Thermal Management of Datacenter
|
|
|
- Oswin Johnathan Perry
- 9 years ago
- Views:
Transcription
1 Thermal Management of Datacenter Qinghui Tang 1
2 Preliminaries What is data center What is thermal management Why does Intel Care Why Computer Science 2
3 Typical layout of a datacenter Rack outlet temperature T out Rack inlet temperature T in Air conditioner supply temperature T s 3
4 State-of-Art Thermal Management of Data Center Power densities are increasing exponentially along with Moore s Law Current cooling solutions at various levels Chip / component level Server/board level Rack level Data center level S/W based Thermal management solutions HP+Duke 4
5 Thermal Management of Datacenter Motivation and significance Compute Intensive Applications (Online Gaming, Computer Movie Animation, Data Mining) requiring increased utilization of Data Center Maximizing computing capacity is a demanding requirement New blade servers can be packed more densely Energy cost is rising dramatically Goal Improving thermal performance Lowering hardware failure rate Reducing energy cost 5
6 Typical layout of a datacenter System Variables Inlet air temperature of servers Outlet air temperature of serve Power consumption of servers Heat Removal Capacity of HVAC Power consumption of air conditioner Heat dissipation rate Temperature threshold of servers Application Profile on servers Temperature threshold of environment Symbol T i_in T i_out P i H i CP i V i TH i C i TH E 6
7 New Challenges Planning perspective: How to design efficient data center? does upgrading 10% blade servers to smart ones help to reduce cost Operation perspective: How to efficiently operate data center and lower the cost? What s the trade-off between utility cost and hardware failure cost Overcooling: wastes energy and increases utility cost Undercooling: increases frequency of hardware failures 7
8 Research Issues of Thermal Management of Datacenter Scheduler Thermal Performance Evaluation Other Impact Factors Cost Optimization Control Abstract Heat Flow Model Power & Load Characterization Modeling Thermal Performance Multiscale & Multimodal Info Analysis Understanding 8
9 Example of multiple granularity and scale Task Map Power Map Temperature Map
10 Multiscale and multimodal nature of datacenter management Information perspective Multiple system variables Different change pattern Different sampling Rate Control perspective Responsiveness Control granularity (spatial and temporal level) Sensitivity Analysis Spatial Scale Room level Row level Chassis level Row level Room level Row level Room level Seconds Minutes Hours Temporal Scale 10
11 Approaches CFD simulation to characterize thermal performance of data center Online measurement and feedback control system 11
12 CFD Simulation CFD real model based on ASU HPC center 12
13 Thermal-aware task scheduling Incoming task Schematic View of Thermal Management Control Policy Scheduling Policy Other Impact factors 6 Scheduler History Sensor Data Policy Controller 5 Cost Analysis Datacenter Onsite survey 1 CFD simulation software 2 Abstract Heat Model 4 Correlation of load & power Map load to power consumption ` Sensor Data Database Collecting environmental data and load information from sensors Current Sensor Data 3 13
14 Two-Pronged Approach Real-time measurement Online lightweight simulation & prediction CFD simulation of Computer Room Temperature Impact on Temperature Control Algorithms Model of CRAC unit Operation Command Simulation Feedback to tune up simulation parameters Design Guidline to evaluate deployment performance Computer Room w/ sensors Sensor Data Control Decision Operation Command Impact on Temperature CRAC unit Online monitoring & control 14
15 Goal: Datacenter energy cost optimization Throughput or Computation Capacity Total cost Thermal distribution Distributed Server model Cooling system model Computation energy cost Cooling energy cost Hardware cost Operation cost 15
16 Different optimization goals Maximizing computation capacity given energy cost constraint Minimizing individual cost (computing cost/cooling cost) Achieving thermal balancing 16
17 Questions and answers 17
Using CFD for optimal thermal management and cooling design in data centers
www.siemens.com/datacenters Using CFD for optimal thermal management and cooling design in data centers Introduction As the power density of IT equipment within a rack increases and energy costs rise,
Airflow Simulation Solves Data Centre Cooling Problem
Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length
Energy Smart Data Center Phase-III R&D. Andrés Márquez. Pacific Northwest National Laboratory
Energy Smart Data Center Phase-III R&D Andrés Márquez Pacific Northwest National Laboratory Overall Task Division Advance spraycooling technology (ISR) Advance 3D chip scale packing technology (Tessera)
Benefits of Cold Aisle Containment During Cooling Failure
Benefits of Cold Aisle Containment During Cooling Failure Introduction Data centers are mission-critical facilities that require constant operation because they are at the core of the customer-business
Data Center Power Consumption
Data Center Power Consumption A new look at a growing problem Fact - Data center power density up 10x in the last 10 years 2.1 kw/rack (1992); 14 kw/rack (2007) Racks are not fully populated due to power/cooling
Leveraging Thermal Storage to Cut the Electricity Bill for Datacenter Cooling
Leveraging Thermal Storage to Cut the Electricity Bill for Datacenter Cooling Yefu Wang1, Xiaorui Wang1,2, and Yanwei Zhang1 ABSTRACT The Ohio State University 14 1 1 8 6 4 9 8 Time (1 minuts) 7 6 4 3
Computational Fluid Dynamics (CFD) Modeling Service
Eaton Data Center Services Computational Fluid Dynamics (CFD) Modeling Service Executive Summary Improve data center energy performance As organizations fill data center enclosures with increasing numbers
Improving Data Center Energy Efficiency Through Environmental Optimization
Improving Data Center Energy Efficiency Through Environmental Optimization How Fine-Tuning Humidity, Airflows, and Temperature Dramatically Cuts Cooling Costs William Seeber Stephen Seeber Mid Atlantic
Dealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe [email protected] AGENDA Business Drivers Challenges
HPC TCO: Cooling and Computer Room Efficiency
HPC TCO: Cooling and Computer Room Efficiency 1 Route Plan Motivation (Why do we care?) HPC Building Blocks: Compuer Hardware (What s inside my dataroom? What needs to be cooled?) HPC Building Blocks:
Power Distribution Units (PDUs): Power monitoring and environmental monitoring to improve uptime and capacity planning
Power Distribution Units (PDUs): Power monitoring and environmental monitoring to improve uptime and capacity planning 2009, Raritan Inc. Overview Corporate America is more dependent than ever on computing
Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers
Data Centre Best Practises Workshop Using Computational Fluid Dynamics (CFD) for improving cooling system efficiency for Data centers Shishir Gupta 17 th March 2009 You are Here Introduction to CFD Data
Data Center 2020: Delivering high density in the Data Center; efficiently and reliably
Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:
DESIGN YOUR DATA CENTER FOR TODAY & TOMORROW.
DESIGN YOUR DATA CENTER FOR TODAY & TOMORROW. A WORKING DATA CENTER IS A COMPLEX SYSTEM IN WHICH EVERY COMPONENT PLAYS A CRITICAL ROLE. HARDWARE, SOFTWARE, SECURITY, NETWORKING, POWER, COOLING, AND THE
Energy management White paper. Greening the data center with IBM Tivoli software: an integrated approach to managing energy.
Energy management White paper Greening the data center with IBM Tivoli software: an integrated approach to managing energy. May 2008 2 Contents 3 Key considerations for the green data center 3 Managing
How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent
Intel Data Center Manager. Data center IT agility and control
Intel Data Center Manager Data center IT agility and control The Data Center Ecosystem 2 Why do we care about Data Center Management? attributed to devices connected to the Internet of Everything (up from
abstract about the GREEn GRiD
Guidelines for Energy-Efficient Datacenters february 16, 2007 white paper 1 Abstract In this paper, The Green Grid provides a framework for improving the energy efficiency of both new and existing datacenters.
How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel
Modeling Rack and Server Heat Capacity in a Physics Based Dynamic CFD Model of Data Centers. Sami Alkharabsheh, Bahgat Sammakia 10/28/2013
Modeling Rack and Server Heat Capacity in a Physics Based Dynamic CFD Model of Data Centers Sami Alkharabsheh, Bahgat Sammakia 1/28/213 2 ES2 Vision To create electronic systems that are self sensing and
Predictive Data Center Infrastructure Management (DCIM)
Predictive Data Center Infrastructure Management (DCIM) A toolset to maximize the return on capital expenditure in the physical data center Sherman Ikemoto, Matt Warner, Akhil Docca, Hassan Moezzi 11/21/2012
Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009
Optimum Climate Control For Datacenter - Case Study T. Prabu March 17 th 2009 Agenda 2 About EDEC (Emerson) Facility Data Center Details Design Considerations & Challenges Layout Design CFD Analysis Of
Statement Of Work Professional Services
Statement Of Work Professional Services Data Center Cooling Analysis using CFD Data Center Cooling Analysis Using Computational Fluid Dynamics Service 1.0 Executive Summary Table of Contents 1.0 Executive
Data Center Power Distribution and Capacity Planning:
Data Center Power Distribution and Capacity Planning: Understanding what you know and don t know about power usage in your data center 2009, Raritan Inc. About This Series Raritan, a leading provider of
Data center upgrade proposal. (phase one)
Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The
Energy Management Services
February, 2012 Energy Management Services Data centers & IT environments are often critical to today s businesses, directly affecting operations and profitability. General & Mechanical Services has the
5 Reasons. Environment Sensors are used in all Modern Data Centers
5 Reasons Environment Sensors are used in all Modern Data Centers TABLE OF CONTENTS 5 Reasons Environmental Sensors are used in all Modern Data Centers Save on Cooling by Confidently Raising Data Center
Data Center Infrastructure Management. optimize. your data center with our. DCIM weather station. Your business technologists.
Data Center Infrastructure Management optimize your data center with our DCIM weather station Your business technologists. Powering progress Are you feeling the heat of your data center operations? Data
Using Simulation to Improve Data Center Efficiency
A WHITE PAPER FROM FUTURE FACILITIES INCORPORATED Using Simulation to Improve Data Center Efficiency Cooling Path Management for maximizing cooling system efficiency without sacrificing equipment resilience
Improving Data Center Efficiency with Rack or Row Cooling Devices:
Improving Data Center Efficiency with Rack or Row Cooling Devices: Results of Chill-Off 2 Comparative Testing Introduction In new data center designs, capacity provisioning for ever-higher power densities
Measure Server delta- T using AUDIT- BUDDY
Measure Server delta- T using AUDIT- BUDDY The ideal tool to facilitate data driven airflow management Executive Summary : In many of today s data centers, a significant amount of cold air is wasted because
How To Improve Energy Efficiency Through Raising Inlet Temperatures
Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD
Design Best Practices for Data Centers
Tuesday, 22 September 2009 Design Best Practices for Data Centers Written by Mark Welte Tuesday, 22 September 2009 The data center industry is going through revolutionary changes, due to changing market
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment
Green HPC - Dynamic Power Management in HPC
Gr eenhpc Dynami cpower Management i nhpc AT ECHNOL OGYWHI T EP APER Green HPC Dynamic Power Management in HPC 2 Green HPC - Dynamic Power Management in HPC Introduction... 3 Green Strategies... 4 Implementation...
Introducing Computational Fluid Dynamics Virtual Facility 6SigmaDC
IT Infrastructure Services Ltd Holborn Gate, 330 High Holborn, London, WC1V 7QT Telephone: +44 (0)20 7849 6848 Fax: +44 (0)20 7203 6701 Email: [email protected] www.itisltd.com Introducing Computational
How High Temperature Data Centers and Intel Technologies Decrease Operating Costs
Intel Intelligent Management How High Temperature Data Centers and Intel Technologies Decrease Operating Costs and cooling savings through the use of Intel s Platforms and Intelligent Management features
How To Run A Data Center Efficiently
A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly
Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360
Autodesk Revit 2013 Autodesk BIM 360 Air, Fluid Flow, and Thermal Simulation of Data Centers with Autodesk Revit 2013 and Autodesk BIM 360 Data centers consume approximately 200 terawatt hours of energy
Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre
Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre S. Luong 1*, K. Liu 2, James Robey 3 1 Technologies for Sustainable Built Environments, University of Reading,
Strategies for Deploying Blade Servers in Existing Data Centers
Strategies for Deploying Blade Servers in Existing Data Centers By Neil Rasmussen White Paper #125 Revision 1 Executive Summary When blade servers are densely packed, they can exceed the power and cooling
Specialty Environment Design Mission Critical Facilities
Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,
Effect of Rack Server Population on Temperatures in Data Centers
Effect of Rack Server Population on Temperatures in Data Centers Rajat Ghosh, Vikneshan Sundaralingam, Yogendra Joshi G.W. Woodruff School of Mechanical Engineering Georgia Institute of Technology, Atlanta,
Energy Efficient Cloud Computing: Challenges and Solutions
Energy Efficient Cloud Computing: Challenges and Solutions Burak Kantarci and Hussein T. Mouftah School of Electrical Engineering and Computer Science University of Ottawa Ottawa, ON, Canada 08 September
Model Manage Monitor Maximize your Data Center
NetZoomDC is the most feature rich, fully-scalable, enterprise Data Center Infrastructure Management (DCIM) software application. It enables data center professionals to Model, Manage, Monitor and Maximize
Data centers have been cooled for many years by delivering
The Increasing Challenge of Data Center Design and Management: Is CFD a Must? Mark Seymour, Christopher Aldham, Matthew Warner, Hassan Moezzi Future Facilities, San Jose, California, USA Mark Seymour,
Minimization of Costs and Energy Consumption in a Data Center by a Workload-based Capacity Management
Minimization of Costs and Energy Consumption in a Data Center by a Workload-based Capacity Management Georges Da Costa 1, Ariel Oleksiak 2,4, Wojciech Piatek 2, Jaume Salom 3, Laura Siso 3 1 IRIT, University
FAC 2.1: Data Center Cooling Simulation. Jacob Harris, Application Engineer Yue Ma, Senior Product Manager
FAC 2.1: Data Center Cooling Simulation Jacob Harris, Application Engineer Yue Ma, Senior Product Manager FAC 2.1: Data Center Cooling Simulation Computational Fluid Dynamics (CFD) can be used to numerically
APC APPLICATION NOTE #92
#92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center
Choosing Close-Coupled IT Cooling Solutions
W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of
Power efficiency and power management in HP ProLiant servers
Power efficiency and power management in HP ProLiant servers Technology brief Introduction... 2 Built-in power efficiencies in ProLiant servers... 2 Optimizing internal cooling and fan power with Sea of
Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency
A White Paper from the Experts in Business-Critical Continuity TM Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency Executive Summary Energy efficiency
DATA CENTER ASSESSMENT SERVICES
DATA CENTER ASSESSMENT SERVICES ig2 Group Inc. is a Data Center Science Company which provides solutions that can help organizations automatically optimize their Data Center performance, from assets to
IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT
DATA CENTER RESOURCES WHITE PAPER IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT BY: STEVE HAMBRUCH EXECUTIVE SUMMARY Data centers have experienced explosive growth in the last decade.
Oil Submersion Cooling for Todayʼs Data Centers. An analysis of the technology and its business implications
Oil Submersion Cooling for Todayʼs Data Centers An analysis of the technology and its business implications Contents Introduction... 2 Data Center Cooling Technologies... 2 Oil Submersion Cooling... 2
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue
Data Center Technology: Physical Infrastructure
Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling
Thermal Aware Scheduling in Hadoop MapReduce Framework. Sayan Kole
Thermal Aware Scheduling in Hadoop MapReduce Framework by Sayan Kole A Thesis Presented in Partial Fulfillment of the Requirement for the Degree Master of Science Approved November 2013 by the Graduate
Alan Matzka, P.E., Senior Mechanical Engineer Bradford Consulting Engineers
Information Technology and Data Centers HVAC Showcase November 26, 2013 Alan Matzka, P.E., Senior Mechanical Engineer Bradford Consulting Engineers Welcome. Today s webinar is being recorded and will be
Application of CFD modelling to the Design of Modern Data Centres
Application of CFD modelling to the Design of Modern Data Centres White Paper March 2012 By Sam Wicks BEng CFD Applications Engineer Sudlows March 14, 2012 Application of CFD modelling to the Design of
I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015
I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 8, Loughborough University, 29 th June 2015 Topics to be considered 1. Progress on project tasks 2. Development of data centre test facility
How To Manage Energy At An Energy Efficient Cost
Hans-Dieter Wehle, IBM Distinguished IT Specialist Virtualization and Green IT Energy Management in a Cloud Computing Environment Smarter Data Center Agenda Green IT Overview Energy Management Solutions
Energy Management in a Cloud Computing Environment
Hans-Dieter Wehle, IBM Distinguished IT Specialist Virtualization and Green IT Energy Management in a Cloud Computing Environment Smarter Data Center Agenda Green IT Overview Energy Management Solutions
Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres
School of something School of Mechanical Engineering FACULTY OF OTHER ENGINEERING Computational Fluid Dynamic Investigation of Liquid Rack Cooling in Data Centres A. Almoli 1, A. Thompson 1, N. Kapur 1,
The CEETHERM Data Center Laboratory
The CEETHERM Data Center Laboratory A Platform for Transformative Research on Green Data Centers Yogendra Joshi and Pramod Kumar G.W. Woodruff School of Mechanical Engineering Georgia Institute of Technology
Data Sheet FUJITSU Server PRIMERGY CX400 S2 Multi-Node Server Enclosure
Data Sheet FUJITSU Server PRIMERGY CX400 S2 Multi-Node Server Enclosure Scale-Out Smart for HPC and Cloud Computing with enhanced energy efficiency The PRIMERGY CX400 Cloud extension servers are Fujitsu
AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY
AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY The Aegis Services Power and Assessment Service provides an assessment and analysis of your data center facility and critical physical
Power and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw
Data center lifecycle and energy efficiency
Data center lifecycle and energy efficiency White Paper Lifecycle management, thermal management, and simulation solutions enable data center energy modernization Introduction Data centers are coming under
Green Wireless Technology Panel Presentation
Green Wireless Technology Panel Presentation Professor Sandeep K. S. Gupta IMPACT (Intelligent Mobile Pervasive Autonomic Computing & Technologies) LAB (http://impact.asu.edu) School of Computing, Informatics,
11 Top Tips for Energy-Efficient Data Center Design and Operation
11 Top Tips for Energy-Efficient Data Center Design and Operation A High-Level How To Guide M e c h a n i c a l a n a l y s i s W h i t e P a p e r w w w. m e n t o r. c o m When is Data Center Thermal
CUSTOMER EXPERIENCE CENTER
v CUSTOMER EXPERIENCE CENTER ABOUT THE CUSTOMER EXPERIENCE CENTER MAKE YOUR DATA CENTER AS DYNAMIC AS YOUR BUSINESS Emerson Network Power continuously strives to provide the best solutions by working collaboratively
Statement Of Work. Data Center Power and Cooling Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary
Statement Of Work Professional Services Data Center Power and Cooling Assessment Data Center Power and Cooling Assessment Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features
Creating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant
RESEARCH UNDERWRITER WHITE PAPER LEAN, CLEAN & GREEN Wright Line Creating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant Currently 60 percent of the cool air that
Data Center Lifecycle and Energy Efficiency
Data Center Lifecycle and Energy Efficiency Lifecycle infrastructure management, power management, thermal management, and simulation solutions enable data center modernization. White Paper October 2014
The Benefits of Supply Air Temperature Control in the Data Centre
Executive Summary: Controlling the temperature in a data centre is critical to achieving maximum uptime and efficiency, but is it being controlled in the correct place? Whilst data centre layouts have
High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.
High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white
The Advantages of Row and Rack- Oriented Cooling Architectures for Data Centers
The Advantages of Row and Rack- Oriented Cooling Architectures for Data Centers By Kevin Dunlap Neil Rasmussen White Paper #130 Executive Summary Room cooling is an ineffective approach for next-generation
Server Technology, Inc.
Server Technology, Inc. Cabinet Power Monitoring, Management & Control Within the Data Center White Paper STI-100-011 2010-Sept-27 by Calvin Nicholson, Senior Director Software and Strategic Alliances,