Energy Smart Data Center Phase-III R&D. Andrés Márquez. Pacific Northwest National Laboratory
|
|
|
- Cornelius Griffith
- 10 years ago
- Views:
Transcription
1 Energy Smart Data Center Phase-III R&D Andrés Márquez Pacific Northwest National Laboratory
2 Overall Task Division Advance spraycooling technology (ISR) Advance 3D chip scale packing technology (Tessera) Evaluate these technologies in conjunction and in comparison with other technologies (PNNL) 2
3 Objectives of ESDC Phase-III R&D: Spraycooling Demonstrate spot spraycooling technology at the facility level by deploying a spraycooled cluster Instrument at processor, server, rack and facility level to acquire realtime data Measure electrical/thermal parameters of an air cooled cluster subsystem as a base-line, determine COP Measure electrical/thermal parameters of a spraycooled cluster, determine COP Characterize TCO Simulate and validate facility CFD Monitor cluster availability and reliability Perform a trade study of spraycooled system delivery and installation Demonstrate +40kW/rack High Power Density Computing Demonstrate indirect spraycooling 3
4 Demonstrate Spot Spraycooling Technology at Facility Level First demonstration at this scale (~10 servers) Enables validation of spraycooling technology with production equipment vs. engineering samples in previous phases Engages HPC OEM in spraycooling technology addressing issues such as integration, deployment and installation 4
5 Instrument at Processor, Server, Rack, and Facility Level First multi-scale instrumentation of spraycooling technology Processor instrumentation enables Tracking processor health Analysis of root failures in worst case scenarios Server and Rack instrumentation enables Tracking system health Monitoring behavior of TMU Measurement of thermal interaction between servers Measurement of thermal loads on the facility per rack Facility instrumentation enables Access to data unavailable in a production facility (Power/Temp/Flows) Populating models with real data (COP/TCO/CFD) Exercising what-if-scenarios (chiller on/off) 5
6 Measure Parameters of Air Cooled Sub-System System Measure Power/Temp/Flows with a conventionally air cooled system enabling Validation of specifications as established by OEM Comparison of competitive technologies under similar conditions by providing a baseline Universal identification of accepted parameters such as COP Validation of models such as TCO/CFD 6
7 Measure Parameters of Spraycooled Cluster Measure Power/Temp/Flows with a spot spraycooled system enabling Validation of specifications as established by OEM+ISR Comparison of competitive technologies under similar conditions by providing a baseline Universal identification of accepted parameters such as COP Validation of models such as TCO/CFD Validation and follow-up experimentation such as chiller bypass, load change, etc. 7
8 Characterize Total Cost of Ownership Plug air cooled and spraycooled measured values into TCO model. 8
9 Simulate and Validate Facility CFD Perform facility CFD simulation Under air cooling conditions Under spraycooling conditions Validate facility CFD with measured data If necessary improve model or change sampling discretization and reiterate Use CFD model to improve air flow conditions and avoid over-engineering that might affect COP/TCO numbers 9
10 Monitor Cluster Availability and Reliability Phase-III production-grade hardware is expected to be fairly stable without requiring interventions and modifications A sub-system of the cluster will be exempt from perturbations resulting from experiments to avoid influencing reliability studies Availability and reliability information will also be used to establish maintenance and servicing criteria 10
11 Perform Trade Study of System Delivery and Installation Mean time to repair Filed repair strategies at different levels Troubleshooting and diagnostics Repair process and tools Material requirements (consumables) Typical cost considerations Reliability, availability, service requirements Design for serviceability Design for manufacturability Service parts strategy Training strategy and requirements Onsite installation and testing Facility modifications and installation requirements 11
12 High Density Computing +40kW/rack Build a combination of a rack with resistive heat loads and some fully spraycooled boards with a thermal load of +40kW Demonstrate high performance density per volume Demonstrate feasibility of spraycooling thermal management 12
13 Indirect Spraycooling Demonstrate the capability of indirect spraycooling to enable component cooling that is not amenable to spot cooling Enable spot and indirect cooling 13
14 Additional Objectives of ESDC Phase-III R&D Alternative Cooling Solutions Conduct studies on alternative cooling solutions. These studies include solutions by established vendors at the data center level as well as various cooling solutions at the chip level DC Power Delivery Investigate conversion and distribution losses on a DC branch and compare with power delivery on AC branch Consider using the High Density Computing platform as DUT Architecture Studies Conduct a study to investigate if these technologies are applicable to high-density hybrid-computing 14
Pacific Northwest National Laboratory (PNNL)
Energy Smart Data Center Phase I Andrés Márquez, Tom Seim, Kevin Regimbal, Steve Elbert, Kevin Fox, and Blanche Wood Pacific Northwest National Laboratory (PNNL) Introduction Our current Environmental
Thermal Management of Datacenter
Thermal Management of Datacenter Qinghui Tang 1 Preliminaries What is data center What is thermal management Why does Intel Care Why Computer Science 2 Typical layout of a datacenter Rack outlet temperature
HPC TCO: Cooling and Computer Room Efficiency
HPC TCO: Cooling and Computer Room Efficiency 1 Route Plan Motivation (Why do we care?) HPC Building Blocks: Compuer Hardware (What s inside my dataroom? What needs to be cooled?) HPC Building Blocks:
How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel
Datacenter Power Delivery Architectures : Efficiency and Annual Operating Costs
Datacenter Power Delivery Architectures : Efficiency and Annual Operating Costs Paul Yeaman, V I Chip Inc. Presented at the Darnell Digital Power Forum September 2007 Abstract An increasing focus on datacenter
SMART SHELTER CONTAINER
Da ta Ce nt er Total Flexibility and Security in a Modular Data Center Advantages Environmentally Friendly Short Delivery Time Smart Shelter Container (SSC) solution provides a fully functional Data Center
Solve your IT energy crisis WITH An energy SMArT SoluTIon FroM Dell
Solve your IT energy crisis WITH AN ENERGY SMART SOLUTION FROM DELL overcome DATA center energy challenges IT managers share a common and pressing problem: how to reduce energy consumption and cost without
High-density modular data center making cloud easier. Frank Zheng Huawei
High-density modular data center making cloud easier Frank Zheng Huawei 2012-10-10 Content 1 2 3 4 Cloud s impact to data center Concerns of DC construction 4S DC making cloud easier Success stories Cloud?
Data Center Power Distribution and Capacity Planning:
Data Center Power Distribution and Capacity Planning: Understanding what you know and don t know about power usage in your data center 2009, Raritan Inc. About This Series Raritan, a leading provider of
Huawei Data Center Facility Integration Solution
Huawei Data Center Facility Integration Solution HUAWEI TECHNOLOGIES CO., LTD. As the growing demand for efficiency, flexibility and low-cost, enterprise need a more flexible and efficient data center
How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent
Statement Of Work Professional Services
Statement Of Work Professional Services Data Center Cooling Analysis using CFD Data Center Cooling Analysis Using Computational Fluid Dynamics Service 1.0 Executive Summary Table of Contents 1.0 Executive
DataCenter 2020: first results for energy-optimization at existing data centers
DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction
Data Center 2020: Delivering high density in the Data Center; efficiently and reliably
Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:
Increasing Data Center Efficiency by Using Improved High Density Power Distribution
Increasing Data Center Efficiency by Using Improved High Density Power Distribution By Neil Rasmussen White Paper #128 Executive Summary A new approach to power distribution for high density server installations
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no
CUSTOMER EXPERIENCE CENTER
v CUSTOMER EXPERIENCE CENTER ABOUT THE CUSTOMER EXPERIENCE CENTER MAKE YOUR DATA CENTER AS DYNAMIC AS YOUR BUSINESS Emerson Network Power continuously strives to provide the best solutions by working collaboratively
How High Temperature Data Centers and Intel Technologies Decrease Operating Costs
Intel Intelligent Management How High Temperature Data Centers and Intel Technologies Decrease Operating Costs and cooling savings through the use of Intel s Platforms and Intelligent Management features
Delivering results with Datacenter Clarity LC TM
Philippe Heim Boston, September 9th, 2015 Delivering results with Datacenter Clarity LC TM siemens.com Intro movie Page 2 20XX-XX-XX Table of contents 1 Challenges 2 Integrated DCIM solution overview 3
Overview of Green Energy Strategies and Techniques for Modern Data Centers
Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.
Specialty Environment Design Mission Critical Facilities
Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,
Data Center Technology: Physical Infrastructure
Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider
Green Data Centre Design
Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
Enabling an agile Data Centre in a (Fr)agile market
Enabling an agile Data Centre in a (Fr)agile market Phil Dodsworth Director, Data Centre Solutions 2008 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without
Reducing Data Center Energy Consumption
Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate
Data Center Power Consumption
Data Center Power Consumption A new look at a growing problem Fact - Data center power density up 10x in the last 10 years 2.1 kw/rack (1992); 14 kw/rack (2007) Racks are not fully populated due to power/cooling
DATA CENTER ASSESSMENT SERVICES
DATA CENTER ASSESSMENT SERVICES ig2 Group Inc. is a Data Center Science Company which provides solutions that can help organizations automatically optimize their Data Center performance, from assets to
The CEETHERM Data Center Laboratory
The CEETHERM Data Center Laboratory A Platform for Transformative Research on Green Data Centers Yogendra Joshi and Pramod Kumar G.W. Woodruff School of Mechanical Engineering Georgia Institute of Technology
Data Center Facility Basics
Data Center Facility Basics Ofer Lior, Spring 2015 Challenges in Modern Data Centers Management, Spring 2015 1 Information provided in these slides is for educational purposes only Challenges in Modern
SmartDesign Intelligent, Integrated Infrastructure For The Data Center. Solutions For Business-Critical Continuity
SmartDesign Intelligent, Integrated Infrastructure For The Data Center Solutions For Business-Critical Continuity Prepare Your Data Center For What s Next Efficiency. Availability. Capacity. Control. One
Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009
Optimum Climate Control For Datacenter - Case Study T. Prabu March 17 th 2009 Agenda 2 About EDEC (Emerson) Facility Data Center Details Design Considerations & Challenges Layout Design CFD Analysis Of
Elements of Energy Efficiency in Data Centre Cooling Architecture
Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total
Data Center Consolidation Trends & Solutions. Bob Miller Vice President, Global Solutions Sales Emerson Network Power / Liebert
Data Center Consolidation Trends & Solutions Bob Miller Vice President, Global Solutions Sales Emerson Network Power / Liebert Agenda Traditional Data Centers Drivers of a Changing Environment Alternate
Data Center Trend: Distributed Power in the White Space
Data Center Trend: Distributed Power in the White Space By Jason Anderson Product Line Manager Eaton Executive summary Cloud computing vendors and colocation data centers make every effort to maximize
Data Sheet FUJITSU Server PRIMERGY CX400 M1 Multi-Node Server Enclosure
Data Sheet FUJITSU Server PRIMERGY CX400 M1 Multi-Node Server Enclosure Data Sheet FUJITSU Server PRIMERGY CX400 M1 Multi-Node Server Enclosure Scale-Out Smart for HPC, Cloud and Hyper-Converged Computing
Direct Contact Liquid Cooling (DCLC ) PRODUCT GUIDE. Industry leading data center solutions for HPC, Cloud and Enterprise markets.
Direct Contact Liquid Cooling (DCLC ) PRODUCT GUIDE Industry leading data center solutions for HPC, Cloud and Enterprise markets. Leadership, Collaboration & Expertise CooIIT Systems Innovates and Delivers
Re Engineering to a "Green" Data Center, with Measurable ROI
Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices
Thermal Analysis, Heat Sink Design and Performance Verification for GE Fanuc Intelligent Platform s WANic 3860 Packet Processor PCI Card
CASE STUDY Thermal Analysis, Heat Sink Design and Performance Verification for GE Fanuc Intelligent Platform s WANic 3860 Packet Processor PCI Card Challenge When GE Fanuc Intelligent Platforms, a leading
Managing Data Center Power and Cooling
White PAPER Managing Data Center Power and Cooling Introduction: Crisis in Power and Cooling As server microprocessors become more powerful in accordance with Moore s Law, they also consume more power
Modeling Rack and Server Heat Capacity in a Physics Based Dynamic CFD Model of Data Centers. Sami Alkharabsheh, Bahgat Sammakia 10/28/2013
Modeling Rack and Server Heat Capacity in a Physics Based Dynamic CFD Model of Data Centers Sami Alkharabsheh, Bahgat Sammakia 1/28/213 2 ES2 Vision To create electronic systems that are self sensing and
Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360
Autodesk Revit 2013 Autodesk BIM 360 Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360 Data centers consume approximately 200 terawatt hours of energy
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise. A White Paper from the Experts in Business-Critical Continuity
Data Center Precision Cooling: The Need For A Higher Level Of Service Expertise A White Paper from the Experts in Business-Critical Continuity Executive Summary Today s data centers are changing rapidly,
Dynamic Power Variations in Data Centers and Network Rooms
Dynamic Power Variations in Data Centers and Network Rooms By Jim Spitaels White Paper #43 Revision 2 Executive Summary The power requirement required by data centers and network rooms varies on a minute
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
Data Center Energy Efficiency. SC07 Birds of a Feather November, 2007 Bill Tschudi [email protected]
Data Center Energy Efficiency SC07 Birds of a Feather November, 2007 Bill Tschudi [email protected] Benchmark results helped to find best practices The ratio of IT equipment power to the total (or its
Benefits of Cold Aisle Containment During Cooling Failure
Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business
Power and Cooling Capacity Management for Data Centers
Power and Cooling Capacity for Data Centers By Neil Rasmussen White Paper #150 Executive Summary High density IT equipment stresses the power density capability of modern data centers. Installation and
INDIAN INSTITUTE OF TECHNOLOGY KANPUR Department of Mechanical Engineering
INDIAN INSTITUTE OF TECHNOLOGY KANPUR Department of Mechanical Engineering Enquiry No: Enq/IITK/ME/JB/02 Enquiry Date: 14/12/15 Last Date of Submission: 21/12/15 Formal quotations are invited for HPC cluster.
StruxureWare for Data Centers
StruxureWare for Data Centers Rafael Alarcon [email protected] All content in this presentation is protected 2008 American Power Conversion Corporation DCIM Definition DCIM Data Center
Guideline for Water and Energy Considerations During Federal Data Center Consolidations
Guideline for Water and Energy Considerations During Federal Data Center Consolidations Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
Accelerate Testing Cycles With Collaborative Performance Testing
Accelerate Testing Cycles With Collaborative Performance Testing Sachin Dhamdhere 2005 Empirix, Inc. Agenda Introduction Tools Don t Collaborate Typical vs. Collaborative Test Execution Some Collaborative
Duke Energy - EPRI DC Powered Data Center Demonstration Executive Summary
Duke Energy - EPRI DC Powered Data Center Demonstration Executive Summary What: Duke Energy and EPRI Sponsored DC Powered Data Center Demonstration Using 380V DC Power When: 2010-2011 Where: Duke Energy
Improving Rack Cooling Performance Using Airflow Management Blanking Panels
Improving Rack Cooling Performance Using Airflow Management Blanking Panels By Neil Rasmussen White Paper #44 Revision 3 Executive Summary Unused vertical space in open frame racks and rack enclosures
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
Dynamic Power Variations in Data Centers and Network Rooms
Dynamic Power Variations in Data Centers and Network Rooms White Paper 43 Revision 3 by James Spitaels > Executive summary The power requirement required by data centers and network rooms varies on a minute
Computational Fluid Dynamics (CFD) Modeling Service
Eaton Data Center Services Computational Fluid Dynamics (CFD) Modeling Service Executive Summary Improve data center energy performance As organizations fill data center enclosures with increasing numbers
Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency. Steve Hammond NREL
Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency NREL 1 National Renewable Energy Laboratory Presentation Road Map A Holistic Approach to Efficiency: Power, Packaging, Cooling, Integration
11 Top Tips for Energy-Efficient Data Center Design and Operation
11 Top Tips for Energy-Efficient Data Center Design and Operation A High-Level How To Guide M e c h a n i c a l a n a l y s i s W h i t e P a p e r w w w. m e n t o r. c o m When is Data Center Thermal
Virtual Platforms Addressing challenges in telecom product development
white paper Virtual Platforms Addressing challenges in telecom product development This page is intentionally left blank. EXECUTIVE SUMMARY Telecom Equipment Manufacturers (TEMs) are currently facing numerous
Energy management White paper. Greening the data center with IBM Tivoli software: an integrated approach to managing energy.
Energy management White paper Greening the data center with IBM Tivoli software: an integrated approach to managing energy. May 2008 2 Contents 3 Key considerations for the green data center 3 Managing
THE WORLD S MOST EFFICIENT DATA CENTER
THE WORLD S MOST EFFICIENT DATA CENTER HP POD 240a Ed Turkel Manager, WW HPC Marketing Hyperscale Business Unit 2011 Hewlett-Packard Development Company, L.P. The information contained herein is subject
Power Consumption and Cooling in the Data Center: A Survey
A M a r k e t A n a l y s i s Power Consumption and Cooling in the Data Center: A Survey 1 Executive Summary Power consumption and cooling issues in the data center are important to companies, as evidenced
Five Essential Components for Highly Reliable Data Centers
GE Intelligent Platforms Five Essential Components for Highly Reliable Data Centers Ensuring continuous operations with an integrated, holistic technology strategy that provides high availability, increased
Dealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe [email protected] AGENDA Business Drivers Challenges
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue
Energy Efficiency and Effective Equipment Cooling In Data Centers. Presentation at ASHRAE Summer Meeting Quebec City, Canada, June 27, 2006
ANCIS TM I N C O R P O R A T E D Energy Efficiency and Effective Equipment Cooling In Data Centers Presentation at ASHRAE Summer Meeting Quebec City, Canada, June 27, 2006 Magnus K. Herrlin, Ph.D., CEM
APC APPLICATION NOTE #92
#92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center
Doc Ref: 2015.06.01.002. 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC
TM 602.783.1112 baselayer.com 2015 BASELAYER TECHNOLOGY, LLC TM D400E Data Module (60Hz) The EDGE D400E is designed to meet high power density requirements for both the HPC and Web Scale environments while
Alternative data center power
Alternative data center power A quantitative TCO comparison of 400V AC and 600V AC power systems Abstract Power efficiency has become a critical focus for IT and facilities managers as they struggle to
Managing Cooling Capacity & Redundancy In Data Centers Today
Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS
Energy Efficient High-tech Buildings
Energy Efficient High-tech Buildings Can anything be done to improve Data Center and Cleanroom energy efficiency? Bill Tschudi Lawrence Berkeley National Laboratory [email protected] Acknowledgements California
Certification: HP ATA Servers & Storage
HP ExpertONE Competency Model Certification: HP ATA Servers & Storage Overview Achieving an HP certification provides relevant skills that can lead to a fulfilling career in Information Technology. HP
HUAWEI Tecal E6000 Blade Server
HUAWEI Tecal E6000 Blade Server Professional Trusted Future-oriented HUAWEI TECHNOLOGIES CO., LTD. The HUAWEI Tecal E6000 is a new-generation server platform that guarantees comprehensive and powerful
Five Nines and Infrared (IR) Testing at Data Centers
Five Nines and Infrared (IR) Testing at Data Centers By Gregory R. Stockton 99.999% uptime five nines. That is what IT (information technology) customers are looking for. Uptime or availability at data
Navigating the Enterprise Database Selection Process: A Comparison of RDMS Acquisition Costs Abstract
Navigating the Enterprise Database Selection Process: A Comparison of RDMS Acquisition Costs Abstract Companies considering a new enterprise-level database system must navigate a number of variables which
Protecting Our Information, Protecting Our Resources
Solutions For Business-Critical Continuity Protecting Our Information, Protecting Our Resources Energy Efficient Power And Cooling For IT And Telecommunications Network Infrastructures The Challenge You
Unified Physical Infrastructure (UPI) Strategies for Thermal Management
Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting