AIRCONDITIONING Cooling Loads Calculations
|
|
|
- Roberta Blake
- 9 years ago
- Views:
Transcription
1 Calculations -1- AIRCONDITIONING Cooling s Calculations Employer : 4M SA Project Location : ASHRAE Office Room : Example from ASHRAE 2013 Handbook - Fundamentals : Chapter 18, Single Room Example (p ) : Atlanta, Georgia
2 Calculations INTRODUCTION This study is based upon the ASHRAE RTS methodology. Furthermore, the following literature was also used: i) ASHRAE Handbook of Fundamentals 2013 ii) ASHRAE Handbook of Systems and Equipment 2012 iii) ASHRAE Handbook of Applications 2011 iv) ASHRAE Standards for Natural and Mechanical Ventilation v) ASHRAE Cooling and Heating Calculation Manual ASHRAE GRP ASSUMPTIONS & RULES OF CALCULATION According to ASHRAE, the general procedure for calculating cooling load for each load component (lights, people, walls, roofs, windows, appliances, etc.) with RTS is as follows: 1. Calculate 24 h profile of component heat gains for design day (for conduction, first account for conduction time delay by applying conduction time series). 2. Split heat gains into radiant and convective parts using radiant and convective parts. 3. Apply appropriate radiant time series to radiant part of heat gains to account for time delay in conversion to cooling load. 4. Sum convective part of heat gain and delayed radiant part of heat gain to determine cooling load for each hour for each cooling load component. Analytically, for each step: 1i. Walls and roofs heat gains calculation using Conduction Time Series (CTS) The heat input calculation is given from the following equation: q i,θ-n =UA(t e,θ-n -t rc ) q i,θ-n : Conductive heat input for the surface n hours ago U : Overall heat transfer coefficient for the surface A : area t e,θ-n : Sol-air temperature n hours ago t rc : Presumed constant room air temperature Conductive heat gain through walls or roofs can be calculated using conductive heat inputs for the current hours and past 23h and conduction time series: q θ = c 0 q i,θ + c 1 q i,θ-1 + c 2 q i,θ-2 + c 3 q i,θ-3 + +c 23 q i,θ-23 q θ q i,θ q i,θ-n : Hourly conductive heat gain for the surface : Heat input for current hour : Heat input n hours ago c 0,c 1, etc. : Conduction time factors 1ii. Fenestration heat gain calculation Fenestration heat gains can be split into three parts: q b =AE t,b SHGC(θ)IAC(θ,Ω) q d =A(E t,d +E t,r )<SHGC> D IAC D q c =AU(T out -T in )
3 Calculations -3- q b : Direct beam solar heat gain Α : Window area Ε t,b : Beam direct irradiance SHGC(θ) : Beam solar heat gain coefficient as a function of incident angle θ IAC(θ,Ω) : Indoor solar attenuation coefficient for beam solar heat gain coefficient q d : Diffuse solar heat gain Α : Window area Ε t,d : Sky diffuse irradiance Ε t,r : Ground-reflected diffuse irradiance <SHGC> D : Diffuse solar heat gain coefficient IAC D : Indoor solar attenuation coefficient for diffuse solar heat gain coefficient q c : Α U T out T in Conductive heat gain : Window area : Overall U-factor, including frame and mounting orientation : Outdoor temperature : Indoor temperature fenestration heat gain Q: Q= q b + q d +q c 1iii. Interior surfaces heat gain calculation Whenever a conditioned space is adjacent to a space with a different temperature, heat transfer through the separating physical section must be considered. The heat transfer rate is given by: q=u*a*(t b -t i ) q U A t b t i : Heat transfer rate : Overall heat transfer coefficient between adjacent and conditioned space : Area of separating section concerned : Average air temperature in adjacent space : Air temperature in conditioned space Where nothing is known for the adjacent space except that it is of conventional construction contains no heat sources and itself receives no significant solar heat gain, t b -t i may be considered the difference between the outdoor air and conditioned space design dry-bulb temperatures minus 3 K. 1iv. Floors heat gain calculation For floors directly in contact with the ground or over an underground basement that is neither ventilated nor conditioned, sensible heat transfer may be neglected for cooling load estimates because usually there is a heat loss rather than a gain. 1v. Internal heat gains calculation 1v.1. Lighting The lighting heat gains are calculated using the following equation: q el = W F ul F sa
4 Calculations -4- FINE HVAC 14 Cooling s q el : Heat gain W : light wattage F ul : Lighting use factor F sa : Lighting special allowance factor 1v.2. People The occupants heat gains are distinguished in sensible and latent heat gains. The calculation equations of sensible and latent heat gains are given bellow: q s = q s, per N q l = q l, per N q s : Occupants sensible heat gain q l : Occupants latent heat gain q s, per : heat gain per person q l, per : heat gain per person N : Number of occupants 1v.3. Appliances The appliances loads are distinguished in sensible load and latent load. The calculation equations are given bellow: q s = Q s x F U F R q l = Q l x N q s : Appliances total sensible load q l : Appliances total latent load Q s : load of appliance Q l, : load of appliance F U : Usage factor F R : Radiation factor N : Number of appliances that operate in the space 1v.4. Ventilation and Infiltration Air-conditioning design often requires the calculation of the sensible and latent heat gain. The equations are given bellow: q s = 1.23 Q s t q l = 3010 Q s W q s : heat gain due to infiltration q l : heat gain due to infiltration Q s : Infiltration airflow at standard air conditions t o : Outdoor air temperature t i : Indoor air temperature W o : Outdoor air humidity ratio W i : Indoor air humidity ratio 1.23 : Air sensible heat factor at standard air conditions
5 Calculations -5- FINE HVAC 14 Cooling s 3010: Air latent heat factor at standard air conditions 2. Separation of heat gains in radiant and convective fractions The cooling load for each load component (lights, people, walls, roofs, windows, appliances etc.) for a particular hour is the sum of the convective portion of the heat gain for that hour plus the time-delayed portion of radiant heat gains for that hour and the previous 23 h. The following table contains recommendations for splitting each of the heat gain components into convective and radiant portions: Radiative fraction Convective fraction Occupants, typical office conditions 0.1 to to 0.2 Equipment varies varies Lighting Conduction heat gain through walls and floors Conduction heat gain through roof Conduction heat gain through windows (SHGC > 0.5) Conduction heat gain through windows (SHGC < 0.5) Solar heat gain through fenestration (without interior shading) varies varies Solar heat gain through fenestration (with interior shading) Infiltration 3. Radiant portion of sensible cooling load The radiant part of sensible cooling load is calculated by applying RTS factors according to the following equation: Q r,θ = r 0 q r,θ + r 1 q r,θ-1 + r 2 q r,θ-2 + r 3 q r,θ-3 + +r 23 q r,θ-23 Q r,θ q r,θ q r,θ-n r 0,r 1, etc. : Radiant cooling load for current hour θ : Radiant heat gain for current hour : Radiant heat gain n hours ago : Radiant time factors 4. Convective portion of sensible cooling load The convective part of sensible cooling load is calculated according to the following equation: Q i,c = q i,c where q i,c is convective portion of heat gain from heat gain element i : q i,c = q i,s (1- F r ) q i,s : heat gain from heat gain element i, F r : Fraction of heat gain that is radiant 5. Cooling s The instantaneous room cooling load is calculated according to the following equations: Q s = ΣQ i,r + ΣQ i,c
6 Calculations -6- Q l = Σq i,l Q s : Room sensible cooling load ΣQ i,r : Radiant portion of sensible cooling load for current hour, resulting from heat gain element i, ΣQ i,c : Convective portion of sensible cooling load resulting from heat gain element i, Q l : Room latent cooling load q i,l : heat gain for heat gain element i, 3. PRESENTATION OF RESULTS The computed results are given both overall and analytically for all calculated hours. In the calculation sheets the results per space are tabulated in the following groups: 1. Building Elements table: type (e.g. W= Wall etc.) Orientation Length (m) Height or Width (m) U-factor (W/m²K or Kcal/hm²C) area (m 2 ) Number of equal surfaces surface area (m 2 ) Subtracted surface area (m 2 ) Calculated surface area (m 2 ) Inside shading Projection shading Arbitrary shading coefficients 2. s of the above table per surface area and time (Btu/h, W, or Kcal/h) 3. Additional loads per hour (Btu/h, W, or Kcal/h) Lighting Population Equipment 4. space loads per hour (Kbtu/h, KW, or Mcal/h) 5. Ventilation loads per hour (and maximum) (Kbtu/h, KW, or Kcal/h) i) The first group includes the geometrical dimensions of the building elements, as well as indications of possible shadow occurrences. ii) In the second group the cooling loads are presented as calculated for each building element, according to the calculation rules that were given above. iii) The third group includes the additional loads, due to lighting, population and appliances, and given in total, sensible and latent loads. iv) In the last group the overall sums of the space loads per hour are given, for sensible, latent and total loads, as well as ventilation load. In a similar way, the system calculation sheets are presented. In these, the loads of the corresponding to each system spaces are grouped and resolved into the different causes. Ventilation loads for each system are also given. Finally, the shadowing coefficients are presented in separate sheets.
7 Calculations -7- BUILDING PARAMETERS City : Atlanta Room Temperature ( C) : 23.9 Indoor humidity (%) : 50 Difference T OUT. - T NOT AIRCOND.SP. ( C) : 5 Difference T Soil - T Indoor ( C) : -5 Number of Levels (Floors) : 2 Typical Level Height (m) : 2.74 Energy Units Calculation Method : W : ASHRAE RTS STRUCTURAL ELEMENTS Typical Elements of Building - External walls Outer Walls Description of ASHRAE CLTD of ASHRAE TFM of ASHRAE RTS* U-Factor (W/m²K) W1 Brick wall (Light) W2 Spandrel wall (Dark) Color * Wall CTS 1 : Spandrel glass, insulation board, gyp board Wall CTS 11 : Brick, insulation board, sheathing, gyp board Typical Elements of Building - Roofs Ceilings Description of of of U-Factor Color ASHRAE CLTD ASHRAE TFM ASHRAE RTS* (W/m²K) C1 Flat metal deck (Light) * Roof CTS 11 : Membrane, sheathing, insulation board, metal deck Typical Elements of Building - Openings O1 Openings Description Width (m) Double glazed window Height (m) Openings U Factor (W/m²K) Frame (Metal or without frame) Glazing system 5d. Uncoated double glazing system
8 Calculations -8- CALCULATIONS Level : Second floor Space : 1 Name : Office room s Orientation U-Factor (W/m²K) Length (m) Height or Width (m) (m2) Occurren ces (m²) Calculated (m²) Projection Shading W1 SE W2 SE O1 SE SHADE W1 SW W2 SW O1 SW SHADE C1 C s Shading Coefficients Calculated (m²) 01:00 02:00 03:00 04:00 05:00 06:00 07:00 08:00 09:00 10:00 11:00 12:00 W1 (SE) W2 (SE) O1 (SE) W1 (SW) W2 (SW) O1 (SW) C Calculated (m²) 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 00:00 W1 (SE) W2 (SE)
9 Calculations -9- FINE HVAC 14 Cooling s O1 (SE) W1 (SW) W2 (SW) O1 (SW) C s per and hour (W) [Roof load absorbed in the return air-stream: 30%] Calculated (m²) 01:00 02:00 03:00 04:00 05:00 06:00 07:00 08:00 09:00 10:00 11:00 12:00 W1 (SE) W2 (SE) O1 (SE) W1 (SW) W2 (SW) O1 (SW) C Calculated (m²) 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 00:00 W1 (SE) W2 (SE) O1 (SE) W1 (SW) W2 (SW) O1 (SW) C
10 Calculations -10- Lighting Data (W) Lighting Coeff. Power (W) 4-lamp pendant fluorescent Lighting Schedule and in Space per Hour Title 01:00 02:00 03:00 04:00 05:00 06:00 07:00 08:00 09:00 10:00 11:00 12:00 Time Schedule (W) Title 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 00:00 Time Schedule (W) People Data (W) Degree of Activity Moderately active office work Coeff. Coeff. Number of Persons People Schedule and in space per hour Title 01:00 02:00 03:00 04:00 05:00 06:00 07:00 08:00 09:00 10:00 11:00 12:00 Time Schedule
11 Calculations -11- Title 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 00:00 Time Schedule Equipment Data (W) of Appliance Computer and personal printer Coeff. Coeff. Equipment Number Equipment Schedule and in Space per Hour Title 01:00 02:00 03:00 04:00 05:00 06:00 07:00 08:00 09:00 10:00 11:00 12:00 Time Schedule Title 13:00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 00:00 Time Schedule
12 Calculations -12- Space s per hour (W) 01:00 02:00 03:00 04:00 05:00 06:00 07:00 08:00 09:00 10:00 11:00 12:00 Lighting People ( s) People ( s) People ( ) Equipment () Equipment () Equipment () Infiltration :00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 00:00 Lighting People ( s) People ( s) People ( ) Equipment () Equipment () Equipment () Infiltration
13 Calculations -13- Space s per Hour (W) 01:00 02:00 03:00 04:00 05:00 06:00 07:00 08:00 09:00 10:00 11:00 12: :00 14:00 15:00 16:00 17:00 18:00 19:00 20:00 21:00 22:00 23:00 00:
14 Calculations -14- TEMPERATURE DATA Date : July, 23 Mean maximum temperature ( C) : 33.3 Daily range ( C) : 11.4 Outdoor Humidity (%) : Hour T o T e NE T e E T e SE T e S T e SW T e W T e NW T e N (45 ) (90 ) (135 ) (180 ) (225 ) (270 ) (315 ) (0 ) GENERAL TABLES Wall & Roof Conduction Time Factors [ASHRAE Ch Tables 16-17] Hour W W C Representative Nonsolar RTS Values for Light to Heavy Construction [ASHRAE Ch Table 19] Medium with Carpet and 50% Glass Hour Space
THERMAL LOSSES Thermal Losses Calculations
Calculations -1- THERMAL LOSSES Thermal Losses Calculations Employer : 4M SA Project Location : ASHRAE Office Room : Example from ASHRAE 2013 Handbook - Fundamentals : Chapter 18, Single Room Example Peak
Software Development for Cooling Load Estimation by CLTD Method
IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) ISSN: 2278-1684Volume 3, Issue 6 (Nov. - Dec. 2012), PP 01-06 Software Development for Cooling Load Estimation by CLTD Method Tousif Ahmed Department
Energy Efficient Building Design College of Architecture Illinois Institute of Technology, Chicago. Ceiling/Airspace
HEAT GAINS and LOSSES : ROOFS and WALLS Wall Roof Ts To Ts To Ti Ceiling/Airspace Ti Roof and wall are analyzed in the same way. In winter the heat loss is simple transmission based on the inside and outside
CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION
CHAPTER 3. BUILDING THERMAL LOAD ESTIMATION 3.1 Purpose of Thermal Load Estimation 3.2 Heating Load versus Cooling Load 3.3 Critical Conditions for Design 3.4 Manual versus Computer Calculations 3.5 Heating
ANSI/ASHRAE Standard 140-2004 Building Thermal Envelope and Fabric Load Tests
ANSI/ASHRAE Standard 140-2004 Building Thermal Envelope and Fabric Load Tests DesignBuilder Version 1.2.0 (incorporating EnergyPlus version 1.3.0) - June 2006 1.0 Purpose The ANSI/ASHRAE Standard 140-2004
HVAC Calculations and Duct Sizing
PDH Course M199 HVAC Calculations and Duct Sizing Gary D. Beckfeld, M.S.E., P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com An
Air Conditioning Clinic
Air Conditioning Clinic Cooling and Heating Load Estimation One of the Fundamental Series April 2011 TRG-TRC002-EN Cooling and Heating Load Estimation One of the Fundamental Series A publication of Trane,
Solar Energy Utilisation in Buildings
Solar Energy Utilisation in Buildings P. Karava, PhD Assistant professor Department of Civil and Environmental Engineering University of Western Ontario 2 Modern Buildings Change in architectural style
Cooling Load Calculations and Principles
Cooling Load Calculations and Principles Course No: M06-004 Credit: 6 PDH A. Bhatia Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774
Cooling Load Estimation and Air Conditioning Unit Selection for Hibir Boat
The International Journal Of Engineering And Science (IJES) Volume 3 Issue 5 Pages 63-72 2014 ISSN (e): 2319 1813 ISSN (p): 2319 1805 Cooling Load Estimation and Air Conditioning Unit Selection for Hibir
HVAC Made Easy: A Guide to Heating & Cooling Load Estimation
PDHonline Course M196 (4 PDH) HVAC Made Easy: A Guide to Heating & Cooling Load Estimation Instructor: A. Bhatia, B.E. 2012 PDH Online PDH Center 5272 Meadow Estates Drive Fairfax, VA 22030-6658 Phone
Eco Pelmet Modelling and Assessment. CFD Based Study. Report Number 610.14351-R1D1. 13 January 2015
EcoPelmet Pty Ltd c/- Geoff Hesford Engineering 45 Market Street FREMANTLE WA 6160 Version: Page 2 PREPARED BY: ABN 29 001 584 612 2 Lincoln Street Lane Cove NSW 2066 Australia (PO Box 176 Lane Cove NSW
Residential HVAC System Sizing
Residential HVAC System Sizing William P. Goss University of Massachusetts, Amherst, Massachusetts, USA Corresponding email: [email protected] SUMMARY Heating, ventilating and air-conditioning (HVAC)
CITY PLAN REVIEW AND INSPECTION. Lisa Fleming Brown, CPM
CITY PLAN REVIEW AND INSPECTION Lisa Fleming Brown, CPM Houston Commercial Energy Conservation Code (2011) A choice of 2009 IECC or ASHRAE 90.1-2007 with amendments. Effective September 2, 2011. Complete
CHAPTER 3 Window design for day lighting, ventilation and to
for day lighting CHAPTER 3 Window design for day lighting 3.1 Guideline: for day lighting 3.2 Mandatory clause 3.2.1 For air-conditioned buildings!"!#$$%& # '()!!"!#$$%& * '()! #!"!#$$% Table 3.2.1: Vertical
Residential HVAC Load Sizing Training October 14, 2015. David Kaiser Green Code Plan Reviewer
Residential HVAC Load Sizing Training October 14, 2015 David Kaiser Green Code Plan Reviewer DCRA - Green Building Division Regulations of green codes including: Green Building Act Green Construction Code
Energy Efficiency in Buildings
Energy Efficiency in Buildings Supplemental Guide to SANS 10400-XA & SANS 204 V. 3.0 Registered to: The Drawing Studio Image: digitalart / FreeDigitalPhotos.net Report Date: 26 August 2014 Practice Name:
Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls
PCA R&D Serial No. 415 Energy Use in Residential Housing: A Comparison of Insulating Concrete Form and Wood Frame Walls by John Gajda and Martha VanGeem 000 Portland Cement Association KEYWORDS Concrete,
Innovent LASER Packaged Fresh Air Conditioning Units
LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent
Below are detailed instructions for using the EMS load calculator.
Introduction The EMS load calculator is designed to make load calculating as painless as possible. For sizing the equipment, only the first three tabs (Steps 1, 2 & 3) need to be completed. This process
The Influence Of Window Type And Orientation On Energy-Saving In Buildings Application To A Single Family Dwelling
The Influence Of Window Type And Orientation On Energy-Saving In Buildings Application To A Single Family Dwelling Urbikain M. K., Mvuama M. C., García Gáfaro C. and Sala Lizarraga J. M. The University
LOW-RISE RESIDENTIAL BUILDINGS ADDITIONS AND ALTERATIONS IN EXISTING LOW-RISE RESIDENTIAL BUILDINGS
SUBCHAPTER 9 LOW-RISE RESIDENTIAL BUILDINGS ADDITIONS AND ALTERATIONS IN EXISTING LOW-RISE RESIDENTIAL BUILDINGS SECTION 150.2 ENERGY EFFICIENCY STANDARDS FOR ADDITIONS AND ALTERATIONS IN EXISTING BUILDINGS
Climate and Energy Responsive Housing in Continental Climates. The Suitability of Passive Houses for Iran's Dry and Cold Climate. Farshad Nasrollahi
Climate and Energy Responsive Housing in Continental Climates The Suitability of Passive Houses for Iran's Dry and Cold Climate Farshad Nasrollahi Table of Contents Abstract German Abstract Introduction
Building Performance Evaluation Guide Version 1.7
Building Performance Evaluation Guide Version 1.7 Prepared by Center for Energy and Environment January 2014 Minnesota Sustainable Building 2030: Building Performance Evaluation Guide p 1 1. Schematic
1/9/2013. Terminology Calculating Heat Transfer Code Requirements Design Examples and Sustainability
1/9/13 By Brett T. Fagan, P.E. Presented by Marie Horan, P.E. Building Diagnostics, Inc. Building Diagnostics Terminology Calculating Heat Transfer Code Requirements Design Examples and Sustainability
Selecting Energy Efficient New Windows in Georgia
Selecting Energy Efficient New Windows in Georgia www.efficientwindows.org January 016 ENERGY STAR Zones 1. Meet the Energy Code & Look for the ENERGY STAR Windows must comply with your local energy code.
Passive Solar Design and Concepts
Passive Solar Design and Concepts Daylighting 1 Passive Solar Heating Good architecture? The judicious use of south glazing coupled with appropriate shading and thermal mass. Summer Winter Passive solar
CHAPTER 4 LOAD CALCULATIONS 4.1 CONTEXT
CHAPTER 4 LOAD CALCULATIONS 4.1 CONTEXT The accurate calculation of heating and cooling loads is essential to provide a sound bridge between fundamental building design decisions and an operating building.
Constructions Database User Guide <Virtual Environment> 5.9
Constructions Database User Guide 5.9 Page 1 of 35 Contents 1. Introduction...3 2. Units...4 3. Main Dialogue Project Constructions...5 3.1. Outline...5 3.2. Construction Classes
IECC Compliance Guide for Homes in Virginia
IECC Compliance Guide for Homes in Virginia Amended Version of 2012 International Energy Conservation Code July 14, 2014 Climate Zone Since the entire state of Virginia falls in the IECC Climate Zone 4,
DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL
DEVELOPMENT OF AN OPEN SOURCE HOURLY BUILDING ENERGY MODELING SOFTWARE TOOL Brittany Hanam, MASc, EIT RDH Building Engineering Ltd. Vancouver, BC John Straube, PhD, P.Eng. Building Engineering Group, Civil
Simplified Procedure For Estimating Air- Conditioning Cooling Load In Ghana
Simplified Procedure For Estimating Air- Conditioning Cooling Load In Ghana Felix A. Uba, YesuenyeagbeA. K. Fiagbeand Emmanuel A. Sarsah Abstract: Undersized or oversized air conditioning equipment leads
Saving Heating Costs In Warehouses
2005, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Reprinted by permission from ASHRAE Journal, (Vol. 47, No. 12, December 2005). This article may not
Load and Energy Calculations
BBSE2008 Air Conditioning and Refrigeration Engineering www.hku.hk/bse/bbse2008/ Load and Energy Calculations Dr. Sam C. M. Hui Department of Mechanical Engineering The University of Hong Kong E-mail:
Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal
Technical Bulletin By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal SUMMARY Refrigeration air coolers (evaporators)
Vestibule Case Study. Vestibule Requirement Intent [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004]
Vestibule Case Study [2003 IECC, 2006 IECC, 2003 IBC, 2006 IBC, 90.1-2001, 90.1-2004] Vestibule Requirement Intent Page 1 of 14 The primary intent behind the requirement for a vestibule is to reduce infiltration
UNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM
Page 1 UNDERSTANDING AND USING THE HVAC DESIGN REVIEW FORM Each of the 38 points of requested information is discussed, and references to the supporting manual are given to substantiate the requirement.
Element D Services Heating, Ventilating, and Air Conditioning
Load Calculation Criteria PART 1 - GENERAL 1.01 OVERVIEW A. This section includes requirements for calculating HVAC cooling and heating loads. B. Load calculations must be performed in accordance with
Measuring The Right Thing For Humidity Control It s the Dew Point Stupid!
Page 1 of 6 Measuring The Right Thing For Humidity Control It s the Dew Point Stupid! By Mike Schell, AirTest Technologies Corp. A version of this article appeared in the June 2004 edition of Indoor Air
Uncovering Myths and Opportunities of Advanced Building Envelope Technologies: BIPV, Roofing and Windows
Uncovering Myths and Opportunities of Advanced Building Envelope Technologies: BIPV, Roofing and Windows Marc LaFrance Technology Development Manager US Department of Energy Building Technology Program
Cooling Load Calculation
for A Probabilistic Approach Taperit Tongshoob 1 Chirdpun Vitooraporn 2 Cooling Load Calculation Abstract 1 Ph.D Student 2 Lecturer at Building Technology Environment Laboratory, Mechanical Engineering
Adaptive strategies for office spaces in the UK climate
International Conference Passive and Low Energy Cooling 631 Adaptive strategies for office spaces in the UK climate I. Gallou Environment & Energy Studies Programme, Architectural Association Graduate
National Building Code of Canada 2010
National Building Code of Canada 2010 Emergency Change Issued by the Canadian Commission on Building and Fire Codes The table that follows lists two emergency changes that apply to the National Building
Diego Ibarra Christoph Reinhart Harvard Graduate School of Design
Building Performance Simulation for Designers - Energy DesignBuilder // EnergyPlus Tutorial #2 Load Schedules GEOMETRY LOADS RESULTS Diego Ibarra Christoph Reinhart Harvard Graduate School of Design OVERVIEW
Energy efficient home design
Energy efficient home design GUIDELINES How an energy efficient home can help you live in comfort and save money An energy efficient home is designed to provide shade and allow cooling breezes to enter
EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation. 1.1.1 The Building Regulations 2010
EFA PSBP Natural Ventilation Strategy Introduction The Baseline Designs Project will provide scheme design details for a number of Primary and Secondary School Exemplars. For the purposes of setting a
New Homes EPS Modeling Frequently Asked Questions. Developed by Energy Trust of Oregon
New Homes EPS Modeling Frequently Asked Questions Developed by Energy Trust of Oregon 1 General Questions 3 REM/Rate questions 4 -Creating custom entries 4 -Modeling Heat Pumps 5 -Modeling HRV/ERV 7 -Modeling
Radiant Panels and Chilled Sails. www.price-hvac.com
Radiant Panels and Chilled Sails www.price-hvac.com Radiant Panels and Chilled Sails Introduction Radiant panels use thermal radiation to modify surface temperatures in order to provide sensible cooling
Certificate of Compliance ENV-1-C and Envelope Component Method ENV-2-C
Certificate of Compliance ENV-1-C and Envelope Component Method ENV-2-C Forms Quality You Can Trust Since 1886... From North America s Largest Roofing Manufacturer CERTIFICATE OF COMPLIANCE (Part 1 of
Selecting Energy Efficient New Windows in Arizona
Selecting Energy Efficient New Windows in Arizona www.efficientwindows.org January 016 ENERGY STAR Zones 1. Meet the Energy Code & Look for the ENERGY STAR Windows must comply with your local energy code.
Energy Savings in High-Rise Buildings Using High-Reflective Coatings
Energy Savings in High-Rise Buildings Using High-Reflective Coatings Executive Summary: Nevertheless, the simulation analyses showed that when designing a building for low energy consumption, even in cold
Comments on How Exterior Paints and Interior Paints Can Play Roles in Conserving Energy. For Tech Traders Inc. By H. F. Poppendiek
Comments on How Exterior Paints and Interior Paints Can Play Roles in Conserving Energy For Tech Traders Inc. By H. F. Poppendiek June 2002 GEOSCIENCE LTD 620 Marindustry Drive San Diego, California 92121
COOLING AND HEATING OF BUILDINGS BY ACTIVATING THEIR THERMAL MASS WITH EMBEDDED HYDRONIC PIPE SYSTEMS -
pcoolingandheating COOLING AND HEATING OF BUILDINGS BY ACTIVATING THEIR THERMAL MASS WITH EMBEDDED HYDRONIC PIPE SYSTEMS - Bjarne W. Olesen, Ph.D. D. F. Liedelt "Velta" Summary Due to intensive use of
FACTSHEET Assessing the Feasibility of Using Solar-Thermal Systems for Your Agricultural or Agri-Food Operation
FACTSHEET Assessing the Feasibility of Using Solar-Thermal Systems for Your Agricultural or Agri-Food Operation Solar-thermal systems collect the sun's energy and convert it into heat. This energy can
3-D Modeller Rendered Visualisations
Recognised energy Dynamic Simulation Modelling (DSM) software DesignBuilder is a user interface to the EnergyPlus DSM. EnergyPlus builds on the most popular features and capabilities of BLAST and DOE-2
2009 IECC Update. Scope. Content. International Energy Conservation Code
2009 IECC Update International Energy Conservation Code Scope The code applies to both residential and commercial buildings. In the code, the United States is divided into eight climate zones which are
INDIANA COMMERCAL ENERGY CODE BASELINE STUDY
INDIANA COMMERCAL ENERGY CODE BASELINE STUDY March 21, 2005 Report Prepared for Indiana Department of Commerce, Energy and Recycling Division One North Capitol Avenue, Suite 700 Indianapolis, IN 46204
RELEASE NOTES EG USA 3.0.0
RELEASE NOTES EG USA 3.0.0 Version 3.0 has a multitude of changes from version 2.8.05. One of the major changes is the ability to break up a home into Blocks with different HVAC systems. This includes
Heating Load Calculation
Heating Load Calculation ME 425 Air Conditioning System Design Keith E. Elder, P.E. Heating Load Calculation The heating load calculation begins with the determination of heat loss through a variety of
Current Programs available to Limited Income Customers. Residential and Multifamily
Current Programs available to Limited Income Customers Residential and Multifamily CAP Program- Residential and Multifamily The City of Austin offers programs to help customers facing temporary and long-term
Spitler, J.D., F.C. McQuiston, K. Lindsey. 1993. The CLTD/SCL/CLF Cooling Load Calculation Method, ASHRAE Transactions. 99(1): 183-192.
This paper has been downloaded from the Building and Environmental Thermal Systems Research Group at Oklahoma State University (www.hvac.okstate.edu) The correct citation for the paper is: Spitler, J.D.,
RULING OF THE MINISTER OF MUNICIPAL AFFAIRS AND HOUSING
BUILDING CODEACT, 1992 RULING OF THE MINISTER OF MUNICIPAL AFFAIRS AND HOUSING Pursuant to clause 29(l)(b) of the Building Code Act, 1992. as amended, the Director of the Building and Development Branch
Ventilation Standard For Health Care Facilities
The following article was published in ASHRAE Journal, October 2008. Copyright 2008 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes
SELECTIVE GLAZING FOR SUN CONTROL
SUN CONTROL GLAZING SELECTIVE GLAZING FOR SUN CONTROL Sun Factor 1st level performance for direct solar energy Solar energy control Solar control coating Only if the glass is exposed to sun rays! 2nd level
Opening the Bonnet. Prof Darren Woolf WYSINWYG 1
Opening the Bonnet Prof Darren Woolf WYSINWYG 1 WYSINWYG What You See Is NOT What You Get: Looking inside the Pandora s Box Prof Darren Woolf WYSINWYG 2 WYSIWYG implies a user interface that allows the
APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application
APPLICATION GUIDE Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application Section Comparison of Latent Cooling Performance of Introduction Most commercial HVAC systems
THE NATIONAL BUILDING REGULATIONS PART XA: ENERGY EFFICIENCY. Presentation by Peter Henshall-Howard: HEAD: BUILDING DEVELOPMENT MANAGEMENT.
THE NATIONAL BUILDING REGULATIONS PART XA: ENERGY EFFICIENCY. Presentation by Peter Henshall-Howard: HEAD: BUILDING DEVELOPMENT MANAGEMENT. A Diagrammatic representation of the relationship between the
Energy Savings with Window Retrofits
Center for Energy and Environment Energy Savings with Window Retrofits Presentation to Energy Design Conference & Expo Duluth, MN February 25, 2014 Agenda v Background v Introduction: What are window retrofits?
Energy Efficiency: Integrated Design and HVAC Systems HEALTHCARE - TOP 5 GREEN BUILDING STRATEGIES
EPA Publication 909-F-07-001 What? Energy use in healthcare facilities is higher than nearly all other building types. With rising energy costs and climate change concerns energy efficiency is financially
Housing Fact Sheets. Moisture Condensation at the Windows
Moisture Condensation at the Windows Housing Fact Sheets This fact sheet discusses the causes of and remedies for wintertime condensation problems that occur on windows, glass, and other glazing materials
Drury B. Crawley U.S. Department of Energy Washington, DC 20585 USA
TESTING AND VALIDATION OF A NEW BUILDING ENERGY SIMULATION PROGRAM Michael J. Witte, Robert H. Henninger, and Jason Glazer GARD Analytics, Inc. Park Ridge, IL 668 USA Drury B. Crawley U.S. Department of
Venice Library Humidity Study. for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205. Report April 13, 2015
for Williams Building Diagnostics, LLC 305 15 th Street West Bradenton, FL 34205 Report April 13, 2015 Moses & Associates, Inc. 2209 NW 40 th Terrace, Suite A Gainesville, FL 32605 FL License EB-0003097
Table 1: Prescriptive Envelope Requirements: Residential WOOD FRAME WALL R-VALUE MASS WALL R-VALUE CEILING R-VALUE
June 24, 2011 North Carolina Has a New Energy Conservation Code! By R. Christopher Mathis Executive Summary On Friday, June 24, 2011, Governor Beverly Perdue signed SB 708 into law and, with it, approved
Radiant Heating and Cooling Systems BY KWANG WOO KIM, ARCH.D., MEMBER ASHRAE; BJARNE W. OLESEN, PH.D., FELLOW ASHRAE
TECHNICAL FEATURE Fundamentals at Work This article was published in ASHRAE Journal, February 2015. Copyright 2015 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically
PROTOCOL FOR BUILDING ENERGY ANALYSIS SOFTWARE For Class 3, 5, 6, 7, 8 and 9 buildings
PROTOCOL FOR BUILDING ENERGY ANALYSIS SOFTWARE For Class 3, 5, 6, 7, 8 and 9 buildings Version 2006.1 AUSTRALIAN BUILDING CODES BOARD JANUARY 2006 TABLE OF CONTENTS Foreword 1. Scope 2. Purpose and context
APPENDIX C FORMS 2010 FLORIDA BUILDING CODE ENERGY CONSERVATION C.1
APPENDIX C FORMS 2010 FLORIDA BUILDING CODE ENERGY CONSERVATION C.1 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = The lower the Energy Performance Index, the more efficient
By Tom Brooke PE, CEM
Air conditioning applications can be broadly categorized as either standard or critical. The former, often called comfort cooling, traditionally just controlled to maintain a zone setpoint dry bulb temperature
Dienstleistung. Certification as "Quality Approved Passive House" Criteria for Residential-Use Passive Houses
Passiv Haus Institut Passivhaus Dienstleistung GmbH Dr. Wolfgang Feist Rheinstr. 44/46 Rheinstr. 44/46 D-64283 Darmstadt D-64283 Darmstadt www.passiv.de www.passivhaus-info.de Certification as "Quality
OREGON BEST COMMERCIALIZATION GRANT PROGRAM FINAL REPORT
OREGON BEST COMMERCIALIZATION GRANT PROGRAM FINAL REPORT Project: Development, Testing, and Pilot Scale Evaluation of a new Retrofit Window Insulation Product The Indow Window PI: David J. Sailor, Ph.D.
Certified Residential Energy Auditor (REA) Study Guide
Certified Residential Energy Auditor (REA) Study Guide This guide provides an overview of the Certified Residential Energy Auditor (REA) Program, including how to register for the REA Training Seminar
Building Energy Codes 101 October 23, 2013. Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance
Building Energy Codes 101 October 23, 2013 Matthew Giudice Building Policy Associate Midwest Energy Efficiency Alliance OVERVIEW 1. Introduction 2. Energy Code Development 3. Adoption Process 4. Elements
Application of Building Energy Simulation to Air-conditioning Design
Hui, S. C. M. and K. P. Cheung, 1998. Application of building energy simulation to air-conditioning design, In Proc. of the Mainland-Hong Kong HVAC Seminar '98, 23-25 March 1998, Beijing, pp. 12-20. (in
Selecting Energy Efficient Replacement Windows in Nevada
Selecting Energy Efficient Replacement Windows in Nevada www.efficientwindows.org January 06 STAR Zones. Meet the Energy Code & Look for the STAR Windows must comply with your local energy code. Windows
UNDERFLOOR AIR DISTRIBUTION
FINAL REPORT NCEMBT-080801 UNDERFLOOR AIR DISTRIBUTION AN EXPERIMENTAL COMPARISON OF AIR DIFFUSION PERFORMANCE BETWEEN UNDERFLOOR AIR DISTRIBUTION AND CONVENTIONAL OVERHEAD AIR DISTRIBUTION SYSTEMS AUGUST
WINDOW FILMS FOR ENERGY CONTROL Value in Weatherization Programs
WINDOW FILMS FOR ENERGY CONTROL Value in Weatherization Programs Darrell Smith, International Window Film Association Introduction to Window Films of Today Primarily a solar control retrofit product From
ELIMINATING AIR CONDITIONERS IN NEW SOUTHERN CALIFORNIA HOUSING
ELIMINATING AIR CONDITIONERS IN NEW SOUTHERN CALIFORNIA HOUSING Murray Milne, Research Professor Department of Architecture and Urban Design UCLA Los Angeles, CA 90095 [email protected] Tim Kohut, Project
HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY
HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY Benson Kwong, CVS, PE, CEM, LEED AP, CCE envergie consulting, LLC Biography Benson Kwong is an independent consultant providing
Energy Recovery Ventilation Equipment
AHRI Standard 1060 (I-P) 2013 Standard for Performance Rating of Airto-Air Exchangers for Energy Recovery Ventilation Equipment IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not
Strategy Guideline: Accurate Heating and Cooling Load Calculations
Strategy Guideline: Accurate Heating and Cooling Load Calculations Arlan Burdick IBACOS, Inc. June 2011 NOTICE This report was prepared as an account of work sponsored by an agency of the United States
Residential Windows, 3 rd edition Corrected index 1
Residential Windows, 3 rd edition Corrected index 1 A absorptance definition, 78 determinants of, 78 79 energy performance and, 78 tinted glass, 84 acoustical properties of windows, 60 61 acrylic glazing