1 Risk Guidance Note 03 Management of In-Rack Automatic Sprinklers (IRAS) Overview In-rack automatic sprinklers (IRAS) are often a fundamental part of the fire protection solution for racked storage areas. They are designed to quickly attack and control a fire at its source, thereby limiting damage through fire, water and smoke. IRAS will achieve this aim and provide minimal inconvenience to normal operations, provided they are correctly installed and managed. This Risk Guidance Note (RGN) provides guidance on the management controls needed for storage facilities in which IRAS are installed, with a view to minimising the risk of accidental damage and maximising the effectiveness of the protection. It includes a checklist which can be used as part of a loss prevention self-inspection programme. Whilst this RGN does discuss some common design or installation issues impacting on the above, it is not intended to be a comprehensive design or installation standard. These aspects are addressed in detail in recognised codes and standards for the design, installation and maintenance of automatic sprinkler installations. This RGN represents typical recognised good practice but it should be noted that there can be minor variances between recognised codes and standards. Mitsui Sumitomo Insurance Underwriting at Lloyd s Limited, 25 Fenchurch Avenue, London EC3M 5AD. Tel: Fax: Website: Mitsui Sumitomo Insurance Underwriting at Lloyd's Limited (Managing Agent for MIT Syndicate 3210 at Lloyd's), Mitsui Sumitomo Insurance (London) Limited and Mitsui Sumitomo Insurance Company Limited are all authorised and regulated by the Financial Services Authority

2 Sprinkler Facts Automatic sprinkler systems have been proven in use for well over 100 years. They are used more than any other fixed fire protection system and over 40 million sprinklers are fitted world-wide each year. In buildings fully protected by sprinklers: 67% of fires involved only 1 sprinkler operating 1 89% of fires involved up to 3 sprinklers operating 1 On average, fire control is achieved within 2 minutes 2 The fire service will apply up to 90% more water to achieve control 2 Accidental discharge of water from all causes is 1 in 500,000 (per year of service) 3 Accidental discharge of water due to manufacturing defects is 1 in 14,000,000 (per year of service) 4 Source: British Automatic Fire Sprinkler Association Ltd, citing 1 NFPA Presentation March, 2006 Lisbon, Portugal 2 Not specified: Extract from BAFA presentation Fire Safety in Warehouses Uses and Benefits of Sprinklers, July UK Loss Prevention Council (LPC) 4 FM (USA) and LPC (UK) statistics In MSI s experience, it remains a common misconception that when sprinklers activate, water is discharged from every sprinkler head. This is not the case and is, in fact, impossible. The only sprinkler head(s) that operate are those directly exposed to the heat from a fire (or which sustain physical damage such as impact). The only exception to this is deluge protection which is restricted to specialist applications and is beyond the scope of this RGN. Sprinkler Risk Management Considerations This RGN considers two types of risk scenarios: 1. Reduction in sprinkler effectiveness, resulting in an increase in fire, smoke and water damage in the event of a fire 2. Accidental damage to sprinklers from normal operations, resulting in water damage to stock The risk management controls needed to help prevent the above share much common ground and can be categorised as: Arrangement of racking and IRAS Management of storage Maintenance of racking and IRAS Incident response Management of change Self-inspection Each of the above is considered in detail in this RGN. 2

3 Arrangement of Racking and IRAS IRAS and/or racking beams should achieve the following: - The pipe work and sprinklers should be installed in a position that will prevent damage when pallets or goods are being loaded or unloaded into the racks. - A minimum clearance of 0.15m* should be maintained between the sprinkler head deflectors and the top of the storage in that level of racking. *0.10m for certain types of sprinkler head. If in doubt and 0.15m cannot be achieved, refer to a listed/approved sprinkler installer and/or MSI. Good practice (sprinkler pipes aligned with beams) Good practice (storage below sprinkler head) The conventional way to achieve both of the above is to align the sprinkler pipework behind the racking beams, as viewed from the face of the rack, with only the sprinkler heads protruding below the level of the beam (a minimum of 25mm). Note: If the top level of IRAS is located above the top tier of storage, then there may be no beams behind which to run the pipework. In this case, to prevent damage it need only be ensured that there is adequate vertical clearance between the sprinkler pipework and the top of the storage. These photographs show examples of good practice. Good practice (head position relative to beam) If the IRAS and/or racking beams are not arranged as described, the following detrimental effects will occur: - The sprinkler pipework and sprinkler heads will be exposed to impact damage from goods being loaded or unloaded into the racks. This increases the risk of subsequent water damage. - In the event of a fire, the water discharge from the sprinklers will be obstructed, impacting on the effectiveness of the protection. 3

4 Poor practice Poor practice These photographs show examples of poor practice. In each case, the IRAS sprinkler pipe runs across the back of the pallet storage locations in that tier, midway between rack beams. Poor practice (note bend in sprinkler pipe) Note: If alterations are proposed, it is essential that the storage/sprinkler configuration remains compliant with recognised sprinkler rules after alteration. This includes not exceeding the maximum vertical separation distance between levels of IRAS, or from the floor to the first level of IRAS. For this reason, a listed/approved sprinkler installer and/or MSI must be consulted prior to making any changes to the sprinkler protection or the location of racking beams. Any alterations to the sprinkler protection must be carried out by a listed/approved sprinkler installer. 4

5 Management of Storage Storage in racks should be managed to achieve the following: - The distance between goods stored in racking and placed back-to-back (i.e. the longitudinal "flue space") should be maintained at a minimum of 0.15m. If necessary, physical pallet stops should be fitted in order to maintain the minimum distance. - A minimum clearance of 0.15m* should be maintained between the sprinkler head deflectors and the top of the storage in that level of racking (repeating the requirement made under the preceding design section) *0.10m for certain types of sprinkler head. If in doubt and 0.15m cannot be achieved, refer to a listed/approved sprinkler installer and/or MSI. 0.15m Back-to-back separation of storage ( flue space ) 0.15m* Example of good practice Vertical separation between sprinkler and storage *0.10m for certain types of sprinkler head. The maintenance of longitudinal flue spaces is important in allowing the heat from a fire to rise and activate the sprinkler head(s) above, and subsequently in allowing the water to reach the seat of the fire and the surrounding combustibles. Maintaining the separation distances as described also has the general benefit of reducing exposure to impact damage and reducing obstructions to sprinkler water discharge, in common with the design issues in the preceding section. 5

6 Poor practice (blocked longitudinal flues) Awareness of good storage discipline for IRAS should be included in the training programme for lift truck drivers 6

7 Maintenance of Racking and IRAS Racking should be correctly installed and maintained in good condition. This is relevant to the management of IRAS due to the need to avoid stresses being placed on IRAS or, in a worst case, racking collapse. All piping should be supported from the storage racks or the building using approved hanging systems. Where in-rack sprinklers are installed in a position at risk of accidental mechanical damage, they should be fitted with a suitable metal guard. All components of the IRAS installation should be maintained in good condition. This includes, pipework, pipe hangers, sprinkler heads and sprinkler head guards. Damaged pipe hanger Poor racking condition Incident Response Every sprinkler protected facility should have an incident response plan that deals with accidental sprinkler operation or sprinkler leakage. However this is particularly important for sites where IRAS are installed because it is a practical reality that IRAS are often more exposed to accidental damage than roof or ceiling level sprinkler protection. In developing an incident response plan for accidental sprinkler operation or sprinkler leakage, the following should be considered: The identification of which sprinkler installation control valve(s) (ICV, also known as riser or alarm valve ) supply the IRAS. Normally, one or more ICV is dedicated to supplying the IRAS. This should be shown on a block plan supplied by the sprinkler installer and displayed adjacent to the ICVs. 7

8 The accessibility of the main stop ( isolation ) valve on the relevant ICV in the event of an incident, including the availability of keys for valve chambers or straps/chains which normally secure the isolation valves in the open position. The availability of persons on site who are familiar with the sprinkler installation and emergency isolation arrangements. Arrangements for incidents outside of normal operating hours. Actions to be taken by those normally tasked with responding to sprinkler or fire alarms. This might include on site security personnel, receptionists, control room operators or third party alarm receiving centres. Normal fire protection impairment management procedures (which would need to be invoked in this event). Arrangements for the prompt repair and restoration of the IRAS. The above is in addition to general site incident response plans covering fire and other events. This is beyond the scope of this RGN but is addressed in MSI RGN 14: Incident Response. Management of Change IRAS must be considered when any change is proposed to the goods in storage or to the racking. It must be ensured that any changes do not introduce non-conformities or poor practices. If there is a formal management of change procedure at the facility, this should already make specific reference to the need for all changes to (or impacting on) sprinkler protection to be properly reviewed and approved by interested parties. Common changes in storage occupancies which can impact on the effectiveness of IRAS in particular include the following: Changes to goods in storage, including their packaging materials Changes to the dimensions of pallet loads (especially height of load, and depth of pallets) The installation (or removal) of slatted or solid shelving Changes to racking configuration or layout, including alterations to beam heights The installation of new racking, or extension of existing There should be early notification and involvement of all interested parties to ensure advice can be costeffectively incorporated into proposals. Referral should not be restricted to projects exceeding the capital expenditure application threshold. This is because operational and/or low cost changes have the potential to impact significantly on the effectiveness of IRAS. A listed/approved sprinkler installer and/or MSI must be consulted prior to making any changes to the sprinkler protection or the location of racking beams. Any alterations to the sprinkler protection must be carried out by a listed/approved sprinkler installer. 8

9 Self-inspection Risk management considerations for IRAS should be incorporated into existing site self-inspection programmes. This might include housekeeping inspections, health & safety audits or racking inspections. Good self-inspection procedures will normally include the following:- Pre-printed checklists covering common property risk related issues Frequent inspections. An initial frequency of every two weeks is recommended, reducing to monthly once good practice becomes instilled in the workforce. Completed forms should be reviewed by senior management. There should be a mechanism for ensuring that all reported defects are rectified without delay. Records should be kept for review. A sample checklist is included as Appendix A. This can either be used as a stand-alone document for IRAS or elements of it can be incorporated into an existing checklist. Note: The checklist in Appendix A relates specifically to the management of IRAS for property (asset) protection purposes. It does not address other loss prevention management subjects such as general housekeeping and racking safety inspections and is not a substitute for the controls needed in these areas. For further assistance on this or any other risk management topic please contact your Account Manager at: Risk Engineering Mitsui Sumitomo Insurance Underwriting at Lloyd s Limited 25 Fenchurch Avenue London EC3M 5AD Telephone + 44 (0) Facsimile + 44 (0)

10 Appendix A Self-inspection Checklist for In-Rack Automatic Sprinklers (IRAS) Note: This checklist relates specifically to the management of IRAS for property (asset) protection purposes. It does not address other loss prevention management subjects such as general housekeeping and racking safety inspections and is not a substitute for the controls needed in these areas. Site Department Name Date Subject Satisfactory? Comments Yes No 1 Arrangement of racking and IRAS a. Sprinkler pipes aligned behind racking beams (unless above height of racked storage) b. Sprinkler heads protrude below the level of the beam (a minimum of 25mm). c. Sprinkler pipework and sprinkler heads are not exposed to impact damage from goods being loaded or unloaded into the racks. 2 Management of storage a. The distance between goods stored back-toback (i.e. the longitudinal "flue space") is a minimum of 0.15m. b. The distance between the sprinkler deflectors and the top of storage in that tier is a minimum of 0.15m 3 Maintenance of racking and IRAS a. Racking is in good condition, or defects already reported and awaiting repair b. Sprinkler pipework properly supported, with no missing or displaced hangers c. Metal guards fitted to vulnerable sprinkler heads d. Sprinkler pipework and sprinkler heads in good condition, with no apparent physical damage 4 Incident Response a. Incident response plans are complete and up to date. b. Personnel with incident response duties are present and aware of correct procedures 5 Management of Change a. Have there been any recent changes to stored goods, storage methods or to racking configuration and layout? b. Are any such changes planned? 10

Fighting Fire in Sprinklered Buildings. Student Guide

Fighting Fire in Sprinklered Buildings. Student Guide Fighting Fire in Sprinklered Buildings Student Guide Fighting Fire in Sprinklered Buildings Student Guide Table of Contents Purpose........................................................... 3 Instruction

More information

About us. Strength. Choice. Fairness. Our secure, risk-managed approach is designed to help you reduce losses and keep premiums down.

About us. Strength. Choice. Fairness. Our secure, risk-managed approach is designed to help you reduce losses and keep premiums down. About us About us Strength. Choice. Fairness. Our secure, risk-managed approach is designed to help you reduce losses and keep premiums down. Mitsui Sumitomo at Lloyd s Excellence in all we do Stability

More information

Insight. Storage Fires. Balanced Risk Engineering Solutions. Understanding the Risk. Commodity Classification. Storage Configuration

Insight. Storage Fires. Balanced Risk Engineering Solutions. Understanding the Risk. Commodity Classification. Storage Configuration Balanced Risk Engineering Solutions Storage Fires Understanding the Risk Many of the most costly fires occur in warehouses and storage areas, where often a high fire risk is combined with high values and/or

More information

Risk Management Guidelines

Risk Management Guidelines Impairment/Restoration of Fire Protection Systems Introduction The importance of ensuring the effectiveness and continuity of fire protection systems cannot be over-stressed. As such it is necessary to

More information

Risk Engineering. Working together to minimise exposures, reduce losses and keep your future premiums as low as possible.

Risk Engineering. Working together to minimise exposures, reduce losses and keep your future premiums as low as possible. Brochure headline Risk Engineering Working together to minimise exposures, reduce losses and keep your future premiums as low as possible. Mitsui Sumitomo at Lloyd s Excellence in all we do Strength through

More information

A Member of the Constructor Group STORAGE SOLUTIONS. Clever Thinking Inside the Box

A Member of the Constructor Group STORAGE SOLUTIONS. Clever Thinking Inside the Box A Member of the Constructor Group STORAGE SOLUTIONS Clever Thinking Inside the Box Dexion Storage Solutions Thinking Inside the Box Cutting Costs, Reducing Inventory, Saving Space and Saving Time 2 Increasing

More information

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT INTRODUCTION No matter how reliable fire protection equipment may seem, periodic maintenance is needed to ensure proper operation. Fire protection

More information

+Health. Accident. Mitsui Sumitomo. Caring for people, caring for business. Mitsui Sumitomo at Lloyd s Excellence in all we do.

+Health. Accident. Mitsui Sumitomo. Caring for people, caring for business. Mitsui Sumitomo at Lloyd s Excellence in all we do. Mitsui Sumitomo Accident+Health Mitsui Sumitomo Accident +Health Caring for people, caring for business Mitsui Sumitomo at Lloyd s Excellence in all we do Why choose Mitsui Sumitomo Insurance (UK)? If

More information

AON SPRINKLER CERTIFICATION

AON SPRINKLER CERTIFICATION Form 1 Application for Approval of Basic Design Parameters for Automatic Sprinkler System Installations 1. Name of Protected Premises Site Name Address 2. Work to be Carried Out New System Extension or

More information

A tradition of respect and fairness, with a fast and accurate service that makes life easier for you.

A tradition of respect and fairness, with a fast and accurate service that makes life easier for you. MSIG at Lloyd s Claims Charter Our Claims Charter A tradition of respect and fairness, with a fast and accurate service that makes life easier for you. MSIG at Lloyd s Excellence in all we do What makes

More information

Stored Palletized, Solid Piled, Bin Boxes, or Shelf Storage (12.2)

Stored Palletized, Solid Piled, Bin Boxes, or Shelf Storage (12.2) Stored Palletized, Solid Piled, Bin Boxes, or Shelf Storage (12.2) Formally part of NFPA 231 12.2.1 General 12.2.2 Protection of Class I - IV Commodities 12.2.3 Protection of Plastic & Rubber Commodities

More information

Fire. The Fire Installers Mate. A guide to fire alarm systems design

Fire. The Fire Installers Mate. A guide to fire alarm systems design Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects

More information

Warehouse Checklist. Warehouse Construction

Warehouse Checklist. Warehouse Construction PAGE 1 Warehouse Checklist Recent NFPA statistics estimate that in 1998 approximately 36,000 fires occurred in structures used for storage, accounting for $687mm of damage (over 10% of total fire damage

More information

Fire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

Fire Sprinkler System Maintenance and Testing Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Page 1 MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting

More information

Inspection and Testing Program Fire Protection Equipment

Inspection and Testing Program Fire Protection Equipment I. Introduction Inspection and Testing Program Fire Protection Equipment State of Minnesota Emergencies seldom give warning before they strike. Thus, it is essential that fire protection equipment be inspected,

More information

CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES

CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES Review the following information pertaining to Construction Fire Safety Planning: B.C. Building Code Sections 8.1 up to and including Subsection 8.2.3 B.C.

More information

Automatic Fire Sprinkler Submittal Requirements

Automatic Fire Sprinkler Submittal Requirements Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance

More information

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to

More information

General Fire Code Requirements Within Commercial Tenant Spaces

General Fire Code Requirements Within Commercial Tenant Spaces FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding

More information

Water Damage on Construction Sites. A guide to loss prevention

Water Damage on Construction Sites. A guide to loss prevention Water Damage on Construction Sites A guide to loss prevention Water damage is the second most frequent cause of loss during building projects and represents a large percentage of Construction All Risk

More information

For the Design, Installation, Commissioning & Maintenance of Fixed Gaseous Fire Suppression Systems

For the Design, Installation, Commissioning & Maintenance of Fixed Gaseous Fire Suppression Systems BAFE Scheme: SP203-3 Version 1: July 2008 Amendment No: 1 Fire Protection Industry Scheme, Reference SP203 Part 3 For the Design, Installation, Commissioning & Maintenance of Fixed Gaseous Fire Suppression

More information

LIFT MANAGEMENT. Version 01 / November 2015 Page 1 of 9 Approved by Health & Safety Committee

LIFT MANAGEMENT. Version 01 / November 2015 Page 1 of 9 Approved by Health & Safety Committee LIFT MANAGEMENT Version 01 / November 2015 Page 1 of 9 Approved by Health & Safety Committee This is a controlled document. It should not be altered in any way without the express permission of the author

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;

More information

NFPA 13 2002 FAQs. 3. Can plastic pipe be used on a sprinkler system complying with NFPA 13?

NFPA 13 2002 FAQs. 3. Can plastic pipe be used on a sprinkler system complying with NFPA 13? NFPA 13 2002 FAQs Responses to FAQs are prepared by NFPA technical staff to assist users in reading and understanding NFPA codes and standards. The responses, however, are not Formal Interpretations issued

More information

FIVE YEAR CERTIFICATION REPORT

FIVE YEAR CERTIFICATION REPORT GARDEN GROVE FIRE DEPARTMENT FIRE PREVENTION DIVISION FIVE YEAR CERTIFICATION REPORT Service and maintenance report of automatic fire extinguishing systems, including fire sprinklers, dry, deluge, and

More information

NUstudenthomes PROPERTY MANAGEMENT SERVICE A GUIDE FOR LANDLORDS

NUstudenthomes PROPERTY MANAGEMENT SERVICE A GUIDE FOR LANDLORDS NUstudenthomes PROPERTY MANAGEMENT SERVICE A GUIDE FOR LANDLORDS NUstudenthomes Student Services Newcastle University King s Gate Newcastle upon Tyne NE1 7RU Tel 0191 208 3333 WHAT IS THE NUstudenthomes

More information

FIRE LOSS STATISTICAL CONSIDERATIONS IN RELATING FAILURE AND BUILDING DAMAGE TO THE BUILDING CODE OBJECTIVES

FIRE LOSS STATISTICAL CONSIDERATIONS IN RELATING FAILURE AND BUILDING DAMAGE TO THE BUILDING CODE OBJECTIVES FIRE LOSS STATISTICAL CONSIDERATIONS IN RELATING FAILURE AND BUILDING DAMAGE TO THE BUILDING CODE OBJECTIVES P.L. Senez*, K.D. Calder, Hsing H (Isabella) Li Sereca Fire Consulting Ltd., Canada INTRODUCTION

More information

Claims Management. Claims Management. Putting fairness at the heart of claims handling. Mitsui Sumitomo at Lloyd s Excellence in all we do

Claims Management. Claims Management. Putting fairness at the heart of claims handling. Mitsui Sumitomo at Lloyd s Excellence in all we do Claims Management Claims Management Putting fairness at the heart of claims handling Mitsui Sumitomo at Lloyd s Excellence in all we do Responsive claims handling At Mitsui Sumitomo at Lloyd s, you will

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result

More information

A cure for water damage in real estate

A cure for water damage in real estate A cure for water damage in real estate Presented for BC Non-Profit Housing Association by Jeff Shearman, Zurich Services Corporation 2010 Zurich Canada Focused on our customer Reduce overall risk by reducing:

More information

PROPERTY INSURANCE: RISK QUALITY ASSESSMENT

PROPERTY INSURANCE: RISK QUALITY ASSESSMENT PROPERTY INSURANCE: RISK QUALITY ASSESSMENT Stuart Kenyon BEng (Hons) C.Eng C.Sci MIChemE Elciem Ltd What makes a company a good insurance risk, and how can the insured reduce their insurance premiums?

More information

RESIDENTIAL SPRINKLER INSTALLATION GUIDE

RESIDENTIAL SPRINKLER INSTALLATION GUIDE RESIDENTIAL SPRINKLER INSTALLATION GUIDE 4077 AIR PARK DRIVE STANDISH, MICHIGAN 48658 PHONE 989-846-4583 800-248-0278 FAX 989-846-9231 www.globesprinkler.com A-15 GLOBE RESIDENTIAL SPRINKLER GUIDE DESCR.,

More information

esfr pendent sprinkler vk510 (k25.2)

esfr pendent sprinkler vk510 (k25.2) January 17, 2014 Sprinkler 124a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition

More information

FLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes

FLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes FLAMMABLE AND COMBUSTIBLE LIQUIDS OSHA Changes Introduction This module covers the two primary hazards associated with flammable and combustible liquids: explosion and fire. In order to prevent these hazards,

More information

Risk Engineering Guideline

Risk Engineering Guideline www.hdi.global HDI Risk Consulting Risk Engineering Guideline Impairment of fire protection systems Basic protection systems should not be impaired without adequate replace compensation with provisions.

More information

Please use a separate sheet for each location Date Notes taken / / By. Name of Company: Tel No: Mobile: Contact at Company: E mail Fax:

Please use a separate sheet for each location Date Notes taken / / By. Name of Company: Tel No: Mobile: Contact at Company: E mail Fax: COMMERCIAL COMBINED FACT FIND M & N Insurance Service Ltd 248 Hendon Way London NW4 3NL Tel: 020 8202 4474 E Mail info@mninsure.com Fax: 020 8202 1943 Please use a separate sheet for each location Date

More information

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600 OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done

More information

Inspection, Testing and Maintenance

Inspection, Testing and Maintenance Page 18 ABOUT CODE CORNER CCFS would like to remind you to check with your local Authority Having Jurisdiction (AHJ) for questions and opinions concerning your local Fire and Building Codes. The information

More information

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the

More information

SPECIFICATIONS FOR APPROVED OFFSITE RECORDS STORAGE FACILITIES

SPECIFICATIONS FOR APPROVED OFFSITE RECORDS STORAGE FACILITIES 1. Bonding and Insurance 2. Facilities (including equipment and materiel e.g., shelving, pallets, containers and other internal fixtures and contents) The storage facility company must be bonded and insured.

More information

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for

More information

Installation Instructions

Installation Instructions Installation Instructions Pedestal Models FS 500 LE FS 800 LE Insert Models IS 500 LE IS 800 LE Pecan Engineering Pty Ltd 13 Acorn Road Dry Creek South Australia 5094 Email info@pecan-eng.com.au Phone:

More information

PROMG4 Install mining backup services

PROMG4 Install mining backup services Overview This standard is about: 1 interpreting information 2 adopting safe and healthy working practices 3 selecting materials, components and equipment 4 preparing, installing, using and removing below

More information

SAFETY SELF-INSPECTION PROGRAM

SAFETY SELF-INSPECTION PROGRAM Palm Beach State College Florida s First Public Community College SAFETY SELF-INSPECTION PROGRAM PALM BEACH STATE COLLEGE SAFETY SELF-INSPECTION PROGRAM 1. INTRODUCTION An important element of any employee

More information

COSVR404 Erect and dismantle plant (cranes and rigs)

COSVR404 Erect and dismantle plant (cranes and rigs) Overview This standard is about interpreting information, adopting safe, healthy and environmentally responsible work practices, selecting materials, components, plant, tools and ancillary equipment, preparing

More information

SITE CONTRACTOR PROCEDURES

SITE CONTRACTOR PROCEDURES SITE CONTRACTOR PROCEDURES Asset Collection Type B Assets are considered High risk ; the site activities must be in accordance with Graysonline contractor procedures and are to be collected by appointment

More information

NATURAL GAS EMERGENCY PROCEDURES AND ACCIDENT PREVENTION

NATURAL GAS EMERGENCY PROCEDURES AND ACCIDENT PREVENTION NATURAL GAS EMERGENCY PROCEDURES AND ACCIDENT PREVENTION Fire and Life-Safety Group (FLS) I. EMERGENCY PROCEDURES The emergency procedures for natural gas emergencies are similar to that for fire emergencies.

More information

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems

More information

Technical Article. Sprinkler Protection for High Bay and Automated Storage in Warehouse-Type Storage Facilities

Technical Article. Sprinkler Protection for High Bay and Automated Storage in Warehouse-Type Storage Facilities Technical Article for High Bay and Automated Storage in Warehouse-Type Storage Facilities Scott Martorano, CFPS Senior Manager Technical Services February, 2010 Worldwide Fire Protection www.vikinggroupinc.com

More information

F.Y.I. Specifying Fire Protection Systems Using Division 13

F.Y.I. Specifying Fire Protection Systems Using Division 13 F.Y.I. Specifying Fire Protection Systems Using Division 13 Automatic fire sprinkler systems and fire alarm and detection systems are increasingly installed in modern buildings. Even where building codes

More information

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT FIRE SAFETY INSPECTION REPORT SURAVEE GARMENTS LIMITED 2/C DARUS SALAM ROAD, MIRPUR OTHER FACTORIES: BABYLON CASUALWEAR LTD & ABONI FASHION March 29, 2014 Page 2 SUMMARY was surveyed for fire safety on

More information

Futures Insurance Certificate Summary - A Guide to Risk Management

Futures Insurance Certificate Summary - A Guide to Risk Management Property Owners Key Facts Property Owner s Insurance Guide and Certificate Summary Fusion-Deliberately Different Fusion has a deliberately different approach to Commercial Insurance. Rather than sell

More information

Firefighter Review. Instructor Guide

Firefighter Review. Instructor Guide Firefighter Review Instructor Guide Session Reference: 3 Topic: Attack Line Handling Level of Instruction: Time Required: Three Hours Materials: Two Fully Equipped Pumpers Structure for Use in Advancing

More information

Electrical Classification

Electrical Classification Electrical Classification Using NFPA 70 and NFPA 499 to Classify Hazardous Locations Electrical classifications are established in accordance with the National Electrical Code, NFPA 70, also referred to

More information

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011, Updated March 2012 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or

More information

Denver Fire Department Idle Pallet Storage Guidelines Per NFPA 13_Chpt 12

Denver Fire Department Idle Pallet Storage Guidelines Per NFPA 13_Chpt 12 Idle wood and plastic pallets introduce a severe fire condition. Stacking idle pallets in piles is the best arrangement of combustibles to promote rapid spread of fire, heat release, and complete combustion.

More information

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS January 1997 PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS 1.0 PERMIT 1.1 After receipt of a Building Permit from the City of San Jose Building Department, submit

More information

AMERICAN SOCIETY OF CERTIFIED ENGINEERING TECHNICIANS

AMERICAN SOCIETY OF CERTIFIED ENGINEERING TECHNICIANS GREEN TAG/RED TAG AMERICAN SOCIETY OF CERTIFIED ENGINEERING TECHNICIANS ORLANDO CHAPTER ORLANDO, FL February 7, 2013 2012 FLORIDA STATUTES 633.082 Inspection of fire control systems, fire hydrants, and

More information

1.0 General. Inspection, Testing, and Maintenance 1 of 8

1.0 General. Inspection, Testing, and Maintenance 1 of 8 1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus

More information

Guidance Note on the Avoidance of Water Damage on Construction Sites

Guidance Note on the Avoidance of Water Damage on Construction Sites Guidance Note on the Avoidance of Water Damage on Construction Sites Introduction Over recent years the incidence and magnitude of water damage claims in the construction industry, arising from internal

More information

Fire Alarm Log Book. Any activity regarding this system must be documented in writing.

Fire Alarm Log Book. Any activity regarding this system must be documented in writing. CASTLE ROCK FIRE AND RESCUE DEPARTMENT 300 Perry Street Castle Rock, Colo. 80104 303-660-1066 Do not remove from the premises: Fire Alarm Log Book Any activity regarding this system must be documented

More information

Standard the the Raising

Standard the the Raising Raising the Standard Introduction to BS 5839-1:2013 An Overview of the BS 5839 1:2013 for professionals who are responsible for the provision of fire detection and alarm systems for buildings Agenda Introduction

More information

Pollution CO CO 2. Carbonaceo us soot H 2 S, NOX, SO2

Pollution CO CO 2. Carbonaceo us soot H 2 S, NOX, SO2 Pollution CO CO 2 Carbonaceo us soot H 2 S, NOX, SO2 The National Building Code (NBC) contains set of minimum provisions, designed to protect the safety of the public with regard to structural sufficiency,

More information

SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST

SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST 1. Working plans shall be drawn to an indicated scale, on sheets of uniform size, with a plan of each floor, and shall show those items from the following

More information

LOSS CONTROL ALERT. Water Damage Prevention Sprinkler Contractors

LOSS CONTROL ALERT. Water Damage Prevention Sprinkler Contractors LOSS CONTROL ALERT Water Damage Prevention Sprinkler Contractors The Problem Claims for water damage arising from sprinkler system leakage are the largest source of general liability losses for Sprinkler

More information

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839 AVAILABLE TO DOWNLOAD ON THE APOLLO APP a guide to Fire Alarm Systems Design BS5839 Part1:2013 The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply! What

More information

focusfirst Construction factsheet Escape of water Things to consider

focusfirst Construction factsheet Escape of water Things to consider 07I08 focusfirst Construction factsheet Escape of water an awareness guide for construction companies The trend of losses in the construction industry has changed significantly in recent years with statistics

More information

Fire Alarm and Protection Impairment Policy and Procedures

Fire Alarm and Protection Impairment Policy and Procedures 1.0 Policy Statement The University of New Haven has developed a Fire Alarm and Protection Impairment Plan in accordance with the National Fire Protection Associations (NFPA) codes. Specific codes referenced

More information

Code Compliance Guideline: Swimming Pool Chemicals

Code Compliance Guideline: Swimming Pool Chemicals A publication of Fairfax County, Virginia CODE COMPLIANCE GUIDELINE SWIMMING POOL CHEMICALS AND FIRE SAFETY REQUIREMENTS RELATED TO POOL OPERATIONS This publication outlines the Fire Prevention Code requirements

More information

Recommendations to improve the safety of existing lifts

Recommendations to improve the safety of existing lifts Recommendations to improve the safety of existing lifts Lift & Escalator Industry Association Lift Safety an introduction Lifts are amongst the very few modes of transport available for continuous unsupervised

More information

Fire Safety Requirements for Child Care Centre

Fire Safety Requirements for Child Care Centre Fire Safety Requirements for Child Care Centre A. Restrictions on Location Child care centre shall not be located : - (a) (b) in any premises designed for residential use; in any industrial building, warehouses,

More information

EFSN Training i Module 1. 90 Minutes

EFSN Training i Module 1. 90 Minutes Introduction to Sprinklers EFSN Training i Module 1 90 Minutes Topics How sprinklers work Performance of sprinkler systems Types of Sprinkler Introduction to sprinkler systems Introduction ti to sprinkler

More information

SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective

SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective The National Fire Alarm Code, NFPA 72, sets the minimum requirements of performance, selection, use and location of automatic detection

More information

FIRE ALARM /FIRE PROTECTION OUTAGE/IMPAIRMENT RESPONSE GUIDELINE

FIRE ALARM /FIRE PROTECTION OUTAGE/IMPAIRMENT RESPONSE GUIDELINE Page 1 of 10 FIRE ALARM /FIRE PROTECTION OUTAGE/IMPAIRMENT RESPONSE GUIDELINE SYSTEM TESTING 1. Testing of the Fire Alarm and Fire Protection Systems 1.1. The Building Engineer, Electrician, Plumber (or

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;

More information

Ontario Association of Fire Chiefs Position Paper Residential Fire Sprinklers

Ontario Association of Fire Chiefs Position Paper Residential Fire Sprinklers Ontario Association of Fire Chiefs Position Paper Residential Fire Sprinklers The Ontario Association of Fire Chiefs (OAFC) supports changes to the Ontario Building Code to require that all new residential

More information

1.1. EMERGENCY PROCEDURE On discovering a fire or being informed of an emergency;

1.1. EMERGENCY PROCEDURE On discovering a fire or being informed of an emergency; Fire Action Plan FIRE ACTION PLAN SEStran aims to provide and maintain safe & healthy working conditions, equipment and systems of work for all our employees, and to provide such information, training

More information

Manual lifting and handling

Manual lifting and handling Manual lifting and handling When installing British Gypsum products and systems care should be taken to ensure that appropriate methods of handling and lifting are adopted. The following guidance details

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business

More information

The Checklist of a Fire Safety Inspection and How it is Managed

The Checklist of a Fire Safety Inspection and How it is Managed Electrical Maintenance How does this affect your company? Electricity is one of the most important tools in our everyday lives, both domestically and in the workplace. However, it is also one of the most

More information

Liberty Mutual Insurance RISK ENGINEERING PROCEDURE. REP 07 Incident Planning For external use

Liberty Mutual Insurance RISK ENGINEERING PROCEDURE. REP 07 Incident Planning For external use Liberty Mutual Insurance RISK ENGINEERING PROCEDURE REP 07 Incident Planning For external use Risk Engineering Procedure Incident Planning CONTENTS Page PURPOSE... 3 BACKGROUND... 4 INCIDENT PLANNING PREPARATION...

More information

Mission-critical fire protection HI-FOG for data centres

Mission-critical fire protection HI-FOG for data centres Mission-critical fire protection HI-FOG for data centres Modern fire protection for a data-driven world We make a strong case that HI-FOG is the best available fire protection for mission-critical data

More information

MEANS OF EXIT / ESCAPE / EGRESS SELF INSPECTION CHECKLIST

MEANS OF EXIT / ESCAPE / EGRESS SELF INSPECTION CHECKLIST OPTIONAL INFORMATION Name of School: Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: MEANS OF EXIT / ESCAPE / EGRESS Guidelines: This checklist covers some of the regulations

More information

Minibus Driving - Code of Practice

Minibus Driving - Code of Practice Minibus Driving - Code of Practice RESPONSIBILITY The Minibus It is the responsibility of Campus Service Supervisor/Fleet Manager to ensure that all minibuses used by the University are in a roadworthy

More information

Sprinkler Identification Number. Page 1 of 6 MARCH 2014 TFP288. Worldwide Contacts. www.tyco-fire.com

Sprinkler Identification Number. Page 1 of 6 MARCH 2014 TFP288. Worldwide Contacts. www.tyco-fire.com Worldwide Contacts www.tyco-fire.com Model EC-HS 80 K-factor, Quick Response Extended Coverage Horizontal Sidewall Sprinklers Installations per VdS CEA 400, Annex E, LH/OH General Description The Model

More information

A Risk Management Standard

A Risk Management Standard A Risk Management Standard Introduction This Risk Management Standard is the result of work by a team drawn from the major risk management organisations in the UK, including the Institute of Risk management

More information

Wyoming State Capitol Building Restoration and Modernization

Wyoming State Capitol Building Restoration and Modernization Wyoming State Capitol Building Restoration and Modernization Level I / II Life Safety and Fire Protection Assessment 25 September 2013 Presentation Overview Project Overview Applicable Codes Non-Conformance

More information

Data Center Due Diligence List

Data Center Due Diligence List Data Center Due Diligence List Name and address of site facility Date constructed Building owner/date purchased by current owner Name of previous owner Adjacent Property Descriptions North South East West

More information

Protection of unoccupied or void properties

Protection of unoccupied or void properties Real Estate Issue one Protection of unoccupied or void properties Introduction The current economic downturn has lead to a greatly increased number of vacant properties. In some countries rates of unoccupancy

More information

Adult Family Home (AFH) LOCAL BUILDING INSPECTION CHECKLIST Code References: 2012 IRC Section R325 (WAC 51-51) APPLICATION NUMBER:

Adult Family Home (AFH) LOCAL BUILDING INSPECTION CHECKLIST Code References: 2012 IRC Section R325 (WAC 51-51) APPLICATION NUMBER: Adult Family Home (AFH) LOCAL BUILDING INSPECTION CHECKLIST Code References: 2012 IRC Section R325 (WAC 51-51) APPLICATION NUMBER: SECTIONS 1, 2, 3, AND 4 MUST BE COMPLETED BY APPLICANT BEFORE INSPECTION

More information

Compliance Schedules and Building Warrant of Fitness

Compliance Schedules and Building Warrant of Fitness Compliance Schedules and Building Warrant of Fitness Purpose of this guidance information The purpose of this guidance information is to help building owners and managers of commercial, industrial or communal

More information

Conditions for ICT Partner Solutions Service Schedule for Phoenix Co-Lo Services

Conditions for ICT Partner Solutions Service Schedule for Phoenix Co-Lo Services Conditions for ICT Partner Solutions Service Schedule for 1. Definitions and Interpretation The following definitions shall apply to the provision of the Service, in addition to those in the General Terms

More information

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT

INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according

More information

OPTIONS. for. Replacing Boiler Plant. Sussex Lodge London W2 & 16 Stanhope Terrace London W2

OPTIONS. for. Replacing Boiler Plant. Sussex Lodge London W2 & 16 Stanhope Terrace London W2 OPTIONS for Replacing Boiler Plant Report to Tenants Sussex Lodge London W2 & 16 Stanhope Terrace London W2 BPME Consulting Engineers Tel: 01932 873 653 13 JULY 2003. Replacing Boiler Plant... 1 1. Existing

More information

History of the SPCC Rule

History of the SPCC Rule 2010 SPCC Training SPCC Rule History of the SPCC Rule The SPCC plan is a document required under the clean water act (CWA) It became effective in 1972 and has changed little in 32 years. The rule was formally

More information

In accordance with NFPA 30, these containers are not to store Class I flammable liquids.

In accordance with NFPA 30, these containers are not to store Class I flammable liquids. In accordance with NFPA 30, these containers are not to store Class I flammable liquids. Zurich recommends storing these containers in dedicated liquid storage rooms, detached buildings, or in listed dispensing

More information

Insurance management policy and guidelines. for general government sector, September 2007

Insurance management policy and guidelines. for general government sector, September 2007 Insurance management policy and guidelines for general government sector September 2007 i Contents 1. Introduction... 2 2. Identifying risk is the first step... 2 3. What is risk?... 2 4. Insurance is

More information

Asbestos Management Policy

Asbestos Management Policy Asbestos Management Policy Originator: Approval date: Policy and Strategy Team Sovini Board PCHA Board OVH Board/EMT 3 rd December 2012 22 nd November 2012 25 th September 2012 Review date: December 2013

More information