NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL



Similar documents
MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

INSTALLATION INSTRUCTIONS MC95HAE-1 MASTER CONTROLLER

Water Leak Detection System

Fire Pump Controllers Remote Alarm Panels

HP 5 Microprocessor Control for Mammoth Water Source Heat Pumps

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions V1 Rev A 11/12)

Master Time Clock MTC-200 MTC-400 MTC-600. Users Manual

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

Electric Panel Pump Control System. Operation, Maintenance and Installation Manual

AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

AMI MARINE (UK) LTD BRIDGE NAVIGATIONAL WATCH ALARM SYSTEM (BNWAS) Operation Manual KW810

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

Understanding Emergency Power Off (EPO)

Contractors Guide Central Inverter System Installation

Advantium 2 Plus Alarm

Operating Manual for the Electronic Built-in Interval Timer. Micro II (Countdown Timer)

Chapter 9 N.C. C. N.O. Single-Pole Double-Throw

INSTALLATION INSTRUCTIONS

IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB

Contact Center CC-165 INSTALLATION & USER'S GUIDE

MTS Power Products MIAMI FL ATS-22AG. Automatic Transfer Switch And Control PLC Operator s Manual

A.1. a Division of Pittway Corporation. Documento: M MGAS-ENG. Edizione: 01/1997 Rev.:

Bypass transfer switch mechanisms

SIS-PM / SiS-PM-841 / SIS-PMS User Manual. Table of contents

SECTION DETECTION AND ALARM

REGULINE 600VA / 1000VA REGULATOR USER MANUAL

HUNTER-PRO 32 Ver. 3.8 Intruder Alarm System RXN-9/416 User Guide

ALARM ANNUNCIATOR ME INSTRUCTION MANUAL

SWITCHGEAR. EGP Switchgear

ViZion Installation Guide

INSTALLATION/PROGRAMMING INSTRUCTIONS E4KP ENTRYCHECK

Conventional Fire Detection and Extinguishant Control System Specification

HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS

DC-8706K Auto Dial Alarm System

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

Operation and Installation Manual

4 Starts to flash when the system triggers an alarm/fault

SMS Alarm Messenger. Setup Software Guide. SMSPro_Setup. Revision [Version 2.2]

EDI Distributor Control Interface Wiring and Setup Instructions

Instruction Manual. 2in1 LAN Tester & Multimeter. Model: LA-1011

NL708 (XWA11V) Walk-In Temp / Door /Alarm / Light Module

CSP Combined Series. Telephone Door Entry. with. Proximity Keyfob Access

In this section we tell you how to set the fault mode selection plug, key your I/O chassis, install your module and make your wiring connections.

MANUAL FOR MODEL MP30 ELECTRIC MOTOR DRIVEN LIMITED SERVICE CONTROLLER

Controller Automation, Model II+

STERILIZERS, LABORATORY DRYING OVENS

PARAGON ELECTRIC, INC. LIQUID LEVEL CONTROLLER USER MANUAL MODELS: LLC-I, LLC-II AND TELEMETRY OPTIONS

Manual for Fire Suppression & Methane Detection System

Applied Electronics. Commercial Dimming System UPDATE NOTICE

SECURITY SYSTEM ADP-CAN

Series /16 DIN Multi-Mode Bar Graph Display Timer TIMERS PRODUCT HIGHLIGHTS

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat

DTW Works Master Specification Version 2006

Lighting Controls ! WARNING RISK OF ELECTRIC SHOCK. Installation Instructions DESCRIPTION

HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply

ACTIVE 5 ENGINEERING MANUAL

MSL1000 Monitored Serial Link Interface Manual V1.01

Owner s Guide Guide du propriétaire Guía para el usuario TH115-AF-GB-10. Programmable thermostat Thermostat programmable Termostato programable

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

TSn SERIES Surge Protective Device

Freeze Protection Thermostats MODELS SST 2. Installation and Operation Manual

AlarmSense 2-wire detection and alarm system. Product Guide

OPL BASIC. Dosing System for Professional Laundry machines. Contents

Car Alarm Series 2 B 2 Buttons

ACS-30-EU-EMDR-10-MOD

Combi B Alarm box. Mounting instructions

WIRELESS ALARM KIT INSTRUCTION MANUAL COMPLETE ALARM SYSTEM FOR HOME OR BUSINESS. Model Number: IT214054

TrueAlarm Fire Alarm Systems

Rain+Birdt. Simple To Set Timer (SST) Setup & Operation Instructions. English RAIN BIRD ( ) or visit

USER MANUAL CHARGING STATIONS FOR ELECTRIC VEHICLES

DC LOAD TESTING Gian Trento June 18 th, 2004

RMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions

EGCP-3 LS Revision L. Explanation of Software Changes Made for the EGCP-3 LS Control. Application Note 51294

The Child Reminder System Installation Manual

SmartVFD Frame 4 Wiring Diagrams and Dimensional Drawings

CONTENTS QUICK SETUP & INSTALLATION USER MANUAL. SUPA8 Quick Setup & User Manual

Water Leak Detector BA/LDT Accessories Termination and Troubleshooting

HM-W536 Install Guide

Application/Connection Examples

WD-AMX Water Detection Controllers

NC-12 Modbus Application

COLOR VIDEO DOOR PHONE CDV-71BE/D

Switchgear and Metal-Enclosed Bus

LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

ANTI-THEFT SYSTEM Volvo 850 DESCRIPTION & OPERATION BASIC ALARM ACCESSORIES & EQUIPMENT Volvo Anti-Theft Systems

INSTALLATION GUIDE. FCC ID NOTICE

NELSON HEAT TRACING SYSTEMS

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W

Table of Contents. 1. Introduction PDU Package Function Installation Web Interface...7

Digital Keypad Use s Manual

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

Single Station Remote Alarm

SECTION 13XXX CONTROL DESCRIPTION (DICP Models NC, 412, 622, 826, 1030)

Transcription:

NELSON VOLTAGE MONITOR INSTALLATION & PROGRAMMING MANUAL

CONTENTS GENERAL INFORMATION...3 INSTALLATION...3 FIELD WIRING...4 PROGRAMMING...4 Circuit Monitor Options...5 Power Frequency...5 Alarm Silence Time-out...6 Scan Speed...6 Alarm Reset Auto/Manual...6 OPERATION...8 Alarm Delay...9 Alarm Silence Button...9 Digital Display Window...9 Sheet 2 of 9

GENERAL INFORMATION The Nelson VM Circuit Monitor is a scanning microprocessor system which sequentially monitors and displays each circuit number and the status of each circuit. The VM is environmentally hardened and requires no protected operative environment. It can be located in a control room or out in a plant. The low voltage, optically isolated design allows the unit to be installed in Division 2 Hazardous Locations. The VM is ideally suited for application where voltage monitoring of critical circuits is required. Monitoring of conventional circuit breakers, ground fault circuit breakers, and monitor wire heater applications and others are easily accommodated. INSTALLATION When routing conduit to panel, avoid top entry into the VM enclosure. Top conduit entry provides a potential moisture path to the electronic circuit boards. Bottom conduit entry is recommended. If top entry cannot be avoided, avoid the area directly over the circuit boards. Drip loops as shown are recommended for side entry and top entry when top entry cannot be avoided. A drip loop is a dip or bend in the circuit wire to block or shed moisture which may follow a wire to the circuit boards! WARNING: Moisture intrusion can damage the VM electronic circuit boards; do not place conduit entry directly over the circuit boards. Top Top Entry (avoid if possible) Enclosure Wall DO NOT USE THESE AREAS FOR CONDUIT ENTRY! Drip Loop Side Entry Drip Loop Display Wire Bottom Entry (recommended) INTERIOR Figure 1 VM Panel Enclosure EXTERIOR Sheet 3 of 9

FIELD WIRING Typical wiring diagrams are included in this manual for field wiring. These are located at the end of this manual. PROGRAMMING The VM is shipped with programming to monitor all available circuits. With this configuration, all 24 circuits will be scanned for voltage alarms. Alarm delay is set for 5 seconds, alarm reset is automatic, and the display speed is fast. Each of these features and options will be covered on the next few pages. However, the system is suitable to be powered in the existing configuration. When programming refer to Figure 10, which is also provided inside the door of the VM enclosure. If all 24 circuits are not active (monitor not required) remove the corresponding programming jumper. Programming can be changed in the field by removing or adding option jumpers as needed. 1-4 1-4 9-12 13-16 17-20 21-24 opt. opt. 9-12 13-16 17-20 21-24 Side View Figure 2 Programming of the VM is accomplished by adding or removing the plastic program jumpers located on the scanner board. Handeling Tab Programming Pins! WARNING: DO NOT TOUCH THE PROGRAMMING PINS. Contact Area Figure 3 Programming Jumper Sheet 4 of 9

Circuit Monitor Options The top 6 rows of option jumpers in the jumper programming area are the circuit monitor jumpers. As the system is shipped, all circuits available in the system will be monitored, or active. If a circuit is deactivated, remove the appropriate programming pin, and the circuit will be skipped in the monitor sequence. 1-4 9-12 13-16 17-20 21-24 Figure 4 Example: If circuit #6 is to be de-activated, remove this jumper. This circuit will not be scanned or monitored until the programming pin is replaced. 1-4 Figure 5 Power Frequency As shipped from factory, the system is suitable for 60hz. If 50hz is required, a jumper must be placed on option #8 programming pin. Open for 60hz - Closed for 50hz - Figure 6 Sheet 5 of 9

Alarm Silence Time-out This establishes the amount of time and acknowledged alarm is silenced before re-alarm. If an alarm is acknowledged (which silences the remote alarm relay), and the voltage problem is not corrected, the system will re-activate the remote alarm relay. Alarm Silence Time-out Figure 7 Scan Speed This is a customer preference option. Recommended practice is to leave this jumper on fast scan (option #16), for installation and set-up, then removed for slow scan operation. Scan Speed Figure 8 Alarm Reset Auto / Manual In auto reset mode (pin installed): The alarm status and remote alarm will clear automatically when a circuit fault clears. In manual mode (pin removed): When a fault is cleared, both the scanner display and the remote alarm output will remain in alarm until the Alarm Reset Button is pressed. (See the OPERATION section.) Auto Reset Figure 9 Note: After any change in the system program, press the Alarm Reset Button on the front of the enclosure. This will reset all options and finalize any changes that have been made by adding or removing programming pins. Sheet 6 of 9

TYPICAL FOR ALL CKTS. OPTION PINS LOCATED ON SCANNER BOARD GC-562 CIRCUIT MONITOR OPTION OPEN: CIRCUIT DISABLED-WILL NOT BE MONITORED CLOSED: CIRCUIT FUNCTIONS-WILL BE MONITORED 1-4 NOTE: JUMPER PLUGS ARE USED TO "CLOSE" OR CONNECT A SET OF PINS. ALL REFERENCES TO "CLOSED" MEANS A JUMPER PLUG IS INSTALLED. A REFERENCE TO " OPEN" MEANS THE JUMPER IS REMOVED. 9-12 13-16 17-20 OPEN: 60HZ. CLOSED: 50HZ ALARM SILENCE TIMEOUT (BEFORE RENUNCIATION) IN MINUTES. (TIMEOUT IS 24 HRS. IF NO PINS CLOSED) OPEN: SLOW (NORMAL) CLOSED: FAST OPEN: EXTERNAL RESET CLOSED: AUTO RESET (ALARM RESETS WHEN FAULT CLEARS) ALARM DELAY IN SECONDS. (TIMEOUT IS 5 MIN. IF NO PINS CLOSED) THIS IS AN ALARM DELAY TO PREVENT TRANSIENT CONDITIONS THAT OCCUR DURING HEATER LOAD SWITCHING FROM TRIGGERING FALSE ALARMS. A 5 MIN. TIMEOUT SHOULD BE USED FOR SELF-REG. HEATER CABLES. 21-24 PROGRAMMING OPTION FEATURES NELSON CABLE MONITOR CAT. VM Figure 10 Sheet 7 of 9

OPERATION After the installation and programming is completed and 120VAC has been applied to TB-1, turn the power switch to ON. For a moment both red and green L.E.D. bars will light, then the system will start scanning. The green light bar will always appear under each active circuit the first scan after powering up or resetting alarms. The green bars will continue to appear under the circuit number until a loss of voltage to the voltage input terminal occurs. Then after the programmed alarm delay time-out, the red bar will light-up and the remote alarm relay will energize. This will continue until power is restored to the heater circuit (and the Alarm Reset Button is pressed if the system is in manual reset mode).! WARNING: During normal operation of the system, the cabinet door will not need to be opened. Therefore, keep door closed and completely fastened to protect the electronics from dirt and moisture. Panel I.D. No. S.O. Number Digital Display Window Alarm Silence Button Alarm Reset Button Figure 11 VM Panel Enclosure Sheet 8 of 9

Alarm Delay This is customer preference. This option establishes the minimum time delay before a loss of voltage condition is registered by the scanner the option ranged is from 5 seconds to 5 minutes. The times shown are in seconds and are additive. A longer time is recommended to prevent alarming of temporary power interruptions. Example: For a 65 second delay; place jumpers on the 60 second and the 5 second pins. 5 sec. 60 sec. 65 sec. Alarm Delay Figure 12 Alarm Silence Button This button will temporarily silence the remote alarm (up to 24 hours depending on the program pins; (see the PROGRAMMING section for Alarm Silence Time-out ). While corrective actions are being taken on failed circuit(s) the alarm will re-enunciate if a new circuit fails when the system is silenced. Pressing the Alarm Silence Button will silence the remote alarm relay and reset the timer. When voltage has been restored to all of the failed circuits, press the Alarm Reset Button to clear all alarms from the system if the Manual Reset has been selected. Digital Display Window As circuits are scanned by the system the circuit numbers being scanned are displayed here. Under the circuit number block is a status area. Conditions: 1. No light bar energized below the circuit number indicates the circuit is de-energized. This is a non-alarm condition. 2. The voltage green light bar energized indicates that the circuit voltage is present. This is a non-alarm condition. 3. The alarm red light bar energized indicates that voltage is not present when the circuit should be energized. This is an alarm condition. Nelson Heat Tracing Systems products are supplied with a limited warranty. Complete Terms and Conditions may be found on Nelson's website at www.nelsonheaters.com. Sheet 9 of 9

Copyright 2005