FIRE ALARM /FIRE PROTECTION OUTAGE/IMPAIRMENT RESPONSE GUIDELINE
|
|
|
- Blaze Mills
- 10 years ago
- Views:
Transcription
1 Page 1 of 10 FIRE ALARM /FIRE PROTECTION OUTAGE/IMPAIRMENT RESPONSE GUIDELINE SYSTEM TESTING 1. Testing of the Fire Alarm and Fire Protection Systems 1.1. The Building Engineer, Electrician, Plumber (or equivalent) shall perform a test of the fire alarm and/or fire protection systems in accordance with City Codes, NFPA and FM Global (University s Property Insurance Carrier) Standards The Building Engineer, Electrician (or equivalent) shall call Pitt Police ( ) and Guardian ( ) to inform them of the testing. Guardian should be provided the following information: caller s name, University of Pittsburgh, building name, time and the associated Password for the building. The hold should be requested only for the time needed to test the alarms At least 30 minutes prior to the testing, all building entrance doors should be posted by the Building Engineer with a sign stating the following: Fire alarm test today. If smoke or fire is noted, call immediately. (See Attachment No. 1) 1.4. After the signs are posted, an announcement by the Building Engineer should be made (in buildings equipped to do so) stating Testing of the fire alarm system is being performed. If smoke or fire is noted, call immediately Immediately after testing is completed, notify Pitt Police and Guardian that the system should be taken off hold. NOTE: Although the alarms will be placed back in service by Guardian at midnight, Guardian should be promptly notified when the testing is complete. Confirmation that the alarm signals were received by Guardian and that the system has been restored should be obtained An announcement should be made by the Building Engineer in buildings so equipped [ testing of the fire alarm system is now complete (repeat) ] and the posted signs removed The testing should be documented with records maintained on file for review.
2 Page 2 of If a problem is detected during the testing, the Building Engineer, Electrician (or equivalent) should attempt to reset the device/panel. If the problem is not cleared or if it involves any system or component of the buildings fire protection systems, an Emergency Outage/Impairment will exist. Procedures for notifying appropriate department (Facilities Management, Housing or Property Management) personnel should be followed along with informing EH&S in accordance with the guidelines specified in Sections 3.0 and/or 6.0 below. FIRE ALARM SYSTEM IMPAIRMENT PROCEDURES 2. Scheduled Outage/Impairment 2.1. The University s procedures for Scheduled Outage/Impairment notification should be followed Upon receipt of the outage/impairment notification , EH&S will notify FM Global and the City Bureau of Fire with applicable details regarding the alarm impairment and precautions being taken For all scheduled outages/impairments, the Building Engineer, Electrician (or equivalent) must be notified by the coordinator, Project Manager or Contractor At least 30 minutes prior to any scheduled outage, the Building Engineer will post a sign at all building entrance doors (and elevator lobbies for buildings without a PA system) stating: WARNING: The fire alarm system is temporarily out of service. If smoke or fire is noted, call immediately. (See Attachment No. 2) If the fire alarm outage is limited to a specific floor, then Attachment No. 2A can be posted The Building Engineer, Electrician (or equivalent) shall call Pitt Police ( ) and Guardian ( ) to inform them of the alarm system outage/impairment. Guardian should be provided the following information: caller s name, University of Pittsburgh, building name, time and the associated Password for the building An announcement should be made by the Building Engineer (in buildings equipped to do so) after the signs are posted (and every 2 hours thereafter when the building is occupied) to inform the occupants that the system is impaired.
3 Page 3 of Per City of Pittsburgh Bureau of Fire requirements, a fire watch consisting of at least one roving individual is needed throughout the duration of the outage. In addition per University requirements, a Building Engineer, Electrician (or equivalent) should be stationed at the fire panel to reactivate any disabled alarms (see Section IV. for additional details). Provisions for the fire watch will be coordinated by the responsible department (Facilities Management, Housing or Property Management) During the scheduled outage, all hot work operations are prohibited in the areas where the alarms are out of service, unless the work is critical to repair of the alarm system. If the work is critical, the FM Global Hot Work Permit System should be utilized When the alarm system is returned to service, the Building Engineer, Electrician (or equivalent) shall call Guardian, Pitt Police and EH&S ( or ). Notification to EH&S should include the date and time the system was restored so that appropriate follow-up information can be sent to FM Global The warning signs should be removed and appropriate announcements made by the Building Engineer (in buildings so equipped). 3. Emergency Outage/Impairment 3.1. The Building Engineer, Electrician (or equivalent) shall call Pitt Police ( ), and Guardian ( ) and EH&S Duty Officer ( ) to inform them of the alarm system outage/impairment. Guardian should be provided the following information: caller s name, University of Pittsburgh, building name, time and the associated Password for the building For all emergency outages/impairments, the Building Engineer, Electrician (or equivalent) will post a sign at all building entrance doors (and elevator lobbies for buildings without a PA system) stating the following: WARNING: The fire alarm system is temporarily out of service. If an actual fire is noted, call immediately. (See Attachment No. 2). If the fire alarm outage is limited to a specific floor, then Attachment No. 2A can be posted.
4 Page 4 of An announcement should be made by the Building Engineer (in buildings equipped to do so) after the signs are posted (and every 2 hours thereafter when the building is occupied) to inform the occupants that the system is impaired When the message is received, EH&S will notify FM Global and the City of Pittsburgh Bureau of Fire that an alarm is impaired and the precautions taken Per City of Pittsburgh Bureau of Fire requirements, a fire watch consisting of at least one roving individual is needed throughout the duration of the outage. In addition per University requirements, a Building Engineer, Electrician (or equivalent) should be stationed at the fire panel to reactivate any disabled alarms (see Section IV. for additional details). Provisions for the fire watch will be coordinated by the responsible department (Facilities Management, Housing or Property Management) During the emergency outage, all hot work operations are prohibited in the areas where the alarms are out of service, unless the work is critical to repair of the alarm system. If the work is critical, the FM Global Hot Work Permit System should be utilized When the alarm system is returned to service, the Building Engineer, Electrician (or equivalent) shall call Guardian, Pitt Police and EH&S. Notification to EH&S should include the date and time so that appropriate follow-up information can be sent to FM Global The warning signs should be removed and appropriate announcements made by the Building Engineer (in buildings so equipped). 4. Construction, Renovations or Demolition Work 4.1. Contractors on site must notify the Project Manager (or equivalent) of any situations that may impact the fire alarm system. The University s Outage/Impairment notification procedures should be followed The Project Manager will notify the Building Engineer/Electrician (or equivalent) to take appropriate action as outlined above for a Scheduled Outage/Impairment (Section 2.0).
5 Page 5 of In the majority of cases, smoke detectors are the primary concern for false signaling due to dust and debris during demolition or construction. In lieu of disabling the detector and/or system, potentially impacted detectors should be bagged and taped off at the start of the work day and removed at the end of each work day or removed when the space will be unattended for more than 1 hour. NOTE: It is a violation of the City of Pittsburgh s Fire Code to disable a fire detection device or the fire alarm system due to work involving construction, renovation, or demolition. Failure to remove the bag covering the detector is also a violation of the Code. A minimal level of detection acceptable to the AHJ must be in service in all areas of the building (including the areas under construction) or a fire watch must be provided in order to occupy the building If there is no other course of action and alarms must be put on hold and/or specific detection devices temporarily disabled (i.e. beam type detectors, duct detectors, etc.), then the above procedures regarding scheduled outages/impairments must be followed. Every effort must be made to minimize the time that the alarms are inactive For additional fire safety details for buildings under construction, renovation or demolition, see the University of Pittsburgh Fire Prevention Plan and Checklist. FIRE PROTECTION SYSTEM IMPAIRMENT PROCEDURES 5. Scheduled Outage/Impairment Procedures 5.1. The University s procedures for Scheduled Outage/Impairment notification should be followed Upon receipt of the outage/impairment notification , EH&S will notify FM Global and the City of Pittsburgh Bureau of Fire with applicable details regarding the fire protection and/or alarm system impairment and precautions being taken For all scheduled outages/impairments, the Building Engineer, Electrician (or equivalent) and Plumbers must be notified by the coordinator, Project Manager or Contractor.
6 Page 6 of The Building Engineer, Electrician (or equivalent) shall call Pitt Police ( ) and Guardian ( ) to inform them of the fire protection system outage/impairment. Guardian should be provided the following information: caller s name, University of Pittsburgh, building name, time and the associated Password for the building At least 30 minutes prior to the outage/impairment, the Building Engineer will post a sign at all building entrance doors and elevator lobbies stating the following: WARNING: The fire protection sprinkler system is temporarily out of service. If smoke or fire is noted, activate the nearest fire alarm pull station and call immediately. (See Attachment No. 3). If the outage of the fire protection sprinkler system is limited to a specific floor, then Attachment No. 3A can be posted The Plumbers (or equivalent) will isolate the valves associated with the sprinkler system, fire pump or public water supplying the fire protection system that will be impaired. The Electricians (or equivalent) will isolate the associated fire pump control panel and/or any associated alarm devices As required by the City of Pittsburgh Bureau of Fire and FM Global, a tag shall be used to indicate that a fire protection system or portion thereof has been removed from service. The FM Global Red Tag Permit is applied to any closed fire protection control valves or impaired system. EH&S will complete Part 1 of the tag when notification is sent (Section 5.2) If the building is not provided with a complete and unaffected fire detection system, a fire watch consisting of at least one roving individual is needed throughout the duration of the outage per City of Pittsburgh Bureau of Fire requirements. In addition per University requirements, a Building Engineer, Electrician (or equivalent) should be stationed at the fire panel to reactivate any disabled alarms (see Section IV. for additional details). Provisions for the fire watch will be coordinated by the responsible department (Facilities Management, Housing or Property Management) During the scheduled outage, all hot work operations are prohibited in the areas where the protection or alarms are out of service, unless the work is critical or associated with getting the protection system back in service. If the work is critical, the FM Global Hot Work Permit System should be utilized.
7 Page 7 of When the impaired fire protection and alarm system is returned to service, the Electrician, Building Engineer (or equivalent) shall notify Guardian, Pitt Police and EH&S. Notification to EH&S should include the date and time so that appropriate follow-up information can be sent to FM Global The warning signs should be removed and appropriate announcements made by the Building Engineer (in buildings so equipped). 6. Emergency Outage/Impairment 6.1. In the event of an emergency outage/impairment, the Building Engineer, Electrician (or equivalent) and Plumbers must be notified by the coordinator, Project Manager or Contractor The Building Engineer, Electrician (or equivalent) shall call Pitt Police ( ) and Guardian ( ) and EH&S Duty Officer ( ) to inform them of the fire protection system outage/impairment Guardian should be provided the following information: caller s name, University of Pittsburgh, building name, time and the associated Password for the building Information provided to EH&S should include the type of system impaired (sprinklers, fire pump, water supply, alarms, etc.), a listing of closed fire protection control valves and/or other associated components, the area affected and estimated duration of the impairment The Building Engineer will post a sign at all building entrance doors and elevator lobbies stating the following: WARNING: The fire protection sprinkler system is temporarily out of service. If smoke or fire is noted, activate the nearest fire alarm pull station and call immediately. (See Attachment No. 3) If the outage of the fire protection sprinkler system is limited to a specific floor, then Attachment No. 3A can be posted The Plumbers (or equivalent) will isolate the valves associated with the sprinkler system, fire pump or public water supplying the fire protection system that will be impaired. The Electricians (or equivalent) will isolate the associated fire pump control panel and/or any associated alarm devices.
8 Page 8 of When the message is received, EH&S will notify FM Global and the City of Pittsburgh Bureau of the fire protection systems that are impaired and the precautions taken As required by the City of Pittsburgh Bureau of Fire and FM Global, a tag shall be used to indicate that a fire protection system or portion thereof has been removed from service. The FM Global Red Tag Permit is applied to any closed fire protection control valves or impaired system. EH&S will complete Part 1 of the tag when notification is sent (Section 6.6) For the emergency outages creating a condition where a complete and unaffected fire detection system is not provided, a fire watch consisting of at least one roving individual is needed throughout the duration of the outage per City of Pittsburgh Bureau of Fire requirements. In addition per University requirements, a Building Engineer, Electrician (or equivalent) should be stationed at the fire panel to reactivate any disabled alarms (see Section IV. for additional details). Provisions for the fire watch will be coordinated by the responsible department (Facilities Management, Housing or Property Management) During the emergency outage, all hot work operations are prohibited in the areas where the protection is out of service, unless the work is critical or associated with getting the protection system back in service. If the work is critical, the FM Global Hot Work Permit System should be utilized When the impaired systems are returned to service, the Building Engineer, Electrician (or equivalent) shall notify Guardian, Pitt Police and EH&S. Notification to EH&S should include the date and time so that appropriate followup information can be sent to FM Global The warning signs should be removed and appropriate announcements made by the Building Engineer (in buildings so equipped). 7. Construction, Renovations or Demolition Work 7.1. Contractors on site must notify the Project Manager (or equivalent) of any situations that may impact the fire protection systems (sprinklers, fire hose standpipes, fire pump and/or water supply). The University s Outage/Impairment notification procedures should be followed The Project Manager will notify the Plumber, Building Engineer, Electrician (or equivalent) to take appropriate action as outlined above for a Scheduled Outage/Impairment (Section 5.0).
9 Page 9 of For additional fire safety details for buildings under construction, renovation or Demolition, please see the University Fire Prevention Plan and Checklist. Fire Watch 8. Fire Watch Definition A temporary measure intended to ensure continuous and systematic surveillance of a building or portion thereof by one or more qualified individuals for the purposes of identifying and controlling fire hazards, detecting early signs of unwanted fire, raising an alarm of fire and notifying the fire department. In addition per University requirements, a Building Engineer, Electrician (or equivalent) should be stationed at the fire panel to reactivate any disabled alarms. A fire watch is needed when a building s fire (or emergency) alarm system cannot notify occupants of a hazardous condition or the need to evacuate the building. A fire watch is also needed when the building s fire protection systems are impaired. This could include the following: 8.1. The fire alarm panel is impaired The notification devices (horns/speakers/strobes) are not active/do not function There is no main or back-up power (emergency generator or battery) available to supply the fire alarm system/panel There is no communication and monitoring system/service in operation with Guardian (land and cell lines) and/or Pitt Police (RS2) The fire detection system (smoke detectors, heat detectors) is not in service (in full or in part would determine the extent of the fire watch area) The fire protection sprinklers are not in service (in full or in part would determine the extent of the fire watch area) The fire pump or the fire protection water supply (underground main break and/or PWSA valve closures) is not in service. A potential issue is that there may not be notification of a fire/hazard as the sprinkler water flow switch may not operate to initiate the alarms.
10 Page 10 of During construction, renovation or demolition projects, when sprinkler systems on entire floors are taken out of service, temporary smoke detectors can be installed to negate the need for a fire watch. This must be addressed in the University Fire Prevention Plan.
Fire Alarm and Protection Impairment Policy and Procedures
1.0 Policy Statement The University of New Haven has developed a Fire Alarm and Protection Impairment Plan in accordance with the National Fire Protection Associations (NFPA) codes. Specific codes referenced
ENVIRONMENTAL HEALTH AND SAFETY. Fire Protection System Impairment Procedure
ENVIRONMENTAL HEALTH AND SAFETY Fire Protection System Impairment Procedure April 2013 Fire Protection System Impairment Procedures Table of Contents I. Purpose II. III. IV. Fire Protection Systems Compliance
UNIVERSITY OF TOLEDO
UNIVERSITY OF TOLEDO SUBJECT: INTERIM LIFE SAFETY MEASURES AND INFECTION Procedure No: LS-08-008 CONTROL PROCEDURE STATEMENT Interim life safety and infection control measures will be implemented to protect
Columbia University Medical Center. Policies and Procedures for Shutdowns and Modifications to Fire Alarm Systems and Fire Suppression Systems
Columbia University Medical Center Policies and Procedures for Shutdowns and Modifications to Fire Alarm Systems and Fire Suppression Systems 1. Modifications to Fire Alarm or Fire Suppression System A.
OVERVIEW SCOPE DEFINITIONS
Procedure No 400.10 Subject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: March 2008 Distribution All Employees Review Date: April 2008 Purpose: To establish
Fire Alarm Log Book. Any activity regarding this system must be documented in writing.
CASTLE ROCK FIRE AND RESCUE DEPARTMENT 300 Perry Street Castle Rock, Colo. 80104 303-660-1066 Do not remove from the premises: Fire Alarm Log Book Any activity regarding this system must be documented
Fire Watch. Fire safety systems may not be deactivated in whole or in part for any reason other than for repairs or hot work.
Emergency Guideline GU.FAC.039 For Team Leaders, Caretakers, Trades, and Project Supervisors Approved by FS Leadership Team, August 28, 2013 Fire Watch A Fire Watch is a temporary surveillance system for
HERNANDO COUNTY FIRE ALARM GUIDELINES
HERNANDO COUNTY FIRE ALARM GUIDELINES To be used for all commercial building fire alarm system plan review. The procedures set forth in this document are the minimum requirements necessary to ensure a
Metropolitan Washington Airports Authority Office of Public Safety Fire & Rescue Department. Fire Code Enforcement Division
Metropolitan Washington Airports Authority Office of Public Safety Fire & Rescue Department Fire Code Enforcement Division Fire Protection System Impairment Requirements For Contractors and Service Personnel
Program No. 1.6.1. Section Heading
ENVIRONMENTAL HEALTH AND SAFETY EHS PROGRAM MANUAL Program Title 1.0 INTRODUCTION The New York City Fire Department (FDNY) is responsible for approving and/or inspecting fire alarm systems, buildings,
City of Bettendorf Fire Alarm System Requirements
City of Bettendorf Fire Alarm System Requirements Section 907 of the 2009 Edition of the International Fire Code (IFC) and Section 10-7-3 of the Municipal Code provide fire alarm requirements. IFC Section
Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines
Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines Red Oak Fire Rescue Office of the Fire Marshal 547 N. Methodist Red Oak, TX 75154 Phone: 469-218-7713 Fax: 468-218-7719
Rancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Revised: January 2014 INTENT The intent
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS
CITY OF PHILADELPHIA DEPARTMENT OF LICENSES AND INSPECTIONS ANNUAL CERTIFICATION FOR FIRE ALARM SYSTEMS PROPERTY ADDRESS (BRT Address Required) TESTING CONTRACTOR (Name and Address) License No. ANNUAL
Emergency Procedures
FIRE AND LIFE SAFETY Building Systems Hayden Ferry Lakeside is state of the art and designed to offer maximum protection to its building occupants. The building is monitored 24 hours a day, seven days
Inspection, Testing and Maintenance
Page 18 ABOUT CODE CORNER CCFS would like to remind you to check with your local Authority Having Jurisdiction (AHJ) for questions and opinions concerning your local Fire and Building Codes. The information
build safe live safe
NYC Buildings Department 280 Broadway, New York, NY 10007 Robert D. LiMandri, Commissioner BUILDINGS BULLETIN 2012-009 Technical Supersedes: Issuer: None Thomas Fariello, R.A. First Deputy Commissioner
Planned and Emergency Utility Outage Guidelines
Revised: April 4, 2014 GUIDELINES: PURPOSE: The purpose of these guidelines is to define roles and responsibilities in requesting, coordinating scheduling, and executing utility outages and restoration
Module 4, Lesson 12 Fire Alarm Systems
Student Manual Module 4, Lesson 12 Fire Alarm Systems Performance Objectives At the conclusion of this lesson, you will be able to: Identify the components and functions of a fire alarm system and determine
Environment of Care Fire Safety Management Plan 2014
Environment of Care Fire Safety Management Plan 2014 Updated 4.29.2014 PURPOSE The purpose of the Fire Safety Management Plan is to ensure that all facilities are designed, constructed, maintained, and
CITY OF HOUSTON HIGH-RISE OFFICE BUILDING FIRE SAFETY PLAN
CITY OF HOUSTON HIGH-RISE OFFICE BUILDING FIRE SAFETY PLAN DATE PROPERTY MANAGER ADDRESS Houston, TX _(Zip Code)_ PHONE NUMBER LIFE SAFETY IS THE GOAL OF THIS PLAN. ALL DUTIES CALLED FOR HEREIN SHOULD
ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR 1910.252 WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600
OSHA REGULATION: 9 CFR 90.5 WELDING, CUTTING, AND BRAZING ( HOT WORK ) A. POLICY. This procedure follows requirements set forth in 9 CFR 90.5.. This policy applies to all Hot Work operations being done
FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION
PERMITS AND INSPECTIONS FIRE ALARM SYSTEM SUBMITTAL CHECKLIST AND APPLICATION 911 Assigned PROJECT LOCATION Subdivision: Lot: Blk: Sec: PROJECT New Construction Addition/Remodel Demolition Other: Number
1.0 General. Inspection, Testing, and Maintenance 1 of 8
1.0 General 1.1 Scope This specifications covers the minimum requirements for the inspection, testing, and maintenance of the existing Notifier fire alarm systems at Bergen Community College (BCC) campus
FIRE SPRINKLER SYSTEM SUPERVISORY SERVICE User s Guide (DamarNet RAR Service)
FIRE SPRINKLER SYSTEM SUPERVISORY SERVICE User s Guide (DamarNet RAR Service) The information provided in this user guide pertains to fire suppression sprinkler system monitoring service provided over
NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems
NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems 1.0 Purpose A. The following guideline provides the minimum standards and requirements for fire alarm systems. 2.0
Fire Safety Report 2014-2015. Fire Statistics 2013-2014-2015
Fire Safety Report 2014-2015 Fire Statistics 2013-2014-2015 Fire Log 2013-2014-2015 The New York Conservatory for Dramatic Arts Annual Fire Safety Report for Campus Housing 2014-2015 In August 2008, the
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL
FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL January, 2003 Environmental Health and Safety Florida Atlantic University 777 Glades Rd. Boca Raton, FL 33431 Phone: 561-297-3129 Fax:
NEW YORK CITY FIRE DEPARTMENT
NEW YORK CITY FIRE DEPARTMENT Notice of Promulgation of two New Rules, 3 RCNY 104-02, entitled Professional Certification of Fire Alarm System Installations, and 3 RCNY 105-01, entitled Approval of Fire
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES
CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES Review the following information pertaining to Construction Fire Safety Planning: B.C. Building Code Sections 8.1 up to and including Subsection 8.2.3 B.C.
BELMONT FIRE DEPARTMENT FIRE ALARM SYSTEM REQUIREMENTS BFD-OFM-10-011
Fire Alarm System plan(s) MUST be reviewed and approved by the Belmont Fire Department prior to the start of construction. The design and any changes must be fully compliant with NFPA 1, NFPA 101, NFPA
NY Fire Safety Institute
NY Fire Safety Institute Presents the FDNY Coordinator of Fire Safety and Alarm Systems Homeless Shelters (Premise Related) Certificate of Fitness F-80 Definitions and Terminology Established 1995 Preparing
Fire Alarm System Plans Review Checklist Property location Date of Review
Fire Alarm System Plans Review Checklist Property location Date of Review 1. Is application completed in entirety? 2. Are the plans review fee submitted with the application? 3. Does floor plan include
946 CMR: MASSACHUSETTS DEVELOPMENT FINANCE AGENCY 946 CMR 7.00: DEVENS REGIONAL ENTERPRISE ZONE FIRE AND POLICE RULES
946 CMR 7.00: DEVENS REGIONAL ENTERPRISE ZONE FIRE AND POLICE RULES Section 7.01: Scope and Purpose 7.02: Definitions - Fire and Police Alarms 7.03: Duties of Fire Chief 7.04: Smoke Detectors in Certain
WORK RULES AND CONTRACTOR REQUIREMENTS FOR ALL UNIT OWNERS & UNIT OWNER CONTRACTORS PERFORMING WORK ON THE PREMISES AT HAWTHORNE PLACE CONDOMINIUMS
WORK RULES AND CONTRACTOR REQUIREMENTS FOR ALL UNIT OWNERS & UNIT OWNER CONTRACTORS PERFORMING WORK ON THE PREMISES AT HAWTHORNE PLACE CONDOMINIUMS 1) GENERAL GUIDELINES a) The following rules, regulations,
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST
TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST In order to provide a comprehensive plan review in a timely manner, and to insure the design and installation of fire alarm systems
LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809
LOUISVILLE FIRE PROTECTION DISTRICT 895 West Via Appia, Louisville, Colorado 80027 303-666-8809 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3 Fire
ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com
ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK Website www.iomfire.com ADDRESS OF PREMISES FIRE CERTIFICATE No. (where applicable).. LOCATION OF LOG BOOK. CONTENTS OF LOG BOOK Useful telephone
Risk Engineering Guideline
www.hdi.global HDI Risk Consulting Risk Engineering Guideline Impairment of fire protection systems Basic protection systems should not be impaired without adequate replace compensation with provisions.
North York General Hospital Policy Manual
Page 1 of 6 POLICY STATEMENT North York General Hospital staff is responsible to follow the guidelines outlined in this document in the event of a fire to minimize injury and/or damage. DEFINITIONS Code
Risk Management Guidelines
Impairment/Restoration of Fire Protection Systems Introduction The importance of ensuring the effectiveness and continuity of fire protection systems cannot be over-stressed. As such it is necessary to
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT
INSTRUCTIONS FOR BUILDINGS WITH FIRE PROTECTION EQUIPMENT FIRE EXTINGUISHERS,SPRINKLER SYSTEMS AND FIRE ALARMS Attachment #1 Inspection of Fire Extinguishers Fire Extinguishers must be tested according
University Design Standard. Fire Alarm Systems
University Design Standard Fire Alarm Systems 1.0 Overview This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit
Fire Safety Director On Site Examination for Hotels and Office Buildings F-58 Study Guide
Fire Safety Director On Site Examination for Hotels and Office Buildings F-58 Study Guide It is recommended that this guide be kept at all times at the Fire Command Center. This publication is provided
Maintaining Fire Protection Systems
Maintaining Fire Protection Systems Fire continues to be a major threat to your business and your personal safety. Each year several thousand people are injured or killed by fires and billions of dollars
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS
SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS I. APPLICATION AND DEFINITIONS 1.01 Authorization for Standards 1.02 Application of Standards 1.03 Definitions
Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007
Telluride Fire Protection District Fire Alarm Systems Policy Version 03/2007 FIRE ALARM SYSTEMS POLICY TELLURIDE FIRE PROTECTION DISTRICT TABLE OF CONTENTS FIRE ALARM PROTECTION POLICY PLAN REVIEW SUBMITTAL
Bold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 2/12 Fire Chief Wes Rhodes Fire Marshal Paul Smith EFD-FMO 3-2 2009 International Fire & Building Code as Amended NFPA Standards Adopted
FIRE ALARM SYSTEM RECORD OF COMPLETION
FUNDAMENTALS OF FIRE ALARM SYSTEMS 72 33 FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. PROTECTED PROPERTY
FIRE ALARM SYSTEM RECORD OF COMPLETION
FIRE ALARM SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance and approval. 1. Protected Property Information Name of property: Description
FIRE-FIGHTING DESIGN BRIEF REPORT
P a g e 1 SECTION 04 (Doc.No.A/DBR 001) FIRE-FIGHTING DESIGN BRIEF REPORT P a g e 2 1.0 SCOPE 2.0 STANDARDS AND CODES 3.0 TYPES OF SYSTEM PROPOSED 4.0 FIRE HYDRANT SYSTEM 5.0 AUTOMATIC SPRINKLER SYSTEM
Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application
PERMIT FEE: $ Finance and Administration Department 907 Billy Mitchell Blvd. P: (210) 228-1022 Fire Alarm Permit Application PAYMENT TYPE: Check Credit Card Charge to Job #: (Please complete all of the
Hotel Fire Safety for staff
Teaching Guide Hotel Fire Safety for staff Seattle Fire Department Fire Prevention Division Hotel Fire Safety Instructor Outline Introduction Goals: To ensure that hotel employees are knowledgeable in
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS
ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS In this document are the fire safety equipment maintenance requirements that are found in Division B of the Alberta Fire Code (AFC 2006) for
Yale Business Continuity Program Emergency Response Guide
Contents Yale Business Continuity Program Emergency Response Guide March 2016 Introduction Immediate Actions Assess the Damage Determining Business Disruption Determining Plan of Action Relocation Checklist
1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri.
GENERAL: 1. The objective of this guideline is to provide minimum standards for design and installation of fire alarm systems for the University of Missouri. 2. Fire alarm systems are Life Safety Systems
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS. 1. All Floors (inspect from top floor to basement): Yes No
General Inspection FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS 1. All Floors (inspect from top floor to basement): Yes are fire exits and directional signs properly illuminated? is the emergency
STATEMENT OF WORK FOR FIRE ALARM SYSTEM TESTING & MAINTENANCE. Project No. SAQMMA-07-C0060 ***OUAGA, BURKINA FASO***
STATEMENT OF WORK FOR FIRE ALARM SYSTEM TESTING & MAINTENANCE Project No. SAQMMA-07-C0060 ***OUAGA, BURKINA FASO*** CONTENTS: 1.0 Introduction 2.0 Objectives 3.0 General Requirements 4.0 Specific Requirements
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS
SECTION 16721 FIRE ALARM AND DETECTION SYSTEMS The equipment requirements of this section apply to the IUB Campus. The IUPUI Campus has a preferred vendor agreement for fire alarm systems. Contact Pat
Overview of Hotel Fire Safety Requirements
Overview of Hotel Fire Safety Requirements in the Fire Code Susan Clarke, P.Eng. Office of the Fire Marshal - January 10, 2012 1 Agenda Regulation History - Hotels Fire Code Overview (Parts 1 to 8) Defined
INSPECTION AND TESTING OF FIRE ALARM SYSTEMS
Page 1 January 2, 2009 INSPECTION AND TESTING OF FIRE ALARM SYSTEMS Introduction Early warning plays a key role in a healthcare facility s ability to safely evacuate its residents during a fire emergency.
FIRE DEPARTMENT CITY OF NEW YORK
FIRE DEPARTMENT CITY OF NEW YORK STUDY MATERIAL FOR THE CERTIFICATE OF FITNESS FOR SUPERVISION OF FIRE ALARM SYSTEMS AND OTHER RELATED SYSTEMS S-95 ALSO INCLUDED IN THIS BOOKLET YOU WILL FIND THE FOLLOWING:
Fire Safety Plan University Stadium
Fire Safety Plan University Stadium Building # 53 Safety, Health, Environment Effective: March 14, 2018 Revised: December 2014 Revision: 1 Approved on: Pending Approval WILFRID LAURIER UNIVERSITY Contact:
What Should I Expect From My Alarm Monitoring Station?
What Should I Expect From My Alarm Monitoring Station? When the alarm goes off... What actions will the operators take? When will they dispatch the authorities? What actions do I need to take? Monitoring
POINT UNIVERSITY CAMPUS SECURITY Emergency Response Plan
POINT UNIVERSITY CAMPUS SECURITY Emergency Response Plan Introduction The Point University Emergency Response Plan establishes guidelines for campus-wide communication, service coordination and safety
NATIONAL FIRE ALARM AND SIGNALING CODE
GAP.11.1.1.0 A Publication of Global Asset Protection Services LLC NATIONAL FIRE ALARM AND SIGNALING CODE INTRODUCTION National Fire Protection Association (NFPA) documents describe a level of fire protection
Commercial Fire Alarm Standards July 1, 2010 Edition Page 1 of 14
City of Mercer Island Development Services Group Fire Code Review and Inspection 9611 SE 36 th Street Mercer Island, WA 98040-3732 PHONE (206) 275-7605 FAX (206) 275-7726 www.mercergov.org Commercial Fire
Winnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
FIRE DETECTION AND ALARM
Scope Provide a fire alarm system, or expand the existing system, as required by Code, the requirements in the Special Instructions to Designers (SID) of the Design Guidelines, and/or as noted in the Program
Chapter 103 Alarm Ordinance 1. PURPOSE.
1. PURPOSE. The purpose of this ordinance is to provide a registration and permit process, with appropriate regulations to facilitate the reduction of false alarm activations, establish procedures for
Emergency Evacuation Plan: 232 King St.
Emergency Evacuation Plan: 232 King St. Effective Date: July 2003 Revisions: 0 Approved on: April 20, 2004 Table of Contents 1.0 Building Resources... 1 2.0 Human Resources... 2 3.0 Definitions... 3 4.0
How To Handle An Emergency
Company Name Address Telephone Contact Name Title Last Revision Date Policy and Organizational Statements Identify the goals and objectives for the emergency response plan. Define what your emergency response
Bemidji State University Building Emergency Preparedness Plan. Building Representatives. Contact Points. Building: Department: Room(s):
Bemidji State University Building Emergency Preparedness Plan Building: Department: Room(s): Preparation Date: Building Emergency Information Emergency Numbers E- 911 Address Internal Shelter Site External
Core & Shell Construction. Rules and Regulations
Core & Shell Construction Rules and Regulations 1. Protection: During the construction Contractor shall endeavor to protect all areas of work from damage caused by workers, weather or equipment. 2. Permits
General Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
The University of Texas at San Antonio Environmental Health, Safety and Risk Management
The University of Texas at San Antonio Environmental Health, Safety and Risk Management TO: FROM: UTSA Campus Community John DeLaHunt, MBA, ARM Risk & Life Safety Manager University Fire Marshal J. Brian
NATURAL GAS EMERGENCY PROCEDURES AND ACCIDENT PREVENTION
NATURAL GAS EMERGENCY PROCEDURES AND ACCIDENT PREVENTION Fire and Life-Safety Group (FLS) I. EMERGENCY PROCEDURES The emergency procedures for natural gas emergencies are similar to that for fire emergencies.
Overview of Fire Alarm Systems and Maintenance
Overview of Fire Alarm Systems and Maintenance By Mr. David Goh Vice President Fire Safety Managers Association Convener of Working Group for CP 10 : 2005 Er. Matthew Kwek Committee Member Fire Safety
Austin Independent School District Police Department Policy and Procedure Manual
Policy 8.07 Austin Independent School District Police Department Policy and Procedure Manual Life Safety Systems I. POLICY The proper operations of the AISD Life Safety Systems (LSS) are essential for
527 CMR: BOARD OF FIRE PREVENTION REGULATIONS
527 CMR 31.00: CARBON MONOXIDE ALARMS Section 31.01: Purpose and Scope 31.02: Definitions 31.03: General Installation Provisions 31.04: Specific Installation Provisions 31.05: Carbon Monoxide Protection:
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS
FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS The attached self-inspection form is intended for staff use at regular, frequent intervals. It should not take the place of two other vital measures
DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION
Phone System Owner Phone System Engineered by: of Record Drawings: of System Manuals: of Test Reports: System Installer 1. GENERAL INFORMATION Phone Delaware License No: Certificate Holder No. System Supplier
Understanding Fire Alarm Requirements & Inspections. Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc
Understanding Fire Alarm Requirements & Inspections Presented By Bill Conroy Technical Sales For Briscoe Protective Systems Inc Introduction Fire Alarm Requirements are structured through a system of codes.
Fire Alarm System Monitoring - CAN/ULC-S561-03
Fire Alarm System Monitoring - CAN/ULC-S561-03 Brian McBain ULC Regulatory Services May 4, 2011 Copyright 1995-2007 Underwriters' Laboratories of Canada. All rights reserved. No portion of this material
SECTION 16721 FIRE ALARM AND DETECTION SYSTEM
1. GENERAL 1.1. Related Documents: 1.2. Scope: 1.1.1. The general provisions of the Contract, including General and Supplementary Conditions and General Requirements apply to the work specified in this
Division 21. Fire Suppression
21 00 00. Fire Suppression For campus projects that require a fire suppression system shut down in a campus facility, a Shut Down Procedure of Fire Safety System Sheet must be completed and filed seven
HOUSTON FIRE DEPARTMENT HIGH-RISE SURVEY CHECKLIST
This is a Fill Out On Computer & Print Form Only! No hand written forms accepted! TOTAL PAPER FORMS NEEDED: 3 - - - Original & 2 Copies HOUSTON FIRE DEPARTMENT HIGH-RISE SURVEY CHECKLIST High-rise Id #
FIRE ALARM PLAN REVIEW. Office of the State Fire Marshal Massachusetts Department of Fire Services December 2009
FIRE ALARM PLAN REVIEW Office of the State Fire Marshal Massachusetts December 2009 SURPRISE QUIZ 1. A fire alarm system is required to be installed by the MSBC, what edition of NFPA 72 do you use? 2.
FIRE SAFETY ONLINE TRAINING
INTRODUCTION This Fire Safety Training module is designed to teach you preventive measures that will eliminate or minimize causes of fire or fire hazards in the workplace, and to teach you proper emergency
BASIC FIRE ALARM TRAINING
BASIC FIRE ALARM TRAINING What is a fire alarm system? Per the defini+on in NFPA 72 A system or por+on of a combina+on system that consists of components and circuits arranged to monitor and annunciate
INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT
CITY OF SPRING LAKE PARK Code Enforcement Department 1301 81 st Avenue NE Spring Lake Park MN 55432 Business Phone 763-784-6491 Fax 763-792-7257 INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS
SECURITY SYSTEM NOTES AREA LISTINGS SPECIAL CODES ENTRY / EXIT DELAY TIMES ARM / DISARM CODES ZONE DESCRIPTIONS
SECURITY SYSTEM NOTES Installing/Service Company For Service Call Area 1 Area 2 Area 3 AREA LISTINGS SPECIAL CODES "Quick Arm" Digit "Partial Arm" Digit "Chime" Digit ENTRY / EXIT DELAY TIMES Exit Delay
NetworX NX-6V2. LED Keypad User Manual
NetworX NX-6V2 LED Keypad User Manual POWER Light is on when AC power is present; flashes to indicate a low battery condition. ARMED Light is on when armed; off when disarmed; flashes to indicate a previous
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems
Fire Alarm System Plans Submittal Guidelines For New and Existing Systems SCOPE The Temecula Fire Prevention Bureau (TFPB) has established the following requirements for the submittal of all fire alarms,
BETTENDORF PUBLIC LIBRARY INFORMATION CENTER EMERGENCY RESPONSE AND FACILITY CLOSURE POLICY
BETTENDORF PUBLIC LIBRARY INFORMATION CENTER EMERGENCY RESPONSE AND FACILITY CLOSURE POLICY PURPOSE This policy serves to provide guidelines for staff and patrons to be used in response to an event or
Duke University Hospital Fire/Life Safety Management Plan 2007
Duke University Hospital Fire/Life Safety Management Plan 2007 Introduction One of the most serious issues facing Duke University Hospital, Medical Center, Duke Clinic and the Health Systems is the threat
Fighting Fire in Sprinklered Buildings. Student Guide
Fighting Fire in Sprinklered Buildings Student Guide Fighting Fire in Sprinklered Buildings Student Guide Table of Contents Purpose........................................................... 3 Instruction
HOT WORK PERMIT PROGRAM TRAINING. John Braun
HOT WORK PERMIT PROGRAM TRAINING John Braun 1.0 INTRODUCTION 1.2 Purpose The Hot Work Permit Program has been developed for University employees that work on or around hot work activities. This program