How High Temperature Data Centers and Intel Technologies Decrease Operating Costs

Size: px
Start display at page:

Download "How High Temperature Data Centers and Intel Technologies Decrease Operating Costs"

Transcription

1 Intel Intelligent Management How High Temperature Data Centers and Intel Technologies Decrease Operating Costs and cooling savings through the use of Intel s Platforms and Intelligent Management features in a High Temperature Data Center Environment Intel Corporation April 2012

2 Contents Executive Summary... 2 Business Opportunity 2 Background: Tellhow Gitong Technology LTD 2 Technical Challenge... 3 High Temperature Ambient Data Center Operations ASHRAE Guidelines 3 Shanghai Climate Data Summary 4 Compute Design Considerations... 4 Modular Data Center Design Considerations 5 Business Value... 5 Without the use of Free Cooling $75,686.40USD: 6 With the use of Free Cooling $42,888.96USD: 6 Total possible saving with Free Cooling : 6 Overall Results... 6 Glossary... 7 Executive Summary A High Temperature Ambient (HTA) Modular Data Center (MDC) will save Gitong customers operational costs. There are three key metrics covered in this whitepaper when considering MDC and HTA: Business Opportunity Increasing compute density in DC s will continue to result in corresponding increase in rack and room power densities. Gitong wants to utilize the latest technologies to gain the best performance and best energy efficiency across their Cloud Computing Business offering. The American Society of Heating, Refrigerating and Air- Conditioning Engineers (ASHRAE) have set out two options that weighs reliability against energy i.e. the use of UPS and cooling in a 2n (redundancy by duplication) configuration is very reliable but requires more energy to operate. 1. Location environmental data 2. Server platform selection 3. Modular Data Center design considerations The objective is to maximize the savings by increasing the MDC operation temperature of the servers by utilizing outside air to remove heat from the MDC. Table 2 - ASHRAE s Technical Committee TC9.9, Mission Critical Facilities, Technology Spaces and Electronic Equipment Modular Data Center (MDC) A Modular Data Center is a rapid method of deploying data center capacity. It can be used as an alternative or in conjunction with a traditional data center. A modular data center can be placed anywhere Data Center/Compute capacity is needed. High Temperature Ambient (HTA) Table 1 MDC and HTA definition Raising the operating temperature within the MDC increases the number of hours that outside air can be used to dissipate heat and increases power utilization efficiency. Background: Gitong Technology LTD a subsidiary of Tellhow Gitong is a leading provider of Green Data Center (GDC) products, offering carrier-grade GDC products that fully meet international standards. Gitong GDC products include container GDC and module GDC featuring worldclass high efficiency, power savings with lower carbon emissions. Gitong has both technical skill and development experience, which comes from years of manufacturing

3 experience. Gitong has incorporated various Global standards to developed methodologies for the GDC, such as PUE and high-efficiency thermal server performance testing in conjunction with Intel. Gitong has a manufacturing and test facilities in Nanchang, Jiangxi Province; People Republic of China. They have sales and service teams throughout the country. Technical Challenge The power and thermal optimization problem becomes one of thermodynamics, i.e.: dissipating heat generated by the servers with a mixture of outside air and/or recirculated air. This is done by passing the air through the servers. The servers transfer the heat to the air and then ducting hot exhaust air. High Temperature Ambient Data Center Operations Before a cloud service provider considers the use of HTA in the data center, the external ambient Class A1: Typically a data center with tightly controlled environmental parameters (dew point, temperature, and relative humidity) and mission critical operations; types of products typically designed for this environment are enterprise servers and storage products. Class A2: Typically an information technology (IT) space with some control of environmental parameters (dew point, temperature, and relative humidity). Class A3/A4: Typically an IT space with some control of environmental parameters listed above. The new guidelines were developed with a focus on providing as much information as possible to the data center operator to allow them to operate in the most energy efficient mode and still achieve the reliability necessary as required by their business. Two new data center classes are created to achieve the most flexibility in the operation of the data center. The four data center classes including the two new ones (A3 and A4) are shown in the psychometric chart below. temperature conditions play a large role in determining how many hours the data center can utilize free cooling. The servers also need to operate within warranty specifications by the server manufacturer ASHRAE Guidelines ASHRAE has defined extended range of operational conditions for IT loads in the Data Center, known as classes. Compliance with a particular environmental Figure 1 - Psychrometric Chart class requires full operation of the equipment over the entire allowable environmental range, based on nonfailure conditions.

4 free cooling most of the year based on the average maximum daily temperature. The number of days that are above 32 C are in the summer (July and August) and free cooling is still possible by increasing the airflow and increasing MDC operating temperature above Table ASHRAE Thermal Guidelines IT Equipment Operations Shanghai Climate Data Summary The 2008 climate data provided by the US Dept of Commerce National Oceanic and Atmospheric Administration (NOAA) was analyzed to investigate operating the Gitong MDC Data Center in HTA mode to decreased cooling costs. Table 4 Shanghai Climate Data 35 C. Compute Design Considerations When selecting a platform for HTA operations the platform must be able to operate at high temperatures without offsetting the benefits of HTA with a platform power increase. The power increase is a result of both fan power, component power and the power conversion for each. The component power increase is a result of an increase in leakage current for some silicon devices. As an example of the usage of Figure 2 Server Increase vs Ambient Temperature for Classes A2 and A3, if a data center is normally operating at a server inlet temperature of 15 C and the operator wants to raise this temperature to 30 C, it could be expected that the server power would increase in the range of 4 to 8%. If the inlet temperature increases to 35 C, the IT equipment power could increase in the range of 7 to 20% compared to operating at 15 C. Table 5 Shanghai Climate Graph The chart above graphs the recorded minimum and maximum temperatures in Shanghai. The graph shows that, if the current data center computer room is set to 35 C, there will be an opportunity to run

5 of the range in Figure 2 Server Increase vs Ambient Temperature for Classes A2 and A3 Modular Data Center Design Considerations The MDC needs to consider the following requirements to ensure that the PUE is maximized. Currently design PUE is 1.8; to move to the goal of 1.02 the MDC needs the following: Figure 2 Server Increase vs Ambient Temperature for Classes A2 and A3 Intel server platform provided by Enterprise Platforms and Services Division (EPSD) documents the requirements for improving energy consumption and computing efficiency in the Enabling Server Platforms for Expanded Thermal Environments 1. The warranty provided by EPSD HTA product SKUs will operate at 35 C and considers this as normal operating temperature. EPSD HTA SKUs support excursions of 40 C for 900hrs or 10% of year and 45 C for 90hrs or 1% of the year. This will yield cost savings as the temperature data shows that Shanghai does will be in the operating temperature listed above. The climate data is not sufficiently granular to depict the hours at 40 C and 45 C respectively. The assumption that even the 29days (696hours) would not be at these temperatures constantly each day, and the MDC could operate within the server warranty specification. New products from manufactures like EPSD will be provided for class A3/4 with improved heat sinks, thermal shadowing and/or fans to properly cool the components, so the power increases is at the low end 1 Document Number:469017, Revision Access to outside air 2. Outside air filter system 3. Humidity control system 4. No Uninterruptable Supply (UPS) 5. Server power monitoring and tracking with Intel Node Manager and Data Center Manager 6. Fan control system All Data Center systems need to be coordinated through a Building Management System (BMS). Business Value The MDC designed with all the design consideration listed above the MDC could improve the PUE from 1.8 to The IT load stays constant at 8kW/rack with 6 racks within each MDC. Table 6 - Without the use of Free Cooling below enumerate the cost savings for a MDC with no HTA and no implementation of the design consideration listed above. The operational cost of power is $75, USD/annum. Table 7 -With the use of Free Cooling below enumerate the cost savings for a MDC with HTA and implementation of the design consideration listed

6 above. The operational cost of power is $42,888.96USD/annum. Without the use of Free Cooling $75,686.40USD: Time Number Units 365 days 24 hours Total Hours 8,760 hours Platform Total 8 kw 6 # of racks 420,480 Efficiency 1.8 PUE MDC 336,384 kw Total 756,864 kw Cost $ 0.10 USD/kWh Total Cost $ 75, USD/kWh Table 6 - Without the use of Free Cooling Overall Results An HTA Modular Data Center based on EPSD server platforms has clearly shown that there are three key metrics covered in this whitepaper when considering MDC and HTA: 1. Location environmental data 2. Server platform selection 3. Modular Data Center design considerations The objective is to maximize the savings by increasing the MDC operation temperature of the servers. This would lead to a potentially yearly operational savings of $32, /annum/mdc. With the use of Free Cooling $42,888.96USD: Time Number Units 365 days 24 hours Total Hours 8,760 hours Platform Total 8 kw 6 # of racks 420,480 Efficiency 1.02 PUE MDC 8,410 kw Total 428,890 kw Cost $ 0.10 USD/kWh Total Cost $ 42, USD/kWh Table 7 -With the use of Free Cooling Total possible saving with Free Cooling : $75, $42, = $32, /annum/mdc

7 Glossary usage effectiveness (PUE) PUE is a measure of how efficiently a computer data center uses its power; specifically, how much of the power is actually used by the computing equipment (in contrast to cooling and other overhead lower PUE is better). BMC MDC DC DCM NM ASHRAE CFD CRAC DC DCIE HTA ODM PUE TCO TAmbient Board Management Controller Modular Data Center Data Center Intel Data Center Manager Intel Intelligent Node Manager The American Society of Heating, Refrigerating and Air-Conditioning Engineers Computational Fluid Dynamics Computer Room Air Conditioner Unit, used inter-changeably with AHU Data Center Data Center Infrastructure Efficiency High Ambient Temperature Original Design Manufacturer Usage Effectiveness Total Cost of Ownership Air temperature at economizer outlet Disclaimers Δ Intel processor numbers are not a measure of performance. Processor numbers differentiate features within each processor family, not across different processor families. See products/processor_number for details. INFORMATION IN THIS DOCUMENT IS PROVIDED IN CONNECTION WITH INTEL PRODUCTS. NO LICENSE, EXPRESS OR IMPLIED, BY ESTOPPEL OR OTHERWISE, TO ANY INTELLECTUAL PROPERTY RIGHTS IS GRANTED BY THIS DOCUMENT. EXCEPT AS PROVIDED IN INTEL S TERMS AND CONDITIONS OF SALE FOR SUCH PRODUCTS, INTEL ASSUMES NO LIABILITY WHATSOEVER, AND INTEL DISCLAIMS ANY EXPRESS OR IMPLIED WARRANTY, RELATING TO SALE AND/OR USE OF INTEL PRODUCTS INCLUDING LIABILITY OR WARRANTIES RELATING TO FITNESS FOR A PARTICULAR PURPOSE, MERCHANTABILITY, OR INFRINGEMENT OF ANY PATENT, COPYRIGHT OR OTHER INTELLECTUAL PROPERTY RIGHT. UNLESS OTHERWISE AGREED IN WRITING BY INTEL, THE INTEL PRODUCTS ARE NOT DESIGNED NOR INTENDED FOR ANY APPLICATION IN WHICH THE FAILURE OF THE INTEL PRODUCT COULD CREATE A SITUATION WHERE PERSONAL INJURY OR DEATH MAY OCCUR. Intel may make changes to specifications and product descriptions at any time, without notice. Designers must not rely on the absence or characteristics of any features or instructions marked reserved or undefined. Intel reserves these for future definition and shall have no responsibility whatsoever for conflicts or incompatibilities arising from future changes to them. The information here is subject to change without notice. Do not finalize a design with this information. The products described in this document may contain design defects or errors known as errata which may cause the product to deviate from published specifications. Current characterized errata are available on request. Contact your local Intel sales office or your distributor to obtain the latest specifications and before placing your product order. Copies of documents which have an order number and are referenced in this document, or other Intel literature, may be obtained by calling , or by visiting Intel s Web site at Copyright 2012 Intel Corporation. All rights reserved. Intel, the Intel logo, Xeon, Xeon inside, and Intel Intelligent Node Manager are trademarks of Intel Corporation in the U.S. and other countries. *Other names and brands may be claimed as the property of others.

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent

More information

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel

More information

Cloud based Holdfast Electronic Sports Game Platform

Cloud based Holdfast Electronic Sports Game Platform Case Study Cloud based Holdfast Electronic Sports Game Platform Intel and Holdfast work together to upgrade Holdfast Electronic Sports Game Platform with cloud technology Background Shanghai Holdfast Online

More information

Intel Core i5 processor 520E CPU Embedded Application Power Guideline Addendum January 2011

Intel Core i5 processor 520E CPU Embedded Application Power Guideline Addendum January 2011 Intel Core i5 processor 520E CPU Embedded Application Power Guideline Addendum January 2011 Document Number: 324818-001 INFORMATION IN THIS DOCUMENT IS PROVIDED IN CONNECTION WITH INTEL PRODUCTS. NO LICENSE,

More information

Intel Atom Processor E3800 Product Family

Intel Atom Processor E3800 Product Family Intel Atom Processor E3800 Product Family Thermal Design Guide October 2013 Document Number: 329645-001 Legal Lines and Disclaimers INFORMATION IN THIS DOCUMENT IS PROVIDED IN CONNECTION WITH INTEL PRODUCTS.

More information

The Case for Rack Scale Architecture

The Case for Rack Scale Architecture The Case for Rack Scale Architecture An introduction to the next generation of Software Defined Infrastructure Intel Data Center Group Pooled System Top of Rack Switch POD Manager Network CPU/Memory Storage

More information

Server Power and Performance Evaluation in High-Temperature Environments

Server Power and Performance Evaluation in High-Temperature Environments WHITE PAPER Intel Xeon Processors with Intel Node Manager Microsoft Windows Server Data Center Cooling and Power Management Intel Corporation: K. Govindaraju, Workloads/Performance Architect; Robin Steinbrecher,

More information

Intel Solid-State Drive Pro 2500 Series Opal* Compatibility Guide

Intel Solid-State Drive Pro 2500 Series Opal* Compatibility Guide Opal* Compatibility Guide 1.0 Order Number: 331049-001US INFORMATION IN THIS DOCUMENT IS PROVIDED IN CONNECTION WITH INTEL PRODUCTS. NO LICENSE, EXPRESS OR IMPLIED, BY ESTOPPEL OR OTHERWISE, TO ANY INTELLECTUAL

More information

Intel Media SDK Library Distribution and Dispatching Process

Intel Media SDK Library Distribution and Dispatching Process Intel Media SDK Library Distribution and Dispatching Process Overview Dispatching Procedure Software Libraries Platform-Specific Libraries Legal Information Overview This document describes the Intel Media

More information

Intel Data Center Manager. Data center IT agility and control

Intel Data Center Manager. Data center IT agility and control Intel Data Center Manager Data center IT agility and control The Data Center Ecosystem 2 Why do we care about Data Center Management? attributed to devices connected to the Internet of Everything (up from

More information

Intel SSD 520 Series Specification Update

Intel SSD 520 Series Specification Update Intel SSD 520 Series Specification Update June 2012 Revision 1.0 Document Number: 327567-001US INFORMATION IN THIS DOCUMENT IS PROVIDED IN CONNECTION WITH INTEL PRODUCTS. NO LICENSE, EXPRESS OR IMPLIED,

More information

Intel Desktop Board D945GCPE Specification Update

Intel Desktop Board D945GCPE Specification Update Intel Desktop Board D945GCPE Specification Update Release Date: July 11, 2007 Order Number: E11670-001US The Intel Desktop Board D945GCPE may contain design defects or errors known as errata, which may

More information

Intel Desktop Board DG41TY

Intel Desktop Board DG41TY Intel Desktop Board DG41TY Specification Update July 2010 Order Number E58490-006US The Intel Desktop Board DG41TY may contain design defects or errors known as errata, which may cause the product to deviate

More information

Intel Desktop Board DG45FC

Intel Desktop Board DG45FC Intel Desktop Board DG45FC Specification Update July 2010 Order Number: E46340-007US The Intel Desktop Board DG45FC may contain design defects or errors known as errata, which may cause the product to

More information

Intel Desktop Board D945GCPE

Intel Desktop Board D945GCPE Intel Desktop Board D945GCPE Specification Update January 2009 Order Number: E11670-003US The Intel Desktop Board D945GCPE may contain design defects or errors known as errata, which may cause the product

More information

Preserving Performance While Saving Power Using Intel Intelligent Power Node Manager and Intel Data Center Manager

Preserving Performance While Saving Power Using Intel Intelligent Power Node Manager and Intel Data Center Manager WHITE PAPER Intel Intelligent Power Node Manager Intel Data Center Manager Data Center Power Management Preserving Performance While Saving Power Using Intel Intelligent Power Node Manager and Intel Data

More information

Intel Desktop Board DG43RK

Intel Desktop Board DG43RK Intel Desktop Board DG43RK Specification Update December 2010 Order Number: E92421-003US The Intel Desktop Board DG43RK may contain design defects or errors known as errata, which may cause the product

More information

Intel Cloud Builder Guide: Cloud Design and Deployment on Intel Platforms

Intel Cloud Builder Guide: Cloud Design and Deployment on Intel Platforms EXECUTIVE SUMMARY Intel Cloud Builder Guide Intel Xeon Processor-based Servers Red Hat* Cloud Foundations Intel Cloud Builder Guide: Cloud Design and Deployment on Intel Platforms Red Hat* Cloud Foundations

More information

The Effect of Data Centre Environment on IT Reliability & Energy Consumption

The Effect of Data Centre Environment on IT Reliability & Energy Consumption The Effect of Data Centre Environment on IT Reliability & Energy Consumption Steve Strutt EMEA Technical Work Group Member IBM The Green Grid EMEA Technical Forum 2011 Agenda History of IT environmental

More information

iscsi Quick-Connect Guide for Red Hat Linux

iscsi Quick-Connect Guide for Red Hat Linux iscsi Quick-Connect Guide for Red Hat Linux A supplement for Network Administrators The Intel Networking Division Revision 1.0 March 2013 Legal INFORMATION IN THIS DOCUMENT IS PROVIDED IN CONNECTION WITH

More information

Intel Service Assurance Administrator. Product Overview

Intel Service Assurance Administrator. Product Overview Intel Service Assurance Administrator Product Overview Running Enterprise Workloads in the Cloud Enterprise IT wants to Start a private cloud initiative to service internal enterprise customers Find an

More information

Intel Network Builders: Lanner and Intel Building the Best Network Security Platforms

Intel Network Builders: Lanner and Intel Building the Best Network Security Platforms Solution Brief Intel Xeon Processors Lanner Intel Network Builders: Lanner and Intel Building the Best Network Security Platforms Internet usage continues to rapidly expand and evolve, and with it network

More information

Intel Desktop Board DP55WB

Intel Desktop Board DP55WB Intel Desktop Board DP55WB Specification Update July 2010 Order Number: E80453-004US The Intel Desktop Board DP55WB may contain design defects or errors known as errata, which may cause the product to

More information

Intel Desktop Board DG31PR

Intel Desktop Board DG31PR Intel Desktop Board DG31PR Specification Update July 2010 Order Number: E30564-007US The Intel Desktop Board DG31PR may contain design defects or errors known as errata, which may cause the product to

More information

Intel Cloud Builder Guide to Cloud Design and Deployment on Intel Platforms

Intel Cloud Builder Guide to Cloud Design and Deployment on Intel Platforms Intel Cloud Builder Guide to Cloud Design and Deployment on Intel Platforms Ubuntu* Enterprise Cloud Executive Summary Intel Cloud Builder Guide Intel Xeon Processor Ubuntu* Enteprise Cloud Canonical*

More information

Intel Desktop Board DG41BI

Intel Desktop Board DG41BI Intel Desktop Board DG41BI Specification Update July 2010 Order Number: E88214-002US The Intel Desktop Board DG41BI may contain design defects or errors known as errata, which may cause the product to

More information

Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers

Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers C P I P O W E R M A N A G E M E N T WHITE PAPER Selecting Rack-Mount Power Distribution Units For High-Efficiency Data Centers By Anderson Hungria Sr. Product Manager of Power, Electronics & Software Published

More information

Intel Desktop Board DQ43AP

Intel Desktop Board DQ43AP Intel Desktop Board DQ43AP Specification Update July 2010 Order Number: E69398-005US The Intel Desktop Board DQ43AP may contain design defects or errors known as errata, which may cause the product to

More information

Intel Core TM i3 Processor Series Embedded Application Power Guideline Addendum

Intel Core TM i3 Processor Series Embedded Application Power Guideline Addendum Intel Core TM i3 Processor Series Embedded Application Power Guideline Addendum July 2012 Document Number: 327705-001 INFORMATION IN THIS DOCUMENT IS PROVIDED IN CONNECTION WITH INTEL PRODUCTS. NO LICENSE,

More information

Intel Simple Network Management Protocol (SNMP) Subagent v6.0

Intel Simple Network Management Protocol (SNMP) Subagent v6.0 Intel Simple Network Management Protocol (SNMP) Subagent v6.0 User Guide March 2013 ii Intel SNMP Subagent User s Guide Legal Information INFORMATION IN THIS DOCUMENT IS PROVIDED IN CONNECTION WITH INTEL

More information

Intel Desktop Board DG43NB

Intel Desktop Board DG43NB Intel Desktop Board DG43NB Specification Update August 2010 Order Number: E49122-009US The Intel Desktop Board DG43NB may contain design defects or errors known as errata, which may cause the product to

More information

Intel Desktop Board DQ45CB

Intel Desktop Board DQ45CB Intel Desktop Board DQ45CB Specification Update July 2010 Order Number: E53961-007US The Intel Desktop Board DQ45CB may contain design defects or errors known as errata, which may cause the product to

More information

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT

IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT DATA CENTER RESOURCES WHITE PAPER IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT BY: STEVE HAMBRUCH EXECUTIVE SUMMARY Data centers have experienced explosive growth in the last decade.

More information

Intel Desktop Board DP43BF

Intel Desktop Board DP43BF Intel Desktop Board DP43BF Specification Update September 2010 Order Number: E92423-004US The Intel Desktop Board DP43BF may contain design defects or errors known as errata, which may cause the product

More information

Affordable Building Automation System Enabled by the Internet of Things (IoT)

Affordable Building Automation System Enabled by the Internet of Things (IoT) Solution Blueprint Internet of Things (IoT) Affordable Building Automation System Enabled by the Internet of Things (IoT) HCL Technologies* uses an Intel-based intelligent gateway to deliver a powerful,

More information

Intel Cloud Builders Guide to Cloud Design and Deployment on Intel Platforms

Intel Cloud Builders Guide to Cloud Design and Deployment on Intel Platforms Intel Cloud Builders Guide Intel Xeon Processor-based Servers RES Virtual Desktop Extender Intel Cloud Builders Guide to Cloud Design and Deployment on Intel Platforms Client Aware Cloud with RES Virtual

More information

Improving Data Center Energy Efficiency Through Environmental Optimization

Improving Data Center Energy Efficiency Through Environmental Optimization Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic

More information

High-Temperature Hosting Data Center

High-Temperature Hosting Data Center White Paper Intel Xeon Processor E5 Family Data Center Efficiency High-Temperature Hosting Data Center Testing to Discover the Opportunities and Challeges in High-Temperature Operating Conditions in a

More information

Intel Technical Advisory

Intel Technical Advisory This Technical Advisory describes an issue which may or may not affect the customer s product Intel Technical Advisory 5200 NE Elam Young Parkway Hillsboro, OR 97124 TA-1054-01 April 4, 2014 Incorrectly

More information

RAID and Storage Options Available on Intel Server Boards and Systems

RAID and Storage Options Available on Intel Server Boards and Systems and Storage Options Available on Intel Server Boards and Systems Revision 1.0 March, 009 Revision History and Storage Options Available on Intel Server Boards and Systems Revision History Date Revision

More information

Intel HTML5 Development Environment. Tutorial Test & Submit a Microsoft Windows Phone 8* App (BETA)

Intel HTML5 Development Environment. Tutorial Test & Submit a Microsoft Windows Phone 8* App (BETA) Intel HTML5 Development Environment Tutorial Test & Submit a Microsoft Windows Phone 8* App v1.00 : 04.09.2013 Legal Information INFORMATION IN THIS DOCUMENT IS PROVIDED IN CONNECTION WITH INTEL PRODUCTS.

More information

Intel and Qihoo 360 Internet Portal Datacenter - Big Data Storage Optimization Case Study

Intel and Qihoo 360 Internet Portal Datacenter - Big Data Storage Optimization Case Study Intel and Qihoo 360 Internet Portal Datacenter - Big Data Storage Optimization Case Study The adoption of cloud computing creates many challenges and opportunities in big data management and storage. To

More information

Intel Desktop Board D945GCZ

Intel Desktop Board D945GCZ Intel Desktop Board D945GCZ Specification Update December 2007 Order Number D23991-007US The Intel Desktop Board D945GCZ may contain design defects or errors known as errata, which may cause the product

More information

Intel Desktop Board D945GCL

Intel Desktop Board D945GCL Intel Desktop Board D945GCL Specification Update December 2007 Order Number D74277-004US The Intel Desktop Board D945GCL may contain design defects or errors known as errata, which may cause the product

More information

Different NFV/SDN Solutions for Telecoms and Enterprise Cloud

Different NFV/SDN Solutions for Telecoms and Enterprise Cloud Solution Brief Artesyn Embedded Technologies* Telecom Solutions Intel Xeon Processors Different NFV/SDN Solutions for Telecoms and Enterprise Cloud Networking solutions from Artesyn Embedded Technologies*

More information

How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems

How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems Paul Mathew, Ph.D., Staff Scientist Steve Greenberg, P.E., Energy Management Engineer

More information

Intel Desktop Board DQ965GF

Intel Desktop Board DQ965GF Intel Desktop Board DQ965GF Specification Update October 2008 Order Number: D65914-005US The Intel Desktop Board DQ965GF may contain design defects or errors known as errata, which may cause the product

More information

The Efficient Data Center

The Efficient Data Center WHITE PAPER Data Center Efficiency and Optimization Data Center Management The Efficient Data Center Using data center instrumentation and server refresh to optimize compute performance in constrained

More information

Intel Desktop Board DG41WV

Intel Desktop Board DG41WV Intel Desktop Board DG41WV Specification Update April 2011 Part Number: E93639-003 The Intel Desktop Board DG41WV may contain design defects or errors known as errata, which may cause the product to deviate

More information

with PKI Use Case Guide

with PKI Use Case Guide Intel Identity Protection Technology (Intel IPT) with PKI Use Case Guide Version 1.0 Document Release Date: February 29, 2012 Intel IPT with PKI Use Case Guide i Legal Notices and Disclaimers INFORMATION

More information

COSBench: A benchmark Tool for Cloud Object Storage Services. Jiangang.Duan@intel.com 2012.10

COSBench: A benchmark Tool for Cloud Object Storage Services. Jiangang.Duan@intel.com 2012.10 COSBench: A benchmark Tool for Cloud Object Storage Services Jiangang.Duan@intel.com 2012.10 Updated June 2012 Self introduction COSBench Introduction Agenda Case Study to evaluate OpenStack* swift performance

More information

Intel Desktop Board DQ35JO

Intel Desktop Board DQ35JO Intel Desktop Board DQ35JO Specification Update May 2008 Order Number E21492-002US The Intel Desktop Board DQ35JO may contain design defects or errors known as errata, which may cause the product to deviate

More information

Intel Identity Protection Technology (IPT)

Intel Identity Protection Technology (IPT) Intel Identity Protection Technology (IPT) Enabling improved user-friendly strong authentication in VASCO's latest generation solutions June 2013 Steve Davies Solution Architect Intel Corporation 1 Copyright

More information

Intel Active Management Technology Embedded Host-based Configuration in Intelligent Systems

Intel Active Management Technology Embedded Host-based Configuration in Intelligent Systems WHITE PAPER Intel vpro Technology Embedded Host-based Configuration in Intelligent Systems Easy activation of Intel vpro technology remote manageability without trade-offs in security, functionality, and

More information

System Event Log (SEL) Viewer User Guide

System Event Log (SEL) Viewer User Guide System Event Log (SEL) Viewer User Guide For Extensible Firmware Interface (EFI) and Microsoft Preinstallation Environment Part Number: E12461-001 Disclaimer INFORMATION IN THIS DOCUMENT IS PROVIDED IN

More information

NFV Reference Platform in Telefónica: Bringing Lab Experience to Real Deployments

NFV Reference Platform in Telefónica: Bringing Lab Experience to Real Deployments Solution Brief Telefonica NFV Reference Platform Intel Xeon Processors NFV Reference Platform in Telefónica: Bringing Lab Experience to Real Deployments Summary This paper reviews Telefónica s vision and

More information

Intel Desktop Board DG33TL

Intel Desktop Board DG33TL Intel Desktop Board DG33TL Specification Update May 2008 Order Number E11661-003US The Intel Desktop Board DG33TL may contain design defects or errors known as errata, which may cause the product to deviate

More information

Introducing AUDIT- BUDDY

Introducing AUDIT- BUDDY Introducing AUDIT- BUDDY Monitoring Temperature and Humidity for Greater Data Center Efficiency 202 Worcester Street, Unit 5, North Grafton, MA 01536 www.purkaylabs.com info@purkaylabs.com 1.774.261.4444

More information

VNF & Performance: A practical approach

VNF & Performance: A practical approach VNF & Performance: A practical approach Luc Provoost Engineering Manager, Network Product Group Intel Corporation SDN and NFV are Forces of Change One Application Per System Many Applications Per Virtual

More information

The Efficient Data Center

The Efficient Data Center WHITE PAPER Data Center Efficiency and Optimization Data Center Management The Efficient Data Center Using data center instrumentation and server refresh to optimize compute performance in constrained

More information

Chiller-less Facilities: They May Be Closer Than You Think

Chiller-less Facilities: They May Be Closer Than You Think Chiller-less Facilities: They May Be Closer Than You Think A Dell Technical White Paper Learn more at Dell.com/PowerEdge/Rack David Moss Jon Fitch Paul Artman THIS WHITE PAPER IS FOR INFORMATIONAL PURPOSES

More information

Intel Data Direct I/O Technology (Intel DDIO): A Primer >

Intel Data Direct I/O Technology (Intel DDIO): A Primer > Intel Data Direct I/O Technology (Intel DDIO): A Primer > Technical Brief February 2012 Revision 1.0 Legal Statements INFORMATION IN THIS DOCUMENT IS PROVIDED IN CONNECTION WITH INTEL PRODUCTS. NO LICENSE,

More information

Intel Desktop Board DG965RY

Intel Desktop Board DG965RY Intel Desktop Board DG965RY Specification Update May 2008 Order Number D65907-005US The Intel Desktop Board DG965RY contain design defects or errors known as errata, which may cause the product to deviate

More information

Intel HTML5 Development Environment. Article - Native Application Facebook* Integration

Intel HTML5 Development Environment. Article - Native Application Facebook* Integration Intel HTML5 Development Environment Article - Native Application Facebook* Integration V3.06 : 07.16.2013 Legal Information INFORMATION IN THIS DOCUMENT IS PROVIDED IN CONNECTION WITH INTEL PRODUCTS. NO

More information

Resetting USB drive using Windows Diskpart command

Resetting USB drive using Windows Diskpart command Resetting USB drive using Windows Diskpart command Simon Huang Technical Product Manager simon.huang@supertalent.com Super Talent Technology October, 2013 Release 1.00 1 Legal Disclaimer INFORMATION IN

More information

Intel Desktop Board D945GNT

Intel Desktop Board D945GNT Intel Desktop Board D945GNT Specification Update Release Date: November 2007 Order Number: D23992-007US The Intel Desktop Board D945GNT may contain design defects or errors known as errata, which may cause

More information

Intel Desktop Board D101GGC Specification Update

Intel Desktop Board D101GGC Specification Update Intel Desktop Board D101GGC Specification Update Release Date: November 2006 Order Number: D38925-003US The Intel Desktop Board D101GGC may contain design defects or errors known as errata, which may cause

More information

Scaling Networking Solutions for IoT Challenges and Opportunities

Scaling Networking Solutions for IoT Challenges and Opportunities Scaling Networking Solutions for IoT Challenges and Opportunities Anil Kumar, Intel. Santa Clara, CA USA April 2015 1 Legal Disclaimer INFORMATION IN THIS DOCUMENT IS PROVIDED IN CONNECTION WITH INTEL

More information

Data Center Environments

Data Center Environments Data Center Environments ASHRAE s Evolving Thermal Guidelines By Robin A. Steinbrecher, Member ASHRAE; and Roger Schmidt, Ph.D., Member ASHRAE Over the last decade, data centers housing large numbers of

More information

Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint

Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment

More information

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre

Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre S. Luong 1*, K. Liu 2, James Robey 3 1 Technologies for Sustainable Built Environments, University of Reading,

More information

Intelligent Business Operations

Intelligent Business Operations White Paper Intel Xeon Processor E5 Family Data Center Efficiency Financial Services Intelligent Business Operations Best Practices in Cash Supply Chain Management Executive Summary The purpose of any

More information

Accelerating Business Intelligence with Large-Scale System Memory

Accelerating Business Intelligence with Large-Scale System Memory Accelerating Business Intelligence with Large-Scale System Memory A Proof of Concept by Intel, Samsung, and SAP Executive Summary Real-time business intelligence (BI) plays a vital role in driving competitiveness

More information

Intel HTML5 Development Environment Article Using the App Dev Center

Intel HTML5 Development Environment Article Using the App Dev Center Intel HTML5 Development Environment Article Using the App Dev Center v1.06 : 06.04.2013 Legal Information INFORMATION IN THIS DOCUMENT IS PROVIDED IN CONNECTION WITH INTEL PRODUCTS. NO LICENSE, EXPRESS

More information

Raising Inlet Temperatures in the Data Centre

Raising Inlet Temperatures in the Data Centre Raising Inlet Temperatures in the Data Centre White paper of a round table debate by industry experts on this key topic. Hosted by Keysource with participants including the Uptime Institute. Sophistication

More information

Intel IXP42X Product Line of Network Processors and IXC1100 Control Plane Processor: Spread-Spectrum Clocking to Reduce EMI

Intel IXP42X Product Line of Network Processors and IXC1100 Control Plane Processor: Spread-Spectrum Clocking to Reduce EMI Intel IXP42X Product Line of Network Processors and IXC1100 Control Plane Processor: Spread-Spectrum Clocking to Reduce EMI Application Note July 2004 Document Number: 254028-002 INFORMATION IN THIS DOCUMENT

More information

Software Solutions for Multi-Display Setups

Software Solutions for Multi-Display Setups White Paper Bruce Bao Graphics Application Engineer Intel Corporation Software Solutions for Multi-Display Setups January 2013 328563-001 Executive Summary Multi-display systems are growing in popularity.

More information

Intel Core TM i7-660ue, i7-620le/ue, i7-610e, i5-520e, i3-330e and Intel Celeron Processor P4505, U3405 Series

Intel Core TM i7-660ue, i7-620le/ue, i7-610e, i5-520e, i3-330e and Intel Celeron Processor P4505, U3405 Series Intel Core TM i7-660ue, i7-620le/ue, i7-610e, i5-520e, i3-330e and Intel Celeron Processor P4505, U3405 Series Datasheet Addendum Specification Update Document Number: 323179 Legal Lines and Disclaimers

More information

Creating Overlay Networks Using Intel Ethernet Converged Network Adapters

Creating Overlay Networks Using Intel Ethernet Converged Network Adapters Creating Overlay Networks Using Intel Ethernet Converged Network Adapters Technical Brief Networking Division (ND) August 2013 Revision 1.0 LEGAL INFORMATION IN THIS DOCUMENT IS PROVIDED IN CONNECTION

More information

Intel RAID RS25 Series Performance

Intel RAID RS25 Series Performance PERFORMANCE BRIEF Intel RAID RS25 Series Intel RAID RS25 Series Performance including Intel RAID Controllers RS25DB080 & PERFORMANCE SUMMARY Measured IOPS surpass 200,000 IOPS When used with Intel RAID

More information

Intel RAID Controllers

Intel RAID Controllers Intel RAID Controllers Best Practices White Paper April, 2008 Enterprise Platforms and Services Division - Marketing Revision History Date Revision Number April, 2008 1.0 Initial release. Modifications

More information

DDR2 x16 Hardware Implementation Utilizing the Intel EP80579 Integrated Processor Product Line

DDR2 x16 Hardware Implementation Utilizing the Intel EP80579 Integrated Processor Product Line Utilizing the Intel EP80579 Integrated Processor Product Line Order Number: 320296-002US Legal Lines and Disclaimers INFORMATION IN THIS DOCUMENT IS PROVIDED IN CONNECTION WITH INTEL PRODUCTS. NO LICENSE,

More information

White Paper: Free Cooling and the Efficiency of your Data Centre

White Paper: Free Cooling and the Efficiency of your Data Centre AIT Partnership Group Ltd White Paper: Free Cooling and the Efficiency of your Data Centre Using free cooling methods to increase environmental sustainability and reduce operational cost. Contents 1. Summary...

More information

High Availability Server Clustering Solutions

High Availability Server Clustering Solutions White Paper High vailability Server Clustering Solutions Extending the benefits of technology into the server arena Intel in Communications Contents Executive Summary 3 Extending Protection to Storage

More information

A Superior Hardware Platform for Server Virtualization

A Superior Hardware Platform for Server Virtualization A Superior Hardware Platform for Server Virtualization Improving Data Center Flexibility, Performance and TCO with Technology Brief Server Virtualization Server virtualization is helping IT organizations

More information

Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360

Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360 Autodesk Revit 2013 Autodesk BIM 360 Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360 Data centers consume approximately 200 terawatt hours of energy

More information

How to Configure Intel X520 Ethernet Server Adapter Based Virtual Functions on Citrix* XenServer 6.0*

How to Configure Intel X520 Ethernet Server Adapter Based Virtual Functions on Citrix* XenServer 6.0* How to Configure Intel X520 Ethernet Server Adapter Based Virtual Functions on Citrix* XenServer 6.0* Technical Brief v1.0 December 2011 Legal Lines and Disclaimers INFORMATION IN THIS DOCUMENT IS PROVIDED

More information

Benefits of. Air Flow Management. Data Center

Benefits of. Air Flow Management. Data Center Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment

More information

Accelerating Business Intelligence with Large-Scale System Memory

Accelerating Business Intelligence with Large-Scale System Memory Accelerating Business Intelligence with Large-Scale System Memory A Proof of Concept by Intel, Samsung, and SAP Executive Summary Real-time business intelligence (BI) plays a vital role in driving competitiveness

More information

Intel Identity Protection Technology Enabling improved user-friendly strong authentication in VASCO's latest generation solutions

Intel Identity Protection Technology Enabling improved user-friendly strong authentication in VASCO's latest generation solutions Intel Identity Protection Technology Enabling improved user-friendly strong authentication in VASCO's latest generation solutions June 2013 Dirk Roziers Market Manager PC Client Services Intel Corporation

More information

Dell s Next Generation Servers: Pushing the Limits of Data Center Cooling Cost Savings

Dell s Next Generation Servers: Pushing the Limits of Data Center Cooling Cost Savings Dell s Next Generation Servers: Pushing the Limits of Data Center Cooling Cost Savings This white paper explains how Dell s next generation of servers were developed to support fresh air cooling and overall

More information

Intel Cloud Builder Guide to Cloud Design and Deployment on Intel Xeon Processor-based Platforms

Intel Cloud Builder Guide to Cloud Design and Deployment on Intel Xeon Processor-based Platforms Intel Cloud Builder Guide to Cloud Design and Deployment on Intel Xeon Processor-based Platforms Enomaly Elastic Computing Platform, * Service Provider Edition Executive Summary Intel Cloud Builder Guide

More information

Cloud Service Brokerage Case Study. Health Insurance Association Launches a Security and Integration Cloud Service Brokerage

Cloud Service Brokerage Case Study. Health Insurance Association Launches a Security and Integration Cloud Service Brokerage Cloud Service Brokerage Case Study Health Insurance Association Launches a Security and Integration Cloud Service Brokerage Cloud Service Brokerage Case Study Health Insurance Association Launches a Security

More information

IT@Intel. Thermal Storage System Provides Emergency Data Center Cooling

IT@Intel. Thermal Storage System Provides Emergency Data Center Cooling White Paper Intel Information Technology Computer Manufacturing Thermal Management Thermal Storage System Provides Emergency Data Center Cooling Intel IT implemented a low-cost thermal storage system that

More information

Intel Internet of Things (IoT) Developer Kit

Intel Internet of Things (IoT) Developer Kit Intel Internet of Things (IoT) Developer Kit IoT Cloud-Based Analytics User Guide September 2014 IoT Cloud-Based Analytics User Guide Introduction Table of Contents 1.0 Introduction... 4 1.1. Revision

More information

Intel Server System S7000FC4UR

Intel Server System S7000FC4UR Intel Server System S7000FC4UR Power Cord Enabling Specification January, 2007 Enterprise Platforms and Services Division - Marketing Intel Server System S7000FC4UR Power Supply Specification Revision

More information

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences

DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no

More information

Intel Platform Controller Hub EG20T

Intel Platform Controller Hub EG20T Intel Platform Controller Hub EG20T General Purpose Input Output (GPIO) Driver for Windows* Order Number: 324257-002US Legal Lines and Disclaimers INFORMATION IN THIS DOCUMENT IS PROVIDED IN CONNECTION

More information

Specification Update. January 2014

Specification Update. January 2014 Intel Embedded Media and Graphics Driver v36.15.0 (32-bit) & v3.15.0 (64-bit) for Intel Processor E3800 Product Family/Intel Celeron Processor * Release Specification Update January 2014 Notice: The Intel

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information