FL ballasts Electronic dimming. PCA T5 BASIC lp Y II, 14 80 W BASIC T5



Similar documents
FL ballasts Electronic dimming. PCA T5 ECO lp Y II, W ECO T5

FL ballasts Electronic dimming. PCA T5 EXCEL one4all lp Y II, W EXCEL T5

FL ballasts Electronic dimming. PCA T5 EXCEL one4all lp Y, 3x14/24 W and 4x14/24 W EXCEL T5

PHASED OUT. Digital dimmable ballasts for fluorescent lamps EXCEL one4all series. PCA TCL EXCEL one4all, W Compact and T5c fluorescent lamps

PHASED OUT. Digital dimmable ballasts for fluorescent lamps ECO series. PCA TCL ECO, W Compact and T5c fluorescent lamps

Electronic ballasts for fluorescent lamps Products for special applications. PC BASIC, 4 28 W Electronic ballast for system output < 25 W

of the LED control gear Compact dimming Uconverter LCAI 55W 900mA 1750mA ECO SR ECO series

LED Driver Compact dimming. Udriver LCAI 100W 900mA 1750mA ECO SR ECO series

LED Driver Compact dimming. Udriver LCAI 35W 350mA 900mA ECO C ECO series

Emergency lighting units EM powerled

basicdim DGC Compact control module

LED control gear. LED control gear

LED light engine / OLED LED compact. Uengine STARK DLE PREMIUM system data sheet STARK DLE

LED light engine / OLED LED linear / area. Umodule STARK QLE G3 lens CLASSIC umodule QLE

LED light engine / OLED LED compact. Umodule STARK CLE CLASSIC / CLE CLASSIC umodule CLE

Digital gear for fluorescent lamps

Product and functional description

LED light engine / OLED LED linear /area. Umodule STARK LLE CLASSIC STARK LLE. Ordering data

DALI DIM/CONVERTER CONTROL (DC NV) 1 10V (0-10 V) analog DALI Converter with (Multi-) Sensor-control and 1 and 2-Switch dim functions

Busch-Watchdog Presence EIB Type:

DALI RC BASIC SO. Control unit Operating instructions

15 Series - Electronic step relay and dimmer. Features SERIE

PWM-90 series IP67 TRC ELECTRONICS, INC Mean Well PWM-90 Series

Installation and User Guide

Operating instructions IV / 2007

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Operating instructions II / 2004

PWM-60 series IP67 TRC ELECTRONICS, INC

ABB i-bus KNX Switch Actuator, x-fold, 16/20 A, MDRC SA/S x , 2CDG 110 1xx R0011

Safety technique. Emergency stop module BO 5988 safemaster

is then retained absolutely without interruption.

650W Single Output Power Supply

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start * see variants. Applications.

650W Single Output Power Supply 15V 24V. 27V 48V Rated Current. 0 ~ 100A 0 ~ 50A 0 ~ 40A 0 ~ 27A 0 ~ 24A 0 ~ 13.6A Rated Power

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

1000W Single Output Power Supply 15V 24V. Protection type: Total Power limit, Latch-style (Recovery after reset AC power ON or inhibit)

APPENDIX A PIN-OUT OF RJ12 / RJ45 CONNECTORS. RJ12 connectors

Technical Manual Functional Description for S800-RSU-H / S800W-RSU 2CCC413022M Schaffhausen 1 / 10

Tilt switches N3 / N4... MEMS technology, one or two axis. Use. Options. + long lifetime and highly reliability due to mechanism-free MEMS technology

HERZ-Thermal Actuators

Switch Actuator, 8-fold, 10 A, MDRC AT/S , GH Q R0111

How To Use A Power Supply On A Powerline 2.2 (Ai)

O WA-120U series IP W Single Output Switching Power Supply. Features. Aplications

Technical data. General specifications. Signal voltage V DC Signal duration. 1 s Input 2. Signal voltage. 1 s Analog output.

38 Series - Relay interface modules A

EBDSPIR-DD, EBDSPIR-DD-IP

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

PHASED OUT. LED light engine / OLED LED compact. Umodule SLE G4 6mm R SNC, SLE G4 10mm R SNC umodule SLE ESSENCE

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Chrome DIN Rail Power Supply 24V 91.2W 1 Phase (Class II & NEC Class 2) / DRC-24V100W1AZ

Shutter Actuator Standard, 4-fold, 230 VAC, MDRC RA/S , GH Q R0111. ABB i-bus EIB

connecdim Gateway G1 Ethernet TCP/IP to DALI

FREEZE Canopy. Canopy lighting. QCS Quick-Connection-System. Daylight. Neutral White. Fresh Meat. Packed Meat

LED DIMMING A HELPFUL GUIDE...

COOL Shelf Quick Connect

Product Manual. ABB i-bus KNX. Universal Dim Actuator, MDRC UD/S Intelligent Installation Systems ABB

Chrome DIN Rail Power Supply 12V 54W 1 Phase (Class II & NEC Class 2) / DRC-12V60W1AG

VX 2400 Dimmer User's Manual

Fundamentals of Power

DIGITAL CONTROLS OVERVIEW

Rack mounted telephone- and leased line modem for industrial applications

OPTOTRONIC LED Power Supply OT180W/UNV/800C/2DIMLT2/P6 - Technical Specifications

Series AMEPR30-AZ up to 2.5A AC-DC / DC-DC LED Driver / Converter

Nominal Power [W] Radiance Angle [ ] Color Temp. [K]

Stove Guard Kit User Manual

13 SERIES. Electronic step relays A

Drayton Digistat +2RF/+3RF

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q R0001

Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in

SMART SENSOR COLLECTION

LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL

38 Series - Relay interface modules A

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Safety automation solutions

I STAR COMPUTER CO., LTD

Contactless Encoder RI360P0-QR24M0-INCRX2-H1181

EBDSPIR-PRM, EBDSPIR-PRM-IP

The most sustainable lighting solution. QL 85W Induction Lighting System

STRATO LED Drivers 70W, Single output

Transmitter Actuator 230V wave UP 560. Operation

PART 1 PRODUCT (GENERAL)...1.

Niko Home Control. Installation Manual

IVIOS LED III. LUM Technical Information

User s Manual Before using the inverter, you need to read and save the safety instructions.

ABB i-bus EIB Shutter Actuators JA/S , JA/S , JA/S , JA/S M, JA/S M, JA/S

Online UPS. PowerWalker VFI 1000R/1U

Electrical connection

MOUNTING AND OPERATING INSTRUCTIONS

Single Output Switching Power Supply

Digidim 458/DIM8 8-Channel Dimmer Module. Installation and User Guide

Telephone- and leased line modem for industrial applications TD-36

Actuator-Sensor-Interface

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

Linear Luminaire for Fluorescent Lamps Series EXLUX 6001

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

Transcription:

T5 TC-L PCA T5 BASIC lp Y II, 1 80 W BASIC T5 Product description Processor-controlled ballast with y II inside Highest possible energy class CELMA EEI = A1 BAT 1 Noise-free precise control via DSI signal, switchdim or corridorfunction Nominal life up to 100,000 h (at ta 50 C with a failure rate max. 0. % per 1,000 h) 5-year guarantee Interfaces DSI switchdim (with memory function) corridorfunction ( preprogrammed profiles) Integrated SMART interface for function with SMART Sensor 5D 19f and corridorfunction plugs Functions Intelligent Temperature Guard (overtemperature protection) Intelligent Voltage Guard (overvoltage indication and undervoltage shutdown) Optimum filament heating in any dimmer setting Disconnection of filament heating from a dimming level of approx. 90 % for maximum energy efficiency (SMART-Heating concept) corridorfunction with ambient light control Automatically triggered emergency lighting value in DC mode, 15 % For emergency lighting systems as per EN 501 Automatic start after replacement of defective lamps Automatic shutdown if the lamp is faulty È Standards, page Wiring diagrams and installation examples, page 8 Ø,1 side fixing feature L D 1,1 0 Technical data Mains voltage range 0 0 V AC voltage range 198 V DC voltage range 1 80 V (lamp start 198 V DC) Mains frequency 0 / 50 / 0 Hz Overvoltage protection 0 V AC, 1 h Typ. power input on standby < 0. W Protective hot restart 0.5 s for AC / 0. s for DC Dimming range 10 100 % Lamp start possible from 10 % Operating frequency ~ 0 10 khz Type of protection IP0 Ordering data Type Article number Packaging, carton Packaging, pallet Weight per pcs. For luminaires with 1 lamp PCA 1x1 T5 BASIC lp Y II 1850 10 pc./pcs. 0 pc./pcs. 0.0 kg PCA 1x1 T5 BASIC lp Y II 185090 10 pc./pcs. 0 pc./pcs. 0.1 kg PCA 1x T5 BASIC lp Y II 18508 10 pc./pcs. 0 pc./pcs. 0.9 kg PCA 1x8 T5 BASIC lp Y II 18508 10 pc./pcs. 0 pc./pcs. 0.0 kg PCA 1x5 T5 BASIC lp Y II 185080 10 pc./pcs. 0 pc./pcs. 0.0 kg PCA 1x9 T5 BASIC lp Y II 18509 10 pc./pcs. 0 pc./pcs. 0. kg PCA 1x9 T5 BASIC lp Y II 18508 10 pc./pcs. 0 pc./pcs. 0.0 kg PCA 1x5 T5 BASIC lp Y II 185088 10 pc./pcs. 0 pc./pcs. 0.0 kg PCA 1x80 T5 BASIC lp Y II 18508 10 pc./pcs. 0 pc./pcs. 0.0 kg www.tridonic.com 1

Ordering data Type Article number Packaging, carton Packaging, pallet Weight per pcs. For luminaires with lamps PCA x1 T5 BASIC lp Y II 1850 10 pc./pcs. 0 pc./pcs. 0. kg PCA x1 T5 BASIC lp Y II 185091 10 pc./pcs. 0 pc./pcs. 0. kg PCA x T5 BASIC lp Y II 18509 10 pc./pcs. 0 pc./pcs. 0. kg PCA x8 T5 BASIC lp Y II 18508 10 pc./pcs. 0 pc./pcs. 0.0 kg PCA x5 T5 BASIC lp Y II 185081 10 pc./pcs. 0 pc./pcs. 0.0 kg PCA x9 T5 BASIC lp Y II 18509 10 pc./pcs. 0 pc./pcs. 0.0 kg PCA x9 T5 BASIC lp Y II 18508 10 pc./pcs. 0 pc./pcs. 0.0 kg PCA x5 T5 BASIC lp Y II 185089 10 pc./pcs. 0 pc./pcs. 0.8 kg PCA x80 T5 BASIC lp Y II 185085 10 pc./pcs. 0 pc./pcs. 0. kg Specific technical data Lamp wattage Lamp type Type For luminaires with 1 lamp Article number Dimensions L x W x H Hole spacing D Lamp power Circuit power EEI Current at 50 Hz 0 V λ at 50 Hz 0 V tc point max. Ambient temperature ta 1 x 1 W T5 PCA 1x1 T5 BASIC lp Y II 1850 0 x 0 x 1 mm 50 mm 1 W 1.0 W A1 BAT 0.08 A 0.95 80 C -5... 0 C 1 x 1 W T5 PCA 1x1 T5 BASIC lp Y II 185090 0 x 0 x 1 mm 50 mm 1 W.0 W A1 BAT 0.11 A 0.95 80 C -5... 0 C 1 x W T5 PCA 1x T5 BASIC lp Y II 18508 0 x 0 x 1 mm 50 mm W 5.5 W A1 BAT 0.1 A 0.9 80 C -5... 0 C 1 x 8 W T5 PCA 1x8 T5 BASIC lp Y II 18508 0 x 0 x 1 mm 50 mm 8 W 0.5 W A1 BAT 0.1 A 0.95 80 C -5... 5 C 1 x 5 W T5 PCA 1x5 T5 BASIC lp Y II 185080 0 x 0 x 1 mm 50 mm 5 W 9.0 W A1 BAT 0.18 A 0.95 85 C -5... 5 C 1 x W TC-L PCA 1x9 T5 BASIC lp Y II 18509 0 x 0 x 1 mm 50 mm W 5.5 W A1 BAT 0.1 A 0.9 80 C -5... 5 C 1 x 9 W T5 PCA 1x9 T5 BASIC lp Y II 18509 0 x 0 x 1 mm 50 mm 8 W 1.5 W A1 BAT 0.19 A 0.9 80 C -5... 5 C 1 x 0 W TC-L PCA 1x9 T5 BASIC lp Y II 18509 0 x 0 x 1 mm 50 mm 0 W.0 W A1 BAT 0.0 A 0.98 80 C -5... 5 C 1 x 9 W T5 PCA 1x9 T5 BASIC lp Y II 18508 0 x 0 x 1 mm 50 mm 9 W 5.0 W A1 BAT 0.5 A 0.9 80 C -5... 0 C 1 x 5 W T5 PCA 1x5 T5 BASIC lp Y II 185088 0 x 0 x 1 mm 50 mm 5 W 58.0 W A1 BAT 0. A 0.98 80 C -5... 0 C 1 x 55 W TC-L PCA 1x80 T5 BASIC lp Y II 18508 0 x 0 x 1 mm 50 mm 55 W 0.0 W A1 BAT 0.8 A 0.9 80 C -5... 0 C 1 x 80 W T5 PCA 1x80 T5 BASIC lp Y II 18508 0 x 0 x 1 mm 50 mm 80 W 85.5 W A1 BAT 0.0 A 0.99 80 C -5... 0 C 1 x 80 W TC-L PCA 1x80 T5 BASIC lp Y II 18508 0 x 0 x 1 mm 50 mm 80 W 85.5 W A1 BAT 0. A 0.98 80 C -5... 0 C For luminaires with lamps x 1 W T5 PCA x1 T5 BASIC lp Y II 1850 0 x 0 x 1 mm 50 mm 8 W 0.5 W A1 BAT 0.1 A 0.9 80 C -5... 0 C x 1 W T5 PCA x1 T5 BASIC lp Y II 185091 0 x 0 x 1 mm 50 mm 1 W 5.5 W A1 BAT 0.1 A 0.9 85 C -5... 0 C x 18 W TC-L PCA x T5 BASIC lp Y II 18509 0 x 0 x 1 mm 50 mm W 8.0 W A1 BAT 0.15 A 0.9 80 C -5... 5 C x W T5 PCA x T5 BASIC lp Y II 18509 0 x 0 x 1 mm 50 mm 5 W 9.5 W A1 BAT 0. A 0.98 80 C -5... 5 C x W TC-L PCA x T5 BASIC lp Y II 18509 0 x 0 x 1 mm 50 mm W 9.0 W A1 BAT 0.1 A 0.98 80 C -5... 5 C x 8 W T5 PCA x8 T5 BASIC lp Y II 18508 5 x 0 x 1 mm 15 mm 5 W 0.5 W A1 BAT 0.8 A 0.9 80 C -5... 0 C x 5 W T5 PCA x5 T5 BASIC lp Y II 185081 0 x 0 x 1 mm 50 mm 0 W.5 W A1 BAT 0. A 0.9 80 C -5... 5 C x W TC-L PCA x9 T5 BASIC lp Y II 18509 0 x 0 x 1 mm 50 mm W 1.0 W A1 BAT 0.1 A 0.98 85 C -5... 5 C x 9 W T5 PCA x9 T5 BASIC lp Y II 18509 0 x 0 x 1 mm 50 mm W 8.0 W A1 BAT 0. A 0.98 85 C -5... 5 C x 0 W TC-L PCA x9 T5 BASIC lp Y II 18509 0 x 0 x 1 mm 50 mm 80 W 8.0 W A1 BAT 0.0 A 0.99 85 C -5... 5 C x 9 W T5 PCA x9 T5 BASIC lp Y II 18508 0 x 0 x 1 mm 50 mm 98 W 105.5 W A1 BAT 0.9 A 0.98 80 C -5... 0 C x 5 W T5 PCA x5 T5 BASIC lp Y II 185089 5 x 0 x 1 mm 15 mm 108 W 11.0 W A1 BAT 0.51 A 0.99 85 C -5... 55 C x 55 W TC-L PCA x80 T5 BASIC lp Y II 185085 5 x 0 x 1 mm 15 mm 110 W 11.5 W A1 BAT 0.5 A 0.99 80 C -5... 55 C x 80 W T5 PCA x80 T5 BASIC lp Y II 185085 5 x 0 x 1 mm 15 mm 10 W 1.0 W A1 BAT 0. A 0.99 80 C -5... 55 C 1 According to the EU directives on ecodesign requirements (EC) No. 5/009 and (EC) No. /010. Valid at 100 % dimming level. +10 C to ta max: unrestricted dimming. -5 C to +10 C: unrestricted dimming from 100 % to 0 %. -5 C to +10 C, dimming below 0 %: malfunction possible but no damage to ECG. This applies to AC and DC operation. www.tridonic.com

Standards EN 55015 EN 099 EN 1000-- EN 1-- EN 15 Suitable for emergency installations according to EN 501 CISPR 15 CISPR IEC 099 IEC 1000-- IEC 1-- IEC 15 Lamp starting characteristics Warm start Starting time 0.5 s with AC Starting time 0. s with DC Start at dimming level from 10 100 % AC operation Mains voltage 0 0 V 50/0 Hz 198 V 50/0 Hz including safety tolerance (±10 %) 0 5 V 50/0 Hz including performance tolerance (+ % / -8 %) Mains currents in DC operation (at 15 % light output) Lamp type Wattage Mains current at Mains current at Type Un = 0 VDC Un = 5 VDC PCA 1x1 T5 BASIC lp Y II T5 1x1 W 0.0 A 0.0 A PCA 1x1 T5 BASIC lp Y II T5 1x1 W 0.05 A 0.0 A PCA 1x T5 BASIC lp Y II T5 1x W 0.05 A 0.05 A PCA 1x8 T5 BASIC lp Y II T5 1x8 W 0.0 A 0.0 A PCA 1x5 T5 BASIC lp Y II T5 1x5 W 0.0 A 0.0 A PCA 1x9 T5 BASIC lp Y II TC-L 1x W 0.0 A 0.0 A PCA 1x9 T5 BASIC lp Y II T5 1x9 W 0.0 A 0.0 A PCA 1x9 T5 BASIC lp Y II TC-L 1x0 W 0.0 A 0.0 A PCA 1x9 T5 BASIC lp Y II T5 1x9 W 0.09 A 0.08 A PCA 1x5 T5 BASIC lp Y II T5 1x5 W 0.11 A 0.10 A PCA 1x80 T5 BASIC lp Y II TC-L 1x55 W 0.11 A 0.10 A PCA 1x80 T5 BASIC lp Y II T5 1x80 W 0.1 A 0.1 A PCA 1x80 T5 BASIC lp Y II TC-L 1x80 W 0.1 A 0.1 A PCA x1 T5 BASIC lp Y II T5 x1 W 0.0 A 0.0 A PCA x1 T5 BASIC lp Y II T5 x1 W 0.08 A 0.0 A PCA x T5 BASIC lp Y II TC-L x18 W 0.0 A 0.0 A PCA x T5 BASIC lp Y II T5 x W 0.09 A 0.09 A PCA x T5 BASIC lp Y II TC-L x W 0.10 A 0.09 A PCA x8 T5 BASIC lp Y II T5 x8 W 0.10 A 0.10 A PCA x5 T5 BASIC lp Y II T5 x5 W 0.1 A 0.11 A PCA x9 T5 BASIC lp Y II TC-L x W 0.1 A 0.11 A PCA x9 T5 BASIC lp Y II T5 x9 W 0.1 A 0.1 A PCA x9 T5 BASIC lp Y II TC-L x0 W 0.1 A 0.1 A PCA x9 T5 BASIC lp Y II T5 x9 W 0.1 A 0.15 A PCA x5 T5 BASIC lp Y II T5 x5 W 0.0 A 0.18 A PCA x80 T5 BASIC lp Y II TC-L x55 W 0.0 A 0.19 A PCA x80 T5 BASIC lp Y II T5 x80 W 0. A 0.5 A DC operation 0 0 V 0 Hz 198 80 V 0 Hz certain lamp start 1 80 V 0 Hz operating range Use in emergency lighting installations according to EN 501 or for emergency luminaires according to EN 1-- appendix J. Mains current for defective or missing lamps at DC operation < 5 ma. Light output level in DC operation Default value is 15 % Emergency units The PCA T5 BASIC lp y II ballasts are compatible with all emergency units from Tridonic. See the table in the data sheet. Also all 5-pole emergency units can be used. When used with other emergency units tests are necessary. Temperature range Unlimited dimming range from 10 C to ta max. -5 C to 10 C: dimming operation from 100 % to 0 %. If dimm level goes below 0 % malfunction possible, but no electronic ballast damage. This applies to AC and DC operation. Ballast lumen factor AC operation (AC-BLF) EN 099 8.1 Type Lamp type Wattage AC-BLF at U = 0 VAC PCA 1x1 T5 BASIC lp Y II T5 1x1 W 1.00 PCA 1x1 T5 BASIC lp Y II T5 1x1 W 0.99 PCA 1x T5 BASIC lp Y II T5 1x W 1.01 PCA 1x8 T5 BASIC lp Y II T5 1x8 W 0.98 PCA 1x5 T5 BASIC lp Y II T5 1x5 W 1.00 PCA 1x9 T5 BASIC lp Y II TC-L 1x W 0.9 PCA 1x9 T5 BASIC lp Y II T5 1x9 W 1.01 PCA 1x9 T5 BASIC lp Y II TC-L 1x0 W 1.05 PCA 1x9 T5 BASIC lp Y II T5 1x9 W 1.00 PCA 1x5 T5 BASIC lp Y II T5 1x5 W 1.0 PCA 1x80 T5 BASIC lp Y II TC-L 1x55 W 1.0 PCA 1x80 T5 BASIC lp Y II T5 1x80 W 1.0 PCA 1x80 T5 BASIC lp Y II TC-L 1x80 W 1.0 PCA x1 T5 BASIC lp Y II T5 x1 W 1.01 PCA x1 T5 BASIC lp Y II T5 x1 W 0.9 PCA x T5 BASIC lp Y II TC-L x18 W 0.90 PCA x T5 BASIC lp Y II T5 x W 1.00 PCA x T5 BASIC lp Y II TC-L x W 0.98 PCA x8 T5 BASIC lp Y II T5 x8 W 1.00 PCA x5 T5 BASIC lp Y II T5 x5 W 1.01 PCA x9 T5 BASIC lp Y II TC-L x W 0.9 PCA x9 T5 BASIC lp Y II T5 x9 W 0.98 PCA x9 T5 BASIC lp Y II TC-L x0 W 1.05 PCA x9 T5 BASIC lp Y II T5 x9 W 1.0 PCA x5 T5 BASIC lp Y II T5 x5 W 1.00 PCA x80 T5 BASIC lp Y II TC-L x55 W 1.0 PCA x80 T5 BASIC lp Y II T5 x80 W 1.0 The ballast lumen factor for AC operation (AC-BLF) does not alter from Un = 198 V AC to Un = 5 V AC. The ballast lumen factor for DC operation (DC-BLF) on the basis of an automatic power reduction of the ballasts (default value is 15 %) will be smaller than AC. It does not alter in the DC operating range (198 80 V DC). www.tridonic.com

Dimming Dimming curve is adapted to the eye sensitiveness. Dimming range 10 % to 100 % Digital control with DSI signal: 8 bit Manchester Code Speed 10 % to 100 % in 0.8 s Control input (, D) Digital DSI signal, push-to-make switch (switchdim) or a motion detector (corridorfunction) can be wired on the same terminals ( and D). Digital signal DSI The control input is non-polar and protected against accidental connection with a mains voltage up to V. The control signal is not SELV. Control cable has to be installed in accordance to the requirements of low voltage installations. Different functions depending on each module. SMART interface An additional interface for the direct connection of the SMART-Sensor 5D 19f 1) or corridorfunction plugs. Application and functionallity see corridorfunction user manual. SMART-Sensor 5D 19f 1) light sensor operating mode: The sensor registers actual ambient light and maintains the individually defined constant lux level. After every mains reset the SMART interface automatically checks for an installed sensor. With the sensor installed the PCA T5 BASIC lp y II automatically runs in the constant lux level mode. ON/OFF switch via mains, switchdim or DSI signal. DSI signal = 0 switches off, DSI signal 1 switches on. With switchdim signals it is possible to change the controlled light level temporarily. Temporarily means that after a switching cycle OFF/ ON command the ballast will start at the preset value determined by the SMART-Sensor 5D 19f. The installation of the two wire bus is according to the appropriate low voltage regulations. 1) SMART-Sensor 5D 19f: article number 85919 switchdim Integrated switchdim function allows a direct connection of a push to make switch for dimming and switching. Brief push (< 0. s) switches ballast ON and OFF. The ballasts switch-on at light level set at switch-off. After switch ON the last settet dimming level will be activated again. When the push to make switch is held, PCA ballasts are dimmed. After repush the PCA is dimmed in the opposite direction. The switchdim fade time is set to s from min. to max. in the factory settings. In installations with PCAs with different dimming levels or opposite dimming directions (e.g. after a system extension), all PCAs can be synchronized to 50 % dimming level by a 10 s push. Use of push to make switch with indicator lamp is not permitted. switchdim and corridorfunction are very simple tools for controlling ballasts with conventional momentaryaction switches or motion sensors. To ensure correct operation a sinusoidal mains voltage with a frequency of 50 Hz or 0 Hz is required at the control input. Special attention must be paid to achieving clear zero Dimming characteristics PCA T5 BASIC lp Y II digital dimming value 55 5 00 15 150 15 100 5 50 5 0 0 10 0 0 DSI 0 50 0 0 80 90 100 relative lighting level in % Energy saving PCA T5 BASIC lp Y II Dimming characteristics as seen by the human eye Note: The dimming level of BASIC can be different to the graphic (dimming level 10 to 100 %) crossings. Serious mains faults may impair the operation of switchdim and corridorfunction. corridorfunction To activate the corridorfunction a voltage of 0 V simply has to be applied for five minutes at switchdim connection. The unit will then switch automatically to the corridorfunction. Note: If the corridorfunction is wrongly activated in a switchdim system (for example a switch is used instead of pushbutton), there is the option of installing a pushbutton and deactivating the corridorfunction mode by five short pushes of the button within three seconds. The corridorfunction offers the added benefit of a second and third preprogrammed profile, which can be activated by the corridorfunction plugs. It is also possible to combine the corridorfunction with the SMART-Sensor 5D 19f light sensor. Application and functionallity of profiles see user manual of the corridorfunction. mains power in % 100 90 80 0 0 50 0 0 0 10 0 100 90 80 0 0 50 0 0 0 15 10 5 1 dimming level in % switchdim PCA T5 BASIC lp Y II DSI N L N L DSI PCA T5 BASIC lp Y II D D corridorfunction PCA T5 BASIC lp Y II D Dimmable ballasts from Tridonic have to be earthed. www.tridonic.com

Loading of automatic circuit breakers (Limitation via inrush current) Automatic circuit breaker type C10 C1 C1 C0 B10 B1 B1 B0 Inrush current (1.5 mm ) Inrush current (.5 mm ) Installation Ø 1.5 mm 1.5 mm 1.5 mm.5 mm 1.5 mm 1.5 mm 1.5 mm.5 mm I max time I max time PCA 1x1 T5 BASIC lp Y II 50 80 150 180 5 0 5 90 19. A 1 µs 19. A 1 µs PCA 1x1 T5 BASIC lp Y II 50 8 1 5 8 5. A 190 µs 5.1 A 19 µs PCA 1x T5 BASIC lp Y II 50 80 150 180 5 0 5 90 19. A 1 µs 19. A 1 µs PCA 1x8 T5 BASIC lp Y II 5 11 1. A 5 µs 8.5 A µs PCA 1x5 T5 BASIC lp Y II 1 8 8 11 1 1 1. A 1 µs 1. A µs PCA 1x9 T5 BASIC lp Y II 50 8 1 5 8 5. A 190 µs 5.1 A 19 µs PCA 1x9 T5 BASIC lp Y II 1 8 8 11 1 1 1. A 1 µs 1. A µs PCA 1x5 T5 BASIC lp Y II 5 11 1. A 5 µs 8.5 A µs PCA 1x80 T5 BASIC lp Y II 1 8 8 11 1 1 1. A 1 µs 1. A µs PCA x1 T5 BASIC lp Y II 50 11 1 5 8.1 A µs 8. A µs PCA x1 T5 BASIC lp Y II 1 8 8 11 1 1. A 0 µs 8. A 0 µs PCA x T5 BASIC lp Y II 50 11 1 5 8.1 A µs 8. A µs PCA x8 T5 BASIC lp Y II 1 0 8 11 15 18 8.9 A 88 µs 0. A 8 µs PCA x5 T5 BASIC lp Y II 1 0 8 11 15 1.0 A 1 µs.9 A 0 µs PCA x9 T5 BASIC lp Y II 1 8 8 11 1 1. A 0 µs 8. A 0 µs PCA x9 T5 BASIC lp Y II 1 0 8 11 15 1.0 A 1 µs.9 A 0 µs PCA x5 T5 BASIC lp Y II 1 0 8 11 15 18 8.9 A 88 µs 0. A 8 µs PCA x80 T5 BASIC lp Y II 8 1 18 0 9 10 8. A 1 µs 50.1 A 58 µs Continuous operation: to calculate the protective saftey switch see main current, page Intelligent Voltage Guard Intelligent Voltage Guard is the name of the electronic monitor from Tridonic. This inno vative feature of the PCA family of control gear from Tridonic immediately shows if the mains voltage rises above certain thresholds. Measures can then be taken quickly to prevent damage to the control gear. If the mains voltage rises above approx. 18 Vrms (voltage depends on the ballast type), the lamp starts flashing on and off. To avoid a damage of the device the mains supply has to be switched off at this signal. Intelligent Temperature Guard The intelligent temperature guard protects the PCA T5 BASIC lp y II from thermal overheating by reducing the output power or switching off in case of operation above the thermal limits of the luminaire or ballast. Depending on the luminaire design, the ITG operates at about 5 to 10 C above tc temperature. www.tridonic.com 5

Harmonic distortion in the mains supply (at 0 V / 50 Hz) Type Lamp type Wattage THD 5 9 11 PCA 1x1 T5 BASIC lp Y II T5 1x1 W 9 1 1 PCA 1x1 T5 BASIC lp Y II T5 1x1 W 9 PCA 1x T5 BASIC lp Y II T5 1x W 9 1 1 PCA 1x8 T5 BASIC lp Y II T5 1x8 W 10 PCA 1x5 T5 BASIC lp Y II T5 1x5 W 10 PCA 1x9 T5 BASIC lp Y II TC-L 1x W 8 1 1 1 PCA 1x9 T5 BASIC lp Y II T5 1x9 W 1 1 1 PCA 1x9 T5 BASIC lp Y II TC-L 1x0 W 1 1 1 1 PCA 1x9 T5 BASIC lp Y II T5 1x9 W 10 8 PCA 1x5 T5 BASIC lp Y II T5 1x5 W 1 1 1 1 PCA 1x80 T5 BASIC lp Y II TC-L 1x55 W 5 1 1 1 PCA 1x80 T5 BASIC lp Y II T5 1x80 W 5 1 1 1 1 PCA 1x80 T5 BASIC lp Y II TC-L 1x80 W 5 1 1 1 1 PCA x1 T5 BASIC lp Y II T5 x1 W 8 1 1 1 PCA x1 T5 BASIC lp Y II T5 x1 W 10 PCA x T5 BASIC lp Y II TC-L x18 W 1 1 1 PCA x T5 BASIC lp Y II T5 x W 5 1 1 1 1 PCA x T5 BASIC lp Y II TC-L x W 1 1 1 1 PCA x8 T5 BASIC lp Y II T5 x8 W 10 PCA x5 T5 BASIC lp Y II T5 x5 W 9 5 1 1 PCA x9 T5 BASIC lp Y II TC-L x W 1 1 1 PCA x9 T5 BASIC lp Y II T5 x9 W 1 1 1 1 PCA x9 T5 BASIC lp Y II TC-L x0 W 1 1 1 1 PCA x9 T5 BASIC lp Y II T5 x9 W 1 1 1 1 PCA x5 T5 BASIC lp Y II T5 x5 W 8 1 1 1 1 PCA x80 T5 BASIC lp Y II TC-L x55 W 1 1 1 PCA x80 T5 BASIC lp Y II T5 x80 W 5 1 1 1 Operating voltage Type Lamp type Wattage Uout PCA 1x1 T5 BASIC lp Y II T5 1x1 W 0 V PCA 1x1 T5 BASIC lp Y II T5 1x1 W 0 V PCA 1x T5 BASIC lp Y II T5 1x W 0 V PCA 1x8 T5 BASIC lp Y II T5 1x8 W 0 V PCA 1x5 T5 BASIC lp Y II T5 1x5 W 0 V PCA 1x9 T5 BASIC lp Y II TC-L 1x W 0 V PCA 1x9 T5 BASIC lp Y II T5 1x9 W 0 V PCA 1x9 T5 BASIC lp Y II TC-L 1x0 W 0 V PCA 1x9 T5 BASIC lp Y II T5 1x9 W 0 V PCA 1x5 T5 BASIC lp Y II T5 1x5 W 0 V PCA 1x80 T5 BASIC lp Y II TC-L 1x55 W 0 V PCA 1x80 T5 BASIC lp Y II T5 1x80 W 0 V PCA 1x80 T5 BASIC lp Y II TC-L 1x80 W 0 V PCA x1 T5 BASIC lp Y II T5 x1 W 0 V PCA x1 T5 BASIC lp Y II T5 x1 W 0 V PCA x T5 BASIC lp Y II TC-L x18 W 0 V PCA x T5 BASIC lp Y II T5 x W 0 V PCA x T5 BASIC lp Y II TC-L x W 0 V PCA x8 T5 BASIC lp Y II T5 x8 W 0 V PCA x5 T5 BASIC lp Y II T5 x5 W 0 V PCA x9 T5 BASIC lp Y II TC-L x W 0 V PCA x9 T5 BASIC lp Y II T5 x9 W 0 V PCA x9 T5 BASIC lp Y II TC-L x0 W 0 V PCA x9 T5 BASIC lp Y II T5 x9 W 0 V PCA x5 T5 BASIC lp Y II T5 x5 W 0 V PCA x80 T5 BASIC lp Y II TC-L x55 W 0 V PCA x80 T5 BASIC lp Y II T5 x80 W 0 V www.tridonic.com

Humidity: 5 % up to max. 85 %, not condensed (max. 5 days/year at 85 %) Storage temperature: -0 C up to max. +80 C The devices have to be within the specified temperature range (ta) before they can be operated. Expected lifetime Type Lamp type Wattage ta = 0 C ta = 50 C ta = 0 C PCA 1x1 T5 BASIC lp Y II T5 1 x 1 W PCA 1x1 T5 BASIC lp Y II T5 1 x 1 W tc 50 C 0 C 0 C PCA 1x T5 BASIC lp Y II T5 1 x W PCA 1x8 T5 BASIC lp Y II T5 1 x 8 W tc 50 C 0 C 0 C PCA 1x5 T5 BASIC lp Y II T5 1 x 5 W PCA 1x9 T5 BASIC lp Y II TC-L 1 x W PCA 1x9 T5 BASIC lp Y II T5 1 x 9 W tc 50 C 0 C 0 C PCA 1x9 T5 BASIC lp Y II TC-L 1 x 0 W PCA 1x9 T5 BASIC lp Y II T5 1 x 9 W tc 55 C 0 C 0 PCA 1x5 T5 BASIC lp Y II T5 1 x 5 W Lifetime > 100,000 h 100,000 h 90,000 h PCA 1x80 T5 BASIC lp Y II TC-L 1 x 55 W tc 5 C 0 C 80 C Lifetime > 100,000 h > 100,000 h 50,000 h PCA 1x80 T5 BASIC lp Y II T5 1 x 80 W tc 5 C 0 C 80 C Lifetime > 100,000 h > 100,000 h 50,000 h PCA 1x80 T5 BASIC lp Y II TC-L 1 x 80 W tc 5 C 0 C 80 C Lifetime > 100,000 h > 100,000 h 50,000 h PCA x1 T5 BASIC lp Y II T5 x 1 W tc 50 C 0 C 0 C PCA x1 T5 BASIC lp Y II T5 x 1 W PCA x T5 BASIC lp Y II TC-L x 18 W Lifetime > 100,000 h > 100,000 h 90,000 h PCA x T5 BASIC lp Y II T5 x W Lifetime > 100,000 h > 100,000 h 90,000 h PCA x T5 BASIC lp Y II TC-L x W Lifetime > 100,000 h > 100,000 h 90,000 h PCA x8 T5 BASIC lp Y II T5 x 8 W tc 55 C 0 C 0 C PCA x5 T5 BASIC lp Y II T5 x 5 W Lifetime > 100,000 h > 100,000 h 80,000 h PCA x9 T5 BASIC lp Y II TC-L x W tc 0 C 0 C 80 C Lifetime > 100,000 h > 100,000 h 90,000 h PCA x9 T5 BASIC lp Y II T5 x 9 W tc 0 C 0 C 80 C Lifetime > 100,000 h > 100,000 h 0,000 h PCA x9 T5 BASIC lp Y II TC-L x 0 W tc 0 C 0 C 80 C Lifetime > 100,000 h > 100,000 h 80,000 h PCA x9 T5 BASIC lp Y II T5 x 9 W tc 5 C 0 C 80 C Lifetime > 100,000 h 80,000 h 50,000 h PCA x5 T5 BASIC lp Y II T5 x 5 W tc 5 C 5 C x Lifetime > 100,000 h 0,000 h x PCA x80 T5 BASIC lp Y II TC-L x 55 W tc 5 C 5 C x Lifetime > 100,000 h 80,000 h x PCA x80 T5 BASIC lp Y II T5 x 80 W tc 5 C 0 C x Lifetime > 100,000 h 80,000 h x x = not permitted www.tridonic.com

Installation instructions Wiring type and cross section The wiring can be solid cable with a cross section of 0.5 to 1.5 mm². For the push-wire connection you have to strip the insulation (8 9 mm). wire preparation: 0.5 1.5 mm² Wiring advice The lead length is dependent on the capacitance of the cable. Ballast Terminal Maximum capacitance allowed Type Cold Hot Cold Hot PCA 1xx T5 BASIC lp Y II 1, 1 15, 1 00 pf 100 pf PCA xx T5 BASIC lp Y II 1, 1, 1 10, 11, 15, 1 00 pf 100 pf 8 9 mm Release of the wiring Loosen wire through twisting and pulling or using a Ø 1 mm release tool. With standard solid wire 0.5/0.5 mm² the capacitance of the lead is 0 80 pf/m. This value is influenced by the way the wiring is made. Lamp connection should be made with symmetrical wiring. Hot leads (10, 11, 15, 1) and cold leads (1, 1, 1) should be separated as much as possible. When using two or more dimmable ballasts in one luminaire with separate dimming controls, the lamp leads must be kept separate. Sensor wires Sensor wires must be routed separately from the lamp wires and mains cables otherwise the lighting control system may malfunction. If separate routing is not possible (for reasons of space) shielded lamp wires and mains cables must be used. Dimmable ballasts from Tridonic have to be earthed. * * control signal D 1 15 1 1 * * control signal D 1 15 1 1 1 11 10 * leads 15, 1 keep wires short, max. 1.0 m leads 1, 1: max..0 m; ballast must be earthed * * digital signal DSI-Signal or switchdim * leads 10, 11, 15, 1 keep wires short, max. 1.0 m leads 1, 1, 1 max..0 m; ballast must be earthed * * digital signal DSI or switchdim PCA T5 BASIC lp Y II 1x1 80 W PCA T5 BASIC lp Y II x1 80 W Dimmable ballasts from Tridonic have to be earthed. RFI Connection to the lamps of the hot leads must be kept as short as possible Mains leads should be kept apart from lamp leads (ideally 5 10 cm distance) Do not run mains leads adjacent to the electronic ballast Twist the lamp leads Keep the distance of lamp leads from the metal work as large as possible Mains wiring to be twisted when through wiring Keep the mains leads inside the luminaire as short as possible General advise Electronic ballasts are virtually noise free. Magnetic fields generated during the ignition cycle can cause some background noise but only for a few milliseconds. Operation on DC voltage Our ballasts are construed to operate DC voltage and pulsed DC voltage. To operate ballasts with pulsed DC voltage the polarity is absolute mandatory. + D Isolation and electric strength testing of luminaires Electronic devices can be damaged by high voltage. This has to be considered during the routine testing of the luminaires in production. According to IEC 0598-1 Annex Q (informative only!) or ENEC 0-Annex A, each luminaire should be submitted to an isolation test with 500 V DC for 1 second. This test voltage should be connected between the interconnected phase and neutral terminals and the earth terminal. The isolation resistance must be at least MΩ. As an alternative, IEC 0598-1 Annex Q describes a test of the electrical strength with 1500 V AC (or 1.1 x 1500 V DC). To avoid damage to the electronic devices this test must not be conducted. For further technical information please visit www.tridonic.com www.tridonic.com 8