Denver Fire Department Idle Pallet Storage Guidelines Per NFPA 13_Chpt 12
|
|
|
- Arron Johnathan Cross
- 9 years ago
- Views:
Transcription
1 Idle wood and plastic pallets introduce a severe fire condition. Stacking idle pallets in piles is the best arrangement of combustibles to promote rapid spread of fire, heat release, and complete combustion. Improperly stored or improperly protected pallets add a significant fuel load to any occupancy and can lead to a catastrophic loss in the event of a fire. The extremely high heat release associated with a fire in a stack of pallets creates a high-velocity plume of fire gases. Sprinkler systems designed for ordinary hazards may be inadequate in combating pallet fires because the rising gases in the plume carry much of the sprinkler water away from the fire, and the high temperatures generated in the intensely burning array evaporate much of the water that does penetrate the plume. With little water reaching the seat of the fire to cool and extinguish the burning material, the fire continues to grow, releasing greater quantities of heat and causing more and more sprinklers to open, until eventually the sprinkler system is overpowered. In most industries, wood pallets are much more frequently encountered than plastic pallets. This familiarity combined with the perception that wood is generally less flammable than plastic, can potentially lead people to view plastic pallets as the real hazard and wood pallets as simply a low-value, somewhat innocuous, necessity for moving goods. While viewing plastic pallets as a high hazard is certainly accurate, the fire challenge posed by wood pallets should not be underestimated. Wood pallets often become dry and frayed during use allowing them to be easily ignited. Once ignited, the large amount of surface area and the open nature of their design create a near perfect geometry for a fast developing fire with very high heat release. A wood pallet fire can have heat release rates more consistent with a plastics or flammable liquids fire than a typical fire involving paper or wood.sk MANAT GIDE Liberty Mutual Property In the case of a plastic pallet, this near perfect fire geometry combined with the higher flammability and heat release of a plastic commodity creates an extremely challenging fire to control. Regardless of the material from which they are constructed, it is critical that we recognize the hazard idle pallets pose and properly arrange any areas where they are stored. If idle pallet storage is a necessity in your facility, it is essential that you address the storage location, arrangement and required sprinkler protection as described on the following pages if the pallets are to be stored safely. The storage of empty wood pallets should not be permitted in an unsprinklered warehouse containing other storage.
2 LOCATION Figure 1 shows the order of preference for storage of idle pallets is as follows: 2 A least 50 Feet away from the main.building. 20feet At At least least feet feet from the property from the property 4 6 Table A Recommended Clearance Between Outside Idle Wood Pallets Storage Recommended Clearance Between Outside Idle Wood Pallets Storage Wall Wall Construction Under 50 Pallets Minimum Pallet Distance from Exterior 50 to 200 Pallets Over 200 Pallets Wall Type Openings Feet Feet Feet Masonry None Masonry- Wire glass outside sprinklers with 1 hour doors Masonry- Wire or plain glass with outside sprinklers and ¾-hour doors Wood or metal with outside sprinklers Wood, metal, or other Outside Storage of wood pallets. Table A Although this is the safest way to store idle pallets, it is not without hazards. Large stacks of pallets can be a serious fire exposure to nearby buildings. Remember, a stack of burning pallets liberates a tremendous amount of heat. Ample separation is essential. A separation of 50 feet is usually adequate for wood pallets, but the more separation that can be provided the greater the margin of safety. Additional separation is needed if the building is constructed of combustible materials or there are openings in the wall in the location of the storage.
3 2. Detached Building. Another acceptable storage location is a detached, low-value building or trailer used exclusively for pallet storage and separated from all other buildings by at least 20 feet. 3. Attached Building. Another alternative is to store pallets in an attached building that shares a common wall with the main building. The common wall should be constructed of on combustible materials with no unprotected openings. 4. Cut-off Room. Pallets are sometimes stored in a cut-off room, located within the main building but having at least one outside wall. The cut-off room should be constructed of noncombustible materials and should be protected by automatic sprinklers as specified for wooden or plastic pallets. 5. Inside Room. If pallets must be kept in a storage room inside the main building, the room should be constructed of noncombustible materials and protected by automatic sprinklers as specified below for wooden or plastic pallet storage. 6. Open Storage Within Main Building. The least desirable location for idle pallets is in an open storage area within a main building. This storage method should be avoided. If this method cannot be avoided, it is essential that the pallets are arranged and protected as outlined in National Fire Protection Association (2010 NFPA) 13, Standard for the Installation of Sprinkler Systems, Section Protection of Idle Pallets. 7. Miscellaneous Combustible (Outside storage). Outside storage of combustible materials shall not be located within 10 feet (3048 mm) of a property line. Exceptions: 1. The separation distance is allowed to be reduced to 3 feet (914 mm) for storage not exceeding 6 feet (1829 mm) in height. OutsideINDOOR OF IDLE WOOD PALLETS GUIDELINES If you must provide inside storage of wooden pallets, follow the guidelines provided in NFPA 13, Standard for the Installation of Sprinkler Systems, Section Protection of Idle Pallets, specifically, sub-section Wood Pallets. Some of the recommendations and guidelines are summarized below. Protect steel columns to provide one hour fire resistance, or provide a side wall sprinkler located 15 feet above the floor and directed toward one side of the column. (This is not a requirement of NFPA 13, but is a sound loss prevention practice.) If a cut-off is provided, it should be constructed of noncombustible materials having a fire resistance of not less than two hours. All openings should be protected by at least 11/ 2 hour listed fire doors.
4 Sprinkler protection for idle wood pallets should meet the minimum requirements outlined in: Tables 1. - Control mode density/area sprinkler protection of Wood Pallets Tables 2. - CMSA sprinkler protection of Wood Pallets Tables 3. - ESFR sprinkler protection of Wood Pallets Tables 4- ESFR sprinkler protection of Plastic Pallets CONTROL MODE DENSITY/AREA SPRINKLER PROTECTION TABLE 1: TABLE (a) TYPE OF SPRINKLER LOCATION OF NOMINAL K-FACTOR CEILING/ROOF SPRINKLER DENSITY AREAS OF OPERATION HIGH TEMP LOW TEMP WATER SUPPLY DURATION (HOURS) Control Mode Density/Area On Floor On Floor On Floor or racks without solid shelves FEET FEET GPM/FEET FEET FEET 8 or larger Up to or larger Up to or larger 8 to to On Floor 16.8 or larger Up to /2 Control mode density/area sprinkler protection provided for the general occupancy shall be considered adequate and no additional protection shall be required for idle wood pallet storage that meets all of the following three conditions: 1. Pallets stored no higher than 6 feet and 2. Each pallet pile contains no more than four stacks (50 square feet) and 3. Each pallet pile is separated from other pallet piles by at least 8 feet of clear space or 25 feet of commodity.
5 CMSA SPRINKLER PROTECTION TABLE 2: TABLE (b) ARRANGEMENT COMMODITY CLASS FEET CEILING/ROOF FEET K-FACTOR /ORIENTATION TYPE OF SYSTEM NUMBER OF DESIGNED SPRINKLERS MINIMUM OPERATING PRESSURE WATER SUPPLY DURATION (HOURS) 11.2 UPRIGHT WET PSI 1 1/2 DRY PSI 2 ON FLOOR IDLE WOOD PALLETS UPRIGHT WET PSI DRY PSI 1 1/ / PENDENT WET PSI PENDENT PENDENT WET WET PSI 1 1/ PSI 1 1/2
6 ESFR SPRINKLER PROTECTION TABLE 3: TABLE (c) TYPE OF SPRINKLER (ORIENTATION) ESFR (PENDENT) ESFR (UPRIGHT) LOCATION OF ON FLOOR OR RACK WITHOUT SOLID SHELVES ON FLOOR NOMINAL K- FACTOR 14.O CEILING/ROOF MINIMUM OPERATING PRESSURE FEET FEET PSI WATER SUPPLY DURATION (HOURS) 1
7 INSIDE : PLASTIC PALLETS Inside storage of plastic pallets (other than those listed for having a demonstrated fire hazard equal to or less than idle wood pallets generally unreinforced polypropylene or high density polyethylene) is not recommended. However, if storage in an attached building, or cut-off room is necessary, follow the guidelines provided in NFPA 13, Standard for the Installation of Sprinkler Systems, Section Protection of Idle Pallets, specifically, sub-section Plastic Pallets. Some of the recommendations and guidelines are summarized below. ***Open storage within the main building should be avoided*** Indoor storage of plastic pallets shall be permitted to be protected in accordance with the following arrangement if you do not have EFSR sprinkler protection: (a) Maximum storage height of 10ft. (b) Maximum ceiling height of 30ft. (c) Sprinkler density 0.6 gpm/ft over 2000 ft. (d) Minimum sprinkler K-factor of Where stored in cutoff rooms, the following shall apply: a. Construct the storage location in an area that has at least one exterior wall. b. The interior walls should be constructed of noncombustible material having a fire resistance rating of at least three hours. c. Stack pallets on the floor, never on racks (unless protected by an ESFR as outlined in Table 4). d. Stack plastic pallets no higher than 12 feet. e. Ceiling height should not be greater than 30 feet. f. Design sprinkler protection to deliver a density of 0.60 gallons per minute per square foot over the entire area of the room. g. Protect steel columns to provide one-hour fire resistance, or provide a side wall sprinkler located 15 feet above the floor and directed toward one side of the column. Where stored without cutoff rooms, the following shall apply: Stack pallets no higher than four feet. Limit storage piles to a maximum of two stacks. Keep each pile separated by eight feet of clear space or 25 feet of stored commodity. Use only 286 F rated high- temperature rated sprinklers.
8 Idle Pallets Stored on Racks, on Shelves and Above Doors. NFPA 13_ Idle wood pallets shall be stored on racks or shelves, except where permitted in , and Idle wood pallets shall be permitted to be stored on the lowest level of storage only where no storage or shelves are located above the stored pallets and the applicable protection criteria referenced in are applied Where idle pallet storage is above a door, the idle pallet storage height shall be calculated from the base of storage above the door using the applicable protection criteria referenced in Section These are general guidelines based on the requirements of NFPA 13 chapter 12.12* and don t represent every protection configuration or storage option. Some plastic pallets have flammability more consistent with wood pallets and therefore have different protection requirements ww.igps.net/pallet_specs.php act Fact Sheet on igps Plastic Pallets- or PDF form-
Warehouse Checklist. Warehouse Construction
PAGE 1 Warehouse Checklist Recent NFPA statistics estimate that in 1998 approximately 36,000 fires occurred in structures used for storage, accounting for $687mm of damage (over 10% of total fire damage
NFPA 13 2002 FAQs. 3. Can plastic pipe be used on a sprinkler system complying with NFPA 13?
NFPA 13 2002 FAQs Responses to FAQs are prepared by NFPA technical staff to assist users in reading and understanding NFPA codes and standards. The responses, however, are not Formal Interpretations issued
Stored Palletized, Solid Piled, Bin Boxes, or Shelf Storage (12.2)
Stored Palletized, Solid Piled, Bin Boxes, or Shelf Storage (12.2) Formally part of NFPA 231 12.2.1 General 12.2.2 Protection of Class I - IV Commodities 12.2.3 Protection of Plastic & Rubber Commodities
Technical Article. Sprinkler Protection for High Bay and Automated Storage in Warehouse-Type Storage Facilities
Technical Article for High Bay and Automated Storage in Warehouse-Type Storage Facilities Scott Martorano, CFPS Senior Manager Technical Services February, 2010 Worldwide Fire Protection www.vikinggroupinc.com
FLAMMABLE AND COMBUSTIBLE LIQUIDS
GAP.8.1.0 A Publication of Global Asset Protection Services LLC FLAMMABLE AND COMBUSTIBLE LIQUIDS INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection
HealthandSafetyOntario.ca. Introduction. Storage Containers. Storing Flammable Liquids
Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario Fire Code, Part 4, and of the Regulations for
In accordance with NFPA 30, these containers are not to store Class I flammable liquids.
In accordance with NFPA 30, these containers are not to store Class I flammable liquids. Zurich recommends storing these containers in dedicated liquid storage rooms, detached buildings, or in listed dispensing
Flammable Liquids Storage
A Health and Safety Guideline for Your Workplace Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario
Flammable Liquids Storage
A Health and Safety Guideline for Your Workplace Flammable Liquids Storage Introduction This guideline is designed to help you store flammable liquids safely. It is based on the requirements of the Ontario
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
Extended Coverage Sprinklers
Extended Coverage Sprinklers Welcome ASPE Wally Barker Sprinkler Systems 101 MATERIALS OF CONSTRUCTION The components that make up a sprinkler head are: Frame or casting Deflector Fusible element or frangible
AON SPRINKLER CERTIFICATION
Form 1 Application for Approval of Basic Design Parameters for Automatic Sprinkler System Installations 1. Name of Protected Premises Site Name Address 2. Work to be Carried Out New System Extension or
Building Code Clarifications - 7. Fire Resistance
Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,
Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal
Ontario Fire Code SECTION 5.13 DIP TANKS Illustrated Commentary Office of the Ontario Fire Marshal Dip Tanks Illustrated Commentary 1 5.13.1. Location 5.13.1.1. Dip tank operations involving flammable
FireLock LP-46 Storage Sprinkler V4601 Pendent FM Approved, culus Listed See Submittal Publication 40.95
.61 FireLock Storage Design Guide This Firelock Storage Design Guide (the "Guide") illustrates the performance characteristics of the full offering of Victaulic Storage s based upon selected design criteria
Automatic Fire Sprinkler Submittal Requirements
Automatic Fire Sprinkler Submittal Requirements All commercial and industrial buildings with a total floor area of 5000 sq. ft. shall have an approved automatic sprinkler system installed. The Windsor-Severance
Flammable and Combustible Liquid
Flammable and Combustible Liquid Storage Challenges Christopher J. Wieczorek, Ph.D., FM Global David Nugent, The Valspar Corporation Global Research Update: High Challenge Storage Protection 27 June 2012,
Fire Protection Requirements of Empty Intermediate Bulk Containers (IBCs)
Research TECHNICAL REPORT Fire Protection Requirements of Empty Intermediate Bulk Containers (s) Fire Protection Requirements of Empty Intermediate Bulk Containers (s) by Seth E. Sienkiewicz FM Global
SECTION FC 2706 NON-PRODUCTION CHEMICAL LABORATORIES
New York City Administrative Code - Title 29 New York City Fire Code SECTION FC 2706 NON-PRODUCTION CHEMICAL LABORATORIES 2706.1 Scope. This section shall govern the storage, handling and use of laboratory
New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings
New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings Note: This information addresses complex issues in a summary fashion. Consideration should be given to the official version of the
Flammable Liquids 29 CFR 1910.106
Flammable Liquids 29 CFR 1910.106 OSHA s Directorate of Training and Education These materials were developed by OSHA s Directorate of Training and Education and are intended to assist employers, workers,
Section III Hazardous Materials Management
Section III Hazardous Materials Management This section of the Everyday Hazmat User s Training Guide covers various types of hazardous materials commonly found in the USDA Forest Service. Federal regulations
High Pressure Water Mist Systems: Alternative Solution For Critical Civil Applications
International Water Mist Conference, London, United Kingdom,23-24 September, 2009 High Pressure Water Mist Systems: Alternative Solution For Critical Civil Applications Fire Fighting In Civil Applications
FLAMMABLE AND COMBUSTIBLE LIQUIDS. n OSHA Changes
FLAMMABLE AND COMBUSTIBLE LIQUIDS OSHA Changes Introduction This module covers the two primary hazards associated with flammable and combustible liquids: explosion and fire. In order to prevent these hazards,
FIRE SPRINKLER SYSTEM DESIGN, ENGINEERING EXEMPTION POLICY FOR (Effective April 1, 2006)
State of Tennessee Department of Commerce and Insurance Board of Architectural and Engineering Examiners 500 James Robertson Parkway Nashville, TN 37243 1142 800 256 5758 615 741 3221 (Nashville Area)
HATFIELD TOWNSHIP. FLAMMABLE and COMBUSTIBLE LIQUIDS PERMIT APPLICATION PROCEDURES
HATFIELD TOWNSHIP FLAMMABLE and COMBUSTIBLE LIQUIDS PERMIT APPLICATION PROCEDURES A flammable and combustible liquids permit is required to store, transport on site, dispense, use or handle flammable and
esfr pendent sprinkler vk510 (k25.2)
January 17, 2014 Sprinkler 124a 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Pendent Sprinkler VK510 incorporates the capability to suppress specific high-challenge fires. The addition
Construction Warehouse. Culminating Experience in Fire Protection Engineering FPE 596 Prepared by Ben Johnson
Construction Warehouse Culminating Experience in Fire Protection Engineering FPE 596 Prepared by Ben Johnson Construction Warehouse Waste Treatment and Immobilization Plant (WTP) Project U.S. Department
c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.
Walmart Standards for Suppliers Section 7. Health and Safety 7. Health and Safety Suppliers must provide workers with a safe and healthy work environment. Suppliers must take proactive measures to prevent
FDNY C14 Certificate of Fitness Quiz
FDNY C14 Certificate of Fitness Quiz Name: Date: 1. Who issues a New York City laboratory permit? a) Department of Environmental Protection (DEP) b) Department of Environmental Conservation (DEC) c) Occupational
Insight. Storage Fires. Balanced Risk Engineering Solutions. Understanding the Risk. Commodity Classification. Storage Configuration
Balanced Risk Engineering Solutions Storage Fires Understanding the Risk Many of the most costly fires occur in warehouses and storage areas, where often a high fire risk is combined with high values and/or
Requirements for Hydrogen Storage and Use
Requirements for Hydrogen Storage and Use I. INTRODUCTION Fire and Life-Safety Group (FLS) The following is a summary of the fire and building code requirements for the storage and use of hydrogen. These
HOT WORK PERMIT PROGRAM TRAINING. John Braun
HOT WORK PERMIT PROGRAM TRAINING John Braun 1.0 INTRODUCTION 1.2 Purpose The Hot Work Permit Program has been developed for University employees that work on or around hot work activities. This program
General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission
General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission Local Fire Alarm 064. FIRE ALARM SYSTEMS 01. Scope 02. Definitions 03.
Working Towards Protection Guidance for Warehouse Storage Li-ion Batteries
Working Towards Protection Guidance for Warehouse Storage Li-ion Batteries Benjamin Ditch, FM Global Tom Long, Exponent Inc. SUPDET 2016, March 1 4, San Antonio TX Experimental Knowledge Timeline Reducedcommodity
CHAPTER 6 CONSTRUCTION TYPES
CHAPTER 6 CONSTRUCTION TYPES SECTION 601 GENERAL 601.1 Scope. Provisions of this chapter shall govern the classification of construction type by materials and fire resistance of its elements and the use
HIGH-PILED COMBUSTIBLE STORAGE
CHAPTER 23 HIGH-PILED COMBUSTIBLE STORAGE SECTION 2301 GENERAL 2301.1 Scope. High-piled combustible storage shall be in accordance with this chapter. In addition to the requirements of this chapter, the
HIGH-PILED COMBUSTIBLE STORAGE
CHAPTER 23 HIGH-PILED COMBUSTIBLE STORAGE SECTION FC 2301 GENERAL 2301.1 Scope. This chapter shall govern high-piled combustible storage, and the design, installation, operation and maintenance of any
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST
FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST Date of Inspection: Conducted by: Location: Reviewed by: Date of Review: Comments or additional corrective action taken as a result
Name Of Occupancy Date. Yes No Describe
FIRE PREVENTION INSPECTION CHECKLIST For Class A Occupancy (For Assembly Buildings, Bars, Restaurants, Gyms, Churches, Arenas, Theatres or wherever people gather) Name Of Occupancy Date Physical Address
Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM STORY HEIGHT
Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE Sec. 58.1. Division D-O occupancies. 58.2. Separation and mixed occupancy. OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM
Clark County Fire Prevention
Clark County Fire Prevention Mission Statement: To provide the highest level of fire protection and related services TITLE: REQUIREMENTS FOR A NEW SPRINKLER SYSTEM IN ACCORDANCE WITH THE 2002 EDITION OF
A Code Review for Emergency Generators and Indoor Use of Portable Generators
A Code Review for Emergency Generators and Indoor Use of Portable Generators By: the Fire and Life-Safety Group (FLS) Fire Code requires that emergency generators be stationary generators. Therefore, a
Queen's University Environmental Health and Safety
April, 2009 1 SOP-Chem-08 1.0 Introduction This document is intended as a guide to the Queen s University requirements for handling and storing flammable and combustible material in non-laboratories areas.
LIFE SAFETY UPDATE. FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc.
LIFE SAFETY UPDATE FULL SPRINKLERING OF ALL NURSING FACILITIES ADDITIONAL CLARIFICATIONS Prepared by Eric Rosenbaum, P.E. Hughes Associates, Inc. The purpose of this update is as follows: Remind all state
Code Compliance Guideline: Swimming Pool Chemicals
A publication of Fairfax County, Virginia CODE COMPLIANCE GUIDELINE SWIMMING POOL CHEMICALS AND FIRE SAFETY REQUIREMENTS RELATED TO POOL OPERATIONS This publication outlines the Fire Prevention Code requirements
OCFRD TENT STANDARD 6000. This Standard operates under the authority of Orange County, Florida Ordinance and State Statutes.
1. Authority Orange County Fire Rescue Department Tents & Membrane Structures Office of The Fire Marshall - 109 E. Church Street, Lower Level - Orlando, Florida 32801-3319 Phone: 407-836-0004 Fax: 407-836-8310
Safe Operating Procedure
Safe Operating Procedure (Revised 07/09) HOT WORK PERMIT OPERATIONS (For assistance, please contact EHS at (402) 472-4925, or visit our web site at http://ehs.unl.edu/) Authority In recognition of the
I.CHEM.E. SYMPOSIUM SERIES NO. 97
FIRE HAZARDS OF FLAMMABLE LIQUIDS IN SMALL CONTAINERS J. F. Siddle* Standards of fire protection for metal drums and smaller metal containers of flammable liquids have been well defined and have proved
PLAN REVIEW GUIDE FOR FIRE ALARM
PLAN REVIEW GUIDE FOR FIRE ALARM PROJECT NAME: PERMIT # PROJECT ADDRESS: CONTACT PERSON: PHONE Fire alarm system installation information shall be provided on the appropriate architectural and electrical
Dennis Fire Department Fire Prevention Mark Dellner Fire Chief
Dennis Fire Department Fire Prevention Mark Dellner Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES (MA Fire Prevention Regulations 527 CMR, MGL Chapter 148) FIRE PREVENTION CHECKLIST-
Spray Booth Guideline
Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that
Pressure Vessels (Air Compressors) and LPG Tanks
Pressure Vessels (Air Compressors) and LPG Tanks 1. Identification of Workplace Hazard Any container, tank or vessel that contains pressurized material is a potential hazard to employees due to the force
Excerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013
Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems April 2013 The National Multi Housing Council and the National Apartment Association (NMHC/NAA) have
Formal Interpretation NFPA 30. Flammable and Combustible Liquids Code. 2012 Edition
Reference: 1.1, Scope F.I. 84-4 Background: Tank trailers and semi-trailers are loaded with flammable or combustible liquid and moved to a storage yard. There, the tank vehicles may be kept for days, weeks,
Approval Standard for Plastic Suspended Ceiling Panels
Approval Standard for Plastic Suspended Ceiling Panels Class Number 4651 February 1978 2002 FM Approvals LLC. All rights reserved. Foreword The FM Approvals certification mark is intended to verify that
LogisticsCentre IV Distribution Center
KCI Intermodal BusinessCentre LogisticsCentre IV LogisticsCentre IV Distribution Center Modern Warehouse/Distribution Space Ranging From 108,000± SF to 432,000± SF 10221 NW Transcon Drive 112th Street
HOT WORK PERMIT PROCEDURES
COLUMBIA UNIVERSITY ENVIRONMENTAL HEALTH & SAFETY HOT WORK PERMIT PROCEDURES COLUMBIA UNIVERSITY MEDICAL CENTER February 2010 1 TABLE OF CONTENTS A. PURPOSE 3 B. SCOPE 3 C. POLICIES AND PROCEDURES 3-4
2007 Edition HAZARD CLASSIFICATION FOR NFPA 13 SPRINKLER DESIGN NFPA 13 HAZARD CLASSIFICATION. Why does it matter? Chapter 11-21
HAZARD CLASSIFICATION FOR NFPA 13 SPRINKLER DESIGN Division of Fire Safety Why does it matter? Chapter 11-21 Sprinkler Demand Hose Demand Duration MFA Course #644 - May 2010 Current NFPA 13? Why does it
ATTACHMENT 12 CONTAINERS
ATTACHMENT 12 CONTAINERS Attachment 12 - Page 1 Table of Contents Table of Contents List of Tables List of Acronyms 12.1 Applicability 12.2 Description of 12.3 Reserved 12.4 Reserved 12.5 Description of
ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600
OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done
General Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
Certification: Building Plans Examiner. Exam ID: B3
Certification: Building Plans Examiner Exam ID: B3 Scope: A Building Plans Examiner will be responsible for reviewing submitted plans to determine if they meet the requirements of the various Building
BP WIND ENERGY POLICIES AND PROCEDURES
BP WIND ENERGY POLICIES AND PROCEDURES Document Control Details 1.0 Purpose/Scope 1.1 This procedure provides the minimum requirements to be followed for the storage of flammable or combustible materials
Static Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity?
A Health and Safety Guideline for Your Workplace What is static electricity? What causes it? How is it hazardous? And, most importantly, how can it be controlled? All of these questions will be answered
Town of Bellingham Fire Department
Town of Bellingham Fire Department OFFICE OF THE Fire Prevention Division Captain Robidoux- [email protected] Lieutenant Bangma- [email protected] Fire Safety Inspection Guidelines for
SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved;
Automatic Fire Sprinkler System Checklist
Fire Prevention rd Location: 701 E. 3 Avenue Mail to: P.O. Box 1579 Moses Lake, WA 98837 (509) 765-2204 www.ci.moses-lake.wa.us Automatic Fire Sprinkler System Checklist Please print in Black or Blue ink
1.0 Purpose... 4. 2.0 Definitions...4. 3.0 Hot Work Operations. 5
HOT WORK PROGRAM Introduction The University of Kentucky recognizes a potential for fire from hot work operations. For that reason this program should be implemented in all departments at the University
OREGON FIRE CODE Interpretations and Technical Advisories
OREGON FIRE CODE Interpretations and Technical Advisories A collaborative service by local and state fire professionals, along with our stakeholders and customers, to provide consistent and concise application
Notes. Material 1. Appropriate Flammable Liquids
29 CFR 1910.106 Flammable Materials Flammable Liquids Preparation 1. Read Applicable Background information and related Company Policy Chapter. 2. Make Copies of this Lesson Plan for Personnel 3. Make
ESFR DRY PENDENT SPRINKLER VK502 (K14.0) TECHNICAL DATA
December 19, 2013 Sprinkler 122j 1. DESCRIPTION Viking Early Suppression Fast Response (ESFR) Dry Pendent Sprinkler VK502 is a fast response fusible element type sprinkler designed for use in storage areas
Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description
Worldwide Contacts www.tyco-fire.com Model WS Specific Application Window Sprinklers Horizontal and Pendent Vertical Sidewall 5.6 K-factor General Description The TYCO Model WS Specific Application Window
Errata NFPA 1. Fire Code. 2015 Edition
Errata NFPA 1 Fire Code 2015 Edition Reference: 2.2, Table 6.1.14.4.1(a) and (b), 13.3.1.6, 13.7.2.13.2.1, 14.11.3.3, 18.5.2, 18.5.3, 20.1.2, 20.1.5.12, 25.1.1, 25.3, 25.4, A.3.3.164.2, and A.13.3.2.9.1
MAJOR 2015 MN RESIDENTIAL CODE CHANGES Effective Date: January 24 th, 2015
MAJOR 2015 MN RESIDENTIAL CODE CHANGES Effective Date: January 24 th, 2015 **Disclaimer: This document is to serve as informational purposes only. This is not a code book or a final interpretation of the
Data Center Due Diligence List
Data Center Due Diligence List Name and address of site facility Date constructed Building owner/date purchased by current owner Name of previous owner Adjacent Property Descriptions North South East West
Antifreeze Solutions in Residential Fire Sprinkler Systems
Antifreeze Solutions in Residential Fire Sprinkler Systems The 2013 edition of NFPA 13D, as amended by TIA 13 1, discourages the use of antifreeze solutions within residential fire sprinkler systems unless
EACH CLASS of fire A, B, C, or D has a different source. Some
Classes of Fires and Types of Extinguishers EACH CLASS of fire A, B, C, or D has a different source. Some principles apply to putting out all fires. However, certain procedures and products are used only
GUIDE FOR DETERMINATION OF NEEDED FIRE FLOW
GUIDE FOR DETERMINATION OF NEEDED FIRE FLOW 545 Washington Boulevard Jersey City, New Jersey 07310-1686 (800) 888-4ISO (4476) www.iso.com www.isomitigation.com EDITION 05-2008 COPYRIGHT ISO PROPERTIES,
Fire testing for BCA compliance
Fire testing for BCA compliance SFS NSW Chapter December 2010 Vince Dowling Fire Science and Technology Australia Standards and Specifications Type Purpose Examples Test method How to do the test and what
Model SW-20 and SW-24 11.2 K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) General Description
Worldwide Contacts www.tyco-fire.com Model SW-20 and SW-24 11.2 K-factor Extended Ordinary Hazard Horizontal Sidewall s (Standard ) General Description 11.2 K-factor, Extended Ordinary s, Standard are
Building Codes Update: The 2009 International Fire Code and the Apartment Industry
! Building Codes Update: The 2009 International Fire Code and the Apartment Industry Apartment operators and developers should be aware of organizational changes in the 2009 edition of the International
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011
FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the
ADMINISTRATIVE SERVICES MANUAL
Purpose Responsibilities Proper Storage and use of flammable liquids can significantly reduce the possibility of accidental fires and injuries. To minimize risk to life and properly, the requirements of
Installation Instructions
Installation Instructions Pedestal Models FS 500 LE FS 800 LE Insert Models IS 500 LE IS 800 LE Pecan Engineering Pty Ltd 13 Acorn Road Dry Creek South Australia 5094 Email [email protected] Phone:
527 CMR: BOARD OF FIRE PREVENTION REGULATIONS 527 CMR 14.00: FLAMMABLE AND COMBUSTIBLE LIQUIDS, FLAMMABLE SOLIDS OR FLAMMABLE GASES
527 CMR 14.00: FLAMMABLE AND COMBUSTIBLE LIQUIDS, FLAMMABLE SOLIDS OR FLAMMABLE GASES Section 14.01: Scope 14.02: Definitions 14.03: Storage 14.04: Handling of Flammable Fluids 14.05: Handling of Flammable
Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description IMPORTANT Always refer
St. John s University
St. John s University Fire Safety Plan Founder s Village Townhouses Page 1 St. John s University Fire Safety Plan Part 1-Building Information Section Founder s Village Townhouses 8000 Utopia Parkway Jamaica
Fire Security Systems
Fire Security Systems Fire Security Systems [email protected] www.fire-security.net P: 1 604 941 1001 F: 1 604 648 9311 Who is Fire Security Systems For 25 years, Fire Security has been involved in
RESIDENTIAL COURSE OF CONSTRUCTION QUESTIONNAIRE
RESIDENTIAL COURSE OF CONSTRUCTION QUESTIONNAIRE Residential Course of Construction policies, also known as Builder s Risk, are designed to cover the property owner for potential loss while the property
CANTON FIRE DEPARTMENT
CANTON FIRE DEPARTMENT Dean Floyd Fire Chief FIRE SAFETY INSPECTION GUIDELINES FOR COMMERCIAL PROPERTIES FIRE PREVENTION CHECKLIST- To review prior to your inspection. 1. Is the address of your property
BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS
DCD-0304 Identification # Rev. 9/08 County Date of Inspection NAME OF OPERATION BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS ADDRESS TELEPHONE: CITY STATE ZIP BUILDING INSPECTORS CERTIFICATE
Composite Panel Firewall Systems
Composite Panel Firewall Systems part of the Protecting more than your business Insulated mineral fibre panels have excellent thermal and acoustic properties, ideal for factory and office partition walls.
Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application
February 2014 Code Requirements and Inspections in Educational Occupancies Presented By: Barry W. Rickert Douglas M. Schanne Fire Marshal Training Program Supervisor Office of Education & Data Management