E Analog Input Termination Module (NIAI02)
|
|
|
- Alfred Blair
- 10 years ago
- Views:
Transcription
1 E Analog Input Termination Module (NIAI02) Process Control and Automation Solutions from Elsag Bailey Group
2 WARNING notices as used in this instruction apply to hazards or unsafe practices that could result in personal injury or death. CAUTION notices apply to hazards or unsafe practices that could result in property damage. NOTES highlight procedures and contain information that assists the operator in understanding the information contained in this instruction. WARNING INSTRUCTION MANUALS DO NOT INSTALL, MAINTAIN, OR OPERATE THIS EQUIPMENT WITHOUT READING, UNDERSTANDING, AND FOLLOWING THE PROPER Elsag Bailey INSTRUCTIONS AND MANUALS; OTHERWISE, INJURY OR DAMAGE MAY RESULT. RADIO FREQUENCY INTERFERENCE MOST ELECTRONIC EQUIPMENT IS INFLUENCED BY RADIO FREQUENCY INTERFERENCE (RFI). CAU- TION SHOULD BE EXERCISED WITH REGARD TO THE USE OF PORTABLE COMMUNICATIONS EQUIP- MENT IN THE AREA AROUND SUCH EQUIPMENT. PRUDENT PRACTICE DICTATES THAT SIGNS SHOULD BE POSTED IN THE VICINITY OF THE EQUIPMENT CAUTIONING AGAINST THE USE OF POR- TABLE COMMUNICATIONS EQUIPMENT. POSSIBLE PROCESS UPSETS MAINTENANCE MUST BE PERFORMED ONLY BY QUALIFIED PERSONNEL AND ONLY AFTER SECURING EQUIPMENT CONTROLLED BY THIS PRODUCT. ADJUSTING OR REMOVING THIS PRODUCT WHILE IT IS IN THE SYSTEM MAY UPSET THE PROCESS BEING CONTROLLED. SOME PROCESS UPSETS MAY CAUSE INJURY OR DAMAGE. AVERTISSEMENT MANUELS D OPÉRATION NE PAS METTRE EN PLACE, RÉPARER OU FAIRE FONCTIONNER L ÉQUIPEMENT SANS AVOIR LU, COMPRIS ET SUIVI LES INSTRUCTIONS RÉGLEMENTAIRES DE Elsag Bailey. TOUTE NÉGLIGENCE À CET ÉGARD POURRAIT ÊTRE UNE CAUSE D ACCIDENT OU DE DÉFAILLANCE DU MATÉRIEL. PERTURBATIONS PAR FRÉQUENCE RADIO LA PLUPART DES ÉQUIPEMENTS ÉLECTRONIQUES SONT SENSIBLES AUX PERTURBATIONS PAR FRÉQUENCE RADIO. DES PRÉCAUTIONS DEVRONT ÊTRE PRISES LORS DE L UTILISATION DU MATÉ- RIEL DE COMMUNICATION PORTATIF. LA PRUDENCE EXIGE QUE LES PRÉCAUTIONS À PRENDRE DANS CE CAS SOIENT SIGNALÉES AUX ENDROITS VOULUS DANS VOTRE USINE. PERTURBATIONS DU PROCÉDÉ L ENTRETIEN DOIT ÊTRE ASSURÉ PAR UNE PERSONNE QUALIFIÉE EN CONSIDÉRANT L ASPECT SÉCURITAIRE DES ÉQUIPEMENTS CONTRÔLÉS PAR CE PRODUIT. L AJUSTEMENT ET/OU L EXTRAC- TION DE CE PRODUIT PEUT OCCASIONNER DES À-COUPS AU PROCÉDÉ CONTRÔLE LORSQU IL EST INSÉRÉ DANS UNE SYSTÈME ACTIF. CES À-COUPS PEUVENT ÉGALEMENT OCCASIONNER DES BLESSURES OU DES DOMMAGES MATÉREILS. NOTICE The information contained in this document is subject to change without notice. Elsag Bailey, its affiliates, employees, and agents, and the authors and contributors to this publication specifically disclaim all liabilities and warranties, express and implied (including warranties of merchantability and fitness for a particular purpose), for the accuracy, currency, completeness, and/or reliability of the information contained herein and/or for the fitness for any particular use and/or for the performance of any material and/ or equipment selected in whole or part with the user of/or in reliance upon information contained herein. Selection of materials and/or equipment is at the sole risk of the user of this publication. This document contains proprietary information of Elsag Bailey, Elsag Bailey Process Automation, and is issued in strict confidence. Its use, or reproduction for use, for the reverse engineering, development or manufacture of hardware or software described herein is prohibited. No part of this document may be photocopied or reproduced without the prior written consent of Elsag Bailey.
3 Preface Termination modules provide an input connection from the plant equipment to the INFI 90 process modules. The Analog Input Termination Module (NIAI02) interfaces thermocouple or millivolt inputs to the Analog Input Slave Module (IMASM02). This manual explains how to install and use the NIAI02 on the INFI 90 system. It has sections that describe the setup and cabling. The appendix contains information about the IMASM02 module that uses the NIAI02. Registered trademark of Elsag Bailey Process Automation. I-E96-434A
4 List of Effective Pages Total number of pages in this manual is 22, consisting of the following: Page No. Change Date Preface Original List of Effective Pages Original iii through vi Original 1-1 through 1-4 Original 2-1 through 2-6 Original 3-1 Original 4-1 through 4-2 Original 5-1 Original A-1 Original Index-1 Original When an update is received, insert the latest changed pages and dispose of the superseded pages. NOTE: On an update page, the changed text or table is indicated by a vertical bar in the outer margin of the page adjacent to the changed area. A changed figure is indicated by a vertical bar in the outer margin next to the figure caption. The date the update was prepared will appear beside the page number. I-E96-434A
5 Safety Summary GENERAL WARNINGS Equipment Environment All components, whether in transportation, operation, or storage must be in a noncorrosive environment. Electrical Shock Hazard During Maintenance Disconnect power or take precautions to ensure that contact with energized parts is avoided when servicing. SPECIFIC CAUTIONS Remove modules from their assigned slots before installing a cable to that slot. Failure to do so could result in damage to the module or station. (p. 2-4, 4-1) It is strongly recommended that all power (cabinet, I/O, etc.) be turned off before doing any termination module wiring. Failure to do so could result in equipment damage. Do not apply power until all connections are verified. (p. 2-5, 4-1) If input or output circuits are a shock hazard after disconnecting system power at the power entry panel, then the door of the cabinet containing these externally powered circuits must be marked with a warning stating that multiple power sources exist. (p. 2-6) I-E96-434A v
6 Sommaire de Sécurité AVERTISSEMENTS D ORDRE GÉNÉRAL Environment de l'equipement Ne pas soumettre les composants a une atmosphere corrosive lors du transport, de l'entreposage ou de l'utilisation. Risques de chocs electriques lor de l'entretien S'assurer de debrancher l'alimentation ou de prendre les precautions necessaires a eviter tout conatact avec des composants sours tension lors de l'entretien. ATTENTIONS D ORDRE SPÉCIFIQUE Retirer les modules de leur position assignée avant d'installer un câble à cette position. Des dommages au module ou au poste pourraient résulter d'un manquement à cette procédure. (p. 2-4, 4-1) Ll est fortement recommande que toutes les alimentations (armoire, E/S, etc.) soient coupees avant d'effectuer quelque raccord que ce soit sur une carte de raccordement. Un manquement a ces instructions pourrait causer des dommages a l'equipment. Ne pas rebrancher les alimentations avant d'avoir verifie tous les raccordements. (p. 2-5, 4-1) Si des circuits d'entree ou de sortie sont alimentes a partir de sources externes, ils presentent un risque de choc electrique meme lorsque l'alimentation du systeme est debranchee du panneau d'entree l'alimentation. Le cas echeant, un avertissement signalant la presence de sources d'alimentation multiples doit etre appose sur la porte de l'armoire. (p. 2-6) vi I-E96-434A
7 Table of Contents SECTION 1 - INTRODUCTION OVERVIEW INTENDED USER MODULE DESCRIPTION FEATURES INSTRUCTION CONTENT HOW TO USE THIS MANUAL GLOSSARY OF TERMS AND ABBREVIATIONS REFERENCE DOCUMENTS NOMENCLATURE SPECIFICATIONS Page SECTION 2 - INSTALLATION INTRODUCTION SPECIAL HANDLING UNPACKING AND INSPECTION SETUP/PHYSICAL INSTALLATION Cable Connections Cable Installation Termination Module Installation Terminal Wiring Power Wiring SECTION 3 - MAINTENANCE INTRODUCTION MAINTENANCE SCHEDULE SECTION 4 - REPAIR/REPLACEMENT PROCEDURES INTRODUCTION REPLACEMENT PROCEDURES SECTION 5 - SUPPORT SERVICES INTRODUCTION REPLACEMENT PARTS AND ORDERING INFORMATION TRAINING TECHNICAL DOCUMENTATION APPENDIX A - THERMOCOUPLE SLAVE INPUT MODULE (IMASM02)... A-1 INTRODUCTION... A-1 I-E96-434A iii
8 List of Tables No. Title Page 1-1. Glossary of Terms and Abbreviations Reference Documents Nomenclature Specifications NIAI02 Cable Applications Maintenance Schedule A-1. Address Switch Settings (SW1)...A-1 List of Figures No. Title Page 1-1. Application Example for NIAI Cable Connections for NIAI Terminal Assignments for NIAI A-1. Address Select Switch (SW1)...A-1 iv I-E96-434A
9 SECTION 1 - INTRODUCTION OVERVIEW One Thermocouple Input Termination Module (NIAI02) is required for each Thermocouple Slave Module (IMASM02). Each NIAI02 can input eight thermocouple or millivolt signals from field equipment to the thermocouple input slave module. The signals pass through the slave module to the Analog Master Module (IMAMM03). This manual explains the purpose, setup, handling precautions and steps to install the NIAI02 module. INTENDED USER System engineers and technicians should read this manual before installing and using the termination module (TM). Put the module into operation only after reading and understanding this instruction. Refer to the Table of Contents to find the information. Refer to the HOW TO USE THIS MANUAL entry in this section to get started. MODULE DESCRIPTION The NIAI02 is a single printed circuit board that uses one slot in a Termination Mounting Unit (NTMU01/02). The termination module (TM) has one card edge connector, P1. It connects to the slave module through a cable. The terminal blocks for field wiring are on the TM. The NIAI02 handles up to 8 thermocouple inputs for the IMASM02. Each input may be thermocouple or millivolt from -100 to +100 millivolts or 0 to 100 millivolts. Figure 1-1 shows an application example for the NIAI02. FEATURES The design of the NIAI02, as with all INFI 90 devices, allows for flexibility in creating a process management system. Refer to the NOMENCLATURE entry of this section for the list of devices that can be used with the TM in an INFI 90 system. A standard factory-wired cable connects the TM to the slave module. Connect I/O wires on terminals at the front edge of the TM. Each TM fits in a standard termination mounting unit. Field wire termination for eight thermocouple or millivolt inputs. Input signal routing to the IMASM02. Source of the local cold junction reference. OVERVIEW I-E96-434A 1-1
10 INTRODUCTION COMMUNICATION HIGHWAY (INFI-NET OR PLANT LOOP) COMMUNICATION MODULES MODULE BUS IMAMM03 OTHER MODULES SLAVE EXPANDER BUS IMASM02 OTHER ANALOG SLAVE MODULES NIAI02 FIELD INPUTS T00680A Figure 1-1. Application Example for NIAI02 INSTRUCTION CONTENT This manual has five sections and an appendix. Introduction Installation Maintenance Repair/Replacement Procedures Support Services Appendix A Contains an overview of the features, description and specifications and a description of the NIAI02. Describes cautions to observe when handling the TM. It shows the steps to install and connect the terminal wiring before applying power. Provides a maintenance schedule. Details how to replace a TM. Describes the support services (repair parts, training, documentation, etc.) available from Bailey Controls Company. Shows the cabling needed for the Thermocouple Slave Input Module (IMASM02). INSTRUCTION CONTENT 1-2 I-E96-434A
11 INTRODUCTION HOW TO USE THIS MANUAL Read this manual before handling the TM. Refer to the sections in this list as needed for more information. 1. Read Section 2 before connecting the NIAI Refer to Appendix A for the IMASM02 slave module. 3. Refer to Section 3 for the maintenance schedule. 4. Refer to Section 4 and Section 5 when needed. GLOSSARY OF TERMS AND ABBREVIATIONS Table 1-1 contains the glossary of terms for this manual. Table 1-1. Glossary of Terms and Abbreviations Term Analog Cold Junction Reference Slave Module Thermocouple TM TMU Definition Continuously variable as opposed to discretely variable. The ambient temperature at the bimetallic junction at the termination point of thermocouple wires. One of a series of modules designed to perform high or low level operations as directed by a master module. A bimetallic sensor used for temperature measurements. Termination Module. Provides input/output connection between plant equipment and the INFI 90/Network 90 modules. Termination Mounting Unit. A card cage that provides housing for INFI 90/Network 90 termination modules. REFERENCE DOCUMENTS Table 1-2 contains the reference documents for the NIAI02. Table 1-2. Reference Documents Document Number I-E I-E I-E I-E Description Analog Master Module and Analog Slave Modules (IMAMM03 and IMASM01/02/03/04) Thermocouple Calibration Module (NIAC02) Analog Master Termination Module (NIAM02) Site Planning and Preparation Registered trademark of Elsag Bailey Process Automation. HOW TO USE THIS MANUAL I-E96-434A 1-3
12 INTRODUCTION NOMENCLATURE Table 1-3 contains the modules and equipment that can be used with the NIAI02 module: Table 1-3. Nomenclature Nomenclature IMASM02 NIAC02 NIAM02 NKTM01 NKTU02 NKTU A1 NTMU01 NTMU02 Description Thermocouple and Millivolt Input Slave Module Thermocouple Calibration Module Analog Master Termination Module Cable, Termination Module (Ribbon) Cable, Termination Module (PVC) Cable, Termination Module (non-pvc) Cable retaining kit used when a round cable connects to the TMU Termination Mounting Unit (Rear Mount) Termination Mounting Unit (Front Mount) SPECIFICATIONS Refer to Table 1-4 for the specifications of the NIAI02 Termination Unit. Table 1-4. Specifications Property Characteristic/Value Power Requirements 24 VDC at 10 ma. Mounting Slides into a single slot in the termination mounting unit NTMU01/02. Environmental Electromagnetic/ Radio Frequency Interference No values available at this time. Keep cabinet doors closed. Do not use communication equipment closer than 2 meters from the cabinet. Ambient Temperature 0 to 70 o C (32 to 158 o F) Relative Humidity 5% to 90% ± 5% up to 55 o C (131 o F) (noncondensing). 5% to 40% ± 5% up to 70 o C (158 o F) (noncondensing). Atmospheric Pressure Sea level to 3 km (1.86 miles). Air Quality Noncorrosive. Cooling Requirements No cooling is necessary when used in Bailey Controls cabinets and operated within stated limits. Surge Protection Meets IEEE Surge Withstand Capability Test 1. Certification CSA certified for use as process control equipment in an ordinary (nonhazardous) location. NOTE: 1. Do not use the NKTM01 cable when compliance with IEEE is necessary. Specifications are subject to change without notice. NOMENCLATURE 1-4 I-E96-434A
13 SECTION 2 - INSTALLATION INTRODUCTION This section explains how to install the Thermocouple Analog Input Termination Module (NIAI02). Read, understand, and complete the steps in the order they appear before using the NIAI02 module. SPECIAL HANDLING Observe these steps when handling electronic circuitry: NOTE: Always use the Bailey Controls Field Static Kit (part number A1 - consisting of two wrist straps, ground cord assembly, alligator clip, and static dissipating work surface) when working with modules. The kit is designed to connect the technician and the static dissipating work surface to the same ground point to prevent damage to the modules by electrostatic discharge. Use the static grounding wrist strap when installing and removing modules. Static discharge may damage MOS devices on modules in the cabinet. Use grounded equipment and static safe practices when working with modules. 1. Use Static Shielding Bag. Keep the modules in the static shielding bag until you are ready to install them in the system. Save the bag for future use. 2. Ground Bags Before Opening. Before opening a bag containing an assembly with CMOS devices, touch it to the equipment housing or ground to equalize charges. 3. Avoid Touching Circuitry. Handle assemblies by the edges; avoid touching the circuitry. 4. Avoid Partial Connection of CMOS Device. Verify that all devices connected to the modules are properly grounded before using them. 5. Ground Test Equipment. 6. Use Antistatic Field Service Vacuum. Remove dust from the module if necessary. 7. Use Grounded Wrist Strap. Connect the wrist strap to the appropriate grounding plug on the power entry panel. The grounding plug on the power entry panel is connected to the cabinet chassis ground. INTRODUCTION I-E96-434A 2-1
14 INSTALLATION UNPACKING AND INSPECTION These are steps to follow for general handling: 1. Examine the module to make sure that no damage has occurred in transit. 2. Notify the nearest Bailey Controls sales office of any damage. 3. File a claim for any damage with the shipping company that handled the shipment. 4. Use the original packing material or container to store the module. 5. Store the module in a place with clean air; free of extremes of temperature and humidity. SETUP/PHYSICAL INSTALLATION This section explains how to configure and install the NIAI02. The required procedures are installing the termination module into the TMU, and connecting the field wiring and communication cables. Cable Connections Before installing the IMASM02, connect either the NKTM01 or NKTU02/12 termination cable. Figure 2-1 shows the cabling for the NIAI02 to the IMASM02 and NIAM02. Install the termination module cable (NKTM01 or NKTU02/ NKTU12) to connect the TM to the slave. The NKTM01 is a flat ribbon cable. The NKTU02 is a round, shielded cable with PVC jacket. The NKTU12 is a round, shielded cable with non-pvc jacket. NIAI02 modules can be interconnected through ribbon cable part number A2 supplied with the NIAI02. Up to eight NIAI02 TMs can connect to a single master module through a NIAM02 master termination module. NOTE: The NIAM02 is used to connect NIAI02 TMs to the IMAMM03 master for local cold junction compensation. The NIAI02 TMs for slaves 1 to 4 connect to J1 of NIAM02, and NIAI02 TMs for slaves 5 to 8 connect to J2 of the NIAM02. Cable Installation The NKTU02/12 and NKTM01 cable connects the NIAI02 to the IMASM02 slave module. The NIAM02 master termination module connects to the NIAI02 through the A2 ribbon cable. Table 2-1 lists the NIAI02 cable applications. UNPACKING AND INSPECTION 2-2 I-E96-434A
15 INSTALLATION TO ADDITIONAL NDIS01 TO REDUNDANT NIAM02 P1 NDIS IMAMM03 P1 P3 P2 NKTM01 NKTU02/12 J3 NIAM02 J2 J1 P1 J NKTD02/12 TO MMU CALIBRATION SLOT NKTM01 NKTU02/12 P1 NIAC IMASM02 P1 P3 P2 NKTM01 NKTU02/12 P1 J2 NIAI02 (½ RTD A) J1 P1 J2 NIAI02 (½ RTD C) J1 IMASM02 P1 P3 NKTM01 NKTU02/12 P1 J2 NIAI02 (½ RTD A) P1 J2 NIAI02 (½ RTD C) P2 J1 J1 TO RTD B ON ADDITIONAL NIAI02s (4 TOTAL) TORTDDONADDITIONAL NIAI02s (4 TOTAL) T00681A Figure 2-1. Cable Connections for NIAI02 Nomenclature/ Description NKTU02 (PVC Jacket) NKTU12 (non-pvc Jacket) Table 2-1. NIAI02 Cable Applications Application Connects NIAI02 to IMASM02. Connector P1 on TM to MMU backplane. Maximum Length 61 m (200 ft) NKTM01 (ribbon) Connects NIAI02 to IMASM02. P1 on TM to MMU backplane. 30 m (100 ft) A2 (one ribbon cable is shipped with each NIAI02) Connects NIAI02 to NIAI02. Connects NIAM02 to NIAM02. Connects NIAM02 to NIAI02 1 thru 4. Connects NIAM02 to NIAI02 5 thru 8. J2 on TM1 to J1 on TM2. J3 on TM1 to J3 on TM2. J1 on NIAM02 to J1 on NIAI02. J2 on NIAM02 to J1 on NIAI m (2 ft) SETUP/PHYSICAL INSTALLATION I-E96-434A 2-3
16 INSTALLATION CAUTION ATTENTION Remove modules from their assigned slots before installing a cable to that slot. Failure to do so could result in damage to the module or station. Retirer les modules de leur position assignée avant d'installer un câble à cette position. Des dommages au module ou au poste pourraient résulter d'un manquement à cette procédure. To install the cable follow these steps: 1. Pull the termination module several inches from the TMU backplane. 2. If round type cables are already installed in the TMU, remove the cable retaining bracket (Bailey part number A1). Use NKTU02/12 or NKTMU01 cables. Round cables and ribbon cables can be mixed when installing multiple TMs. 3. Insert the J2 end of the termination module cable into the MMU backplane slot assigned to the slave module. The cable should latch securely in place. Card edge connector P3 of the slave module connects to this end of the cable. 4. If NKTU02 or NKTU12 cables are used, connect the shield wire extending from the J2 end of the cable to the shield bar. 5. Insert the J1 end of the cable into the TMU backplane slot assigned to the NIAI02 module. The cable should latch securely in place. Card edge connector P1 of the NIAI02 module connects to this end of the cable. 6. Up to four NIAI02 TMs (1-4) can be interconnected by connecting J2 on the first TM to J1 on the second TM with ribbon cable part number A2. Install the A2 cable for each NIAI Connect J1 of the first NIAI02 in the interconnection with TM-1 through TM-4 to J1 on the NIAM Up to four additional NIAI02 TMs (5-8) can be interconnected by connecting J2 on the first TM to J1 on the second TM with ribbon cable part number A2. Install the A2 cable for each NIAI Connect J1 of the first NIAI02 in the interconnection with TM-5 through TM-8 to J2 on the NIAM Replace or add the cable retaining bracket if round type cables are installed in the TMU. SETUP/PHYSICAL INSTALLATION 2-4 I-E96-434A
17 INSTALLATION Termination Module Installation The NIAI02 inserts into a standard INFI 90 termination mounting unit (TMU) and occupies one slot. To install: 1. Verify slot assignment of the NIAI02 module. 2. Align the NIAI02 module with the guide rails in the TMU and partially insert the module. Leave enough room to connect terminal wiring and cables. Completely seat the module after cabling and termination wiring is attached. Terminal Wiring CAUTION ATTENTION It is strongly recommended that all power (cabinet, I/O, etc.) be turned off before doing any termination module wiring. Failure to do so could result in equipment damage. Do not apply power until all connections are verified. Ll est fortement recommande que toutes les alimentations (armoire, E/S, etc.) soient coupees avant d'effectuer quelque raccord que ce soit sur une carte de raccordement. Un manquement a ces instructions pourrait causer des dommages a l'equipment. Ne pas rebrancher les alimentations avant d'avoir verifie tous les raccordements. Connect the wiring from the thermocouple or millivolt signal sensing the process to the termination module terminals. For new installations, refer to the Site Planning and Preparation manual for information on I/O wiring. Figure 2-2 shows the terminal assignments for each input and a field input termination example. COLD JUNCTION REFERENCE RTD J2 SOCKET (OUT) NIAI TERMINAL NUMBERS CARD EDGE CONNECTOR P1 J1 SOCKET (IN) CHANNEL NUMBERS TYPICAL CONNECTION FOR ATHERMOCOUPLE TO AN NIAI02 + TYPICAL CONNECTION FOR A DIFFERENTIAL MILLIVOLT INPUT TO AN NIAI02 T00682A Figure 2-2. Terminal Assignments for NIAI02 SETUP/PHYSICAL INSTALLATION I-E96-434A 2-5
18 INSTALLATION Power Wiring CAUTION ATTENTION If input or output circuits are a shock hazard after disconnecting system power at the power entry panel, then the door of the cabinet containing these externally powered circuits must be marked with a warning stating that multiple power sources exist. Si des circuits d'entree ou de sortie sont alimentes a partir de sources externes, ils presentent un risque de choc electrique meme lorsque l'alimentation du systeme est debranchee du panneau d'entree l'alimentation. Le cas echeant, un avertissement signalant la presence de sources d'alimentation multiples doit etre appose sur la porte de l'armoire. Connect field inputs with 14 to 22 gauge wire. To connect field wiring follow these steps: 1. Remove the front cover. 2. Ensure the NIAI02 module is pulled out far enough to gain access to the terminal strip. 3. Feed the field wiring into the terminal strip area and connect them to the appropriate terminals. 4. Insert the module until it locks securely into place. 5. Replace the front cover to maintain thermal stability for the local cold junction reference RTD. The NIAI02 is ready for operation if: 1. The circuit board is mounted in the termination mounting unit. 2. All required cables are connected to the termination module. 3. All required field wires are connected to the termination module. SETUP/PHYSICAL INSTALLATION 2-6 I-E96-434A
19 SECTION 3 - MAINTENANCE INTRODUCTION The Analog Input Termination Module (NIAI02) requires limited maintenance. This section contains a maintenance schedule. MAINTENANCE SCHEDULE Execute the tasks in Table 3-1 at the specified intervals. Table 3-1. Maintenance Schedule Task Clean and tighten all power and grounding connections. Interval Every 6 months or during plant shutdown, whichever occurs first. Use a static safe vacuum cleaner to remove dust from: Termination Mounting Unit Termination Modules INTRODUCTION I-E96-434A 3-1
20 SECTION 4 - REPAIR/REPLACEMENT PROCEDURES INTRODUCTION This section explains the replacement procedures for the Analog Input Termination Module (NIAI02). No special tools are required to replace the module. REPLACEMENT PROCEDURES If a NIAI02 is faulty, replace it with a new one. Do not try to repair the module. Replacing components may affect performance and certification. CAUTION ATTENTION It is strongly recommended that all power (cabinet, I/O, etc.) be turned off before doing any termination module wiring. Failure to do so could result in equipment damage. Do not apply power until all connections are verified. Ll est fortement recommande que toutes les alimentations (armoire, E/S, etc.) soient coupees avant d'effectuer quelque raccord que ce soit sur une carte de raccordement. Un manquement a ces instructions pourrait causer des dommages a l'equipment. Ne pas rebrancher les alimentations avant d'avoir verifie tous les raccordements. CAUTION ATTENTION Remove modules from their assigned slots before installing a cable to that slot. Failure to do so could result in damage to the module or station. Retirer les modules de leur position assignée avant d'installer un câble à cette position. Des dommages au module ou au poste pourraient résulter d'un manquement à cette procédure. To replace a NIAI02 termination module: 1. Remove the termination module front cover. 2. Pull the termination module several inches from the TMU backplane. 3. Label and remove all power and field wiring from the terminal blocks. 4. Slide the TM out of the TMU. 5. Slide the new TM into the same slot as the module that was removed. INTRODUCTION I-E96-434A 4-1
21 REPAIR/REPLACEMENT PROCEDURES 6. Connect all power and field wiring removed in Step Verify that wiring and cabling to the TM is correct. 8. Fully insert the termination module into the TMU. 9. Replace the termination module front cover. 10. Turn on the cabinet power supply that provides power to the TM. 11. Turn on any external power supplies providing I/O power. REPLACEMENT PROCEDURES 4-2 I-E96-434A
22 SECTION 5 - SUPPORT SERVICES INTRODUCTION Bailey Controls Company is ready to help in the use, application and repair of its products. Contact the nearest sales office to make requests for sales, applications, installation, repair, overhaul and maintenance contract services. REPLACEMENT PARTS AND ORDERING INFORMATION When making repairs, order replacement parts from a Bailey Controls sales office. Provide this information: 1. Part description, part number and quantity. 2. Model and serial numbers (if applicable). 3. Bailey instruction manual number, page number and reference figure that identifies the part. Order parts without commercial descriptions from the nearest Bailey Controls Company sales office. TRAINING Bailey Controls Company has modern training facilities that provide service and repair instruction. On-site training is also available. Contact a Bailey Controls Company sales office for specific information and scheduling. TECHNICAL DOCUMENTATION Additional copies of this manual, or other Bailey Controls Company manuals, can be obtained from the nearest Bailey Controls Company sales office at a reasonable charge. INTRODUCTION I-E96-434A 5-1
23 APPENDIX A - THERMOCOUPLE SLAVE INPUT MODULE (IMASM02) INTRODUCTION The Thermocouple Analog Slave Input Module (IMASM02) uses an NIAI02 for termination of field wiring. Each NIAI02 accepts up to eight thermocouple or millivolt inputs. This appendix contains figures and tables that show the dipswitch location on the IMASM02 and its settings. This information is provided as a quick reference guide for personnel installing the NIAI02. Figure A-1 shows the address select switch (SW1). Table A-1 lists the binary addresses for setting SW1. Refer to the IMAMM03 instruction for more detailed information to install and configure the slave. MODULE STATUS LED P1 P3 S OPEN P2 SLAVE/GROUP ADDRESS SWITCH T00468A Figure A-1. Address Select Switch (SW1) Table A-1. Address Switch Settings (SW1) Addr MSB LSB MSB LSB Addr OPEN = OFF = 1 CLOSED = ON = 0 INTRODUCTION I-E96-434A A - 1
24 Index A Address select switch (SW1)... A-1 Address switch settings (SW1)... A-1 Application example for NIAI C Cable connections for NIAI G Glossary of terms and abbreviations I Input circuit for NIAI M Maintenance schedule N NIAI02 cable applications Nomenclature R Reference documents Replacement parts Replacement procedures S Setup/physical installation Cable connections Cable installation Power wiring Terminal wiring Termination module installation Special handling Specifications T Technical documentation Terminal assignments for NIAI Training U Unpacking and inspecting I-E96-434A Index - 1
25 Visit Elsag Bailey on the World Wide Web at Our worldwide staff of professionals is ready to meet your needs for process automation. For the location nearest you, please contact the appropriate regional office. AMERICAS Euclid Avenue Wickliffe, Ohio USA Telephone Telefax ASIA/PACIFIC 152 Beach Road Gateway East #20-04 Singapore Telephone Telefax EUROPE, AFRICA, MIDDLE EAST Via Puccini Genoa, Italy Telephone Telefax GERMANY Graefstrasse 97 D Frankfurt Main Germany Telephone Telefax Form I-E96-434A Litho in U.S.A. 592 Copyright 1992 by Elsag Bailey Process Automation, As An Unpublished Work Registered Trademark of Elsag Bailey Process Automation Trademark of Elsag Bailey Process Automation
SECTION 7 - REPAIR/REPLACEMENT PROCEDURES
SECTION 7 - REPAIR/REPLACEMENT PROCEDURES INTRODUCTION Although the modular power system is designed to give long, troublefree service, some components may need to be replaced periodically. This section
Express5800/120Ed. Rack Mount Kit Installation Procedures PN: 455-01607-001
Express5800/120Ed Rack Mount Kit Installation Procedures PN: 455-01607-001 Proprietary Notice and Liability Disclaimer The information disclosed in this document, including all designs and related materials,
Backup Scanner Module
Backup Scanner Module Catalog Number 1747-BSN Installation Instructions 2 Backup Scanner Module Important User Information Because of the variety of uses for the products described in this publication,
READ AND FOLLOW ALL SAFETY INSTRUCTIONS 1. DANGER RISK OF SHOCK DISCONNECT POWER BEFORE INSTALLATION
UR Series LED Upgrade Kit Includes: 48" Linear Option IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed including the following: READ AND FOLLOW ALL
Read this document before using this product.
VistaMAX Series Safety Precautions Read this document before using this product. Download and read the full user manual for complete information (see the VistaMAX Support File Access document for download
Operation Instructions PowerCool Series
Operation Instructions PowerCool Series TOP VIEW BOTTOM VIEW PDCOOL-05RA PDCOOL-00RK PDCOOL-5R PDCOOL-0R ALSO AVAILABLE Thank you for purchasing the PowerCool Series component cooler and power distribution.
MCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
Direct AC Wiring Option Installation Guide
Revision A Direct AC Wiring Option Installation Guide The direct AC wiring option enables you to wire AC power directly in to the ADP InTouch. The option kit contains the following parts. 25mm 12mm Caution:
About the HotWire 7900 10-Slot Standalone Shelf
TM HotWire Model 7900 10-Slot Standalone Shelf Installation Instructions Document Number 7900-A2-GN10-10 About the HotWire 7900 10-Slot Standalone Shelf The HotWire 7900 10-Slot Standalone Shelf is designed
ColdGuard Bi-PARTING DOOR INSTALLATION INSTRUCTIONS
EHD TRACK LEVEL, (SET LEVEL ON PLASTIC HEADER. DO NOT PLACE LEVEL ON ALUMINUM TRACK.) TRACK IS FLUSH WITH TOP OF HEADER JUNCTION BOX IDLER PULLEY LOCATOR PINS LOCATOR PINS OPERATOR DOOR STOP JUNCTION BOX
SNQ-60x0-320 Series Data Center Switch. Quick Installation Guide
Introduction This guide is to assist the reader with the most basic form of installation and connection to switches in this series. As there is more than one switch in this series, the diagrams might slightly
Sun Enterprise Optional Power Sequencer Installation Guide
Sun Enterprise Optional Power Sequencer Installation Guide For the Sun Enterprise 6500/5500 System Cabinet and the Sun Enterprise 68-inch Expansion Cabinet Sun Microsystems, Inc. 901 San Antonio Road Palo
BroadBand PowerShield. User Manual
BroadBand PowerShield User Manual 990-0375G 12/2006 Chapter 1 General Information The PowerShield provides a power source for broadband telephony and other DC applications. Safety This Safety Guide contains
Instruction Sheet PDS SERIES. Single Circuit Power Sequencer FRONT VIEW POWER ON I. DOWN 120V 12A 60Hz REAR VIEW. (PDS-615R Shown)
Instruction Sheet PDS SERIES Single Circuit Power Sequencer FRONT VIEW POWER ON I SEQUENCE SYSTEM OFF 120V-12A-60Hz UNSWITCHED STATUS REMOTE 5 6 CLOSED - All channels on OPEN - All channels off UP COM
2-3 SAS/SATA II HDD Canister USER S MANUAL XC-23D1-SA10-0-R. Document number: MAN-00076-A
2-3 SAS/SATA II HDD Canister XC-23D1-SA10-0-R USER S MANUAL Document number: MAN-00076-A ii Preface Important Information Warranty Our product is warranted against defects in materials and workmanship
AU-110 racking guide NBXPN: 023
AU-110 racking guide NBXPN: 023 1. Overview NIMBOXX AU-110 Rack Installation This guide provides setup instructions for installing your NIMBOXX AU-110 in a rack. Following these steps in the order given
Rack Installation. Unpacking the System. Choosing a Setup Location. General Server Precautions. Barracuda Appliances
This set of instructions applies to racking and rail kit installation for 6XX and above. The Rack Mounting Instructions section below provides information on installing the SC825 chassis into a rack unit
Smart-UPS RT External Battery Pack Stack/Rack-Mount 6U
Smart-UPS RT External Battery Pack Stack/Rack-Mount 6U SURT192RMXLBP2 SURT192RMXLBP2J English 990-2485B 02/2009 Introduction About this UPS The American Power Conversion (APC ) SURT192RMXLBP2 external
GSM-EXT Cable Assembly Installation Guide
GSM-EXT Cable Assembly Installation Guide For Documentation and Online Support: http://www.security.honeywell.com/hsc/resources/mywebtech General Information The GSM-EXT cable assembly is used to connect
HP ProLiant DL380 G6 Carrier-Grade Server Read Before Install
HP ProLiant DL380 G6 Carrier-Grade Server Read Before Install Carrier-Grade Instructions HP Part Number: AM275-9001A Published: July 2012 Edition: 3 Copyright 2009, 2012 Hewlett-Packard Development Company,
Intel RAID Maintenance Free Backup Unit 4 Quick Installation User's Guide
Intel RAID Maintenance Free Backup Unit 4 Quick Installation User's Guide Thank you for buying an Intel RAID Maintenance Free Backup Unit 4. The Intel RAID Maintenance Free Backup Unit 4 supports the Intel
Compact I/O End Caps/Terminators
Installation Instructions Compact I/O End Caps/Terminators Catalog Numbers 1769-ECL, 1769-ECR Topic Page Important User Information 2 Environment and Enclosure 3 North American Hazardous Location Approval
Rail Kit Install Guide: Intel Modular Server System MFSYS25 A Guide for Technically Qualified Assemblers of Intel Identified Subassemblies/ Products
Rail Kit Install Guide: Intel Modular Server System MFSYS25 A Guide for Technically Qualified Assemblers of Intel Identified Subassemblies/ Products Intel Order Number: E12567-002 Disclaimer Information
Wideband Optical Splitters FOS Series
Wideband Optical Splitters FOS Series Guide to Installation and Operation M949-9100-103 13 Mar 2014 Miranda Technologies 3499 Douglas-B.-Floreani St-Laurent, Québec, Canada H4S 2C6 Tel. 514-333-1772 Fax.
16-Port Gigabit Green Switch (TEG-S16Dg) 24-Port Gigabit Green Switch (TEG-S24Dg)
16-Port Gigabit Green Switch (TEG-S16Dg) 24-Port Gigabit Green Switch (TEG-S24Dg) ŸGuide d'installation rapide (1) ŸTechnical Specifications (3) ŸTroubleshooting (4) 1.02 1. Avant de commencer Contenu
StorTrends 3400 Hardware Guide for Onsite Support
StorTrends 3400 Hardware Guide for Onsite Support MAN-3400-SS 11/21/2012 Copyright 1985-2012 American Megatrends, Inc. All rights reserved. American Megatrends, Inc. 5555 Oakbrook Parkway, Building 200
How To Install A Power Supply (Uplast) With A Battery Pack
APC Smart-UPS RT SURTA48XLBP/SURTA48XLBPJ External Battery Pack User Manual Introduction/Before Installation About this Manual The APC Smart-UPS RT external battery pack (SURTA48XLBP or SURTA48XLBPJ) connects
Rack Mount Kit Install Guide: Intel Entry Server Chassis SC5295-E UP/DP/WS/BRP Intel Entry Server Chassis SC5299-E DP/WS/BRP
Rack Mount Kit Install Guide: Intel Entry Server Chassis SC5295-E UP/DP/WS/BRP Intel Entry Server Chassis SC5299-E DP/WS/BRP A Guide for Technically Qualified Assemblers of Intel Identified Subassemblies/Products
About the BitStorm 6051 POTS Splitter
BitStorm 6051 Installation Instructions Document Number 6051-A2-GZ40-10 July 2002 About the BitStorm 6051 The BitStorm system enables simultaneous high-speed digital data access and analog voice service
4x3.5" Hot-Swap Drive Cage Kit Installation Guide for Intel Server Chassis/System
4x3.5" Hot-Swap Drive Cage Kit Installation Guide for Intel Server Chassis/System Order Number: G23758-002 G23758-002 This document provides instructions for installing the following accessory kit: FUP4X35HSDK
Hard Disk Drive (HDD)
Installation Instructions Hard Disk Drive (HDD) Catalog Number 6189V-35HDDST80, 6189V-35HDDST160 Topic Page About This Publication 1 Important User Information 2 Electrostatic Discharge (ESD) Precautions
Keysight N4877A Clock Data Recovery and Demultiplexer 1:2
Keysight N4877A Clock Data Recovery and Demultiplexer 1:2 Getting Started Getting Started with the Keysight N4877A Clock Data Recovery and Demultiplexer 1:2 You only need a few minutes to get started
HP UPS R1500 Generation 3
HP UPS R1500 Generation 3 Installation Instructions Part Number 650952-001 NOTE: The rating label on the device provides the class (A or B) of the equipment. Class B devices have a Federal Communications
AI120 AIswitch Series 120 Chassis
AI120 AIswitch Series 120 Chassis Guide INSTALLATION GUIDE Westell Technologies Part # 030-300715 Rev. A Copyright 2015 by Westell Technologies. All Rights Reserved. Westell, Kentrox and Optima Management
In this section we tell you how to set the fault mode selection plug, key your I/O chassis, install your module and make your wiring connections.
Installation Data This document provides information on: important pre-installation considerations power supply requirements initial handling installing the module using the indicators for troubleshooting
UPDATEUPDATEUPDATE. Converting the tower chassis to a rack-mount chassis. A - M5 13 8 To mount outer member to rack
UPDATEUPDATEUPDATE Converting the tower chassis to a rack-mount chassis Rail overview Converting your Server to Rack-Mount The rail kit includes the following: Two rail units Five packages of screws (labeled
ATS Overhead Table Shelf System INSTRUCTION MANUAL
ATS Overhead Table Shelf System INSTRUCTION MANUAL ATS Overhead Table Shelf System Instruction Manual Warranty Newport Corporation warrants this product to be free of defects in material and workmanship
Triple Expansion Chassis
Triple Expansion Chassis AP9604 Installation Manual Contents Introduction............................. 1 Installation.............................. 2 Power Considerations...................... 5 Operations..............................
Mercury Helios 2 ASSEMBLY MANUAL & USER GUIDE
Mercury Helios 2 ASSEMBLY MANUAL & USER GUIDE TABLE OF CONTENTS INTRODUCTION...1 1.1 MINIMUM SYSTEM REQUIREMENTS 1.1.1 Apple Mac Requirements 1.1.2 PC Requirements 1.1.3 Supported PCIe Cards 1.2 PACKAGE
PS6500 Storage Arrays Rack Mount Instructions
PS6500 Storage Arrays Rack Mount Instructions Part Number: R724M Rev. A01 Copyright 2010 Dell, Inc. All rights reserved. Dell is a trademark of Dell, Inc. EqualLogic is a registered trademark. All trademarks
SLC 500 Analog Input Module
Installation Instructions SLC 500 Analog Input Module (Catalog Number 1746NI8) Inside Important User Information... 2 For More Information... 3 Hazardous Location Considerations... 4 Environnements dangereux...
Conductor VMS Software
Bailey Hartmann & Braun TM Conductor VMS Software Data Sheet Highlights Conductor VMS is a full-featured Human System Interface (HSI) specifically designed for Bailey Hartmann & Braun Symphony Enterprise
Backup Battery Kit Install Guide: Intel Storage Controller AXXSCM3S
Backup Battery Kit Install Guide: Intel Storage Controller AXXSCM3S A Guide for Technically Qualified Assemblers of Intel Identified Subassemblies/ Products Intel Order Number: E13860-004 Disclaimer Information
APPENDIX A - ON-LINE CONFIGURATION
APPENDIX A - ON-LINE CONFIGURATION INTRODUCTION This section provides a basic procedure for on-line configuration, and shows both the state of LEDs 7 and 8 as well as the contents of the second module
BODi rs BD004 Series Bandwidth-on-Demand Internet with Reliability and Survivability. Quick Start Guide NOTES
NOTES BODi rs BD004 Series Bandwidth-on-Demand Internet with Reliability and Survivability Quick Start Guide This is a Class A device and is not intended for use in a residential environment. Important
Replace the Pump Tube Classic
Entire document: 7 pages THIS DOCUMENT CONTAINS GENERAL INSTRUCTION FOR SERVICING STENNER PRODUCTS. PLEASE BE SURE TO READ ALL SAFETY INFORMATION. NOTICE: Indicates special instructions or general mandatory
FERRORESONANT BATTERY CHARGERS
WorkHorse SERIES 1 FERRORESONANT BATTERY CHARGERS Installation and Operating Instructions Applied Energy Solutions, LLC. One Technology Place Caledonia, New York 14423 (585) 538-4421 www.appliedenergysol.com
Uninterruptible Power Supply. 500 kva - 750 kva
9 315 Uninterruptible Power Supply 500 kva - 750 kva T1 and T3 Installation Addendum 164201244-001 Rev. A ------------------------------------------------------------------------ ------------------------------------------------------------------------
Altiris Patch Management Solution for Windows 7.6 from Symantec Third-Party Legal Notices
Appendix A Altiris Patch Management Solution for Windows 7.6 from Symantec Third-Party Legal Notices This appendix includes the following topics: Third-Party Legal Attributions CabDotNet MICROSOFT PLATFORM
Small form factor bay converter and hard drive installation
Small form factor bay converter and hard drive installation HP xw6600 and HP xw8600 Workstations This document describes how to convert HP xw6600 and HP xw8600 Workstation 3.5-inch hard drive bays to hold
Media Changer/Recorder VGP-XL1B. Safety Information
Media Changer/Recorder VGP-XL1B Safety Information Notice 2006 Sony Electronics Inc. Reproduction in whole or in part without written permission is prohibited. All rights reserved. This manual and the
UniStream CPU-for-Panel
UniStream CPU-for-Panel Installation Guide USC-P-B10 Unitronics UniStream platform comprises control devices that provide robust, flexible solutions for industrial automation. This guide provides basic
Installation Instructions
Installation Instructions ControlNet PCI Communication Interface Card Catalog Number 9904-PCIC This document describes how to install the 9904-PCIC ControlNet TM communication interface card. Topic: Page:
INSTRUCTION MANUAL MODEL PCD-88
INSTRUCTION MANUAL MODEL PCD-88 CLOSED CAPTION DECODER LINK ELECTRONICS, INC. 2137 Rust Avenue Cape Girardeau, Missouri 63703 Phone: 573-334-4433 Fax: 573-334-9255 e-mail: sales @ linkelectronics.com website:
FortiFone QuickStart Guide for FON-670i and FON-675i
FortiFone QuickStart Guide for FON-670i and FON-675i FortiFone QuickStart Guide for FON-670i and FON-675i Revision 2 September 25, 2015 Copyright 2015 Fortinet, Inc. All rights reserved. Fortinet, FortiGate,
Zebra RW 420 Mobile Battery Eliminator Kits
Zebra Technologies Corporation 475 Half Day Road, Suite 500 Lincolnshire, IL 60069 USA Zebra RW 420 Mobile Battery Eliminator Kits Installation Instructions September, 2010 RW 420 Mobile Battery Eliminator
1-Port DS3 IMA Module Description and Technical Specifications. The 1-Port DS3 IMA module is illustrated in Figure 1. FAIL ACTIVE DS3 IMA L0S
1-Port DS3 IMA Module Description and Technical Specifications Purpose of This Document This document identifies and describes the 1-Port DS3 IMA module and related safety information. It also includes
Sun StorEdge A5000 Installation Guide
Sun StorEdge A5000 Installation Guide for Windows NT Server 4.0 Sun Microsystems, Inc. 901 San Antonio Road Palo Alto, CA 94303-4900 USA 650 960-1300 Fax 650 969-9131 Part No. 805-7273-11 October 1998,
Tyan Computer. Transport PX22. Service Engineer s Manual
Tyan Computer Transport PX22 Service Engineer s Manual 1 Precaution To read through the user manual, check all assembly and follow setup process before any operation on this server To keep paper clips,
Dolphin 9900 Mobile Computers
Dolphin 9900 Mobile Computers Dolphin 9900 Dolphin 9950 Dolphin 9951 with Windows Mobile 6.1 Quick Start Guide Dolphin 9900 Series Quick Start Guide Out of the Box Verify that the box contains the following
Altiris Patch Management Solution for Windows 7.5 SP1 from Symantec Third-Party Legal Notices
Appendix A Altiris Patch Management Solution for Windows 7.5 SP1 from Symantec Third-Party Legal Notices This appendix includes the following topics: Third-Party Legal Attributions CabDotNet XML-RPC.NET
Installation Instructions for FT-10 Network PowerCommand ATS Communication Module (NCM) Kits 541 0812 and 541 0868
Instruction Sheet 10-2004 Installation Instructions for FT-10 Network PowerCommand ATS Communication Module (NCM) Kits 541 0812 and 541 0868 PowerCommand is a registered trademark of Cummins Inc. InPower
T7560A,B,C Digital Wall Module
T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital
Wall-Mounting your HP computer. User Guide
Wall-Mounting your HP computer User Guide The only warranties for Hewlett-Packard products and services are set forth in the express statements accompanying such products and services. Nothing herein should
RIGOL. Quick Guide. DS1000CA Series Oscilloscope. Aug. 2011. RIGOL Technologies, Inc.
Quick Guide DS1000CA Series Oscilloscope Aug. 2011 Technologies, Inc. Guaranty and Declaration Copyright 2011 Technologies, Inc. All Rights Reserved. Trademark Information is a registered trademark of
Regulatory Compliance Statement
Regulatory Compliance Statement 0560 EU Declaration of Conformity The declaration of conformity may be consulted at www.kobo.com/userguides SAR Limits The exposure standard for wireless devices employs
Gateway Port Replicator User Guide
Gateway Port Replicator User Guide Using the Port Replicator Identifying features Connecting and disconnecting the port replicator 1 Using the Port Replicator Top Power button Component Icon Description
Cascade Profiler Fibre Channel SAN Attached Storage Installation Guide. Version 8.2 March 2009
Cascade Profiler Fibre Channel SAN Attached Storage Installation Guide Version 8.2 March 2009 Trademarks Riverbed, the Riverbed logo, Riverbed Cascade, and Cascade are trademarks of Riverbed Technology,
Advantium 2 Plus Alarm
ADI 9510-B Advantium 2 Plus Alarm INSTALLATION AND OPERATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia
Compaq Presario Desktop Products. Upgrading and Servicing Guide
Compaq Presario Desktop Products Upgrading and Servicing Guide The information in this document is subject to change without notice. Hewlett-Packard Company makes no warranty of any kind with regard to
Service Guide. Gateway M275
Service Guide Gateway M275 Contents Replacing Gateway M275 Components.................................... 1 Identifying the convertible tablet PC model...................................... 2 Identifying
Model 1756 Test Lead Kit
Keithley Instruments 28775 Aurora Road Cleveland, Ohio 44139 1-888-KEITHLEY http://www.keithley.com Model 1756 Test Lead Kit Gerneral Purpose Test Lead Information Description These test leads allow you
767 Diagnostic System
767 Diagnostic System 3.5v 767 Wall Transformer Patent Pending Listed to: UL 60601-1 CSA C22.2 No. 601 Thank you for purchasing the Welch Allyn 3.5v 767 Wall Transformer. This manual is meant to provide
HP ProLiant DL165 G7 Server. Installation Instructions
HP ProLiant DL165 G7 Server Installation Instructions Identifying server components Front panel components Figure 1 Front Panel Components / 4 3.5 HDD Item 1 Thumbscrews for rack mounting 2 Drive status
Installation Guide. Wyse VX0L and VX0LE Thin Clients 1-GB RAM Upgrade Option Kit. Issue: 022808 PN: 883884-07L Rev. A
Installation Guide Wyse VX0L and VX0LE Thin Clients 1-GB RAM Upgrade Option Kit Issue: 022808 PN: 883884-07L Rev. A ii Copyright Notice 2008, Wyse Technology Inc. All rights reserved. This manual and the
Instruction Manual PC55O. With PC5OORK Keypad. 1996, 2002 Digital Security Controls Ltd. Toronto, Canada Printed in Canada 29000534 R3
Instruction Manual 1996, 2002 Digital Security Controls Ltd. Toronto, Canada Printed in Canada 29000534 R3 PC55O With PC5OORK Keypad Industry Canada Notice NOTICE: The Industry Canada label identifies
Sun Management Center Change Manager 1.0.1 Release Notes
Sun Management Center Change Manager 1.0.1 Release Notes Sun Microsystems, Inc. 4150 Network Circle Santa Clara, CA 95054 U.S.A. Part No: 817 0891 10 May 2003 Copyright 2003 Sun Microsystems, Inc. 4150
SIMATIC S7-300. Getting Started for First Time Users. Order No.: 6ZB5310-0NC02-0BA0 04/2007 A5E01094750-01
SIMATIC S7-300 Getting Started for First Time Users Order No.: 6ZB5310-0NC02-0BA0 04/2007 A5E01094750-01 Safety Guidelines This manual contains notices you have to observe in order to ensure your personal
AD511 Active Iridium Antenna User Manual Mar 12 V4.0
AD511 Active Iridium Antenna User Manual Mar 12 V4.0 AD511 Active Iridium Transmitter/Receiver Antenna with up to 160 metres of coaxial down-lead and DC Power Break-In Box for Iridium Satellite Systems
PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit
PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit Installation Instructions This document provides instructions for the installation of a DC bus connector kit for PowerFlex 700S and 700H frame 12 drives
SPARC Enterprise T5140 and T5240 Servers. StorageTek SAS RAID Eight-Port Internal HBA Installation Guide
SPARC Enterprise T5140 and T5240 Servers StorageTek SAS RAID Eight-Port Internal HBA Installation Guide Part No. 820-4754-12 Manual Code: C120-E521-03XA August 2010 Copyright 2008, 2010, Oracle and/or
First Data FD130 Terminal. Quick Set-up Guide
First Data FD130 Terminal Quick Set-up Guide Thanks for choosing a First Data Terminal. First Data Terminals are some of the fastest, most secure point-of-sale terminals available. Installation is quick
FortiFone QuickStart Guide for FON-370i
FortiFone QuickStart Guide for FON-370i FortiFone QuickStart Guide for FON-370i Revision 2 August 17, 2015 Copyright 2015 Fortinet, Inc. All rights reserved. Fortinet, FortiGate, FortiCare and FortiGuard,
Installation Guide Smart-UPS X External Battery Pack SMX120BP
Installation Guide Smart-UPS X External Battery Pack SMX120BP Inventory Inspect the contents upon receipt. Notify the carrier and dealer if there is damage. Two bezels Tie brackets used to secure multiple
Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment
Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment FAST SHIPPING AND DELIVERY TENS OF THOUSANDS OF IN-STOCK ITEMS EQUIPMENT DEMOS HUNDREDS OF MANUFACTURERS SUPPORTED
ProLiant DL380 Generation 2 Server Maintenance and Service Guide
ProLiant DL380 Generation 2 Server Maintenance and Service Guide Second Edition (June 200) Part Number 203840-002 Spare Part Number 228520-00 Compaq Computer Corporation Notice 200 Compaq Computer Corporation
Lumencor SOLA light engine Instruction Manual
Lumencor SOLA light engine Instruction Manual Lumencor, Inc. 14964 NW Greenbrier Parkway, Beaverton, OR 97006 T 503.213.4269 F 503.536.6741 www.lumencor.com Emissions Certifications This equipment has
Set Up Your MXI -Express x1 System
Set Up Your MXI -Express x1 System Terminology This document explains what is needed to set up various MXI-Express x1 hardware configurations. The products covered by this guide are the NI PCI-8361, NI
IP DSLAM IDL-2402. Quick Installation Guide
IP DSLAM IDL-2402 Quick Installation Guide Table of Contents Package Contents... 3 Overview... 4 Setup the IDL series IP DSLAM... 5 Safety Instruction... 5 Hardware Installation... 6 WEB Configuration...
User Manual. RK-2d / RK-2t. dedicated KVM switch and rackmount screen technology. Designed and manufactured by Austin Hughes
dedicated KVM switch and rackmount screen technology User Manual RK-2d / RK-2t 1U Short Depth Keyboard Drawer Designed and manufactured by Austin Hughes 751 Legal Information First English printing, October
BRACKET LOCKING SCREW
Solutions SW800 Data Center Cabinets CDU Installation Guide (SW8XP-x Series) There are two procedures in this installation guide. The first procedure, Cable Distribution Unit (CDU) Replacement, describes
HP R12000 and R18000 DirectFlow UPS User Guide
HP R12000 and R18000 DirectFlow UPS User Guide Abstract This document includes installation, configuration, and operation information for the HP R12000 and R18000 DirectFlow UPS. This document is for the
HP 36-Port InfiniBand Switch Cable Management Kit Installation Guide
HP 36-Port InfiniBand Switch Cable Management Kit Installation Guide HP Part Number: 574412-doc Published: May 2009 Copyright 2009 Hewlett-Packard Development Company, L.P. The information contained herein
Installing Your 960 or 980 Server into a Rackmount Cabinet
Installing Your 960 or 980 Server into a Rackmount Cabinet 1 2 Contents Installing Your Gateway Server into a Rackmount Cabinet...1 Identifyingpartsintheaccessorykit...2 Rackmounthandlekit... 2 Rackmountrailkit...
WARNING CANADIAN D.O.C. WARNING
Each product and program carries a respective written warranty, the only warranty on which the customer can rely. Avery Dennison Corp. reserves the right to make changes in the product, the programs, and
TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions
TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions TRACETEK TraceTek TTDM Replacement Parts General Information These instructions detail the steps to
Perle Protocol Transparent Media Converter Modules
Perle Protocol Transparent Media Converter Modules Installation Guide C-4GPT-DSFP CM-4GPT-DSFP Part# 5500335-10 Overview This document contains instructions necessary for the installation and operation
Upgrading and Servicing Guide
Upgrading and Servicing Guide The only warranties for Hewlett-Packard products and services are set forth in the express statements accompanying such products and services. Nothing herein should be construed
PCIe XMC x8 Lane Adapter
Adapts PCI Express XMC to Desktop with P16 High Speed Communications Ports and JN4 Digital IO FEATURES Adapt one XMC PCI Express VITA 42.3 module to a desktop PCI Express slot Supports up to 8 lanes Transparent