High Altitude HVAC. Silvertip Integrated Engineering Consultants
|
|
|
- Baldwin Day
- 9 years ago
- Views:
Transcription
1 Presentation to: Rocky Mountain ASHRAE 2013 Tech Conference April 19, 2013 High Altitude HVAC Design Considerations by: Michael D. Haughey, PE, HBDP, CEM, LEED TM AP 2013 Silvertip Integrated Engineering Consultants 1 HIGH ALTITUDE HVAC DESIGN CONSIDERATIONS Goals Overview A Few Examples Thought Process Why (In the words of...) Understand, rather than... NOT Cookbook Substitute for engineering 2 Altitude Effects Baseball Home run distance Basketball Doug Moe Era Football Field goal distance Similarities??? Relation to air density Gravity??? Function of oxygen content Heat Rejection 3 1
2 Mitigating Factors Equipment counteracts using: Temperature Pressure Humidity Heat transfer Equipment design basis 4 Altitude Dependent System/ Equipment Examples Airflow calculations Fans, ductwork (sizing, pressure) Air-cooled equipment Condensers, chillers Motors, electrical and electronic equipment Combustion equipment Boilers, furnaces, generators, engines, gas absorption Pumps Evaporative coolers, Cooling towers Balancing, VAV box 5 Airflow Calculations (Sensible Only) cfm = (Btu / hr) / (C P * p * 60 * DT) Let C P * p * 60 = F CFM = CFM transfer factor cfm = (Btu / hr) / (F CFM * DT) 6 2
3 Airflow Calculations (Sensible Only) OR cfm * F CFM * DT = Btu / hr Look up F CFM in tables (handout, 1st page) THEN Check on Psych Chart 7 Reference page
4 10 Airflow Calculations (page 2) Example - sea level 10,000 Btuh, 20F DT cfm = (Btu / hr) / (F CFM * DT) cfm = 10,000 Btuh / (1.08 * 20) = Airflow Calculations (page 3) Example - 5,200 ft. elevation 10,000 Btuh, 20F DT cfm = (Btu / hr) / (F CFM * DT) cfm = 10,000 Btuh / (0.891 * 20) = 561 Note, for simplicity, many applications are close enough using 0.9 in lieu of o
5 Standard and Actual Air Standard air, SCFM, is at sea level and 70 F Actual air, ACFM, is at actual conditions To convert, correct for density change due to both altitude and temperature For altitude: SCFM = ACFM * (density ratio) Example, 5,200 ft. elevation (equiv. mass): 825 SCFM = 1,000 ACFM * Fan and Duct System Calculations (Example) Separate items using sea level data from items using altitude data (e.g. duct friction) Example (5,200 ft. elevation, 10,000 CFM) 14 Example (5,200 ft. elevation, 10,000 CFM) Sea level DP Alt. DP w.c. w.c. Cooling coil (computer sel.) 0.6 Heating coil (computer sel.) 0.2 Ductwork (ductilator) 1.5 Fittings (ASHRAE tables) 2.0 Other (diffuser, louvers, dampers) 1.5. Total
6 Example (5,200 ft. elevation, 10,000 CFM) (page 2) (example continued) Correct sea level items: 5.0 * = Total = = at alt. At sea level = 4.925/.825 = 6 Fan selection Use computer selection at altitude, OR 16 Example (5,200 ft. elevation, 10,000 CFM) (page 3) Select from sea level tables or graphs: RPM is the same at higher altitude (e.g RPM) CFM is the same at higher altitude (e.g. 10,000 CFM) Correct brake horsepower by density ratio, for example 10 HP from sea level chart becomes 10 * = 8.25 at 5,200 ft. altitude (More on pg. 7 of handout) 17 Reference page 7 Altitude Correction factors Temperature Correction factors 18 6
7 19 20 Fan and Duct System Calculations (page 3) The selection is thus 10,000 CFM, 1200 RPM, 4.9 s.p., AT 5200 FT. ALTITUDE Remember, derate the motor due to less motor cooling at higher altitude and add appropriate safety factors 21 7
8 Condensers, Air-cooled Chillers Packaged equipment: Lower air density = less heat rejection = higher temperatures = more heat rejection Therefore, counteracting forces. Net capacity reduction is typically less than air density ratio 22 Packaged equipment (page 2) Function of specific equipment design, refrigerant pressures, operating conditions, etc. Use manufacturer published corrections for altitude or call the manufacturer. Note in one Mfg s literature that correction factors for 5000 ft. elevation for air cooled condensers is 0.90 and for air cooled chillers is 0.97 for SPECIFIC series of equipment. 23 Air-cooled Chillers (page 1) Note Mfg A, Model B chiller data lists an 0.97 capacity correction factor for 6000 ft. altitude. Get the data for your specific application and selection if you need the accuracy. 24 8
9 Air-cooled Chillers (page 2) Mfg C, Model D literature lists capacity correction factors which combine fouling factor, chilled water DT, and altitude, and varies from to 0.96 for 6000 ft. altitude. The correction for the standard condition (sea level, 10F DT, fouling factor, is Reference Page 3 Altitude Correction factors
10 Reference Page Air-cooled Electric Motors Limited by allowable temperature Higher altitude = less air = less cooling = lower rated capacity Standard motors rated at 1,000 meters (3,300 ft.) altitude Again, manufacturer's design details are a factor. When critical, get data from the selected manufacturer
11 Reference page 39 Motor Rating limits Air-cooled Electric Motors (page 2) ANSI / NEMA Standard MG-1 Motors rated at 40C which are intended for use above 1000 meters should have the allowable temperature rise reduced in accordance with their formula Mfg E listed a correction factor for their Model F induction motor of 0.94 at altitudes from 5,001 ft. to 6,600 ft
12 Reference Page 36 Altitude Correction factors Combustion Equipment Gravity, packaged equipment, AGA: de-rate by 4% / 1,000 ft. (volume of combustion air flue gas increases about 4%/1,000 ft.) Typically de-rate when above 2,000 ft. elevation Often reduce gas orifice size to match gas input to altitude air One boiler manufacturer has a new (2012) condensing boiler with lower altitude derates
13 Combustion Equipment (page 2) Design Options Decrease gas manifold pressure Increase gas orifice pressure loss (smaller orifices) Increase airflow with power burner fan, forced draft fan, or induced draft fan 37 Combustion Equipment (page 3) Gas Heat Content Reduces according to the air density ratio Typically 1,000 BTU per Cu. Ft. at sea level, 830 BTU per Cu. Ft. at 5,000 ft. altitude, etc. Some utilities vary the heat content, therefore call the utility for the specific location. Some increase the heat content to achieve 1,000 BTU per Cu. Ft. at 5,000 ft. altitude. (see Boiler House Journal, near end of handout) 38 Combustion Equipment (page 4) Flue Design Available draft decreases substantially at higher altitudes Follow the manufacturer s procedures or ASHRAE procedures, which account for altitude barometric pressure 39 13
14 Pumps Three concerns: NPSH Cavitation Motor cooling / rating All are air density related Use the standard formulas with actual barometric pressure data NPSH: less barometric pressure on open systems, 6 ft. less at 5000 ft. altitude Cavitation: less barometric pressure on open systems 40 Reference Page 41 NPSH Formula
15 Reference page 47 NPSH Formula Evaporative Coolers Significant Parameters Mass Velocity Air Density Heat Transfer Coefficient, turbulence at boundary layer Water Vapor Pressure Density and heat transfer coefficient and vapor pressure effects are compensating Data hard to find, typically not derated for altitude Accurate selections typically not needed 45 15
16 Reference Page 73 Humidification Effectiveness Formula Cooling Towers Some controversy Don t derate but increase fan motor HP Don t derate Don t derate and reduce fan motor HP Add capacity at higher altitude 48 16
17 Cooling Towers For some (or most typical, higher WB) operating conditions, increased water partial pressure at higher altitudes may have a greater effect in increasing capacity than reduced density does in reducing capacity Cold air operation economizers: less capacity. 49 Cooling Towers Data hard to find, normally included in selection software Some info at CTI.org/tech_papers 50 Reference Page 74 One Method 51 17
18 52 Cooling Towers (page 2) Increased capacity factor due to increased enthalpy at higher altitudes is more pronounced at higher entering wetbulb temperature. Per one manufacturer s representative, 1/2% per 1000 ft. for 65F EWB and 1.25% per 1000 ft. for 78 F EWB. 53 Cooling Towers (page 3) What about much lower EWB, such as hydronic economizer applications??? Lower density overpowers the added capacity from increased vapor pressure at higher altitude 54 18
19 Summary Use Mfg data where available, BUT check it to be sure reasonable Consider density Heat transfer Motor cooling Vapor pressure Mass flow Be aware of counteracting factors Use altitude psych charts Be sure of the altitude for data Use absolute barometric pres. 55 The End 56 Questions? 57 19
20 Supplemental Handouts, LEED AP 58 20
21
22
23
24
25
26
27
28
29
30
31
32
Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks
Presentation Outline Common Terms / Concepts HVAC Building Blocks Plant Level Building Blocks Description / Application Data Green opportunities Selection Criteria Air Distribution Building Blocks same
HVAC Simplified Approach Option
HVAC Simplified Approach Option Part I Project Address: City: HVAC System Designer of Record: Date: Zip: Qualification The building is 2 stories or less in height and has a gross floor area is less than
HVAC Basic Science - System Capacity
HVAC Basic Science - System Capacity Btu/hour, btu/h, b/h, btuh. btu?? 1 MBH = 1000 btu/hour 1 KBH = 1000 btu/hour 1 ton of cooling= 12,000 btu/hour 1 watt = 3.414 btu/hour 1 kilowatt = 1000 watts = 3,414
Characteristics of Evaporators
Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of
HVAC Systems: Overview
HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct
Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida
Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes
CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
HOT & COLD. Basic Thermodynamics and Large Building Heating and Cooling
HOT & COLD Basic Thermodynamics and Large Building Heating and Cooling What is Thermodynamics? It s the study of energy conversion using heat and other forms of energy based on temperature, volume, and
Percent per Degree Rule of Thumb for Refrigeration Cycle Improvement
7 Percent per Degree Rule of Thumb for Refrigeration Cycle Improvement Steve Doty, PE, CEM [email protected] ABSTRACT A value of 1-1.5% power reduction per degree Fahrenheit (F) has been used successfully
COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers
COMMERCIAL HVAC EQUIPMENT Condensers and Cooling Towers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics.
Optimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
Fan Applications & System Guide
Fan Applications & System Guide Airflow for general ventilation can be calculated by; Area Method Air Change Method Occupancy Method Ventilation Calculation Methods Area Method Derives the ventilation
HVAC FORMULAS. TON OF REFRIGERATION - The amount of heat required to melt a ton (2000 lbs.) of ice at 32 F. 288,000 BTU/24 hr. 12,000 BTU/hr.
HVAC FORMULAS TON OF REFRIGERATION - The amount of heat required to melt a ton (2000 lbs.) of ice at 32 F 288,000 BTU/24 hr. 12,000 BTU/hr. APPROXIMATELY 2 inches in Hg. (mercury) = 1 psi WORK = Force
Total Heat Versus Sensible Heat Evaporator Selection Methods & Application
Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Scope The purpose of this paper is to provide specifying engineers, purchasers and users of evaporators in industrial refrigeration
The formula for finding CFM is: CFM = BTUH OUTPUT_ Temp Rise (ACF)* *Altitude correction factor below 1000ft = 1.08
Air Volume Requirement Air conditioning systems are engineered with a specific amount of indoor air passing across the surface of the evaporator coil. The amount of air is measured in cubic feet per minute.
The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.
MSV: Square Footage: 24,844 No. of Floors: 1 Year Built: 1963 Type of Use: Lounge and dining area open all night for snacks Steam Water-cooled condenser, 50-Ton York unit with a 6 cylinder-reciprocating
INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER
INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER The instructions that follow are to assist you in completing the information required when making a fan or blower selection. If you need additional
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
Principals of Condensing Boiler System Design
Principals of Condensing Boiler System Design Dennis Jones, P.E. Member ASHRAE ABSTRACT Condensing boilers can provide significant energy savings due to operating efficiencies as high as 98% as compared
Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
Presented By: WALTER E. JOHNSTON, PE CEM, CEA, CLEP, CDSM, CPE <[email protected]
Presented By: WALTER E. JOHNSTON, PE CEM, CEA, CLEP, CDSM, CPE
Commissioning - Construction Documents (Page 1 of 6)
Commissioning - Construction Documents (Page 1 of 6) A. General Information Climate Zone: Building Type: Conditioned Area (sf): Reviewer's Name: Reviewer's Agency: Note: Design Review for each system/subsystem
Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages
Objectives Increase awareness of the types of economizers currently used for data centers Provide designers/owners with an overview of the benefits and challenges associated with each type Outline some
Energy Efficiency in Industrial HVAC Systems
Energy Efficiency in Industrial HVAC Systems Heating, ventilation and air conditioning (HVAC) constitutes up to 35 percent of energy used in manufacturing facilities. This fact sheet is geared towards
KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM
KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM AIR HANDLING UNITS... 1 CHILLERS... 2 COOLING TOWERS... 2 CLOSED LOOP COOLERS... 2 MISCELLANEOUS SUPPLY FANS...
Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal
Technical Bulletin By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal SUMMARY Refrigeration air coolers (evaporators)
Building Energy Systems. - HVAC: Heating, Distribution -
* Some of the images used in these slides are taken from the internet for instructional purposes only Building Energy Systems - HVAC: Heating, Distribution - Bryan Eisenhower Associate Director Center
Fans and Air Handling Units. Will Rea and Paul Pilutti February 16 th, 2011
Fans and Air Handling Units Will Rea and Paul Pilutti February 16 th, 2011 HTS Lunch and Learns Available Online Visit www.htseng.com Engineering Tools Resource Center Contents Fans Fan Curves Fan Laws
Calculating System Flow Requirements
Calculating System Flow Requirements To select a pump, we need to know the flow rate (the amount of fluid to be pumped) and the system resistance or head. In the U.S., flow rates are given in gallons per
UNIVERSITY OF MISSOURI 23 0000 - Heating Ventilating and Air-Conditioning (HVAC) March 2015.01
GENERAL: This section provides general standards for overall sizing and design of Heating, Ventilating, and Air Conditioning (HVAC) systems. Other sections contain specific standards for each system per
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing
AND SIMPLE HVAC SYSTEMS
The City of New York Mayor Michael R. Bloomberg NYC Buildings Robert D. LiMandri, Commissioner BUILDING HVAC (1) REQUIREMENTS MANDATORY REQUIREMENTS AND SIMPLE HVAC SYSTEMS CHAPTER 5 COMMERCIAL ENERGY
How To Design A Building In New Delhi
ENERGY EFFICIENT HVAC DESIGN FOR COMPOSITE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce energy consumption
Chapter 3.4: HVAC & Refrigeration System
Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE
ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE Overview of Design Conditions: Air conditioning system consumes most of the energy that a building needs in its operation. In order to reduce
STULZ Water-Side Economizer Solutions
STULZ Water-Side Economizer Solutions with STULZ Dynamic Economizer Cooling Optimized Cap-Ex and Minimized Op-Ex STULZ Data Center Design Guide Authors: Jason Derrick PE, David Joy Date: June 11, 2014
THE PSYCHROMETRIC CHART AND ITS USE
Service Application Manual SAM Chapter 630-16 Section 3A THE PSYCHROMETRIC CHART AND ITS USE Psychrometry is an impressive word which is defined as the measurement of the moisture content of air. In broader
TECHNICAL MANUAL GDS8 & GHS8
TECHNICAL MANUAL AL GDS8 & GHS8 33-3/8" 80% Gas Furnace Units Refer to Service Manual RS6610004 for installation, operation, and troubleshooting information. All safety information must be followed as
SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP
research journal 2013 / VOL 05.01 www.perkinswill.com SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP ARCHITECTURE AND ENGINEERING OF SUSTAINABLE BUILDINGS Current Trends in Low-Energy HVAC Design
Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures
Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle
Wet Bulb Temperature and Its Impact on Building Performance
Wet Bulb Temperature and Its Impact on Building Performance By: Kurmit Rockwell, PE, CEM, LEED AP and Justin Lee, PE, LEED, AP BD+C Energy Solution Services, AtSite, Inc. 1 What is Wet Bulb Temperature?
Cooling Systems 2/18/2014. Cooling Water Systems. Jim Lukanich, CWT ChemCal, Inc. Grapevine, TX
Cooling Systems Jim Lukanich, CWT ChemCal, Inc. Grapevine, TX Cooling Water Systems Water is used for cooling because of its capacity to remove and store heat and availability. Cooling water is used in
How to Build a Data Centre Cooling Budget. Ian Cathcart
How to Build a Data Centre Cooling Budget Ian Cathcart Chatsworth Products Topics We ll Cover Availability objectives Space and Load planning Equipment and design options Using CFD to evaluate options
ACFM vs. SCFM vs. ICFM Series of Technical White Papers from Ohio Medical Corporation
ACFM vs. SCFM vs. ICFM Series of Technical White Papers from Ohio Medical Corporation Ohio Medical Corporation 1111 Lakeside Drive Gurnee, IL 60031 Phone: (800) 448-0770 Fax: (847) 855-6304 [email protected]
Heat Recovery In Retail Refrigeration
This article was published in ASHRAE Journal, February 2010. Copyright 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not
3/29/2012 INTRODUCTION HVAC BASICS
INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.
How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page.
Demystifying HVAC Test Your HVAC Knowledge By Ron Prager How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page. 1)
CHAPTER 4 LOAD CALCULATIONS 4.1 CONTEXT
CHAPTER 4 LOAD CALCULATIONS 4.1 CONTEXT The accurate calculation of heating and cooling loads is essential to provide a sound bridge between fundamental building design decisions and an operating building.
Strategy Guideline: HVAC Equipment Sizing
Strategy Guideline: HVAC Equipment Sizing Arlan Burdick IBACOS, Inc. February 2012 This report received minimal editorial review at NREL NOTICE This report was prepared as an account of work sponsored
Example Retrocommissioning Measure: Opening Throttled Discharge Valves
Opening Throttled Discharge Valves This 21-story building, constructed in 1997, is located in Oregon and contains 589,000 gross square feet of mostly office occupancy. The HVAC system includes six large
Duct Design. Presented by Dave Janquart
Duct Design Presented by Dave Janquart Overview of Topics Duct design Duct insulation SMACNA Standards Factors Influencing Duct Design Equipment Losses Air Velocity Duct Material Duct Size & Shape Length
Johnson Air-Rotation Systems
AR Series TM Johnson Air-Rotation Systems Solution TM D Series TM FF Series TM 80/20 PR Series TM Johnson Air-Rotation systems announces a major addition to its product line, completing its line of high
HVAC and REFRIGERATION
This is a preview. Some pages have been omitted. PE principles and practice prracticce of engineering mechanical: HVAC and REFRIGERATION sample questions + solutions Copyright 2011 by NCEES. All rights
Energy Efficiency. Energy Efficient Home Cooling:
Energy Efficiency Energy Efficient Home Cooling: Choosing an air conditioning system is an important decision. A poor choice may be costly to purchase and operate and yet fail to provide the desired cooling
Product Data Bulletin
Product Data Bulletin Adjustable Frequency Drives and HVAC Systems An Application Guide September, 1994 Raleigh, NC, U.S.A. INTRODUCTION All buildings pose the same problem: how to heat or cool the air
ENHANCED LABORATORY HVAC SYSTEM
ENHANCED LABORATORY HVAC SYSTEM INTRODUCTION Since the early 1980's the attention to more energy efficient laboratory designs has been on the rise due to the increase in energy cost and the emergence of
HVAC INDOOR MAKE-UP AIR HANDLERS
GIAC-7 HVAC INDOOR MAKE-UP AIR HANDLERS Application Manual PACKAGED INDOOR ARRANGEMENTS FOR MAKE-UP AIR, HEATING AND COOLING Contents 2 PAGE GENERAL INFORMATION 2, 3 MODEL NUMBER DESCRIPTION 4 INDOOR DUCT
Lower Energy Costs with Rooftop Air-Conditioning Package Units
Lower Energy Costs with Rooftop Air-Conditioning Package Units Sponsored by Mike West, PhD, PE Advantek Consulting, Inc Package Unit Efficiency Factors Sensible and latent performance ratings Unit efficiency
Effects of Ultra-High Turndown in Hydronic Boilers By Sean Lobdell and Brian Huibregtse January 2014
Effects of Ultra-High Turndown in Hydronic Boilers By Sean Lobdell and Brian Huibregtse January 2014 Today, hydronic boilers are producing greater efficiencies than previously thought possible, all due
1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%
1 1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53% 2. How much money do commercial facilities spend per square foot on energy costs
Advanced Heat Reclaim Systems. Harrison Horning, PE, CEM Delhaize America - Hannaford
Advanced Heat Reclaim Systems Harrison Horning, PE, CEM Delhaize America - Hannaford Outline Basic refrigeration cycle Conventional series heat reclaim Full-condensing parallel heat reclaim Direct Hydronic
In the compression-refrigeration loop (air conditioning), which is likely to be warmer? 1. Condenser coil 2. Evaporator coil
In the compression-refrigeration loop (air conditioning), which is likely to be warmer? 1. Condenser coil 2. Evaporator coil Answer: (1) Condenser coil See the video. A.R.E. Building Systems Study Guide
Innovent LASER Packaged Fresh Air Conditioning Units
LASER Latent And Sensible Energy Reduction Latent And Sensible Energy Reduction For Outside Air Innovent LASER Packaged Fresh Air Conditioning Units Innovent LASER units provide both sensible and latent
AABC Specifications for Testing and Balancing HVAC Systems
AABC Specifications for Testing and Balancing HVAC Systems The Associated Air Balance Council (AABC) Total System Balancing Specifications for HVAC Testing, Balancing and Performance Verification TOTAL
2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT
Presentation Synopsis Heating, Ventilating and Air Conditioning Building Condition Assessment Vancouver, B.C. Prepared for: EPIC Prepared by: Douglas Spratt, P.Eng Douglas Spratt & Associates Ltd. www.dspratt-associates.com
Data Center Heat Rejection
This article was published in ASHRAE Journal, March 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not be
Demand Based Static Pressure Reset Control for Laboratories
LLC Demand Based Static Pressure Reset Control for Laboratories Laboratories are generally the largest users of energy in any facility. Whether in a pharmaceutical research facility, a university or a
ULTRA-EFFICIENT HVAC DESIGN AND CONTROL
CASE STUDY ULTRA-EFFICIENT HVAC DESIGN AND CONTROL MAJOR HEATING, VENTILATING AND AIR- CONDITIONING REPLACEMENT AT THE COUNTY OF SAN DIEGO CRIME LAB December 30, 2005 8520 Tech Way, Suite 110 San Diego,
Data Centers WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1
WHAT S ONTHEHORIZON FOR NR HVAC IN TITLE 24 2013? SLIDE 1 Data Center CASE Scope Existing Title 24 2008 Scope Current scope ( 100 T24-2008) exempts process space from many of the requirements, however
Glossary of HVAC Terms
Glossary of HVAC Terms Heating, Ventilation and Air Conditioning (HVAC) is a major sub- discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other
Appendix C. Minimum Equipment Efficiency Standards
Appendix C Minimum Equipment Efficiency Standards Appendix C: Minimum Equipment Efficiency Standards This Appendix is an overview of building and equipment standards in the State of California that have
Balancing of a water and air system
Balancing of a water and air system Roger D. Holder MSME A well performed testing, adjusting and balancing (TAB) of a HVAC system is essential for the proper performance of that system and can enhance
Challenges and Failures in Green Building Design Using Under-Floor Air Distribution. Ken Urbanek, PE, HBDP, LEED AP Director of Engineering
Challenges and Failures in Green Building Design Using Under-Floor Air Distribution Ken Urbanek, PE, HBDP, LEED AP Director of Engineering Agenda UFAD Overview Challenges / Failures Steps for a Successful
Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. www.titus-hvac.com
Chilled Beam Solutions ADVANCING THE SCIENCE OF AIR DISTRIBUTION k-12 education Redefine your comfort zone. www.titus-hvac.com woodgrains dual-function energy solutions table of contents The CBAL-24 is
> Executive summary. Explanation of Cooling and Air Conditioning Terminology for IT Professionals. White Paper 11 Revision 2. Contents.
Explanation of Cooling and Air Conditioning Terminology for IT Professionals White Paper 11 Revision 2 by Tony Evans Click on a section to jump to it > Executive summary As power densities continue to
Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations
Stephen Lowe ASHRAE Hampton Roads Chapter Past President AECOM Design Mechanical Engineering Discipline Manager, Virginia Beach Division Professional Engineer Commonwealth of Virginia, NCEES BSME University
Preliminary Final Proposal
1 Butler Memorial Hospital New Inpatient Tower Senior Capstone Project Mechanical Option Preliminary Final Proposal Mechanical System Re-design and Breadth Topics Butler Memorial Hospital New Inpatient
THE HUMIDITY/MOISTURE HANDBOOK
THE HUMIDITY/MOISTURE HANDBOOK Table of Contents Introduction... 3 Relative Humidity... 3 Partial Pressure... 4 Saturation Pressure (Ps)... 5 Other Absolute Moisture Scales... 8 % Moisture by Volume (%M
HIGH PERFORMANCE CHILLED WATER SYSTEMS. EarthWise HVAC. EarthWise HVAC High Performance CHW Plants
HIGH PERFORMANCE CHILLED WATER SYSTEMS EarthWise HVAC Simon Ho e: [email protected] 2012 EarthWise HVAC High Performance CHW Plants Low Flow Low Temperature Systems Variable Flow Systems Variable CHW Variable
Enclosed Football Stadium Design History and Lessons Learned
Enclosed Football Stadium Design History and Lessons Learned Robert L. Towell, P.E., LEED AP, QCxP [email protected] CxE Group LLC St. Louis, Missouri 314-436-6543 With thanks to the St. Louis Convention
Evaporative Cooling for Residential and Light-Commercial
EMERGING TECHNOLOGIES This article was published in ASHRAE Journal, October 2011. Copyright 2011 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org.
for Plans Examiners and Building Inspectors
Building Technologies Program HVAC Controls Guide for Plans Examiners and Building Inspectors September 2011 Authors: Eric Makela, PNNL James Russell, PECI Sarah Fujita, PECI Cindy Strecker, PECI Prepared
HVAC Checklist - Long Form
HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,
Smart School Symposium Heating Ventilation and Air Conditioning Session HVAC Products. Richard Lord
Smart School Symposium Heating Ventilation and Air Conditioning Session HVAC Products Richard Lord Overview and Agenda My goal today is to give you quick an overview of the current status of HVAC products
M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace
TECHNICAL SPECIFICATIONS M7RL Series High Efficiency / Direct Vent Condensing Downflow Gas Furnace Induced Draft - 9%+ AFUE Input 4,000 thru 7,000 Btuh The high efficiency downflow gas furnace is especially
Defining Quality. Building Comfort. Precision. Air Conditioning
Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air
Makeup Air For Exhaust Systems In Tight Houses. Tony Jellen Engineering Projects
Makeup Air For Exhaust Systems In Tight Houses Tony Jellen Engineering Projects PA Housing & Land Development Conference February 23, 2012 Effects of Kitchen Ventilation on Residential Dwellings Anthony
High School Graduation years 2013, 2014, 2015. Unit/Standard Number
1 Secondary Task List 100 INTRODUCTION TO HVAC 101 Identify HVAC systems. 102 Describe career opportunities in the HVAC profession. 103 Demonstrate awareness of the occupational requirements. 104 Explain
2015 C&I HVAC RETROFIT APPLICATION FOR PRESCRIPTIVE REBATES
2015 C&I HVAC RETROFIT APPLICATION FOR PRESCRIPTIVE REBATES WELCOME TO THE POWER MOVES C&I HVAC RETROFIT PROGRAM. We look forward to working with you. If you have questions after reading this application,
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
Evaluate, Clean, and Tune Guidance
Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system
Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues
Design Guide Retrofitting Options For HVAC Systems In Live Performance Venues Heating, ventilation and air conditioning (HVAC) systems are major energy consumers in live performance venues. For this reason,
Below are detailed instructions for using the EMS load calculator.
Introduction The EMS load calculator is designed to make load calculating as painless as possible. For sizing the equipment, only the first three tabs (Steps 1, 2 & 3) need to be completed. This process
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
Modeling Guide for Daikin VRV in EnergyPro 6
Modeling Guide for Daikin VRV in EnergyPro 6 Table of Contents Introduction... 1 Program Installation... 2 Importing Designated VRV Product File... 3 System Modeling... 6 Modeling air-cooled outdoor units...
REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS
REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS Ken L. Hansen P.E. University of Nebraska Medical Center [email protected] 402-559- 5301 402-630-