Specification guide no. 9 Active harmonic conditioner from 20 to 480 A



Similar documents
Galaxy 7000: Unitary Specification guide: Single UPS, three-phase, 160 to 500 kva

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply

Low Voltage Products

How To Understand The Electrical Power Supply Of A Power Supply System

Multi DIALOG MDM/MDT. MDM 10-20kVA single/single-phase and three/single-phase MDT 10-80kVA three/three-phase NETWORK RANGE

MGE Galaxy /200/250/300/400/500 kva Power efficiency for business continuity

LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

Power Meter Series 700

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

SURGE PROTECTIVE DEVICES

Unified requirements for systems with voltages above 1 kv up to 15 kv

City of Leesburg, Florida I.T. Data Center APPENDIX A TOSHIBA UPS INFORMATION

Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

7 - Phaseo power supplies and transformers

Schneider Electric GALAXY VM Data Center Grade Three Phase Uninterruptible Power Supply Guide Specifications kva UPS

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

Arc Terminator Active Arc-Resistant Switchgear

Project Name: Nortrax Section Project No: SURGE PROTECTION DEVICES Page 1

Liebert GXT MT+ CX UPS, 1000VA VA Intelligent, Reliable UPS Protection. AC Power for Business-Critical Continuity

Cable Solutions for Servo and Variable Frequency Drives (VFD)

15 Series - Electronic step relay and dimmer. Features SERIE

TM7BDM8B expansion block - TM7 - IP67-8 DI/DO - 24V DC A - M8 connector

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

Galaxy VM. Three-phase power protection. schneider-electric.com

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

on-line LOCAL AREA NETWORKS (LAN) SERVERS DATA CENTERS internet centers (isp/asp/pop) industrial plcs industrial applications

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Three-phase UPS DELPHYS MX from 250 to 900 kva the Mega Power protection up to 5.4 MVA

Heating Controller. Building Technologies HVAC Products

GE Digital Energy. SG-CE Series UPS kva three phase 400 Vac Uninterruptible Power Supply (UPS) imagination at work

Diesel Engine Driven Generators Page 1 of 6

10000HXL31/15000HXL31/20000HXL31

RIELLO ELETTRONICA. Master HP

STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase

Series AMEPR30-AZ up to 2.5A AC-DC / DC-DC LED Driver / Converter

Waveguide Access Point WGA631. Product Guide

Voltage Regulator SPAU 341 C. Product Guide

Commission communication in the framework of the implementation of the Council Directive 89/336/EEC (2002/C 190/03)

ABB PV + Storage REACT-3.6/4.6-TL 3.6 to 4.6 kw

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 15kVA and 20kVA Smart-UPS RT 230VAC Uninterruptible Power Supply

Energy Management Energy Meter Type EM23 DIN

Remote Monitoring and REC 501 Control Unit Product Guide

REGULINE 600VA / 1000VA REGULATOR USER MANUAL

LAB 1 TECHNICAL DOC 3 IN ONE LAB DEVICE. Velleman Legen Heirweg Gavere Belgium

Three-phase monitoring relay CM-PFE

Chrome DIN Rail Power Supply 24V 30W 1 Phase (Class II & NEC Class 2) / DRC-24V30W1AZ

Specifying a Variable Frequency Drive s

RVL470. Heating Controller. Building Technologies HVAC Products. Series B

APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out

R.C.C.B. s two-pole LEXIC

DC UPS. RTB.e A. IMB.e/ITB.e kva. E2001.e/E3001.e kva. Input voltage: 110/125/220 Vdc. 115/120/230 Vac, 1-phase (IMB.

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

Telephone- and leased line modem for industrial applications TD-36

EGSTON Standard E2xFxWx 12W

MICROSENS. Central 48 V DC Power Supplies for PoE-Components. Description. Features

Harmonics in your electrical system

Always On UPS Systems Inc., # Campion Road, Kelowna, BC Canada V1X 7S8

REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16

Theoretical review. Contents

SG Series UPS kva three phase 400 Vac

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Quick Connect. quick - simple - efficient.

Low Voltage Products. Switches Automatic Transfer Switches

GE Digital Energy. SG-CE Series UPS kva three phase 400 Vac Uninterruptible Power Supply (UPS) imagination at work

Electronic ballasts for fluorescent lamps Products for special applications. PC BASIC, 4 28 W Electronic ballast for system output < 25 W

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

Product and functional description

User s Manual Before using the inverter, you need to read and save the safety instructions.

is then retained absolutely without interruption.

NIKY and NIKY S. UPS SINGLE-PHASE from 600 to 3000 VA GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES

Permissible ambient temperature Operation Storage, transport

Technical Description. Transistor D.C. Chopper Controller Type GS 24 S

Inverter technology. bulletin

Match. GE Digital Energy. Uninterruptible Power Supply VA. Technology for the Digital World. Match UPS. GE Digital Energy.

Electrical Shore Connections / Cold Ironing

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

Online UPS. PowerWalker VFI 1000R/1U

7. Reactive energy compensation

GE Digital Energy. TLE Series UPS kw three phase 400 Vac. with best-in-class efficiency. gimagination at work

UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

AIS 3000 APC AIS kVA 208V w/2 Batt. Module Exp. To 4, Start-Up 5X8, Internal Maintenance Bypass

APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 1000VA, 2000VA & 3000VA Smart-UPS RC 230VAC Uninterruptible Power Supply

LIBRA USV-Anlagen von EBT (10-800KVA) LIBRA pro. UPS kva three-phase / single-phase kva three-phase / three-phase.

The UPS for the highest security in industry and data centres

Guidance for upgrading to GB (IEC : 2005, MOD)

Contents. Clean Control Center Harmonic Correction Unit. Selection Dimensions Specifications. Description

SmartOnline V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial

Phase Modular Finally the benefits of Modular ups are for all

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument D

Transcription:

Active harmonic conditioner from 20 to 480 A Contents 1 - Installations concerned... 2 1.1 - New installations... 2 1.2 - Existing installations... 2 2 - General... 2 2.1 - Scope... 2 2.2 - Applicable voltage distortion limits... 2 2.3 - Location of the equipment in the installation... 2 3 - System description... 3 3.1 - Operation principle... 3 3.2 - Technology... 3 3.3 - Functions... 3 4 - Normal service conditions... 3 4.1 - Conditioned current... 3 4.2 - Voltage distortion... 3 4.3 - On/off... 3 4.4 - Self-adaptation to the load... 3 4.5 - Independence with respect to the source... 3 5 - Overload conditions... 4 6 - Multi-unit configurations... 4 6.1 - Active parallel configuration... 4 6.2 - Cascade configuration... 4 6-3 - "Multi-feeder" configuration... 4 7 - System status and control panel... 4 7.1 - System status... 4 7.2 - System control... 4 7.3 - Display panel... 4 8 - Installation and protection... 5 8.1 - Point of connection... 5 8.2 - Installation... 5 8.3 - Installation of current sensors... 5 8.4 - Active harmonic conditioner protection... 5 9. - AC-source characteristics... 5 10 - Environmental conditions... 5 11 - Standards and tests... 5 11.1 - Compliance with standards... 5 11.2 - Certification of conformity... 6 12 - Test procedure and quality system... 6 13 - Start-up... 6 14 - Replacement parts... 6 15 - Warranty... 6 16 - Installation Services... 6 17 - Electrical diagrams... 7 Appendix: List of characteristics... 8 APC by Schneider Electric 05/2009 edition ch. 6 spec. 9 p.1

1 - Installations concerned This specification applies to buildings or industrial sites where the circulation of harmonic currents may disturb electrical installations. It covers the requirements for electronic equipment specified hereafter aimed at harmonic cancellation, and known as Active Harmonic Conditioners (or Active Filters). 1.1 - New installations This specification shall be used to apply a preventive solution, to problems such as voltage distortion (THDU), particularly when long cables are used, and cable overheating (e.g. neutral conductor). This solution shall be considered in any new installation where the following equipment shall be used: computers (e.g. PC network, etc.), lifts (i.e. variable speed drives), battery chargers, fluorescent tubes, TV/radio transmitter-receivers, etc. Particular attention shall be paid to installations having limited power and a standby generator set (i.e. high subtransient reactance). 1.2 - Existing installations This specification shall be used to apply a corrective solution, to installations where the following problems are encountered: increase in voltage distortion (THDU) and current distortion (THDI), cable overheating (e.g. neutral conductor), unexplained tripping of circuit-breakers, temperature rise in transformers, flicker of fluorescent lighting, etc. Installations that are particularly sensitive to these phenomena include: high-rise commercial buildings where sensitive equipment, such as computers, medical apparatus, etc., are used; telecommunications, television and broadcast stations where harmonic currents may affect the quality of transmission and the reliability of sophisticated electronic equipment, certain industrial processes, for example those implementing real time computerized management systems. 2 - General 2.1 - Scope Active Harmonic Conditioners (AHC), shall be used to eliminate harmonic currents circulating within the electrical installation. They shall limit the individual harmonic content of designated current harmonics and the voltage total harmonic distortion (THDU) to a given percentage of the nominal fundamental voltage (voltage at 50 Hz or 60 Hz). For a precise definition of this percentage, reference shall be made to sensitive equipment specifications (i.e. acceptable THDU % for trouble-free operation), or to the applicable standards for the point of connection to the public AC system. 2.2 - Applicable voltage distortion limits At the design stage, before the equipment has been completely defined, the following values shall be considered as a maximum for the voltage distortion (THDU): computers: < 5%, telecommunications bays: < 5%, television studios: < 5%, general distribution: < 8%, industrial equipment: <8%, point of connection to the public AC system: < 5 to 8% according to applicable standards. These values have been taken from standards IEC 61000-2-2 and 61000-2-4 (harmonic compatibility) and EN 50160-3 (network quality). 2.3 - Location of the equipment in the installation The Active Harmonic Conditioner shall be installed in parallel with the AC distribution system of the building (shunt connected), wherever attenuation of harmonic currents is needed. It shall be located preferably close to those loads generating harmonic currents, in order to avoid circulation of the currents in the building cables. APC by Schneider Electric 05/2009 edition ch. 6 spec. 9 p.2

3 System description 3.1 Operation principle The Active Harmonic Conditioner shall be of shunt -type topology, i.e. connected in parallel with the AC line. It shall analyze continuously the harmonic currents drawn by the load, and inject the same harmonic current with the appropriate phase. Consequently, the current supplied by the source remains virtually sinusoidal under all operating conditions. The Active Harmonic Conditioner shall be compatible with any type of load, and shall guarantee efficient harmonic conditioning, even when changes are made to the installation. 3.2 - Technology The Active Harmonic Conditioner shall use an IGBT (Isolated Gate Bipolar Transistor) bridge to inject the proper harmonic current. It shall be controlled by a microprocessor-based system, and shall use a DSP (Digital Signal Processing) microcontroller to monitor the harmonic currents. 3.3 - Functions As a minimum, the Active Harmonic Conditioner shall include the following functions: conditioning of harmonic currents from H2 (2 nd harmonic) to H25 (25 th harmonic) included, conditioning of the phase displacement (cos ϕ). To guarantee efficient harmonic conditioning, customization of certain parameters shall be possible: overall conditioning or conditioning of selected harmonics, control parameter for conditioning of the phase displacement (cos ϕ), control parameter for the load type: single-phase load, three-phase load, combination of single and three-phase loads. 4 - Normal service conditions 4.1 - Conditioned current The Active Harmonic Conditioner shall be capable of delivering its rated output harmonic current to the point of connection whatever the load conditions. The rated output current shall be indicated in Amperes (rms) per phase. In the neutral conductor, the Active Harmonic Conditioner shall also be capable of conditioning a harmonic current three times greater than the phase current (i.e. condition third-order harmonic currents and multiples), when the phases are balanced. 4.2 - Voltage distortion The Active Harmonic Conditioner shall be capable of reducing the Voltage Total Harmonic Distortion (THDU) to a specified level in % of the fundamental voltage (voltage at 50 Hz or 60 Hz). (See "General Applicable voltage distortion limits" for specified values.) When used at its rated current (i.e. Ιrms of harmonic currents consumed by the load equal to Ιrms of harmonic current supplied by the Active Harmonic Conditioner), the Active Harmonic Conditioner shall reduce THDI by a factor of at least 10. 4.3 - On/off It shall be possible to start and stop the Active Harmonic Conditioner manually via pushbuttons. Remote control shall be also possible. After an AC source failure, it shall be possible to set the Active Harmonic Conditioner so that it restarts automatically. 4.4 - Self-adaptation to the load It shall be possible to use the Active Harmonic Conditioner with all types of loads. It shall adapt automatically to any changes in the harmonic spectrum of the load. 4.5 - Independence with respect to the source The Active Harmonic Conditioner shall also be compatible with all types of sources and shall in particular operate independently with respect to the source impedance. APC by Schneider Electric 05/2009 edition ch. 6 spec. 9 p.3

5 - Overload conditions Should the Active Harmonic Conditioner be overloaded during transient operation of certain loads (e.g. motor startup, particular sequences, etc.), or permanently, this shall not affect the reliability of its operation. In such cases, the Active Harmonic Conditioner shall operate in a current limiting mode, and still deliver to the load its rated harmonic current. In this case, harmonic conditioning capacity shall be limited to the following ratio: Conditioner rating (rms value of harmonic currents delivered) / Ι(rms) load harmonic currents. For better adaptation to all types of installations, the Active Harmonic Conditioner shall be capable of operating in association with other harmonic-reduction systems (e.g. LC filters, 12-pulse bridges, etc.). 6 - Multi-unit configurations To enhance conditioning at a given point in the installation, it shall be possible to connect several Active Harmonic Conditioners in various configurations: 6.1 - Active parallel configuration To increase the conditioning capacity, or to increase the dependability, it shall be possible to connect up to 4 units in parallel, using a single set of current transformers (measurement sensors). In this mode of operation, each Active Harmonic Conditioner shall produce 1/n of the injected harmonic current, where n conditioners are parallel connected. 6.2 - Cascade configuration To condition the harmonics at different levels of the distribution system, it shall be possible to connect two Active Harmonic Conditioners in a series or cascade configuration. The downstream conditioner shall condition a specific load, while the upstream conditioner shall provide overall conditioning. 6.3 - "Multi-feeder" configuration It shall be possible to condition up to three feeders using three sets of current transformers, one set per feeder, connected to a single Active Harmonic Conditioner. 7 System status and control panel 7.1 - System status As a minimum, the Active Harmonic Conditioner shall include the following indications: a green LED to indicate normal operation, an orange LED to indicate current limiting, a red LED to indicate conditioner shutdown or alarm condition. Two pushbuttons shall control ON/OFF operation. 7.2 - System control A complete display panel shall guide the operator to monitor the system properly, and shall provide help for startup, maintenance and diagnostics. 7.3 - Display panel The displayed information shall be available in 5 languages: French, English, German, Italian and Spanish. The display shall include detailed measurements such as: total current distortion (load and source), total rms current (load and source), harmonic current distortion per order, up to the 13th order. APC by Schneider Electric 05/2009 edition ch. 6 spec. 9 p.4

8 - Installation and protection 8.1 - Point of connection For best results, conditioning of harmonic currents shall take place at their point of origin, i.e. close to the harmonicgenerating loads. However, depending of the power-quality objectives (THDU), it shall be possible to connect Active Harmonic Conditioners anywhere in the installation in configurations described in the "Multi-unit configurations" section. 8.2 - Installation The Active Harmonic Conditioner shall be as small as possible, so that it can be installed anywhere. Particularly, it shall be possible to install the conditioner in low voltage switchboards or motor control centers. Finally, wall mounting shall also be possible in plants or electrical rooms. 8.3 - Installation of current sensors To facilitate installation of the current sensors, they shall be of the split type. 8.4 - Active harmonic conditioner protection A three or four pole circuit breaker shall be installed close to the point of connection to the AC system to protect the connection cables. It shall be selected according to general selection practice for circuit breakers and manufacturer recommendations. In addition, the Active Harmonic Conditioner shall include the following protection functions: thermal-overload protection; internal short-circuit; inverter bridge for abnormal operation. 9 - AC-source characteristics The Active Harmonic Conditioner shall be suitable for connection to an AC electrical installation having the following characteristics: 3 phases with or without neutral (3 or 4 wires); all types of system earthing arrangements; 400 V - 20%, + 15%; 50 Hz or 60 Hz ± 8%. 10 - Environmental conditions The Active Harmonic Conditioner enclosure shall provide an IP30 degree of protection as per IEC 60529. The Active Harmonic Conditioner shall be able to operate without derating under the following ambient conditions: continuous temperature 0 to 40 C; relative humidity 95% without condensation; altitude above sea level: 1000 m maximum. To allow installation in any location, the Active Harmonic Conditioner shall have a noise level between 55 dba and 65 dba (as per ISO 3746) depending on the rating. 11 Standards and tests 11.1 - Compliance with standards The Active Harmonic Conditioner shall comply with international standards applicable to this type of equipment and, in particular, meet the recommendations of the following: construction and safety: EN 50091-1, design: IEC 60146, EMC, conducted and radiated emissions: EN 55011 class A, EMC, immunity to electrostatic discharges: IEC 61000-4-2 / level 3, EMC, immunity to radiated fields: IEC 61000-4-3 / level 3, EMC, immunity to low-energy impulse waves: IEC 61000-4-4 / level 4, EMC, immunity to high-energy impulse waves: IEC 61000-4-5 / level 4. IEC 439: Low-voltage switchgear and controlgear assemblies. IEC 60529: Degrees of protection provided by enclosures (IP Code). ISO 3746: Sound power levels. CE marking. What is more, the equipment must comply with environmental-protection standards, with production taking place on premises certified ISO 14001. APC by Schneider Electric 05/2009 edition ch. 6 spec. 9 p.5

11.2 - Certification of conformity The manufacturer shall provide, on request, a complete qualification file demonstrating compliance with the above standards. What is more, the indicated levels of performance shall be confirmed by certification from independent laboratories (e.g. TÜV or Veritas). 12 - Test procedure and quality system 12.1 - Test procedure The equipment manufacturer shall provide proof of a stringent Quality Assurance programme. In particular, the main equipment manufacturing stages shall be sanctioned by appropriate tests such as: incoming components inspection, discrete subassembly testing, complete functional checks on the final product. Equipment shall undergo on-load burn-in before leaving the factory. Final inspection and adjustments shall be documented in a report drawn up by the supplier s Quality Inspection department. ISO 9001 or 9002 certification of the production site shall be compulsory. 12.2 - Quality system The equipment design procedure shall be covered by an ISO 9001 quality system as well as a dependability study to ensure maximum reliability. 13 - Start-up Equipment start-up on site shall be carried out by the manufacturer or an approved representative. It shall include on-site acceptance during which a check on system characteristics shall be made. 14 - Replacement parts 15 - Warranty 16 - Services The suppler undertakes to provide replacement parts for at least ten years following the date of delivery. A set of emergency spare parts shall be supplied with the equipment. The equipment shall be guaranteed (parts and labor on site) for one year following the start-up date. Required services include: supply of the Active Harmonic Conditioner and any accessory parts or elements; carriage-paid equipment transportation and delivery to the site. Options: equipment handling and installation on the site; connection of input cables; connection of output cables. APC by Schneider Electric 05/2009 edition ch. 6 spec. 9 p.6

17 - Electrical diagrams Fig. Active Harmonic Conditioner operating principle Fig. Example of an Active Harmonic Conditioner (AHC) installation APC by Schneider Electric 05/2009 edition ch. 6 spec. 9 p.7

The characteristics specified for the Active Harmonic Conditioner shall include the following: Electrical characteristics Input rated voltage 400 V -20 % + 15 % rated frequency 50 Hz / 60 Hz +/- 8 % number of phases 3 phases without or with neutral (operation possible with single-phase or unbalanced loads) connection type 3 or 4 wires Features conditioning of harmonics overall or selected harmonics phase displacement (cos ϕ) conditioning adjustable, up to 0.94 Configurations single unit yes parallel configuration up to four units Technical characteristics harmonic-conditioning per phase 20 A rms, 30 A rms, 45 A rms, 60 A rms, 90 A rms, 120 A rms capacity: in the neutral conductor 60 A rms, 90 A rms, 135 A rms, 180 A rms, 270 A rms, 360 A rms harmonic orders conditioned H2 to H25 overall or selective conditioning response time < 40 ms attenuation ratio THDI load / THDI source > 10 at rated current THDI = Iharmonic / Ifundamental power factor correction up to 1 overload conditioning limited to nominal rms current, but continuous operation with overload possible inrush current < 2 times the nominal peak current losses < 1000 W 20 A 2600 W 60 A < 1300 W 30 A 4200 W 90 A < 2100 W 45 A 5200 W 120 A ventilation forced air (entry through bottom and exit through top) audible noise (according to ISO 3746) < 55 dba 20 A & 30 A < 60 dba 45 A & 60 A < 65 dba 90 A & 120 A Configuration and front panel Configuration languages French, UK English, Italian, Spanish, German, Dutch, US English type of AC system with or without neutral current sensor ratings 300/1, 500/1, 600/1, 1000/1, 1500/1, 2000/1, 3000/1, 4000/1 conditioning of phase displacement (cos ϕ) YES or NO, selectable remote control YES or NO, selectable selection of harmonic orders to condition YES or NO, selectable operation in parallel active parallel or cascade modes; up to 4 units User interface indications green LED : normal operation red LED : OFF or alarm orange LED : overload/limitation operation 7-language alphanumeric display measurements and alarms start-up assistance help menu for diagnostics and maintenance custom menu control ON pushbutton OFF pushbutton remote indications 3 relay contacts 2 x ON / OFF 1 x overload/limitation operation APC by Schneider Electric 05/2009 edition ch. 6 spec. 9 p.8

Environment conditions/reference standards Environment ambient temperature < 25 C recommended, 0 to 40 C continuous relative humidity < 95% without condensation altitude < 1000 m Reference standards construction/safety EN 50091-1 design IEC 146 degree of protection IP 30 (IEC 529) Electromagnetic compatibility conducted and radiated emissions EN 55011 class A immunity to electrostatic discharges IEC 61000-4-2 level 3 immunity to radiated fields IEC 61000-4-3 level 3 immunity to low-energy impulse waves IEC 61000-4-4 level 4 immunity to high-energy impulse waves IEC 61000-4-5 level 4 APC by Schneider Electric 05/2009 edition ch. 6 spec. 9 p.9