SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL



Similar documents
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design

Application/Connection Examples

3. TYPES OF SERVICE AVAILABLE. 3.1 Scope

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

Installation Guide Solar Connect-11

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

Solar monitoring gateway quick start guide

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument D

Approved Meter Sockets and Cabinets

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80

Rule Fast Track Analysis for National Life Insurance Co.

LEHI CITY POWER NET METERING STANDARDS For Customer-Owned Electric Generating Systems

Current Transformer (CT) Selection Guide

DANGER! HIGH VOLTAGE HAZARD

National Craft Assessment and Certification Program S P E C I F I C A T I O N S

AC and DC Drive System Installation Information

Request for Proposals for Photovoltaic System Installation

A. Shop Drawing submittals shall include, but not be limited to, the following:

Chapter 24. Three-Phase Voltage Generation

IRRIGATION PUMPING Table of Contents - Section 900

Section 10 Electric Switchboards: 0 Through 600 Volts

Power Meter Series 700

ELECTRIC UTILITY SERVICE EQUIPMENT REQUIREMENTS COMMITTEE, EUSERC

How To Get A Power Line Extension

BACnet Automation Interface Module (Network Version)

Equipment: Power Supply, DAI, Variable resistance (8311), Variable inductance (8321)

Short Circuit Current Calculations

SWITCHGEAR. EGP Switchgear

Power Plant Electrical Distribution Systems

FTW 175 VERIZON Wireless Monitoring System Reference Manual Part Number VERIZON

Three-Phase Electric Power Distribution for Computer Data Centers

12VDC MAGNETIC LED DIMMABLE POWER SUPPLIES SPEC SHEET DIGEST

SmartBlock Power and Energy Monitor With Rogowski Coil (di/dt) Support HE579ACM302

SOLAR PV STANDARD ELECTRICAL PLAN Microinverter Systems for Single Family Dwellings

TSn SERIES Surge Protective Device

CURRENT TRANSFORMERS INSTALLATION GUIDE

OEM Manual MODEL 2350 ELECTRONIC DUAL CYLINDER SCALE

3-Phase AC Calculations Revisited

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

E-Version SECTION CHLORINATION SYSTEM PART 1 - GENERAL PART 2 - PRODUCT

Unified requirements for systems with voltages above 1 kv up to 15 kv

SECTION 16002C CAMPUS CENTRAL METERING SYSTEM DESIGN CRITERIA 1. General

Learning Module 13: Panelboards and Switchboards. 101 Basic Series

Owner s Manual. For Automatic Transfer Switch Amp, Service Entrance/Non-Service Entrance

LIEBERT VNSA Installation Sheet

SECTION ELECTRICAL ACCEPTANCE TESTS

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions

Cable/Conduit Conversion

pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2, /0.65/0.

READ THIS MANUAL BEFORE PROCEEDING WITH THE INSTALLATION. FAILURE TO FOLLOW THE INSTALLATION INSTRUCTIONS MAY VOID YOUR WARRANTY!

PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit

73 Chevy C10 Ammeter to Volt Gauge Conversion Mark and Michael Olson 2013 Rev 1.0

Three-phase AC circuits

Water Leak Detection System

FIT TIER 2 Application

Radial Distribution Test Feeders

Argus Technologies Pathfinder10kW to Cordex3.6kW Shelf Replacement Procedure

Sample - No Commercial Use

HM-W536 Install Guide

TECHNICAL BRIEF. Commercial PV in Australia and New Zealand Using the Enphase Microinverter System

Contractors Guide Central Inverter System Installation

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Modular I/O System Analog and Digital Interface Modules

San Diego Community College District

Ampere's Law. Introduction. times the current enclosed in that loop: Ampere's Law states that the line integral of B and dl over a closed path is 0

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

Parallel Redundant Uninterruptible Power Supply

NEI-30 VEI-30 Dinion Infrared Imager NEI VEI Series. Quick Install Guide

Project Name: Nortrax Section Project No: SURGE PROTECTION DEVICES Page 1

How To Choose A Transformer

Primary and Secondary Electrical Distribution Systems

Motor Circuit Protection Tables

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

VOLTAGE REGULATOR AND PARALLEL OPERATION

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.

Current Transformers

Air-cooled Generator Battery Charger Installation Guidelines

Customer Low-Voltage Switchboards Service Cable Terminal Compartment Arrangements and Clearances

Electronic Control Devices The European Product Catalogue 2007

48 SERIES Relay interface modules 10 A

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

CURRENT TRANSFORMER MODEL 546 UL1015 #16 AWG LEAD WIRE, STANDARD LENGTH IS 24" 1 X

BASIC NEC CODE RULES AND DESIGN PRACTICE

Product Guide. Low voltage grounding system. Answers for industry.

Owner's/Installation Manual

Case Study - University at Buffalo State University of New York. Lower Energy Usage Costs with Real Time Monitoring, Campus-wide

SECTION LOW VOLTAGE LIGHTING CONTROLS

Transcription:

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated hardware within a separate metering compartment of new or existing switchgear or switchboard. B. For new switchgear or switchboard installation, the Power Monitor, CT's, PT's, shorting block, fusing, and wiring shall be provided by and installed by the switchgear or switchboard manufacturer within a separate metering section of the gear. C. For existing switchgear or switchboard installation, the Power Monitor, CT's, PT's, shorting block, fusing, and wiring shall be provided and installed by the Electrical Contractor. D. [Note to AE: For special circumstances and with prior approval by the Owner, Power Monitor and accessories can be mounted within a 20-inch by 20-inch by 10-inch Hoffman enclosure with the display mounted on front hinged cover.] E. Standard utility metering shall be required for pole mounted or outdoor installations. See Section 26 27 13 - Electrical Metering. F. The Power Monitor CT s and PT s shall be different that the CT s and PT s used for electrical metering in the same unit substation. 1.2 SECTION INCLUDES A. Power monitoring devices B. Enclosures, including 1. Equipment requirements 2. Wiring requirements 3. Grounding requirements 4. Labeling requirements C. Electrical apparatus, including but not limited to: 1. Switchgear and switchboard components in support of the power monitoring devices. D. Current transformers E. Potential transformers F. Communications networks such as: 1. Ethernet 2. ControlNet 3. Data Highway Plus 4. Remote I/O 5. DeviceNet 1.3 DEFINITIONS A. PM Power Monitor B. CT Current Transformer U OF I FACILITIES STANDARDS 26 09 13-1 POWER MONITOR FOR ELECTRICAL,

C. PT Potential Transformer 1.4 INSTALLATION DESCRIPTION A. The full installation shall consist of digital power monitors, support and/or supply hardware and appropriate communication networks. The equipment shall be fully installed and tested. B. A 1-inch conduit for dedicated Ethernet connection (with unique IP address) shall be installed for communication. This should be coordinated with the U of I Campus Information Technologies and Educational Services (CITES) department. C. The steam condensate meter shall have pulsed output capability. A separate 3/4-inch conduit with a twisted pair signal cable shall be installed by the electrical Contractor from the steam condensate meter to the electric meter within the switchgear or switchboard metering section so that the pulse output from the steam condensate meter can be monitored by the Power Monitors Status Input "S1". D. The water meter shall have pulse output capability. A separate 3/4-inch conduit and signal cable shall be installed by the electrical Contractor from the water meter to the electric meter within the switchgear or switchboard metering section so that the pulse output from the water meter can be monitored by the Power Monitors Status Input "S2". 1.5 TESTS, INSPECTION AND DOCUMENTATION A. The fully installed and configured system shall be tested. It is important that PM s be installed according to the instructions listed on instruction sheet. PM s which are not installed correctly will produce erroneous readings, which can result in unfair energy allocations, injury or death. B. One power monitoring checklist, available from the Energy Service Division within F&S, shall be completed for each power monitor installed. C. Only qualified personnel shall execute this procedure. Installation personnel shall be properly trained in working with electrical circuits. Carefully follow all health and safety procedures. D. Record the name or number of the switchboard and breaker to which the PM is connected. If a breaker has a name, record the name. If a breaker is a spare or space, record the breaker number. E. Current transformers 1. Write down the CT ratio. 2. Write down all CT nameplate data including manufacturer, part number, accuracy class, etc. 3. Verify that CT s are adequately mounted and secured. 4. Verify the polarity of the CT s. The dotted or H1 side of the CT opening shall always face the source of power. In the case of tie breakers, the dotted or H1 side of the CT opening shall always face the lower numbered or lettered switchboard or bus. Neutral CT s shall match the polarity of the phase CT s on the same PM. 5. Verify that the CT secondary wiring is correct. When CT s are properly installed, a positive current flowing into the dotted or H1 side of the CT opening will produce a positive current flowing out of the dotted or X1 terminal of the CT. The dotted or X1 terminal of the CT shall be connected to the appropriate I+ current input terminal on the PM. 6. Verify that CT shorting blocks are correctly installed. 7. Verify that the CT s are connected to the correct phase inputs. Proper CT phasing is important. F. Voltage transformers / connections (PT s are required when the Line-to-Ground voltage is greater than 120 volts.) U OF I FACILITIES STANDARDS 26 09 13-2 POWER MONITOR FOR ELECTRICAL,

1. Write down the PT ratio. If the PM is connected directly to the line, note the nominal line-to-line voltage for PM s. 2. Write down all PT nameplate data including manufacturer, part number, accuracy class, etc. 3. Verify that PT s are adequately mounted and secured. 4. Verify that PT s and PM inputs are properly fused. 5. Note the location of the voltage connection. Load-side of the breaker. Correct if necessary to the load-side. 6. Verify that the PT s or voltage connections are terminated on the correct phase inputs. Proper PT phasing is important and must match the CT phasing. G. PM display 1. Using an RMS reading digital multi-meter, measure the line-to-line and line-to-neutral voltages and verify that the readings observed on the DMM match those observed on the PM display module. Note that values shall agree to within the sum of the accuracy s for the PM, DMM and PT s. 2. Using an RMS reading clamp-on ammeter, measure the line and neutral currents and verify that the readings observed on the ammeter match those observed on the PM display module. Note that values shall agree to within the sum of the accuracies for the PM, clamp-on ammeter and CT s. 3. Verify that the power (kw), reactive power (KVAR) and total apparent power (KVA) values are positive for loads. 4. Verify that the power factor is reasonable. Inductive load shall have a lagging or negative power factor. Capacitive loads shall have a leading or positive power factor. 5. Using the PM display module, verify that the phase rotation is correct (ABC). 6. As each test is completed, the Energy Service Division within F&S representative shall initial the checklist signifying that the test has been successfully completed. PART 2 - PRODUCTS 2.1 SYSTEM COMPONENTS 2.2 MATERIALS A. Unless otherwise noted, all materials and equipment supplied shall be new, of the type, capacity and quality specified and free from defect. 2.3 WIRING CONVENTIONS 1. AC power shall be provided by the 120 v. or 208 volt service or by the fused secondary side of the PT s. a. 120VAC, 240VAC and 480VA hot conductors shall be black. b. All grounded, neutral conductors shall be white or natural gray. 2. AC control. Control wiring originates from where AC power has been switched by relay contacts or is connected to the secondary side of a transformer. a. All hot control conductors up to 120VAC shall be red. b. All grounded, neutral conductors shall be white or natural gray. 3. Externally powered interlock circuits, where control power is supplied from an external power source. a. All hot control conductors shall be yellow. b. All grounded, neutral conductors shall be white or natural gray. U OF I FACILITIES STANDARDS 26 09 13-3 POWER MONITOR FOR ELECTRICAL,

4. DC control and power a. All + conductors shall be blue. b. All - conductors shall be blue with a white trace. 5. All ground conductors shall be green. 6. Potential transformer and/or voltage tap conductors shall be black. 7. Current transformer wiring shall be red. B. All wiring shall be of the following minimum size: 1. Power wiring shall be #12 AWG SIS wire. 2. Ground terminals shall be connected to the enclosure ground bus with #8 AWG SIS wire. 3. Current transformer secondary wiring shall be #10 AWG SIS wire. C. Cabling: 1. All communications wiring shall cross AC conductors at a 90-degree angle. Where communication wiring must run parallel to AC conductors, a minimum of 2 separation shall be maintained. 2. Data Highway Plus (DH+) and Remote I/O (R I/O) communications circuits shall be wired with Belden 9463 or equivalent, twin-axial, shielded cable. 3. DeviceNet communications shall be wired with flat media Dnet cable A-B type 1485C- P1E or equal. 4. ControlNet communications shall be wired with quad-shielded coax type RG-6, A-B type 1786-RG6F or equal. 5. Ethernet communications shall be wired with screened twisted pair cable, (ScTP). D. Termination: 1. Conductors connected to terminal blocks without pressure-plates shall be terminated with insulated, fork-tongue type crimp lugs. 2. Conductors connected to studs, grounding screws and meters shall be terminated with insulated, ring-type crimp lugs. 3. Conductors for the current transformers shall be terminated with insulated, ring-type crimp lugs. 2.4 LABELING REQUIREMENTS A. An engraved device tag showing the name of each device, as shown on the electrical and mechanical Drawings shall be placed on the sub-panel as near as practicable to each physical device. Engraved device tags shall have a white face with black lettering. B. Engraved device tags shall be no smaller than 1/2 inch high by 1-1/2 inches long with 1/4 inch high text and shall be affixed to the sub-panel with adhesive. C. Incoming AC power conductors shall be labeled as follows: 1. Single-phase 120VAC circuits: L1 and N. 2. Single-phase 240VAC and 480VAC circuits: L1 and L2. 3. All three phase circuits: L1, L2 and L3. 4. Current transformer secondary leads to Ix+ and Ix-: where x = phase representation, (1, 2, 3 etc.) D. Wiring labels shall be printed on white shrink tubing and applied such that they are read from left to right on wires which terminate horizontally and from top to bottom on wires which terminate vertically. On wires where the numeral 0 appears, the numeral shall be printed with a slash in order to distinguish it from the letter O (example: Ø). U OF I FACILITIES STANDARDS 26 09 13-4 POWER MONITOR FOR ELECTRICAL,

2.5 TRANSFORMER REQUIREMENTS A. Current transformers shall be of Metering class and Revenue grade. There shall be 1 CT for each phase and the neutral conductor if present. 1. Transformers shall be chosen for proper voltage and insulation class. 2. Accuracy shall be 0.1%. 3. Accuracy Class 0.3. 4. CT s shall be selected with a burden rating sufficient to supply the total/summation of the circuit wiring VA and the VA of the power monitor (0.5VA for PMII or PM3000). Total burden shall not exceed the rated burden of the CT. 5. Ratio, primary current to secondary current, such that the primary is equal to that of the system current and the secondary current is 5 Amps. 6. Neutral transformer (if required) ratings and ratio shall be equal to those of the phase CT s. B. Separate Potential (Voltage) transformers (required above 120 V. to ground) Number of PT s supplied shall be as required for the system configuration to be monitored; i.e. two for single phase, two for 3 phase-3 wire Open-Delta, three for 3 phase-3 wire Wye and Delta and three for 3 phase-4 wire Wye. 1. Power Monitor(s) shall have separate voltage transformers. 2. Transformers shall be chosen for proper voltage and insulation class and BIL Rating. 3. Accuracy shall be 0.1%. a. Accuracy Class 0.3. 4. Burden shall be determined by summation of the VA of the circuit wiring and VA of connected power monitor. 5. Ratio, primary voltage to secondary voltage, such that the primary is equal to that of the system voltage and secondary voltage is 120V. PART 3 - EXECUTION 3.1 INSTALLATION A. Switchboard or Switchgear Manufacturer shall provide all labor, materials, and equipment to install the system in accordance with the Energy Service Division within F&S instructions as indicated and as specified herein. B. Installation Contractor shall verify the following items: 1. All power monitors shall be properly installed and wired in accordance with the manufacturer s recommendations. 2. All communications cables have been properly installed and all devices are connected. 3. All hardware is free from damage, clean and ready for startup. 4. All transformers are solidly mounted and secure. 5. All transformer polarities are consistent and point to the supply of power. C. Good workmanship shall be evidenced in the installation of all electrical materials equipment. All materials shall be firmly secured in place and adequately supported and permanent. The requirements of the codes are minimum standards. The recommendations of the National Electrical Contractors Association Standard of Installation shall be followed except where otherwise specifically directed. 3.2 TRANSFORMER INSTALLATION REQUIREMENTS A. Current transformer secondary shall be wired to shorting terminal blocks. 1. Shorting terminal block, rated 600V, 30A. U OF I FACILITIES STANDARDS 26 09 13-5 POWER MONITOR FOR ELECTRICAL,

2. Block shall be one piece and shall be UL compliant. 3. Terminals shall accommodate #10 AWG with ring type crimp lugs. 4. Terminals shall have barrier separations and be at a minimum spacing of 13/32. 5. Adjacent terminals shall be at a spacing of 5/8 inch. 6. Number of poles shall be based upon number of CT s utilized. (2 poles per CT). 7. Shorting terminal blocks shall be located in the low voltage compartment with the PM and shall be accessible from the front of the enclosure. 8. There shall be no intermediate connections made to the CT circuit between the CT and the shorting terminal block. 9. CT s shall be grounded at the Shorting terminal block. 10. There shall be no additional terminations to allow for shipping splits. If CT circuit wiring is to cross a shipping split, the secondary leads shall be coiled back for shipment and connected to the shorting block at installation. 11. Current transformers shall be solidly mounted and secured. 12. Polarity markings shall be always point/face to the source of power. B. Separate potential transformers connection requirements: 1. Primary protection shall consist of a 30 ampere 3-pole switch (or circuit breaker) and pull out fuse blocks, rated 600V, 30A. with Class J type fusing. Bussmann Fusing shall be sized per NEC for PT's. 2. Number of poles shall be based upon the PT configuration of the system. 3. Switch and Fuse blocks shall be located in the low voltage compartment with the PM and shall be accessible from the front of the enclosure. 4. Primary connections shall be made at the secondary, or load side of the circuit disconnecting means, i.e. circuit breaker. C. Separate potential, (Voltage) tap connection requirements to Power Monitor line terminals L1 and L2 (208-240 Volts). 1. Power Monitor(s) shall have separate voltage taps. 2. Protection shall consist of pull out fuse blocks, rated 600V, 30A. with 1 Amp, Class J type Bussmann fusing. 3. One wire from each phase (Phase A & B) shall be from the tap point(s) to the PM (L1 & L2 Terminals) 4. Fuse blocks shall be located in the low voltage compartment with the PM and shall be accessible from the front of the enclosure. 5. Tap connections shall be made at the secondary, or load, side of the circuit disconnect means, i.e. circuit breaker. 3.3 POWER MONITOR MODULE(S) INSTALLATION REQUIREMENTS A. Power Monitor shall be installed in the low voltage compartment and shall be accessible from the front of the enclosure. END OF SECTION 26 09 13 This section of the U of I Facilities Standards establishes minimum requirements only. It should not be used as a complete specification. U OF I FACILITIES STANDARDS 26 09 13-6 POWER MONITOR FOR ELECTRICAL,