

More information

Shutter Actuator Standard, 4-fold, 230 VAC, MDRC RA/S 4.230.1, GH Q631 0076 R0111. ABB i-bus EIB

Shutter Actuator Standard, 4-fold, 230 VAC, MDRC RA/S 4.230.1, GH Q631 0076 R0111. ABB i-bus EIB , GH Q631 0076 R0111 2CDC 071 240 F0003 The Shutter Actuator Standard is used to control a maximum of four independent 230 VAC drives for positioning shutters, blinds, awnings and other hangings as well

More information

USER MANUAL OPERATION AND USE OF CAR WITH. Diego G3 / NEVO SEQUENTIAL GAS INJECTION SYSTEM

USER MANUAL OPERATION AND USE OF CAR WITH. Diego G3 / NEVO SEQUENTIAL GAS INJECTION SYSTEM USER MANUAL OPERATION AND USE OF CAR WITH Diego G3 / NEVO SEQUENTIAL GAS INJECTION SYSTEM Page 2 z 7 Table of contents 1. STARTING THE ENGINE... 3 2. CONTROL PANEL... 3 2.1 Indication of the current level

More information

Fire Alarm Control Panel. Family. Operating Manual

Fire Alarm Control Panel. Family. Operating Manual Fire Alarm Control Panel Family Operating Manual CONTENTS System Description AH-03312 System Characteristics... Fire Signal Receiving Board Description-4L... Fire Signal Receiving Board Description-8L...

More information

DC-8706K Auto Dial Alarm System

DC-8706K Auto Dial Alarm System DC-8706K Auto Dial Alarm System User Guide Basic Contents: 1x the host unit; 1x wireless door (window) magnet; 1x wireless infrared detector; 2x remote control; 1x siren; 1x phone core; 1x AC to DC power

More information

14. Troubleshooting Guide

14. Troubleshooting Guide 14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include

More information

User s Information Guide R1A

User s Information Guide R1A HSC505-R Home Security Controller - User Manual Release R1a Pi HSC505 and Pi HSC505R Home Security Controller User s Information Guide R1A Page 1 QD Dynamics (Pty) Ltd reserves the right to make changes

More information

BREEAM CRITERIA WATER LEAK DETECTION SYSTEM Type WG2 - CONTROL PANEL CONNECTIONS

BREEAM CRITERIA WATER LEAK DETECTION SYSTEM Type WG2 - CONTROL PANEL CONNECTIONS BREEAM CRITERIA WATER LEAK DETECTION SYSTEM Type WG2 - CONTROL PANEL CONNECTIONS WG2 Dimensions: LxHXW: 26 x 14.5 x 29.5 cm INTERNAL Alarm Terminals EXTERNAL Alarm Terminals WG2 Control Unit WaterGuard

More information

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data. 425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and

More information

PhoneWatch Smart Security System User Manual - Domonial

PhoneWatch Smart Security System User Manual - Domonial PW0002 10/13 Customer Support: 1850 753 753 PhoneWatch Ltd., Unit 3/4, Sandyford Park, Burton Hall Rd, Sandyford Industrial Estate, Dublin 18. Email: [email protected] PhoneWatch Smart Security System

More information

ICP-CP500. User's Guide ICP-CP500 Codepads

ICP-CP500. User's Guide ICP-CP500 Codepads ICP-CP500 EN User's Guide ICP-CP500 Codepads ICP-CP500 User's Guide 1.0 ICP-CP500 Series Codepads Overview EN 2 1.0 ICP-CP500 Series Codepads Overview The codepad is the communications interface between

More information

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems EN Security System CM705B CM705B - Universal Expander Module The CM705B universal expander provides a cost effective way

More information

INSTRUCTION MANUAL PC255O

INSTRUCTION MANUAL PC255O INSTRUCTION MANUAL PC255O Canadian Department of Communications Notice NOTICE: The Canadian Department of Communications label identifies certified equipment. This certification means that the equipment

More information

TT 49 MICROPROCESSOR-BASED DIGITAL ELECTRONIC TIMER. OPERATING INSTRUCTIONS Vr. 01 (ENG) - cod.: ISTR 06050. TECNOLOGIC S.p.A.

TT 49 MICROPROCESSOR-BASED DIGITAL ELECTRONIC TIMER. OPERATING INSTRUCTIONS Vr. 01 (ENG) - cod.: ISTR 06050. TECNOLOGIC S.p.A. TT 49 MICROPROCESSOR-BASED DIGITAL ELECTRONIC TIMER INDEX..2 2 2. 2.2 2.3 3 3. 3.2 3.3 3.4 4 4. 4.2 4.3 4.4 4.5 5 5. 5.2 6 6. 6.2 7 7. 7.2 7.3 7.4 7.5 INSTRUMENT DESCRIPTION GENERAL DESCRIPTION FRONT PANEL

More information

IDS X-Series User Manual 700-398-01D Issued July 2012

IDS X-Series User Manual 700-398-01D Issued July 2012 1 2 Contents 1. Introduction to the IDS X-Series Panels... 7 2. Before Operating Your Alarm System... 7 3. Understanding the Keypad LEDs... 8 3.1 Viewing Data on an LED Keypad... 12 3.1.1 LED Status Indicators...

More information

Redundancy Module QUINT-DIODE/40

Redundancy Module QUINT-DIODE/40 Redundancy Module QUT DIODE provides: 00% decoupling of power supplies connected in parallel Can be installed in potentially explosive areas Load currents up to 60 A supported Easy assembly by snapping

More information

HomeSafe-Basic VT-PS99E. User s Manual. PSTN Home Alarm System. Page: 1 / 15

HomeSafe-Basic VT-PS99E. User s Manual. PSTN Home Alarm System. Page: 1 / 15 HomeSafe-Basic VT-PS99E User s Manual PSTN Home Alarm System Page: 1 / 15 Table of Contents 1. Product Overview:... 3 2. Main Functions & Features... 3 3. For Your Safety... 4 4. VT-PS99E Characteristics...

More information

Electronic Pressure Switch EDS 300

Electronic Pressure Switch EDS 300 Electronic Pressure Switch EDS 300 User manual Page 2 of 16 Content 1. Functions of the EDS 300...3 2. Mounting...3 3. Operating keys on the membrane keypad...4 4. Digital display...4 5. Output function...5

More information

LW-2000-3A. Wireless Auto Dial Alarm System. Sentry Plus User Manual By Global Gadgets

LW-2000-3A. Wireless Auto Dial Alarm System. Sentry Plus User Manual By Global Gadgets LW-2000-3A Wireless Auto Dial Alarm System Sentry Plus User Manual By Global Gadgets Main Features Simple to use keypad for operation and control. The system can store up to 9 telephone numbers: positions

More information

MOBILE CALL GSM alarm system

MOBILE CALL GSM alarm system MOBILE CALL GSM alarm system User s Manual Profile For a better understanding of this product, please read this user manual thoroughly before using it. - 1 - Catalogue: Function Introduction 2 SMS Number

More information

SECTION 23 90 13 NOx, CO AND NATURAL GAS DETECTION, MONITORING AND ALARM CONTROL SYSTEMS

SECTION 23 90 13 NOx, CO AND NATURAL GAS DETECTION, MONITORING AND ALARM CONTROL SYSTEMS SECTION 23 90 13 NOx, CO AND NATURAL GAS DETECTION, MONITORING AND ALARM CONTROL SYSTEMS PART 1 - GENERAL 1.01 Section Includes A. Requirements for provision of the Natural Gas (CH4), Carbon Monoxide (CO)

More information

Drayton Digistat +2RF/+3RF

Drayton Digistat +2RF/+3RF /+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer

More information

EX-TECH SAS CP/PB 150 EXPLOSIONPROOF MANUAL CALL POINT/ PUSH BOTTON TECHNICAL MANUAL

EX-TECH SAS CP/PB 150 EXPLOSIONPROOF MANUAL CALL POINT/ PUSH BOTTON TECHNICAL MANUAL PRODUCT NAME: CP/PB -150- EXPLOSION-PROOF-MANUAL CALL POINT/ PUSH BOTTON DOC NO.: EX-TECH SAS-12-CP-PB150-TM REV01 EXPLOSION-PROOF MANUAL CALL POINT/ PUSH BOTTON II 2GD EPL Gb, Db Ex d IIC T6, IP66 Ex

More information

Switch Actuator, 8-fold, 10 A, MDRC AT/S 8.10.1, GH Q631 0075 R0111

Switch Actuator, 8-fold, 10 A, MDRC AT/S 8.10.1, GH Q631 0075 R0111 , GH Q631 0075 R0111 The 8-fold switch actuator is a DIN rail mounted device for insertion in the distribution board. It is connected to the EIB via a bus terminal. In the event of bus voltage failure,

More information

642 LCD Keypad User Manual

642 LCD Keypad User Manual 642 LCD Keypad User Manual TABLE OF CONTENTS Introduction...3 Legend... 3 Basic Operation...5 Keypad Indicator Lights... 5 Visual Feedback... 5 Auditory Feedback... 6 Info List... 7 Access Codes...8 User

More information

Firewall. Propane flame projector Safety instructions and operating manual

Firewall. Propane flame projector Safety instructions and operating manual Firewall Propane flame projector Safety instructions and operating manual TBF-PyroTec GmbH Lichterfelder Str. 5A 21502 Geesthacht Tel.: +49(0)4152 157 9950 [email protected] www.tbf-pyrotec.de 1 Flame

More information

SECTION 13850 DETECTION AND ALARM

SECTION 13850 DETECTION AND ALARM SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring

More information

USER S MANUAL HSC-24A

USER S MANUAL HSC-24A AIRREX AIR CONDITIONER USER S MANUAL HSC-24A Thank you for purchasing an AIRREX AIR CONDITIONER. BEFORE operation please read this user s manual carefully. Keep this manual readily available. It is ESSENTIAL

More information

COMPLETE MANUAL. Version: Optic. September 2015 (English), version 1.0. EnergyOT Optic Developed and Manufactured by Genoa Spark, lda Made in Portugal

COMPLETE MANUAL. Version: Optic. September 2015 (English), version 1.0. EnergyOT Optic Developed and Manufactured by Genoa Spark, lda Made in Portugal Version: Optic COMPLETE MANUAL September 2015 (English), version 1.0. EnergyOT Optic Developed and Manufactured by Genoa Spark, lda Made in Portugal Specifications are subject to change without notice.

More information

Thermo Top - Troubleshooting Tree

Thermo Top - Troubleshooting Tree Thermo Top - Troubleshooting Tree 07-15-2002 CAUTION Troubleshooting requires comprehensive knowledge about the structure and theory of operation of the Thermo Top heater. Troubleshooting and repairs may

More information

Magnetic field sensor for pneumatic cylinders BIM-INT-Y1X-H1141

Magnetic field sensor for pneumatic cylinders BIM-INT-Y1X-H1141 ATEX category II 1 G, Ex zone 0 ATEX category II 1 D, Ex zone 20 SIL2 as per IEC 61508 Rectangular, height 6mm Plastic, PA12 Magnetic-inductive sensor DC 2-wire, nom. 8.2 VDC Output acc. to DIN EN 60947-5-6

More information

ACS-30-EU-EMDR-10-MOD

ACS-30-EU-EMDR-10-MOD Multi-application heat tracing Control and Monitoring in commercial and residential buildings Roof & Gutter de-icing sensor module Technical Information Approvals Module IP rating Ambient operating temperature

More information

DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS. Construction Automotive Industry

DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS.  Construction Automotive Industry DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS www.rehau.com Construction Automotive Industry SCOPE This guide gives instruction regarding REHAU Programmable Digital Thermostat installation and operation.

More information