The Use of Fresh Air in the Data Centre

Size: px
Start display at page:

Download "The Use of Fresh Air in the Data Centre"

Transcription

1 The Use of Fresh Air in the Data Centre White paper of a round table debate by industry experts on this key topic. Hosted by Keysource with participants including the Uptime Institute. Sophistication Through Simplicity

2 The Use of Fresh Air in the Data Centre The white paper shares the findings of a round table consisting of the industry s leading experts and commentators. Representatives from the Uptime Institute, Operational Intelligence, Colt, Fujitsu, Vocalink, Norland Managed Services and The 451 Group joined Keysource for the round table. The event was designed to generate healthy debate based on real experiences on one of the industry s key topics. This is one of two white papers produced from the round table discussion. Executive Summary There is very little to choose between the on-going operational efficiency (lowest annualised PUE*) of a direct fresh air or an optimised re-circulating indirect system. Generally the CAPEX cost is greater for a direct fresh air system, which due to the operational performance (risk) needs for full mechanical backup, when compared to a re-circulating system. Space requirements depend on site-specific variables and the type of solution chosen, but direct fresh air systems often require more integration with the physical building, increasing complexity and cost over a system that utilises chilled water. It is common to integrate direct fresh air into a modular data centre which mainly overcomes this challenge. There is an ever-increasing drive to remove the need for mechanical cooling such as chillers entirely. Depending on a customer s operational requirements and risk analysis this should be achievable with either a direct or an indirect system. The main consideration with a direct system is whether a customer can afford to turn off the facility due to external factors other than temperature, which are out of their control. There is no one size fits all. The key is to weigh up a number of variables such as climate, temperature, humidity and location - along with the nature of an organisation s business and the type of equipment it will house. There will always be facilities and operators that will not adopt a chillerless environment, with resilience being of far greater importance than energy efficiency or any other consideration. These organisations will become a smaller percentage over time and we are likely to see a considerable change in the landscape over the next ten years in the approach to data centre design. An often forgotten consideration which needs to be factored in is that a peak PUE or max power demand can have a huge impact on CAPEX cost and wasted capacity. This involves reserving mains power to run mechanical systems, even if only occasionally, or in testing and the oversizing of electrical infrastructure and standby power. The choice over different designs can affect the peak demand dramatically. An overriding theme, no matter what system is being used, is if you use direct fresh air and do not have full backup then you must accept the fact that at some point you may have to shut down the data centre. * Note: Power usage effectiveness (PUE) is the industry-recognised metric for infrastructure energy efficiency for data centres, developed by The Green Grid Association and is the ratio of total facilities energy to IT equipment energy. Keysource frequently use the PUEL2,YC measure for client facilities. This is a Category 2 measurement of PUE (as defined by the Green Grid and a 12 month total kwh consumption). 2 The Use of Fresh Air in the Data Centre

3 Key Areas of Discussion There are two types of free cooling systems: Direct uses filtered fresh air directly into the data centre. In-Direct uses a plate heat exchanger or something similar, to achieve a fully re-circulating system. It s almost impossible to achieve a one-fit solution as there are too many parameters such as location, temperature, humidity, resilience and risk factors. Fresh air drivers direct or indirect It is possible to analyse and compare the different types of cooling technology on a general and site-by-site basis. But when comparing two separate sites it is important to take many different factors into consideration. Whilst it is not easy to have one common perspective, given the range of variables such as location and climate, it is important that there are measures in place to reduce energy use regardless of the design used. For UK or colder climates the energy usage is practically the same for both a direct or a well-designed optimised indirect cooling solution, so it often comes down to other considerations. In warmer climates an indirect system is advantageous given the need to deal with high humidity. The main issue that was raised with direct cooling systems was the effect of contaminants in the air and the impact on the equipment housed in the data centre. It was generally agreed that systems do provide very good levels of filtration. However in many locations - such as the middle of a seaport, industrial estate or other areas of high contamination - it is not often sensible to use direct fresh air due to the amount of filtration needed and the risk of damage from corrosion or particles. However, in many locations in a normal everyday situation, it would be possible to use a direct fresh air system and still have a very clean data centre. From an initial CAPEX cost perspective, direct fresh air systems were in the main marginally more expensive, when full mechanical backup is required. This is partly due to the additional equipment and often due to the additional construction and integration into the physical building for the required airflow in and out. With an indirect system the free cooling and any mechanical systems can be integrated into one system and so there is far greater potential to achieve a total chillerless solution. In this configuration the main consideration is external ambient temperatures and not air contamination in normal or extreme conditions (e.g. fire). A view-point discussed was whether the use of direct fresh air has led to a plethora of new and recently completed projects over the last few years. These projects are partly and in some cases entirely because of the perception that it is green technology, but the risk has not been effectively evaluated. Furthermore, it was asked if a green rush syndrome was effectively blinding some organisations and preventing them developing solutions that met their real needs, rather than dealing with a perceived quick win. This is obviously not always the case and there are some excellent examples of well-designed systems however there was broad agreement that some were simply looking for a tick in the box (What is the PUE? Has it got fresh air-cooling?) and failing actually to come up with a solution that is more considered, i.e. necessary resilience and total operational performance now and during the facilities lifecycle. Without all of the facts around risk, peak PUE, part load performance and the difficulty in comparing different systems, the decision is often based simply on what an owner or operator wants. It was agreed that both direct and indirect provide the ability to raise server inlet temperatures due to the way the air is controlled and for either approach this normally gives additional hours of free cooling, holding off the need for any supplementary mechanical cooling. Calculating the risks Some concerns were raised about how risk was calculated when opting for fresh air. It was suggested that a risk profile is often developed for individual data centres, but there was not a standard approach because the impact is often so different for each organisation. There was a feeling that such a process was possible to model, but fairly complex so people simply did not undertake the exercise. Moreover, the general view was that actual risk modelling on pure direct fresh air, without a backup, does not really matter. This is because it comes down to the fact that if you need the data centre to stay up, then you would not actually run direct fresh air without the necessary backup systems. Therefore, the decision to use fresh air depends very much on the application and how an organisation calculates the risk. There was also agreement in the figures provided by the Uptime Institute that human error accounts for around 75% of data centre downtime. On that basis, increased complexity can make it harder to manage and potentially more likely to get wrong. Therefore the decisions around design need to factor in the simplicity of normal and failure operation, as well as how it is to be maintained. This is likely to play a major factor in the availability of the overall system. 3 The Use of Fresh Air in the Data Centre

4 It is widely recognised that different organisations have very different approaches to risk and how they factor it into their decisions: Large single application businesses with multiple facilities can accommodate downtime in a given location, as they can serve their customer base seamlessly from another location. Organisations with high volume and critical applications or transactions cannot afford to lose any services due to the financial and operational implications. It was agreed that even organisations in the same industry can take very different approaches to data centre strategy and design, both when building their own data centres but also outsourcing to a third party. Regardless of any of these approaches, there was an overriding feeling that calculating risk was not becoming more sophisticated. Different people within the same business have different attitudes to risk but were not really aware of those actually calculating it. However there is thought to be greater use of FMECA (Failure Mode Effects and Criticality Analysis) that does provide an indication of what will happen if a certain set of events occur. Design considerations An organisation requiring high availability is unlikely to install a direct fresh air system without 100% backup on the mechanical cooling. This is because the risks associated with the unknowns of what could happen outside, however infrequent, are generally out of the operators control. Indirect systems pose less or no risk from external pollutants and contaminants. Indirect systems do not require integration into the building fabric, where a direct system often needs large ducts or modifications to the shell. This can increase complexity and cost if, due to space or building height, it is even achievable. Direct systems often require more humidification control depending on which ranges are to be met. With most efficient systems there is some form of adiabatic cooling. With direct systems there is often a reliance on the water to provide capacity rather than simply improve efficiency. In this case there is a much greater reliance on water for normal operation and to maintain availability, which can lead to the need for water storage or other measures. The metric of WUE (Water Usage Effectiveness) needs to be considered. Many data centre facilities are already built with very inefficient cooling solutions. In such cases direct fresh air solutions provide an excellent opportunity to retrofit and run as the primary method of cooling, with the existing inefficient systems as back up. As the backup system is already in place this is often a very affordable option with a clear ROI. One of the biggest advantages for an indirect system is the potential for zero refrigeration. Half of the USA could take this route and even places people would never consider such as Madrid or even Dubai. This inevitably requires the use of and reliance on lots of water, as well as the acceptance of increasing server inlet temperatures during the warmer periods. Density of IT equipment does not make any impact to direct or indirect designs. It is the control of air and the method of air delivery within the space that dictates capacity and air volume requirements. There may be additional considerations for how backup systems and the control strategy between switching cooling methods works in high-density environments due to the risk of thermal increase in very short periods, but this is down to each individual design. Following the agreement that direct fresh air is going to require some sort of a backup system in order to meet availability and customer risk requirements, it is worth considering what benefits might exist for opting for either this or indirect design. Partly due to the different solutions in these two areas and partly because there are other variables on a site specific basis there are not many clear benefits either way, but there are a few considerations included: 4 The Use of Fresh Air in the Data Centre

5 The chillerless data centre The final area of discussion looked at the feasibility of chillerless data centre designs. It is recognised that this type of facility is already out there but they are not the norm and are often in climate-specific locations. These types of organisations also have different profiles for the services they deliver and include the likes of Facebook, Google and Yahoo! In many of these cases, whilst they can operate most if not all of the year without chillers, they can also be shut down for a period of time unlike most data centres in the world. If you would like to discuss any of the points raised in this white paper please contact marketing at Keysource and we will be happy to put you in touch with the right specialist. You may also be interested in the second white paper from the round table Raising Inlet Temperatures in the Data Centre. Moving away from single application facilities, other areas without chillers include specialist HPC (High Performance Computing) systems that may have low availability requirements and consume large amounts of power and facilities such as switch sites housing telecoms equipment. Generally there was a view that there is a significant challenge and no great desire for a typical end user or commercial operator to move to this type of design in the UK and most of mainland Europe. Moving forward there was agreement that chillerless solutions will start to become more widely used, especially where an indirect approach is taken and operators push the upper limits of server inlet temperatures. However this is not going to happen quickly when tight Service Level Agreements are in place or the cost of downtime is high. It is most likely a hybrid system will be the norm with a focus on reducing the peak PUE combined with reducing resilience on mechanical systems where they are only used for small periods of time. We would like to thank: Phil Collerton - Managing Director EMEA at the Uptime Institute, Alfonso Aranda - Consultant at the Uptime Institute, Luke Neville - Senior Technical Lead, Design Authority, Data Centre Services (DCS) at Colt, Andy Lawrence - Research Director at The 451 Group, Jim McGregor - Head of Engineering and Data Centre Management at Vocalink and Mike West - Managing Director of Keysource, as well as representatives from Operational Intelligence, Norland Managed Services and Fujitsu for joining us and sharing their expertise. 5 The Use of Fresh Air in the Data Centre

6 Keysource focuses on the full cycle of infrastructure technology in the data centre through consultation, design, build, ongoing management and optimisation. When high-performing resilient environments are needed to meet the latest demands of high-density IT and cloud technology, Keysource is trusted for simplifying the delivery of innovative data centre and integrated management solutions. We deploy the latest IT technology and reduce power consumption and operating costs for our customers through our own high performance cooling solution, ecofris. T: +44 (0) E: W: Keysource has delivered award winning data centres for some of the most established and innovative brands and organisations in the UK and globally. Our openness and honesty and vendor neutrality mean you ll get a straight, uncomplicated answer and the right solution for your business. The The Use of Fresh Air in the Data Centre white paper is published by Keysource (Copyright Keysource Ltd). All rights reserved. No part of this publication may be reproduced, copied or transmitted in any form or by any means, or stored in a retrieval system, without the prior permission of Keysource except as permitted by the provisions of the Copyright, Designs and Patents Act 1988 and related legislation. Application for permission to reproduce all or part of the Copyright material should be made to Keysource Ltd, North Heath Estate, Horsham, West Sussex, RH12, 5QE. Although the greatest care has been taken in the preparation and compilation of The Use of Fresh Air in the Data Centre white paper, no liability or responsibility of any kind (to extent permitted by law), including responsibility for negligence is accepted by Keysource or its agents. Keysource has reported the views and opinions of participants of the round table and does not endorse these views unless specifically stated. All information is believed correct at time of publication but there is no assurance or guarantee with respect to its accuracy. 6 The Use of Fresh Air in the Data Centre

7 T: +44 (0) E: W:

Raising Inlet Temperatures in the Data Centre

Raising Inlet Temperatures in the Data Centre Raising Inlet Temperatures in the Data Centre White paper of a round table debate by industry experts on this key topic. Hosted by Keysource with participants including the Uptime Institute. Sophistication

More information

White Paper: Free Cooling and the Efficiency of your Data Centre

White Paper: Free Cooling and the Efficiency of your Data Centre AIT Partnership Group Ltd White Paper: Free Cooling and the Efficiency of your Data Centre Using free cooling methods to increase environmental sustainability and reduce operational cost. Contents 1. Summary...

More information

Excool Indirect Adiabatic and Evaporative Data Centre Cooling. World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling

Excool Indirect Adiabatic and Evaporative Data Centre Cooling. World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Excool Indirect Adiabatic and Evaporative Data Centre Cooling World s Leading Indirect Adiabatic and Evaporative Data Centre Cooling Indirect Adiabatic and Evaporative Data Centre Cooling Solutions by

More information

VISIT 2010 Fujitsu Forum Europe 0

VISIT 2010 Fujitsu Forum Europe 0 VISIT 2010 Fujitsu Forum Europe 0 Virtualization & Automation Room 13a Shaping tomorrow with you. Green Data Center Services Martin Provoost Director, Data Centers and Networks, Fujitsu UK & Ireland 14:00

More information

AIRAH Presentation April 30 th 2014

AIRAH Presentation April 30 th 2014 Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining

More information

Analysis of data centre cooling energy efficiency

Analysis of data centre cooling energy efficiency Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe

More information

Greening Commercial Data Centres

Greening Commercial Data Centres Greening Commercial Data Centres Fresh air cooling giving a PUE of 1.2 in a colocation environment Greater efficiency and greater resilience Adjustable Overhead Supply allows variation in rack cooling

More information

European Code of Conduct for Data Centre. Presentation of the Awards 2013

European Code of Conduct for Data Centre. Presentation of the Awards 2013 European Code of Conduct for Data Centre Presentation of the Awards 2013 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results Started

More information

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Server Rooms Description & Heat Problem Trends

More information

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy

More information

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre S. Luong 1*, K. Liu 2, James Robey 3 1 Technologies for Sustainable Built Environments, University of Reading,

More information

ALWAYS ON GLOBALSWITCH.COM

ALWAYS ON GLOBALSWITCH.COM ALWAYS ON GLOBALSWITCH.COM Data Centre Design Considerations Kelvin Fong Managing Director, Hong Kong ALWAYS ON GLOBALSWITCH.COM Agenda 1. Introduction to Global Switch 2. Customer Requirements 3. Development

More information

Measuring Power in your Data Center

Measuring Power in your Data Center RESEARCH UNDERWRITER WHITE PAPER LEAN, CLEAN & GREEN Raritan Measuring Power in your Data Center Herman Chan, Director, Power Solutions Business Unit, and Greg More, Senior Product Marketing Manager There

More information

Environmental Data Center Management and Monitoring

Environmental Data Center Management and Monitoring 2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor

More information

Data Center Environments

Data Center Environments Data Center Environments ASHRAE s Evolving Thermal Guidelines By Robin A. Steinbrecher, Member ASHRAE; and Roger Schmidt, Ph.D., Member ASHRAE Over the last decade, data centers housing large numbers of

More information

Chiller-less Facilities: They May Be Closer Than You Think

Chiller-less Facilities: They May Be Closer Than You Think Chiller-less Facilities: They May Be Closer Than You Think A Dell Technical White Paper Learn more at Dell.com/PowerEdge/Rack David Moss Jon Fitch Paul Artman THIS WHITE PAPER IS FOR INFORMATIONAL PURPOSES

More information

How High Temperature Data Centers and Intel Technologies Decrease Operating Costs

How High Temperature Data Centers and Intel Technologies Decrease Operating Costs Intel Intelligent Management How High Temperature Data Centers and Intel Technologies Decrease Operating Costs and cooling savings through the use of Intel s Platforms and Intelligent Management features

More information

State of the Art Energy Efficient Data Centre Air Conditioning

State of the Art Energy Efficient Data Centre Air Conditioning - White Paper - State of the Art Energy Efficient Data Centre Air Conditioning - Dynamic Free Cooling - Release 2, April 2008 Contents ABSTRACT... 3 1. WHY DO I NEED AN ENERGY EFFICIENT COOLING SYSTEM...

More information

Managing Data Centre Heat Issues

Managing Data Centre Heat Issues Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design

More information

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no

More information

DATA CENTRE CONSOLIDATION; WHAT CAN ORGANISATIONS ACHIEVE? White Paper

DATA CENTRE CONSOLIDATION; WHAT CAN ORGANISATIONS ACHIEVE? White Paper DATA CENTRE CONSOLIDATION; WHAT CAN ORGANISATIONS ACHIEVE? White Paper Publication date: November 2012 EXECUTIVE SUMMARY Data centre costs constitute a large part of most organisations IT budget. As they

More information

Minimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis

Minimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis Minimising Data Centre Total Cost of Ownership Through Energy Efficiency Analysis Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. info@dc-oi.com

More information

Data Centers That Deliver Better Results. Bring Your Building Together

Data Centers That Deliver Better Results. Bring Your Building Together Data Centers That Deliver Better Results Bring Your Building Together 1 Meeting the high demands of your data center Meeting the increasing heat loads associated with growing computational needs requires

More information

Direct Fresh Air Free Cooling of Data Centres

Direct Fresh Air Free Cooling of Data Centres White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The

More information

SURVEY RESULTS: DATA CENTER ECONOMIZER USE

SURVEY RESULTS: DATA CENTER ECONOMIZER USE WHITE PAPER #41 SURVEY RESULTS: DATA CENTER ECONOMIZER USE EDITOR: Jessica Kaiser, Emerson Network Power CONTRIBUTORS: John Bean, Schneider Electric Tom Harvey, Emerson Network Power Michael Patterson,

More information

Common mistakes in datacentre planning

Common mistakes in datacentre planning Common mistakes in datacentre planning White Paper Last edited: March 2013 Document Control Document Information Title Author Common mistakes in datacentre planning Nick Ewing This document is based upon

More information

How To Find A Sweet Spot Operating Temperature For A Data Center

How To Find A Sweet Spot Operating Temperature For A Data Center Data Center Operating Temperature: The Sweet Spot A Dell Technical White Paper Dell Data Center Infrastructure David L. Moss THIS WHITE PAPER IS FOR INFORMATIONAL PURPOSES ONLY, AND MAY CONTAIN TYPOGRAPHICAL

More information

Overview of Green Energy Strategies and Techniques for Modern Data Centers

Overview of Green Energy Strategies and Techniques for Modern Data Centers Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.

More information

NIGERIA S PREMIUM DATA CENTRE

NIGERIA S PREMIUM DATA CENTRE NIGERIA S PREMIUM DATA CENTRE TIER III DESIGN CERTIFIED SECURE RELIABLE SCALABLE 1 WHY WOULD YOU WANT TO BUILD A DATA CENTRE? IT TAKES MILLIONS OF US DOLLARS TO BUILD AN EFFICIENT DATA CENTRE. A KEY ASSET,

More information

Datacenter Efficiency

Datacenter Efficiency EXECUTIVE STRATEGY BRIEF Operating highly-efficient datacenters is imperative as more consumers and companies move to a cloud computing environment. With high energy costs and pressure to reduce carbon

More information

Energy Saving Fact Sheet Air Conditioning

Energy Saving Fact Sheet Air Conditioning Energy Saving Fact Sheet Air Conditioning Get your air conditioning into better shape Everyone wants air conditioning. But don t let your existing system, or one that you re considering installing, burn

More information

Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling

Energy Efficient Server Room and Data Centre Cooling. Computer Room Evaporative Cooler. EcoCooling Energy Efficient Server Room and Data Centre Cooling Computer Room Evaporative Cooler EcoCooling EcoCooling CREC Computer Room Evaporative Cooler Reduce your cooling costs by over 90% Did you know? An

More information

Absolute and relative humidity Precise and comfort air-conditioning

Absolute and relative humidity Precise and comfort air-conditioning Absolute and relative humidity Precise and comfort air-conditioning Trends and best practices in data centers Compiled by: CONTEG Date: 30. 3. 2010 Version: 1.11 EN 2013 CONTEG. All rights reserved. No

More information

Technical Systems. Helen Bedford

Technical Systems. Helen Bedford Technical Systems in Data Centres Helen Bedford Technical Systems in Data Centres Overview Cooling IT and Peripheral Equipment Security: Access and Control Building Management System (BMS) Data Centre

More information

Time better spent. Take your organisation somewhere new with Fujitsu Mobile Business Solutions. Reshaping ICT, Reshaping Business

Time better spent. Take your organisation somewhere new with Fujitsu Mobile Business Solutions. Reshaping ICT, Reshaping Business Time better spent Take your organisation somewhere new with Fujitsu Mobile Business Solutions. Reshaping ICT, Reshaping Business Welcome to What would it mean to your organisation if your people were able

More information

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS

International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES

More information

Can you afford to ignore energy costs of IT infrastructure? A practical guide to more efficient data operations. Powering IT

Can you afford to ignore energy costs of IT infrastructure? A practical guide to more efficient data operations. Powering IT Can you afford to ignore energy costs of IT infrastructure? A practical guide to more efficient data operations. Powering IT Executive Summary Energy costs are expected to double over the next 10 years.

More information

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling

Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com

More information

Re Engineering to a "Green" Data Center, with Measurable ROI

Re Engineering to a Green Data Center, with Measurable ROI Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices

More information

Three Steps To Perfectly Green

Three Steps To Perfectly Green R E S E A R C H U N D E R W R I T E R W H I T E P A P E R LEAN, CLEAN & GREEN Deerns Consulting Engineers Three Steps To Perfectly Green By Wouter M. Kok, Manager, Cleanroom, Laboratory, and Data Center

More information

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information

AIR-SITE GROUP. White Paper. Green Equipment Room Practices

AIR-SITE GROUP. White Paper. Green Equipment Room Practices AIR-SITE GROUP White Paper Green Equipment Room Practices www.air-site.com Common practices to build a green equipment room 1 Introduction Air-Site (www.air-site.com) is a leading international provider

More information

Data centres that deliver ENQUIRIES@DATACENTRE-MEA.AE

Data centres that deliver ENQUIRIES@DATACENTRE-MEA.AE Data centres that deliver ENQUIRIES@DATACENTRE-MEA.AE DATA CENTRE INFRASTRUCTURE MANAGEMENT (DCIM) DCIM solutions are designed to collect and manage information about a data centre s assets, resource use

More information

The Effect of Data Centre Environment on IT Reliability & Energy Consumption

The Effect of Data Centre Environment on IT Reliability & Energy Consumption The Effect of Data Centre Environment on IT Reliability & Energy Consumption Steve Strutt EMEA Technical Work Group Member IBM The Green Grid EMEA Technical Forum 2011 Agenda History of IT environmental

More information

Guide to Minimizing Compressor-based Cooling in Data Centers

Guide to Minimizing Compressor-based Cooling in Data Centers Guide to Minimizing Compressor-based Cooling in Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By: Lawrence Berkeley National Laboratory Author: William Tschudi

More information

T: 0344 875 4555 ENQUIRIES@DATACENTRE-UK.COM

T: 0344 875 4555 ENQUIRIES@DATACENTRE-UK.COM T: 0344 875 4555 ENQUIRIES@DATACENTRE-UK.COM DATACENTRE UK INTRODUCTION Datacentre UK are specialist providers of energy efficient data centre and physical infrastructure solutions across the UK, Europe

More information

- White Paper - Data Centre Cooling. Best Practice

- White Paper - Data Centre Cooling. Best Practice - White Paper - Data Centre Cooling Best Practice Release 2, April 2008 Contents INTRODUCTION... 3 1. AIR FLOW LEAKAGE... 3 2. PERFORATED TILES: NUMBER AND OPENING FACTOR... 4 3. PERFORATED TILES: WITH

More information

How and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners

How and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners How and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners White Paper #56 Revision 2 Executive Summary Today's technology rooms require precise, stable environments in order for

More information

Top 5 Trends in Data Center Energy Efficiency

Top 5 Trends in Data Center Energy Efficiency Top 5 Trends in Data Center Energy Efficiency By Todd Boucher, Principal Leading Edge Design Group 603.632.4507 @ledesigngroup Copyright 2012 Leading Edge Design Group www.ledesigngroup.com 1 In 2007,

More information

The NREN s core activities are in providing network and associated services to its user community that usually comprises:

The NREN s core activities are in providing network and associated services to its user community that usually comprises: 3 NREN and its Users The NREN s core activities are in providing network and associated services to its user community that usually comprises: Higher education institutions and possibly other levels of

More information

DATA CENTER ASSESSMENT SERVICES

DATA CENTER ASSESSMENT SERVICES DATA CENTER ASSESSMENT SERVICES ig2 Group Inc. is a Data Center Science Company which provides solutions that can help organizations automatically optimize their Data Center performance, from assets to

More information

White paper. The 8 pillars of colocation. Written By: Adelle Desouza Matthew Gingell Rowdy VanRijn Victor Smith

White paper. The 8 pillars of colocation. Written By: Adelle Desouza Matthew Gingell Rowdy VanRijn Victor Smith White paper The 8 pillars of colocation Written By: Adelle Desouza Matthew Gingell Rowdy VanRijn Victor Smith Executive Summary With Gartner suggesting colocation grew by 8% last year alone, many are turning

More information

Building a data center. C R Srinivasan Tata Communications

Building a data center. C R Srinivasan Tata Communications Building a data center C R Srinivasan Tata Communications Introduction Data Center as defined by TIA 942 A building or a portion of a building whose primary function is to house a computer room and its

More information

THE WORLD S MOST EFFICIENT DATA CENTER

THE WORLD S MOST EFFICIENT DATA CENTER THE WORLD S MOST EFFICIENT DATA CENTER HP POD 240a Ed Turkel Manager, WW HPC Marketing Hyperscale Business Unit 2011 Hewlett-Packard Development Company, L.P. The information contained herein is subject

More information

Green Data Centre Design

Green Data Centre Design Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS

More information

BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0

BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 To achieve GREEN MARK Award Pre-requisite Requirement All relevant pre-requisite requirements for the specific Green Mark Rating are to be complied

More information

Introducing AUDIT-BUDDY

Introducing AUDIT-BUDDY Introducing AUDIT-BUDDY Optimize the Data Center with AUDIT-BUDDY Executive Summary Proper temperature and humidity for the inlet air into the servers is essential to efficient data center operation. Several

More information

The Mission Critical Data Center Understand Complexity Improve Performance

The Mission Critical Data Center Understand Complexity Improve Performance The Mission Critical Data Center Understand Complexity Improve Performance Communications Technology Forum Fall 2013 Department / Presenter / Date 1 Rittal IT Solutions The State of the Data Center Market

More information

THE GREEN DATA CENTER

THE GREEN DATA CENTER GREEN IT THE GREEN DATA CENTER WHERE ECOLOGY MEETS ECONOMY We truly live in an information age. Data Centers serve a very important purpose they provide the global community with nearly unlimited access

More information

System solution for data centres

System solution for data centres 1 System solution for data centres Energy-efficient air conditioning with ServeLine Cooling IT infrastructure, high availability, low energy costs and communication with DCIM systems all in one from your

More information

The European Programme for Energy Efficiency in Data Centres: The Code of Conduct

The European Programme for Energy Efficiency in Data Centres: The Code of Conduct The European Programme for Energy Efficiency in Data Centres: The Code of Conduct Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 Why Data Centres? Continuing demand for

More information

Power and Cooling for Ultra-High Density Racks and Blade Servers

Power and Cooling for Ultra-High Density Racks and Blade Servers Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw

More information

How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems

How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems Paul Mathew, Ph.D., Staff Scientist Steve Greenberg, P.E., Energy Management Engineer

More information

How To Save Money On Your Phone System

How To Save Money On Your Phone System Top Tips for Recruitment Companies upgrading to IP Telephony With the UK employment market on the way back up, many recruitment agencies are looking at how modern communications technology can help them

More information

CIBSE ASHRAE Group. Data Centre Energy Efficiency: Who, What, Why, When, Where & How

CIBSE ASHRAE Group. Data Centre Energy Efficiency: Who, What, Why, When, Where & How CIBSE ASHRAE Group Data Centre Energy Efficiency: Who, What, Why, When, Where & How Presenters Don Beaty PE, FASHRAE Founder, President & Managing Director DLB Associates Consulting Engineers Paul Finch

More information

Free Cooling for Data Centers

Free Cooling for Data Centers Free Cooling for Data Centers Release 1, September 2015 Contents 1. Abstract... 3 2. Introduction... 3 3. Data Center Temperatures and Free Cooling... 4 4. Direct Free Cooling... 4 5. Indirect Free Cooling...

More information

Data Center Technology: Physical Infrastructure

Data Center Technology: Physical Infrastructure Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider

More information

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT DATA CENTER RESOURCES WHITE PAPER IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT BY: STEVE HAMBRUCH EXECUTIVE SUMMARY Data centers have experienced explosive growth in the last decade.

More information

Alfa Laval Abatigo. Redefining adiabatic cooling

Alfa Laval Abatigo. Redefining adiabatic cooling Alfa Laval Abatigo Redefining adiabatic cooling Experience and expertise recognized throughout the world With decades of broad experience and practical expertise in heat transfer, Alfa Laval is today a

More information

Scalable. Affordable. Flexible. Fast.

Scalable. Affordable. Flexible. Fast. Modular Data Center Solutions Scalable. Affordable. Flexible. Fast. Build the data center you need today with the flexibility to meet tomorrow s challenges The only constant in business is change. Fluctuations

More information

Data Center Infrastructure Management - a special report

Data Center Infrastructure Management - a special report Copyright 2012 S1NED Limited all rights reserved Data Center Infrastructure Management - a special report It s not all about cost June 2012 How do I know if my Data Center is about to fail? The simple

More information

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency

More information

Questions to be responded to by the firm submitting the application. Why do you think this project should receive an award? How does it demonstrate:

Questions to be responded to by the firm submitting the application. Why do you think this project should receive an award? How does it demonstrate: Questions to be responded to by the firm submitting the application Why do you think this project should receive an award? How does it demonstrate: innovation, quality, and professional excellence transparency

More information

Modular Chiller Plants for data centers. Downtime isn t acceptable

Modular Chiller Plants for data centers. Downtime isn t acceptable Modular Chiller Plants for data centers Downtime isn t acceptable Reducing risk with Quick Start A direct solution to your most important challenge uptime. At Johnson Controls we protect our customers

More information

Defining Quality. Building Comfort. Precision. Air Conditioning

Defining Quality. Building Comfort. Precision. Air Conditioning Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air

More information

Critical Environment Risk Management

Critical Environment Risk Management DATA CENTRE SECTOR Critical Environment Risk Management for Data Centres Exceptional Service, Exceptional People Data centre experience Norland supports some of the world s leading enterprise data centres

More information

Guideline for Water and Energy Considerations During Federal Data Center Consolidations

Guideline for Water and Energy Considerations During Federal Data Center Consolidations Guideline for Water and Energy Considerations During Federal Data Center Consolidations Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings

Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Kenneth G. Brill, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies, Inc. 505.798.0200

More information

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates

More information

Who do the biggest names in servers, search, healthcare, cloud & financial services trust to provide power management solutions?

Who do the biggest names in servers, search, healthcare, cloud & financial services trust to provide power management solutions? Who do the biggest names in servers, search, healthcare, cloud & financial services trust to provide power management solutions? The first team in power management ......... The world s best cabinet power

More information

The Green Grid, Metrics and DCMM. Presented by: Jay Taylor

The Green Grid, Metrics and DCMM. Presented by: Jay Taylor The Green Grid, Metrics and DCMM Presented by: Jay Taylor About The Green Grid A not-for-profit international consortium committed to advancing resource efficiency in business computing ecosystems and

More information

Table of Contents. 2 Why IT Organizations Everywhere Need to go Green. 3 Greening the Data Center

Table of Contents. 2 Why IT Organizations Everywhere Need to go Green. 3 Greening the Data Center WHITE PAPER: Energy Efficiency Go Green: Energy Efficiency for the IT Organization Table of Contents 2 Why IT Organizations Everywhere Need to go Green 3 Greening the Data Center 5 Savvis Commitment to

More information

The Elephant in the Room is Lost Capacity

The Elephant in the Room is Lost Capacity The Elephant in the Room is Lost Capacity How your short term drivers erode your long term goals Executive Summary In the world of economics, short-termism, the policy of concentrating on short-term profit

More information

Data Centre Cooling Air Performance Metrics

Data Centre Cooling Air Performance Metrics Data Centre Cooling Air Performance Metrics Sophia Flucker CEng MIMechE Ing Dr Robert Tozer MSc MBA PhD CEng MCIBSE MASHRAE Operational Intelligence Ltd. info@dc-oi.com Abstract Data centre energy consumption

More information

Data Centre Outsourcing a Buyer s Guide

Data Centre Outsourcing a Buyer s Guide Data Centre Outsourcing a Buyer s Guide The inside guide to deciding whether to outsource your data centre facility and operations and how to select an appropriate partner. This Guide will help you Determine

More information

How To Improve Energy Efficiency In A Data Center

How To Improve Energy Efficiency In A Data Center Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

Energy Savings in the Data Center Starts with Power Monitoring

Energy Savings in the Data Center Starts with Power Monitoring Energy Savings in the Data Center Starts with Power Monitoring As global competition intensifies, companies are increasingly turning to technology to help turn mountains of data into a competitive edge.

More information

Introduction to Hitachi Group Environment- conscious Data Center Programme for inspiring change

Introduction to Hitachi Group Environment- conscious Data Center Programme for inspiring change Introduction to Hitachi Group Environment- conscious Data Center Programme for inspiring change DATA CENTRE LOCATIONS Forum Kouvola, Finland Hitachi in Europe September 2011 By Ian Blond Head of Data Centre

More information

IT@Intel. Thermal Storage System Provides Emergency Data Center Cooling

IT@Intel. Thermal Storage System Provides Emergency Data Center Cooling White Paper Intel Information Technology Computer Manufacturing Thermal Management Thermal Storage System Provides Emergency Data Center Cooling Intel IT implemented a low-cost thermal storage system that

More information

M2G Intelligent Boiler Load Optimisation

M2G Intelligent Boiler Load Optimisation M2G Intelligent Boiler Load Optimisation Intelligent, real-time, individual boiler control for more efficient boilers, lower costs and lower carbon emissions M2G M2G is a patented intelligent boiler load

More information

An Introduction to Cold Aisle Containment Systems in the Data Centre

An Introduction to Cold Aisle Containment Systems in the Data Centre An Introduction to Cold Aisle Containment Systems in the Data Centre White Paper October 2010 By Zac Potts MEng Mechanical Engineer Sudlows October 2010 An Introduction to Cold Aisle Containment Systems

More information

THE GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCiE

THE GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCiE THE GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCiE 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any

More information

Reducing Data Center Energy Consumption

Reducing Data Center Energy Consumption Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate

More information

Data Centre Infrastructure Assessment

Data Centre Infrastructure Assessment Data Centre Infrastructure Assessment Prepared for: ACME INC SAMPLE REPORT Attention: Mr DC Manager This report represents a generic sample data centre audit for a generic customer by Focus Group Technologies.

More information

Data Center Equipment Power Trends

Data Center Equipment Power Trends Green field data center design 11 Jan 2010 by Shlomo Novotny Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. explores water cooling for maximum efficiency - Part 1 Overview Data

More information

The Intelligent Data Centre

The Intelligent Data Centre The Intelligent Data Centre VIRTUS: Ahead of the Intelligent Data Centre Curve So What is an Intelligent Data Centre? The role of the data centre has changed. Over the last few years it has transitioned

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE

HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE HIGHLY EFFICIENT COOLING FOR YOUR DATA CENTRE Best practices for airflow management and cooling optimisation AIRFLOW MANAGEMENT COLD AND HOT AISLE CONTAINMENT DC ASSESSMENT SERVICES Achieving true 24/7/365

More information

Critical Infrastructure for the World s Leading Data Centers

Critical Infrastructure for the World s Leading Data Centers Critical Infrastructure for the World s Leading Data Centers 2 YOU MAY KNOW US BY OUR BRAND NAMES THE EXPERTISE OF MANY. THE POWER OF ONE. Nortek Air Solutions provides critical infrastructure for the

More information